WALL CONNECTOR, 8OA SINGLE PHASE

INSTALLATION MANUAL

Approved Markets: North America, Japan, Taiwan

For additional languages, please visit: www.tesla.com/wallconnector

Page 2: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL
Page 3: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

About this Manual...........................2Product Specifications.............................................. 2Communications Regulations.................................2Errors or Inaccuracies................................................2Copyrights and Trademarks....................................2

Safety Information..........................3Important Safety Instructions................................ 3Warnings.........................................................................3Cautions..........................................................................3Notes................................................................................4

Specifications................................... 5

Features..............................................6Circuit Ratings..............................................................6Self-Monitoring and Recovery................................6Power Outages.............................................................6Load Sharing.................................................................6

Planning Your Installation............ 7Minimum Requirements............................................ 7Service Wiring.............................................................. 7Single-Phase With Neutral.......................................7Single-Phase Without Neutral................................7120V Above Ground................................................... 8Ground Connection.................................................... 8240V Single-Phase..................................................... 8200V Single-Phase.....................................................8208V 3-Phase Wye-Connected............................. 9240V Three-Phase Delta-Connected.................. 9Determine the Circuit BreakerRequirements................................................................9Choose the Best Location for the WallConnector.....................................................................10Installation Considerations...................................... 11

Check the Box Contents............. 13

Step-by-Step InstallationInstructions...................................... 15Tools and Materials Required................................ 15Overview of Installation Steps.............................. 15

Install the Low Profile Bracket for Rearor Bottom Entry Wiring.......................................... 16Install the Top Entry Bracket for Rear orTop Entry Wiring........................................................ 17Prepare for Installation............................................ 18Connect the Wiring...................................................19Set the Operating Current......................................21Secure the Cover and Power Up.........................22

Troubleshooting............................24Reset..............................................................................27Questions?...................................................................28

Appendix A: Testing forProper Operation......................... 29

Appendix B: OptionalConnection for Load Sharing.. 30Daisy Chaining Multiple Wall Connectors....... 30Example of the Communication Wiring............31Other Load Sharing Behaviors............................. 31

Contents

Page 4: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Product Specifications

All specifications and descriptions containedin this document are verified to be accurate atthe time of printing. However, becausecontinuous improvement is a goal at Tesla, wereserve the right to make productmodifications at any time.

Communications Regulations

This device complies with Part 15 of the FCCrules and Industry Canada license-exempt RSSstandard(s). Operation is subject to thefollowing two conditions: (1) This device maynot cause harmful interference and (2) thisdevice must accept any interference received,including interference that may causeundesired operation.

Important: Changes or modifications tothis product not authorized by Teslacould void the FCC compliance.

Errors or Inaccuracies

To communicate any inaccuracies oromissions, or to provide general feedback orsuggestions regarding the quality of thismanual, send an email to:

[email protected]

Copyrights and Trademarks

All information in this document is subject tocopyright and other intellectual propertyrights of Tesla, Inc. and its licensors. Thismaterial may not be modified, reproduced orcopied, in whole or in part, without the priorwritten permission of Tesla, Inc. and itslicensors. Additional information is availableupon request. The following are trademarks orregistered trademarks of Tesla, Inc. in theUnited States and other countries:

All other trademarks contained in thisdocument are the property of their respectiveowners and their use herein does not implysponsorship or endorsement of their productsor services. The unauthorized use of anytrademark displayed in this document or onthe vehicle is strictly prohibited.

About this Manual

2

Page 5: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Important Safety Instructions

This document contains important instructionsand warnings that must be followed wheninstalling and maintaining the Wall Connector.

Warnings

Warning: Read all the instructions beforeusing this product.

Warning: This device should besupervised when used around children.

Warning: The Wall Connector must begrounded through a permanent wiringsystem or an equipment groundingconductor.

Warning: Do not install or use the WallConnector near flammable, explosive,harsh, or combustible materials,chemicals, or vapors.

Warning: Turn off input power at thecircuit breaker before installing orcleaning the Wall Connector.

Warning: Use the Wall Connector onlywithin the specified operatingparameters.

Warning: Never spray water or any otherliquid directly at the wall mounted controlbox. Never spray any liquid onto thecharge handle or submerge the chargehandle in liquid. Store the charge handlein the dock to prevent unnecessaryexposure to contamination or moisture.

Warning: Stop using and do not use theWall Connector if it is defective, appearscracked, frayed, broken, or otherwisedamaged, or fails to operate.

Warning: Do not attempt to disassemble,repair, tamper with, or modify the WallConnector. The Wall Connector is not userserviceable. Contact Tesla for any repairsor modification.

Warning: When transporting the WallConnector, handle with care. Do notsubject it to strong force or impact orpull, twist, tangle, drag, or step on theWall Connector, to prevent damage to itor any components.

Warning: Do not touch the WallConnector’s end terminals with fingers orsharp metallic objects, such as wire, tools,or needles.

Warning: Do not forcefully fold or applypressure to any part of the WallConnector or damage it with sharpobjects.

Warning: Do not insert foreign objectsinto any part of the Wall Connector.

Warning: Use of the Wall Connector mayaffect or impair the operation of anymedical or implantable electronic devices,such as an implantable cardiacpacemaker or an implantable cardioverterdefibrillator. Check with your electronicdevice manufacturer concerning theeffects that charging may have on suchelectronic devices before using the WallConnector.

Cautions

Caution: Do not use private powergenerators as a power source forcharging.

Caution: Incorrect installation and testingof the Wall Connector could potentiallydamage either the vehicle’s Batteryand/or the Wall Connector itself. Anyresulting damage is excluded from theNew Vehicle Limited Warranty and theCharging Equipment Limited Warranty.

Caution: Do not operate the WallConnector in temperatures outside itsoperating range of -22°F to 122°F (-30°Cto +50°C).

Safety Information

Safety Information 3

Page 6: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Notes

Note: Ensure that the Wall Connector’scharging cable is positioned so it will not bestepped on, driven over, tripped on, orsubjected to damage or stress.

Note: Do not use cleaning solvents to cleanany of the Wall Connector’s components. Theoutside of the Wall Connector, the chargingcable, and the connector end of the chargingcable should be periodically wiped with aclean, dry cloth to remove accumulation ofdirt and dust.

Note: Be careful not to damage the circuitboards or components during installation.

Note: Use a cable sheath or similarcontainment to cover the supply cables. Thecolor black is recommended.

Safety Information

4

Page 7: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

The maximum power rating for the Wall Connector is 20 kW or 80A at 250V AC single-phasepower.

Description Specifications

Voltage and Wiring 208V or 240V AC single-phase: L1, L2, and earth

Current Maximum output: 80A, 72A, 64A, 56A, 48A, 40A, 36A,32A, 28A, 24A, 20A, 16A, 12A

Frequency 50 to 60 Hz

Cable Length 8.5' (2.6 m) and 24' (7.4 m)

Wall Connector Dimensions Height: 15.0" (380 mm)

Width: 6.3" (160 mm)

Depth: 5.5" (140 mm)

Top Entry Bracket Dimensions Height: 10.8" (275 mm)

Width: 5.1 " (130 mm)

Depth: 2.0" (50 mm)

Weight (including bracket) 20 lb (9 kg)

Operating Temperature -22°F to 122°F (-30°C to 50°C)

Storage Temperature -40°F to 185°F (-40°C to 85°C)

Enclosure Rating Type 3R

Agency Approvals cULus listed for United States and Canada under filenumber E354307, FCC Part 15.

Ventilation Not Required

Specifications

Specifications 5

Page 8: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Circuit Ratings

Use a single-phase circuit breaker rated for100A single phase to obtain the fastestcharging.

In certain installation locations, this level ofpower isn’t readily available. Therefore, youcan adjust the circuit breaker rating on theWall Connector from 15A to 100A (refer to Setthe Operating Current on page 21).

Note: Actual amperage draw will depend onthe on-board charger of the vehicle. ContactTesla if you have questions about the on-board charger of a specific vehicle.

Self-Monitoring and Recovery

The Wall Connector has a ground monitoringcircuit that continuously checks for thepresence of a safe ground connection andautomatically recovers from faults. Manualtesting and resetting is not required.

Temporary problems such as ground faults orutility power surges are overcomeautomatically. If a residual current fault occursthat interrupts charging, the Wall Connectorautomatically tries to clear the fault and re-attempt charging.

If the problem is immediately sensed a secondtime, the Wall Connector waits 15 minutesbefore trying to charge. This process repeats 4times and if all attempts are unsuccessful,power is removed and no further attempts aremade. In this case, you will see a red error lighton the front panel (refer to Troubleshootingon page 24). It is recommended that whenyou see a red error light, you power off theWall Connector by switching off the upstreamcircuit breaker, and then power it back onagain.

The Wall Connector can alternatively be resetwhen a red error light is encountered usingthe RESET button (refer to Reset on page27).

Power Outages

If a power outage occurs, the Wall Connectorautomatically resumes charging when poweris restored. If the charging cable is pluggedinto the vehicle when power is restored, thelights blink and the unit does not energize thecharging cable for approximately 15 secondsto three minutes. This prevents the utility gridfrom experiencing a large surge when power isrestored and allows vehicles to begin drawingcurrent at random times, rather than all atonce.

Load Sharing

The Wall Connector provides the capability towire 4 Wall Connectors to a single circuit withautomatic load management, giving vehicleowners reassurance that they can chargemultiple vehicles at home (refer to AppendixB: Optional Connection for Load Sharing onpage 30).

Features

6

Page 9: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Minimum Requirements

Installation of the Wall Connector requires thatyou:

• Calculate the existing electrical load todetermine the maximum operatingcurrent.

• Calculate the distance to ensure minimalvoltage drop.

• Obtain any necessary permits from thelocal authority that has jurisdiction andconfirm that the follow-up inspection hasbeen scheduled by an electrician after theinstallation is complete.

• Use only copper conductors.• Use conductors that are sized in

accordance with local wiring regulations.The selected cable must be able to sustainperiods of constant load of up to themaximum amperage selected by theelectrician.

• Use protective devices. The circuitprotection device chosen mustincorporate overcurrent protection inrelation to the electrical load selected.

Note: Consult with an electrician to ensurethat the installation meets local regulations.

Service Wiring

Warning: The Wall Connector is a single-phase device. Do not connect all threephases of a three-phase feed.

Warning: Before installing the WallConnector, identify the type of utilityservice connection available on site.

Caution: If a 240V three-phase feed isfrom a Delta-connected secondary, theleg used must have a center tap. Thiscenter tap must be grounded. Only thetwo phases on either side of thecentertapped leg can be used.

Only three wires are connected, but care mustbe taken that the service transformersecondary connection is definitely known, andthat the three wires from the main circuitbreaker panel are correctly connected andlabeled.

Caution: The two phases used must eachmeasure 120V to neutral. Earth groundmust be connected to neutral at only onepoint, usually at the breaker panel.

Single-Phase With Neutral

For single-phase use of a Wye-connectedsecondary, only a single-phase (L1) and neutralshould be connected. The phase to neutralvoltage measurement are shown in theillustration below.

Warning: The Wall Connector in thisconfiguration operates only from a single-phase (L1). Do not connect the remainingphases (L2 and L3).

Warning: Before installing the WallConnector, identify the type of utilityservice connection available on site. If youare unsure about the type of connectionavailable at the service panel, consult anelectrician, or contact Tesla for assistance.

Note: Consult with your local electrician orrefer to your local code for proper wire sizingappropriate for the currents in your WallConnector.

Single-Phase Without Neutral

For installations without a neutral and220-240V from phase to phase, connect anytwo phases (L1, L2, or L3 in the illustration) tothe L1 and N positions on the Wall Connectorterminal block.

L1

L2

N

L3

G

220V - 240V

Planning Your Installation

Planning Your Installation 7

Page 10: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

120V Above Ground

Warning: The Wall Connector is a single-phase device. Do not connect all threephases of a three-phase feed.

Warning: Before installing the WallConnector, identify the type of utilityservice connection available on site. If youare unsure about the type of connectionavailable at the service panel, consult anelectrician, or contact Tesla for assistance.

Caution: The two phases used must eachmeasure 120V to neutral. Earth groundmust be connected to neutral at only onepoint, usually at the breaker panel.

Caution: If a 240V three-phase feed isfrom a Delta-connected secondary, theleg used must have a center tap. Thiscenter tap must be grounded. Only thetwo phases on either side of the center-tapped leg can be used.

Only three wires are connected, but care mustbe taken that the service transformersecondary connection is definitely known, andthat the three wires from the main circuitbreaker panel are correctly connected andlabeled.

Note: The L1, L2, and ground outputs labeledon the illustrations correspond to the inputson the Wall Connector.

Ground Connection

Always connect the Neutral at the service toEarth Ground. Ground fault protection is notpossible unless the Neutral (center tap on theservice transformer) is connected to an EarthGround. If ground is not provided by theelectrical service, you must install a groundingstake nearby. the grounding stake must beconnected to the ground bar in the mainbreaker panel, and Neutral connected toGround at that point.

240V Single-Phase

L2

L1

120V

120V

GND

240VNEUTRAL(NOT USED)

Note: Illustrations in this document are fordemonstration purposes only.

200V Single-Phase

L2

L1

100V

100V

GND

200VNEUTRAL

Note: Illustrations in this document are fordemonstration purposes only.

Planning Your Installation

8

Page 11: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

208V 3-Phase Wye-Connected

With a Wye-connected secondary, any two ofthe legs can be used to provide 208V to theWall Connector. For example, L1 and L2, or L1and L3, or L2 and L3. The two used phasesmust each measure 120V to neutral.

Note: A current-carrying neutral is notrequired.

120V 208V

120V

L1

NEUTRAL(NOT USED)

L3 (NOT USED)

L2

GND

Caution: The unused leg (L3 in theillustration) must remain open. Do notconnect to a neutral bar, or to earthground.

Caution: The center point of the threephases (normally used as neutral) mustbe grounded to earth at only one point.This is usually at the breaker panel.

240V Three-Phase Delta-Connected

With the delta connection, one leg must becenter tapped, and only the two phases oneither side of the center tap can be used. Thetwo used phases must each measure 120V toneutral.

Consult the transformer manufacturer’sliterature to verify that the single leg cansupply the required power.

Note: The Wall Connector’s contactor closesonly if it detects the presence of an earthground wire connected to a neutral point onthe transformer secondary.

L1

L2

GND

120V

120V

240V

L3 (NOT USED)

NEUTRAL(NOT USED)

Caution: The third line (L3 in theillustration) of the delta is 208V, withrespect to neutral, and is sometimesreferred to as a “stinger.” Do not use thisthird line.

Caution: Do not use a three-phase delta-connected transformer secondarywithout a center tap on one leg. Noneutral point is available for the requiredearth ground connection.

Determine the Circuit BreakerRequirements

To determine the type of upstream circuitbreaker you need, examine the distributionpanel or circuit breaker box to identify theamperage available at the installation site.

Planning Your Installation

Planning Your Installation 9

Page 12: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

The Wall Connector has an internal rotaryswitch that allows you to adjust its operatingcurrent (refer to Set the Operating Current onpage 21). The circuit breaker should be ratedfor the continuous current of: 12, 16, 20, 24, 28,32, 36, 40, 48, 56, 64, 72, or 80A.

Note: Refer to the circuit breaker currentratings specified on IEC 60898 when installingthe Wall Connector. If in doubt, check withyour local building electrical inspector.

Choose the Best Location for theWall Connector

Determine the parking location of the vehicleto ensure that the charge cable reaches thecharge port. The Wall Connector should belocated:

• In an enclosed garage, typically on thevehicle's charge port side.

• In a well-ventilated area. Avoid installationin an enclosed box, or adjacent to hotappliances.

• 4 ft (1.2 m) above the floor.• 8 in (190 mm) from any obstructions to

allow for cable looping.

Note: The Wall Connector is approved foroutdoor use, but it is not designed forcomplete immersion in liquid. Protection fromrain is recommended but not required.

Planning Your Installation

10

Page 13: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Installation Considerations

Three methods are available to install the Wall Connector. The location of the conduit determineswhich installation method to follow. If the conduit runs along the floor or low on the wall, use thebottom entry configuration. If the conduit comes from inside the wall, use the rear entryconfiguration. If the available conduit comes from the ceiling, use the top entry installation.

Note: Throughout the manual, “conduit” is used as the standard term for the protective tubingthat houses the service wiring. In regions where conduit is not used (Europe for example), a cablecomprised of service wiring enclosed in a protective jacket may be substituted for conduit ifallowed by local regulations.

Here are some additional guidelines:

• Conduit openings are sized for 1" (25 mm) conduit.• Conduit needs to meet all local regulations.• Use an appropriate circuit breaker.• To keep the housing weatherproof, use cable glands.• Use a UL approved conduit connector to ensure proper seal.

Bottom or Rear Entry

Planning Your Installation

Planning Your Installation 11

Page 14: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Top Entry

Planning Your Installation

12

Page 15: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

The shipping box contains parts for all installation methods, as well as this manual. If any parts aredamaged or missing, contact Tesla (refer to Questions? on page 28).

Note: Not shown is the supplied cardboard template.

1 2 3 4

5 6 7 8 9

10 11 12 13 14

Item Description (Quantity)

1 Wall Connector

2 Top entry bracket*

3 Low profile bracket **

4 Low profile bracket screws (2) **

5 Bottom or rear entry power conduit plug

6 Bottom or rear entry signal conduit plug

7 Top entry signal conduit plug*

8 Top entry power conduit plug*

9 Bottom conduit sealing gasket*

10 Top bracket-to-housing screw covers (2)

11 Bottom bracket-to-housing screw covers (2)

Check the Box Contents

Check the Box Contents 13

Page 16: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Item Description (Quantity)

12 Bottom bracket-to-housing screws (2)

13 Top bracket-to-housing screws (2)

14 Top entry bracket mounting screws (2)*

* Items used in only top entry installations.

** Items used in only bottom or rear entry installations.

Check the Box Contents

14

Page 17: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Tools and Materials Required

Before installing the Wall Connector, gather the following tools and materials:

• Pencil or marker

• Hole punch (optional, to push through cardboard template)

• Wire stripper

• Voltmeter or digital multimeter (to measure AC voltage at the installation site)

• Phillips screwdriver

• Small flathead screwdriver

• Large flathead screwdriver (optional, to remove plastic knock-outs)

• T20 security pin Torx driver

• T10 Torx driver

• M20 and M32 cable glands (also known as sealing hubs)

• Ferrules (the diameter of the ferrule depends on the diameter of the power wiring and the

construction)

• Wiring (use twisted pair communication cable 18AWG (Max diameter: 0.04 in (1.02 mm); Max

cross-sectional area: 0.03 in2 (0.82 mm2) for a maximum of 49 ft (15 m) between Wall

Connectors)

• Level

• Machine drill

• Torque driver (for terminal block connections)

Overview of Installation Steps

Warning: After you run service wiring to the installation site using metal flame retardantconduit, install the appropriate upstream circuit breaker, TURN OFF AND VERIFY POWER ISOFF BEFORE CONTINUING.

Then follow these steps to install the Wall Connector:

• Install the Low Profile Bracket for Rear or Bottom Entry Wiring on page 16• Install the Top Entry Bracket for Rear or Top Entry Wiring on page 17• Prepare for Installation on page 18• Connect the Wiring on page 19• Set the Operating Current on page 21• Secure the Cover and Power Up on page 22

Step-by-Step Installation Instructions

Step-by-Step Installation Instructions 15

Page 18: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Install the Low Profile Bracket forRear or Bottom Entry Wiring

Use the low profile bracket, shown below, towire the Wall Connector from the rear orbottom.

1. Use the low profile bracket as a guide tomark the location on the wall for themounting screws.

• Use a level to ensure that the marksare perfectly vertical.

• Space the holes 4.5" (114 mm) apart.

• For U.S.A. installations, position thebracket so that the Wall Connector islocated at a maximum of 60" (150 cm)from floor level. The minimum heightis 18" (45 cm) if mounting indoors,

and 48" (122 cm) if mountingoutdoors.

• If using the rear entry conduit, use atleast one set of the edge mountingholes so that the conduit does notinterfere with the wall stud.

• If using the bottom entry conduit, usethe two center mounting holes.

Note: Ensure that the minimum andmaximum height of the bracket is carefullyselected. It should be installed out of theway of any reasonably foreseeableimpacts.

2. Attach the bracket using fasteners thatare appropriate for the type of wallmaterial, drilling pilot holes if necessary.Use the supplied screws only if mountingthe bracket directly to a wooden stud. Ifmounting to another type of wall (hollow,masonry, etc.), use fasteners that are longenough to securely anchor the WallConnector and can hold at least 80 lb (36kg).

Step-by-Step Installation Instructions

16

Page 19: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Install the Top Entry Bracket forRear or Top Entry Wiring

The top entry bracket enables you to route theservice wiring into the Wall Connectorenclosure from the top of the enclosure, asshown below.

1. Use the cardboard template and a level asa guide to mark the location on the wallfor the mounting screws.

• Use a level to ensure that the marksare perfectly vertical.

• Space the holes 6.1" (155 mm) apart.• Position the bracket so that the Wall

Connector is located at a maximum of60" (150 cm) from floor level. Theminimum height is 18" (45 cm) ifmounting indoors, and 48" (122 cm) ifmounting outdoors.

Note: Ensure that the minimum andmaximum height of the bracket is carefullyselected. It should be installed out of theway of any reasonably foreseeableimpacts.

2. (Optional) There are two additionalmounting holes. To use these holes, use aflat-head screwdriver to knock-out theplastic that is closing the holes. Theseholes are spaced 2.75" (70 mm) apart.

3. Attach the bracket using fasteners thatare appropriate for the type of wallmaterial, drilling pilot holes if necessary.Use the supplied screws only if mountingthe bracket directly to a wooden stud. Ifmounting to another type of wall (hollow,masonry, etc.), use fasteners that are longenough to securely anchor the WallConnector and can hold at least 80 lb (36kg).

Step-by-Step Installation Instructions

Step-by-Step Installation Instructions 17

Page 20: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Prepare for Installation

Follow these instructions to remove the coverand route the service wiring into the WallConnector.

1. Use a T10 Torx driver to remove the screwat the bottom of the outer cover. Carefullydisengage the snaps on the sides and topusing a flathead screwdriver andcompletely remove the cover. Save thescrew and cover for reassembly.

2. Use a T20 security pin Torx driver toremove the six screws on the sealingcover. Carefully remove the sealing coverand disconnect the ribbon cable. Save thescrews and cover for reassembly.

Caution: Do not allow the sealingcover to hang from the ribbon cable.Doing so can damage the ribboncable or its connectors.

3. For top entry configuration, install thewiring to the terminal block in the topentry bracket as shown in Connect theWiring on page 19, then return to thissection and proceed to the next step. Forback or bottom entry configurations, skipto the next step.

4. Place and hold the Wall Connector on thebracket, ensuring that all four mountingtabs are properly aligned.

5. Use a T20 Torx driver to install the twotop housing mounting screws. Push thecosmetic screw covers into place.

6. Use a T20 Torx driver to install the twobottom housing mounting screws. Pushthe cosmetic screw covers into place.

Step-by-Step Installation Instructions

18

Page 21: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Connect the Wiring

Note: Consult with your local electrician orrefer to your local code for proper wire sizingappropriate for the currents in your WallConnector.

Note: It is the installer's responsibility toidentify whether additional grounding isrequired to ensure that local regulations aremet. Grounding must be installed at the powersource and not at the cable entry to the WallConnector.

Warning: Do not connect service wiringuntil you have read and fully understandthe concepts described in this section. Ifyou are uncertain about the type ofpower available at the service panel,consult an electrician, or contact Tesla forassistance.

1. Turn off the power.

Warning: RISK OF ELECTRIC SHOCK!Before continuing, use a voltmeter toensure the power is off by confirmingthat NO VOLTAGE is present at theservice wiring or terminals.

2. For top entry installation, pull the servicewiring into the top entry bracket or theWall Connector. Use a 1" (25 mm) cablegland to seal the power conduit or cable.For 80A operation, use 3AWG 167°F(75°C) rated copper wire or follow localregulations.

Note: The meaning of wiring colors mightvary from country to country. Follow allapplicable national and local regulationsconcerning wiring color codes.

The following illustration shows anexample of the wiring for the top entrybracket.

The following illustration shows anexample of the wiring for the low profilebracket.

3. Strip the service wires going to theterminal block on the top entry bracket3/4" (18 mm). Ferrules are recommended.

Note: For top entry installation, theflexible pre-installed wires that go fromthe top entry bracket to the housing arealready terminated and do not need to bestripped.

Step-by-Step Installation Instructions

Step-by-Step Installation Instructions 19

Page 22: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

4. Lead the preconnected service wires inthe main housing and connect thepreconnected service wires to the mainterminal block with L1 (or line), L2 (orneutral), and ground wires going to thelocations shown in the followingillustration.

Caution: Cut each of the wire strandsand insert them fully into each theterminal block.

Note: To ensure proper operation, verifythat neutral is connected to the neutralline inside the circuit breaker box or themain electrical panel.

5. Tighten the terminal block to therecommended torque:

• 35 in-lb (4.0 N-m) for the terminalblock on the top entry bracket.

• 33 in-lb (3.8 N-m) for the terminalblock in the main housing.

• 18 in-lb (2.0 N-m) for the groundterminal block in the main housing.

6. Check for miswiring using a multimeterand verify that there are no shorts beforeturning the upstream circuit breaker ON.

Step-by-Step Installation Instructions

20

Page 23: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Set the Operating Current

Follow these instructions to configure the DIPswitch. The following illustration shows anenlarged view of the DIP and rotary switches.

Warning: Power MUST remain OFF beforesetting or changing the DIP or rotaryswitches. Changing these switches withthe power ON will not be recognized bythe system and is dangerous due to therisk of electric shock.

1. Turn OFF power.2. Use a non-conductive object to adjust the

DIP switch settings:

• Switch Position 1:

• For a Line to Line connection(240V or less) set the DIP switchDOWN.

• For a Line to Neutral connection(greater than 240V) set the DIPswitch to UP (the ON position).

Warning: Before you set the DIPswitches, confirm which type ofinput service the utility provides.

• Switch Position 2:

• DIP Switch Position 2 shouldalways be set to UP.

Wiring/Connection DIP SwitchPosition

Line to Neutral(greater than250V)

Line to Line (240Vor less)

3. Set the rotary switch for the appropriatecurrent setting supported by your circuitbreaker. Typical circuit breaker ratings are:15A, 20A, 25A, 30A, 35A, 40A, 45A, 50A,60A, 70A, 80A, 90A, and 100A.

Use a small flathead screwdriver to adjustthe rotary switch to the appropriate circuitbreaker capability setting. Thecorresponding rotary switch settings forthe typical circuit breakers are shown inthe following table:

Step-by-Step Installation Instructions

Step-by-Step Installation Instructions 21

Page 24: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

RotarySwitchPosition

MaximumOutputCurrent

CircuitBreaker

0 Test mode N/A

1 12A 15A

2 16A 20A

3 20A 25A

4 24A 30A

5 28A 35A

6 32A 40A

7 36A 45A

8 40A 50A

9 48A 60A

A 56A 70A

B 64A 80A

C 72A 90A

D 80A 100A

E Not a validselection

N/A

F Followermode N/A

4. Reattach the ribbon cable to the sealingcover.

5. Reinstall the sealing cover. Use a T20security pin Torx driver to lightly securethe sealing cover by installing only the topscrew.

6. Turn ON power.7. If the installation is successful, the LEDs

briefly sequentially illuminate green with apattern that ends with the top green LEDstaying solid ON. If there is a solid orflashing red LED, refer to Troubleshootingon page 24 and resolve the error beforeyou continue.

Note: To review the pattern of blinkinglights, press and hold the RESET buttonfor 5 seconds.

8. Turn OFF power.9. Write the contact information of the

installer on the label on the inside of theWall Connector.

Secure the Cover and Power Up

1. Use a T20 security pin Torx driver toinstall the remaining screws on the sealingcover. Ensure that the cover is properlyaligned before tightening the screws to8.8 in-lb (1.0 N-m).

2. Attach the outer cover to the sealingcover starting with the latch at the top.Engage the snaps on the sides and alignthe mounting tab with the housing at thebottom.

3. Use a T10 Torx driver to install the screwthat secures the bottom of the outer coverto the housing. Tighten the screw to 4.4in-lb (0.5 N-m).

4. Close any unused openings with powerand signal conduit plugs.

Note: There should not be any visibleopenings to the inside of the WallConnector, and the Wall Connector shouldbe completely sealed from theenvironment.

5. Turn ON the power. The installation iscorrect if the LEDs go through a sequenceof flashing, ending with the top GreenLEDs staying solidly ON. If there is a solidor flashing Red LED, resolve the errorbefore you continue (refer toTroubleshooting on page 24).

Note: To review the pattern of blinkinglights, press and hold the Reset button for5 seconds.

6. Attempt to charge the vehicle to ensurethe Wall Connector is operating correctlyand charging at the selected operatingcurrent. For instructions on how to charge,

Step-by-Step Installation Instructions

22

Page 25: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

refer to the owner information providedwith the vehicle.

Step-by-Step Installation Instructions

Step-by-Step Installation Instructions 23

Page 26: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

GreenLights

YellowLight

Red Light Auto-Retry What it Means What to Do

Top lighton

Off Off Notapplicable

Power on. The WallConnector ispowered and instandby but notcharging thevehicle.

Not applicable.

Streaminglights

Off Off Notapplicable

The Wall Connectoris charging thevehicle.

Not applicable.

Streaminglights

1 flash Off Notapplicable

Charging current isreduced due to hightemperaturedetected in theVehicle Connector.

Make sure theconnector is fullyinserted into thecharge inlet in thevehicle's chargingport, is not covered byanything, and there isno heat source isnearby. If the problempersists in normalambient temperatures(under 100°F or38°C), contact Tesla.

Streaminglights

2 flashes Off Notapplicable

Charging current isreduced due to hightemperaturedetected in the wallplug or on the inputterminals to theWall Connector.

If the Wall Connectoris hard-wired, makesure it is not coveredby anything, and thereis no heat sourcenearby. If the problempersists in normalambient temperatures(under 100°F or38°C), contact Tesla.

Streaminglights

3 flashes Off Notapplicable

Charging current isreduced due to hightemperaturedetected inside theWall Connector.

Make sure the WallConnector is notcovered by anythingand there is no heatsource nearby. If theproblem persists innormal ambienttemperatures (under100°F or 38°C),contact Tesla.

Troubleshooting

24

Page 27: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

GreenLights

YellowLight

Red Light Auto-Retry What it Means What to Do

Off Off 1 flash After 15minutes andup to 4times

Groundfault. Current isleaking through anunsafe path.Possible Line toground or Neutralto ground fault.

Try again bydisconnecting theWall Connector fromthe vehicle andreconnecting. If theproblem persists, turnOFF the circuitbreaker servicing theWall Connector, wait10 seconds, turn thecircuit breaker ONagain, then tryreconnecting the WallConnector to thevehicle. If the problempersists, contact Tesla.

Off Off 2 flashes After 1minute andup to 4times

No groundconnectiondetected in the WallConnector.

Make sure the WallConnector is properlygrounded. If uncertain,consult yourelectrician to ensureproper grounding atyour circuit breaker orpower distributionbox and thatappropriateconnections are madeto the Wall Connector.

Off Off 3 flashes No Input miswired:possibly Line andNeutral areswapped.

The wiring betweenthe wall power andthe Wall Connectorhas been incorrectlyinstalled. Consult yourelectrician.

Off Off 4 flashes After 1minute andup to 4times

Over or undervoltage protection.

Consult yourelectrician to ensureappropriate voltageon the circuit breakerthat services the WallConnector.

Troubleshooting

Troubleshooting 25

Page 28: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

GreenLights

YellowLight

Red Light Auto-Retry What it Means What to Do

Off Off 5 flashes After 1minute retry(no limit onretries)

Over currentprotection.

Reduce the vehicle'scharge currentsetting. If the problempersists and theattached vehicle ismanufactured byTesla, contact Tesla. Ifthe problem persistsand If the attachedvehicle is notmanufactured byTesla, contact theoriginal manufacturer.

Off Off 6 flashes After 1minute retry(no limit onretries)

A communicationerror occurredbetween the WallConnector and thevehicle.

Try again bydisconnecting theWall Connector fromthe vehicle andreconnecting. Ifpossible, plug thevehicle into anotherWall Connector or aMobile Connector todetermine if thevehicle is able tocommunicate withother chargingequipment. If theproblem persists,contact Tesla.

Top lighton

Off 1 flash No Over temperatureprotection (latch-off)

Make sure the WallConnector, vehicleconnectors, and wallplug (if used) are notcovered by anythingand there is no heatsource nearby. If theproblem persists innormal ambienttemperatures (under100°F or 38°C),contact Tesla.

Top lighton

Off 2 flashes No Non-Tesla vehicleattemptingconnection to non-compatible inputdistribution.

Compatible inputdistributions are:single-phasedistribution or 400V,three-phasedistribution.

Top lighton

Off 3 flashes No Incorrect rotaryswitch setting.

Consult yourelectrician.

Troubleshooting

26

Page 29: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

GreenLights

YellowLight

Red Light Auto-Retry What it Means What to Do

Top lighton

Off 4 flashes NotApplicable

Circuit Breaker Sharing Network: More than one Wall Connector is set to Leader.

Only one Wall Connector can be set to a leader configuration. All other linked Wall Connectors must be set to follower (position F). Set one of the Wall Connectors to Follower.

Top lighton

Off 5 flashes NotApplicable

Circuit Breaker Sharing Network: More than three Wall Connectors are set to Follower.

Move one or moreWall Connectors to adifferent circuit anddisconnect it from thisCircuit BreakerSharing Network.

Top lighton

Off 6 flashes NotApplicable

Circuit BreakerSharing Network:The networked WallConnectors havedifferent maximumcurrent capabilities.

Contact Tesla.

Off Off Solid red No Wall Connectorhardware failure.Possible failuresinclude thefollowing:

• Contactor failed• Self test failed

in CCIDcircuitry

• Other possiblehardwarefailures mightbe MCU,3V3output, orthe thermalsensor.

Contact Tesla.

Reset

If a fault causes a RED error light to illuminate or flash and the fault condition is corrected, you useRESET the Wall Connector to resume normal operation. There are two ways to REST the WallConnector:

• Press the RESET button for two to three seconds until the top lights changes from RED toGREEN. This clears the fault message but does not reboot the Wall Connector.

• In a rare situation, you might need to force the Wall Connector to reboot without recycling theinput power. Hold the RESET button for five seconds. When the top light changes from REDto GREEN, release the RESET button. The top light should continue to illuminate GREEN. If thelight returns to flashing RED, the fault state has not been corrected.

Troubleshooting

Troubleshooting 27

Page 30: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Questions?

• United States and Canada:

[email protected]• +1-650-681-6133

Troubleshooting

28

Page 31: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

1. Turn OFF power.

Warning: RISK OF ELECTRIC SHOCK!Before continuing, use a voltmeter toensure the power is off by confirmingthat NO VOLTAGE is present at theservice wiring or terminals.

2. Use a non-conductive object to adjust theDIP switches to the appropriate gridsetting and circuit breaker sharing setting(refer to Set the Operating Current onpage 21).

3. Use a small flathead screwdriver to set therotary switch to position "0" to put theWall Connector into Test Mode.

Warning: Power MUST remain OFFbefore setting or changing the DIP orrotary switches. Changing theseswitches with the power ON will notbe recognized by the system and isdangerous due to the risk of electricshock.

4. Reattach the ribbon cable to the sealingcover.

5. Use a T20 security pin Torx driver tolightly secure the sealing cover byinstalling only the top screw.

6. Turn ON the circuit breaker.7. Watch for any Red LEDs to be ON after a

sequence of LED display; if so, there is afault in the installation.

8. Listen for the click of a contactor or relayclosing and opening.

9. Watch for Green streaming LEDs (for 5seconds).

LEDs will revert to top Green LED ON andRed LEDs flashing (3 times).

Note: To review the pattern of blinkinglights, press and hold the Reset button for5 seconds.

10. Turn OFF the circuit breaker.11. Remove the sealing cover screw, sealing

cover. Disconnect the ribbon cable.

Caution: Do not allow the sealingcover to hang from the ribbon cable.Doing so can damage the ribboncable or its connectors.

12. Reposition the rotary switch to theappropriate setting (refer to Set theOperating Current on page 21).

13. Reattach the ribbon cable to the sealingcover.

14. Replace all the screws and reinstall theouter cover (refer to Secure the Cover andPower Up on page 22).

Appendix A: Testing for Proper Operation

Appendix A: Testing for Proper Operation 29

Page 32: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

The Wall Connector includes an automaticload management feature whereby WallConnector to Wall Connector communicationallows you to split the maximum available loadover a maximum of 4 Wall Connectors. Thewire used for this local network must:

• Share the main power cable conduit or behoused in a separate conduit. In otherwords, the high voltage wires must bebranched to a junction box from eachindividual unit.

• Be at least 18 AWG, 2 conductor, shielded,twisted-pair wire.

Warning: When load sharing, high voltage(L1, L2, Neutral, Earth) cabling must bespliced in a separate NEMA ratedenclosure.

Note: Take additional precautions intoconsideration to prevent water ingress at theWall Connectors when installing themoutdoors.

Note: Consult with an electrician to ensurethat the installation meets local regulations.

Daisy Chaining Multiple WallConnectors

Each Wall Connector has one terminal blockdedicated for the communication wiring asshown below. The left hand side of theterminal block is the input terminal and theright hand side the output terminal.

1. Form a daisy-chained network by connecting the cables from OUT to IN and always from positive to positive and negative to negative between each of the participating Wall Connectors (refer to Example of the Communication Wiring on page 31).

• The signal wires between each Wall Connector should run in signal conduit. Use a 1/2" (13 mm) UL approved conduit hub to seal the signal conduit opening.

• If the signal wire is routed in the power conduit with the power wires, the insulation rating of the signal wire should be equal to or greater than that of the power wires.

• The maximum distance between Wall Connectors is 49 ft (15 m).

2. Set one Wall Connector as the leader by setting the Rotary Switch Position from 1 through D, depending on the maximum available output current. Set up to 3 Wall Connectors as followers by setting the Rotary Switch Positions to F. In the load sharing network, only one unit can be designated

Appendix B: Optional Connection for Load Sharing

30

Page 33: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

as the leader (refer to Set the Operating Current on page 21).

3. Confirm that the load sharing network isproperly installed by observing the LEDindicators in the Wall Connector. Whenstarting up the circuit breaker for the firsttime, green lights turning ON for 5seconds indicate a proper installation. Thefinal display is:

GreenLights

YellowLight

RedLight

What itMeans...

On (topandbottom)

Off Off Leaderunit

On(bottom)

Off Off Followerunit

Example of the Communication Wiring

Wall Connector 1LEADER

Wall Connector 2FOLLOWER

Wall Connector 3FOLLOWER

Wall Connector 4FOLLOWER

8

Rotary Switch

D+ D- D+ D-In Out

FRotary Switch

D+ D- D+ D-In Out

FRotary Switch

D+ D- D+ D-In Out

FRotary Switch

D+ D- D+ D-In Out

Other Load Sharing Behaviors

• Available current is redistributed equally among all connected vehicles whenever a new vehicle is plugged or unplugged from the network.

• During steady-state operation, the load sharing network toggles available current to each vehicle in 2A increments, every minute, to asses vehicle need. When a battery approaches full charge, the power consumption will taper until charging is complete. If the leader unit detects that a vehicle is no longer using all of its available current, it will reduce the current allocated to that vehicle

• A follower Wall Connector will not charge if communication is lost with the leader Wall Connector.

• In rare cases, firmware updates on a leader Wall Connector will interrupt charging on the follower Wall Connector(s). This is normal behavior, and charging should resume once the firmware update is complete (15 minutes).

Appendix B: Optional Connection for Load Sharing

Appendix B: Optional Connection for LoadSharing

31

Page 34: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Bbottom or rear entry

configurations, dimensions and spacing 11example of the service wiring 19installing the low profile bracket for 16

Ccardboard template, using the 16cautions 3check the box contents 13circuit breaker

corresponding rotary switch settings 21requirements 9

circuit ratings, optional 6communications regulations 2conduit, about 11connect the wiring 19copyrights 2cover

removing the outer 18removing the sealing 18securing the outer 22

Ddimensions 5DIP switches, configuring 21documentation errors, sending feedback 2

Ffeatures

circuit ratings, optional 6load sharing 6recovery from power outages 6self-monitoring and recovery 6

Iinstallation

for rear or bottom entry wiring 16for top entry wiring 17information, about 2planning your 7preparing for 18tools and materials required 15torque recommendations 19

installation overview 15installation, testing 29

Llights, diagnostic 6lights, LED 24load sharing

about 6configuring the DIP and rotary switches21example of the communication wiring 31

low profile bracketinstalling the 16

Mminimum requirements 7

Nnotes 4

Pplanning your installation

circuit breaker requirements 9location of the wall connectors 10minimum requirements 7service wiring 7types of installations 11

power outages, recovery from 6power ratings 5power up 22product specifications 2

Rremoving the outer cover 18reset button 6, 27, 29rotary switches, configuring 21

Ssafety instructions 3, 4securing the outer cover 22self-monitoring and recovery 6service wiring 7, 19set the operating current 21specifications

dimensions 5power ratings 5temperature limits 5

Index

32

Page 35: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL

Ttemperature limits 5terminal blocks

connecting the service wiring to the 19torque recommendations 19

Tesla, contacting 28testing for proper operation 29top entry

bracket, installing the 17configurations, dimension and spacing 11example of the service wiring 19wiring, installing the top entry bracket for17

trademarks 2troubleshooting 24, 27, 28, 30

Wwall connectors

checking the box contents 13connecting the terminal blocks 30daisy chaining 30example of the communication wiring 31location of 10optional configuration 30power up 22reset 27, 29troubleshooting 30

warnings 3wiring for load sharing 30

Index

Index 33

Page 36: WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL