Voltage Stability
Manu Parashar, Vijay Sukhavasi (Alstom)
Dino Lelic, Guorui Zhang (Quanta Technology)
Ron Markham, Vahid Madani (PG&E)
WECC JSIS Meeting
Salt Lake City, June 12th, 2013
Copyright ALSTOM Grid
EMS & Online-DSA Applications
VSAT
CA
RAS
A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach
Real-Time Voltage Instability Indicator (RVII) Detect WHEN in danger!
PMU measurements
Estimate equivalent parameters in real-time
PMUs Real-Time Voltage Instability Indicator (RVII)
Predict HOW to respond….
Bus Voltage (V) Equivalent Impedance (Zeq) Reactive Margin (Qmargin)
Predict Qmargin changes under “worst case” contingency.
Provide recommendations on corrective actions.
MEAS
UREM
ENT-B
ASED
MO
DEL-B
ASDE
D
Measurement-based voltage stability monitoring applicable to the following scenarios:
- Bus (with measurements at the local bus)
- Corridor (with measurements at both ends
- Load Center (with measurements on all tie lines)
Real-Time Voltage Instability Indicator (RVII)
Copyright ALSTOM Grid
Bus
Corridor
Load Center
Validating RVII at PG&E’s Proof-of-Concept (PoC) lab
Impact of PMU observability on tracking Qmargin using RVII: - CASE 1: PMUs at both sending & receiving ends (--)
- CASE 2: PMU at sending end only (--).
- CASE 3: PMU at receiving end only (--).
Consistent results!
RVII Engineering User Interface (UI)
Monitored Corridors
Monitored Busses
Real Time PQ Curve and P,Q Operating Point
Real Time Voltage(kV)
Real Time Equivalent Impedance and Load Impedance(p.u)
Real Time Active Power(MW)
Real Time Reactive Power(MVAR)
Input Frame Rate Display Duration
Monitored Bus or Corridor Status/Alarms
Historical Data Settings
Copyright ALSTOM Grid
Real Time Chart Display
Real Time Bus and Corridor Status Monitor
Real Time Status/Alarms Status bar
Copyright ALSTOM Grid
Other Functionalities
Sub Second Zoom
Cursor Point Display
Comprehensive Voltage Stability Alarms Linking WAMS “Wide-Area” Low Voltage Alarms to Operator Guides in EMS
PMU Voltage Stability Indicators
WAMS indicate the simultaneous occurrence of Low Voltage over a broad region.
AND
Operator Guides in EMS
Reactive Reserve Monitoring in EMS Decision making: Operator Guides (e.g. “Switch On Capacitor Banks”). Arm Special Protection Schemes
Reactive Reserve (MVAR) monitoring for user-defined areas in EMS.
Detect WHEN to Take Action... and HOW to Respond!
Voltage Stability Assessment in e-terravision Voltage Contours, MW Margins, Weak Elements, Remedial Actions
Identify weak elements (i.e. regions most
prone
to voltage instability)
MW Transfer Margins
Control
Recommendations