Voltage Stability

Manu Parashar, Vijay Sukhavasi (Alstom)

Dino Lelic, Guorui Zhang (Quanta Technology)

Ron Markham, Vahid Madani (PG&E)

WECC JSIS Meeting

Salt Lake City, June 12th, 2013

Copyright ALSTOM Grid

Page 2: Voltage Stability - WECC · A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach Real-Time Voltage Instability Indicator

EMS & Online-DSA Applications

VSAT

CA

RAS

A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach

Real-Time Voltage Instability Indicator (RVII) Detect WHEN in danger!

PMU measurements

Estimate equivalent parameters in real-time

PMUs Real-Time Voltage Instability Indicator (RVII)

Predict HOW to respond….

Bus Voltage (V) Equivalent Impedance (Zeq) Reactive Margin (Qmargin)

Predict Qmargin changes under “worst case” contingency.

Provide recommendations on corrective actions.

MEAS

UREM

ENT-B

ASED

MO

DEL-B

ASDE

D

Page 3: Voltage Stability - WECC · A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach Real-Time Voltage Instability Indicator

Measurement-based voltage stability monitoring applicable to the following scenarios:

- Bus (with measurements at the local bus)

- Corridor (with measurements at both ends

- Load Center (with measurements on all tie lines)

Real-Time Voltage Instability Indicator (RVII)

Copyright ALSTOM Grid

Bus

Corridor

Load Center

Presenter
Presentation Notes
Remove Load Center?? -RVII contains only two types of classification in the present implementation Bus and Corridor
Page 4: Voltage Stability - WECC · A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach Real-Time Voltage Instability Indicator

Validating RVII at PG&E’s Proof-of-Concept (PoC) lab

Impact of PMU observability on tracking Qmargin using RVII: - CASE 1: PMUs at both sending & receiving ends (--)

- CASE 2: PMU at sending end only (--).

- CASE 3: PMU at receiving end only (--).

Consistent results!

Presenter
Presentation Notes
-Remove Slide??
Page 5: Voltage Stability - WECC · A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach Real-Time Voltage Instability Indicator

RVII Engineering User Interface (UI)

Monitored Corridors

Monitored Busses

Real Time PQ Curve and P,Q Operating Point

Real Time Voltage(kV)

Real Time Equivalent Impedance and Load Impedance(p.u)

Real Time Active Power(MW)

Real Time Reactive Power(MVAR)

Input Frame Rate Display Duration

Monitored Bus or Corridor Status/Alarms

Historical Data Settings

Page 6: Voltage Stability - WECC · A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach Real-Time Voltage Instability Indicator

Copyright ALSTOM Grid

Real Time Chart Display

Presenter
Presentation Notes
-Treeview Select: Multiple signals can be displayed at a time
Page 7: Voltage Stability - WECC · A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach Real-Time Voltage Instability Indicator

Real Time Bus and Corridor Status Monitor

Real Time Status/Alarms Status bar

Presenter
Presentation Notes
Status Bar changes color when atleast one of the Busses/Corridor monitored raises alarms
Page 8: Voltage Stability - WECC · A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach Real-Time Voltage Instability Indicator

Copyright ALSTOM Grid

Other Functionalities

Sub Second Zoom

Cursor Point Display

Presenter
Presentation Notes
Deep level zoom
Page 9: Voltage Stability - WECC · A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach Real-Time Voltage Instability Indicator

Comprehensive Voltage Stability Alarms Linking WAMS “Wide-Area” Low Voltage Alarms to Operator Guides in EMS

PMU Voltage Stability Indicators

WAMS indicate the simultaneous occurrence of Low Voltage over a broad region.

AND

Operator Guides in EMS

Reactive Reserve Monitoring in EMS Decision making: Operator Guides (e.g. “Switch On Capacitor Banks”). Arm Special Protection Schemes

Reactive Reserve (MVAR) monitoring for user-defined areas in EMS.

Detect WHEN to Take Action... and HOW to Respond!

Page 10: Voltage Stability - WECC · A Hybrid Approach to Voltage Stability Assessment An integrated “measurement-based” and “model-based “ approach Real-Time Voltage Instability Indicator

Voltage Stability Assessment in e-terravision Voltage Contours, MW Margins, Weak Elements, Remedial Actions

Identify weak elements (i.e. regions most

prone

to voltage instability)

MW Transfer Margins

Control

Recommendations