This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way imply IEEE endorsement of any of Helsinki University of Technology's products or services. Internal or personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution must be obtained from the IEEE by writing to [email protected]. By choosing to view this document, you agree to all provisions of the copyright laws protecting it.

Voltage Sag Analysis Taken Into Account In

Embed Size (px)

DESCRIPTION

Voltage Sag Analysis Taken Into Account InDistribution Network Design

Citation preview

  • This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way imply IEEE endorsement of any of Helsinki University of Technology's products or services. Internal or personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution must be obtained from the IEEE by writing to [email protected]. By choosing to view this document, you agree to all provisions of the copyright laws protecting it.

  • PUBLICATION I

    2001 IEEE. Reprinted, with permission, from the publisher

    Heine, P., Lehtonen, M., Lakervi E., Voltage Sag Analysis Taken into Account in Distribution Network Design, 2001 IEEE Porto PowerTech2001, Porto, Portugal, September 10-13, 2001, Volume III, Paper PSP-222, 6 p.

  • Voltage Sag Analysis Taken Into Account InDistribution Network Design

    P. Heine, M. Lehtonen and E. Lakervi,

    !"#!$%&

    '

    (

    ) )*

    I. INTRODUCTION

    A voltage sag is a sudden reduction in the supply voltagemagnitude followed by a voltage recovery after a shortperiod of time. Voltage sags are mainly caused by shortcircuits, overloads and starting of large motors. The im-portance of voltage sags has increased due to problemssags cause to many types of equipment. To be able to esti-mate the damage voltage sags cause to customers also newtools and analysis programs are needed.

    Network information systems (AM/FM-GIS) (Auto-mated Mapping/Facilities Management Geographic In-formation System) are widely used in power distributioncompanies. These systems include tools for case-specificsteady state analysis for different purposes, e.g. programsfor load flow calculations, fault current analysis, loadgrowth estimation and reliability analysis. Also voltage saganalysis could be included in this list of programs.

    This paper presents typical voltage sag distributions cal-culated for Finnish rural and urban networks. Voltage sagspropagate throughout the power system and a sag sensitivecustomer can experience sags caused by faults at the same,higher or lower voltage levels. In this paper the main inter-est is distribution companies and their possibilities in de-creasing the impact of voltage sags. Thus only voltage sagscaused by short circuit faults on MV radially operated net-works and experienced by LV customers are studied.

    Network characteristics have influence on voltage sagdistribution. In this paper it is shown that while one in-vestment may be justified e.g. in the sense of reliability thesame investment may worsen the situation related to volt-age sags. This is one basis to include sag analysis in net-work information systems. The platform used for network

    planning in power distribution companies and includingvoltage sag analysis is presented.

    II. SAGS IN MV SYSTEMS

    In power systems having isolated neutral voltage sagsare mainly caused by short circuit faults. A short circuitfault on one radially operated distribution feeder causes asagged voltage on the substation busbar. This sagged volt-age is further experienced by all the customers supplied bythe same HV/MV transformer.

    To explain voltage sag characteristics a voltage dividermodel is often used, (1).

    .1.0p.u*ZZ

    ZU

    FS

    Fsag +

    = (1)

    where Usag is the remaining voltage during the sag, ZF theimpedance of the feeder from the substation to the faultplace including the fault impedance, ZS the impedance ofthe fault current path on the source side of the PCC (pointof common coupling) [1], [2].

    Fig. 1. Voltage divider model.

    In this model load currents were neglected. The modelcan be used for the calculation of symmetrical three phasefaults. In a case of unsymmetrical faults e.g. the calculationof symmetrical components should be included.

    Not all fault types cause voltage sags. E.g. in neutralisolated or coil earthed medium voltage networks singlephase to ground faults do not cause any voltage sags at thelow voltage customer location.

    It is also important to estimate how often customers ex-perience sags. This estimation requires a probabilistic ap-proach and network reliability data. The fault frequencyrates of network components are combined with the saganalysis results [1], [2]. As a result a sag distribution (sagmagnitude, duration, frequency) can be determined foreach customer. Often a cumulative sag frequency of sags

    ZS

    ZF

    faultcustomer

    USag

    Power Systems Unit

  • having remaining voltage below a threshold magnitude andlasting longer than a threshold duration is of interest.

    III. VOLTAGE SAG DISTRIBUTION OF RURALAND URBAN COMPANIES

    Rural and urban networks have their typical networkcharacteristics which further contribute typical characteris-tics of rural and urban voltage sag distributions. Below isdiscussed the effects of network characteristics on sag dis-tribution caused by faults on the neighbouring MV feedersof the sag sensitive customer. Sags are less harmful if theremaining voltage during the sag is higher and if the sagfrequency is lower.

    Compared to rural areas urban areas have typicallyhigher loading, more looped and stronger transmissionsystem and larger transformers at HV/MV substation.Stronger source and larger transformers mean higher re-maining voltage during a sag, (1).

    Urban networks consist typically of underground cableshaving larger cross sections than rural overhead line net-works. Larger cross section means smaller line impedanceand thus lower remaining voltage during the sag, (1). Onthe other hand the lower fault frequency of undergroundcables means less faults and sags.

    Urban HV/MV substations have more feeders per sub-station than rural ones. The more adjacent feeders the sagsensitive customer has the more feeder length is exposed tofaults that cause the most severe voltage sags.

    Feeder lengths are in urban areas typically shorter (

  • IV. DISTRIBUTION DESIGN AND VOLTAGE SAGS

    Traditionally the network information systems (AM/FM-GIS) used in power distribution companies do not includetools for sag analysis although a lot of data is available forsuch calculation. To be able to serve the increasing numberof sag sensitive customers distribution companies shouldhave tools also for voltage sag analysis. While voltage saganalysis may suggest network solutions that are not accept-able from another point of view, voltage sag analysis must

    not be kept as a separate analysis but included as one toolamong the other network planning and operation tools, e.g.load flow, fault current and reliability analysis.

    Traditionally one aim of network design and operation isto minimise the impact of interruptions to customers. Un-derground cable networks seem to be superior compared tooverhead line networks because of their lower fault fre-

    05

    10152025303540

    10 20 30 40 50 60 70 80 90

    Sag magnitude (%)

    Sag

    frequ

    ency

    (1/a

    )

    01020304050607080

    10 20 30 40 50 60 70 80 90

    Sag magnitude (%)

    Sag

    frequ

    ency

    (1/a

    )

    05

    10152025303540

    10 20 30 40 50 60 70 80 90

    Sag magnitude (%)

    Sag

    frequ

    ency

    (1/a

    )

    05

    10152025303540

    10 20 30 40 50 60 70 80 90

    Sag magnitude (%)

    Sag

    frequ

    ency

    (1/a

    )

    0.000.050.100.150.200.250.300.350.40

    10 20 30 40 50 60 70 80 90

    Sag magnitude (%)

    Sag

    frequ

    ency

    (1/a

    )

    0.000.050.100.150.200.250.300.350.40

    10 20 30 40 50 60 70 80 90

    Sag magnitude (%)

    Sag

    frequ

    ency

    (1/a

    )

    Fig. 2. Sag frequency of rural company R1.

    Fig. 4. Sag frequency of rural company R3.

    Fig. 6. Sag frequency of urban company U1. Fig. 7. Sag frequency of urban company U2.

    Fig. 3. Sag frequency of rural company R2.

    Fig. 5. Sag frequency of rural company R4.

  • quency. When having sag sensitive customers in mixedunderground cable and overhead line networks the way ofthinking is no more this straightforward. The aim of de-creasing interruptions and voltage sags can bring compet-ing aspects to network design.

    Underground cable networks have compared to overheadline networks lower fault frequency. Less faults mean less interrup-

    tions and voltage sags. larger cross sections. Larger cross sections mean lower

    remaining voltage during a sag. In addition the area ofvulnerability is wider in underground cable networks.

    Three cases of mixed networks were analysed: half of the overhead line main feeder (the half closer

    to the PCC) is replaced by underground cable+ the whole overhead line main feeder is replaced by

    an underground cable, all the overhead line laterals are replaced by under-

    ground cables.

    Fig. 8. MV feeder.

    It was assumed that the fault frequency of undergroundcable networks is 10% of the fault frequency of overheadline networks.

    The results are presented compared to results of ruralcompanies performed in previous Chapter III. The percen-tual changes in interruptions and sag frequencies Usag

  • In a case of main feeder of an underground cable (Fig. 9:A, B) the sag frequency of the most severe sags is de-creased because the lower fault frequency of undergroundcable. A special attention should be paid to a result that thearea of vulnerability of sags 30%
  • The result of voltage sag analysis offers the economicimpact of sags to be included into a technical and economicoptimisation problem of distribution network design. Inthat the long term total costs including costs of invest-ments, losses, outages and poor power quality is minimisedwithin relevant constraints.

    V. CONCLUSIONS

    Voltage sag distributions were calculated for four ruraland two urban Finnish distribution companies. Urban cus-tomers seem to experience less sags compared to ruralcustomers the main reason being the shorter total feederlength of urban underground cable networks. Urban sagdistributions lack the shallowest less severe sags, on theopposite in rural systems the share of the shallowest sags isremarkably higher than the share of the most severe sags.In addition in rural networks the feeder length may be solong that part of it can be neglected in sag analysis. As wellin urban as rural systems the feeder branches can have aremarkable effect on voltage sag distribution.

    It was shown that while the replacement of an overheadline with an underground cable means typically a decreaseof interruptions it might in mixed networks mean an in-crease in sag frequency. Especially investments in theneighbourhood of PCC need a separate sag analysis to beperformed to avoid unexpected impacts to sag sensitivecustomers.

    Voltage sag analysis should be linked as a part of com-prehensive network design. Almost all the data needed insag analysis is already available in network and customerdata base. The sag analysis needs further research of dif-ferent fault types and more understanding about the sagsensitive equipment and the economic impact of voltagesags.

    VI. REFERENCES

    [1] M. H. J. Bollen, 8QGHUVWDQGLQJ SRZHU TXDOLW\ SUREOHPV 9ROWDJHVDJVDQGLQWHUUXSWLRQV New Jersey, USA: IEEE Press, 1999, 541 p.

    [2] ,(((*ROG%RRN,(((5HFRPPHQGHG3UDFWLFHIRU'HVLJQRI5HOLDEOH,QGXVWULDODQG&RPPHUFLDO3RZHU6\VWHPV New York, USA:IEEE, 1998, 504 p.

    [3] M. Lehtonen, S. Krkkinen and J. Partanen, Kokonaisvaltainenshklaitosautomaatiokonsepti Suomessa (Future distributionautomation system for Finnish utilities), Valtion teknillinen tut-

    kimuskeskus, VTT Tiedotteita Meddelanden Research Notes1621, Espoo, 1995, 68 p. + App. 35 p. (in Finnish)

    [4] P. Heine, P. Pohjanheimo, M. Lehtonen and E. Lakervi, Estimat-ing the annual frequency and cost of voltage sags for customers offive Finnish distribution companies, &,5(' , June 18-21,2001, Amsterdam, Netherlands, Technical Theme 2 Power qual-ity and EMC, Paper 2.25, 5 p.

    [5] R. C. Degeneff, R. Barss and S. Ready, Reducing the effect ofsags and monentary interruptions: A total owning cost prospective,,&+43, October, 1-4, 2000, Orlando, Florida, pp. 397413.

    [6] S.-H. Yun, O. Hwan, J. C. Kim and S. J. Rim, An enhancedmethod for assessing the effect of voltage sag in power distributionsystem, ,(((3(66XPPHU0HHWLQJ, July 18-22, Edmonton,Alberta, Canada, Vol. 1, pp. 518523.

    [7] R. Lamedica, A. Patrizio, A. Prudenzi, E. Tironi and D. Zaninelli,Power quality costs and upgrading solutions: the energy centre,,&+43, October, 1-4, 2000, Orlando, Florida, pp. 691696.

    VII. BIOGRAPHIES

    3LUMR +HLQH was born in Rauma on August 29,1963. She received the Master of Science degreefrom Tampere University of Technology in 1987.Now she is a researcher at the Power SystemsLaboratory of Helsinki University of Technology.Her main interests are in power quality issues ofdistribution networks.

    0DWWL/HKWRQHQ (1959) has been with VTT En-ergy, Espoo, Finland since 1987 and since 1999with Helsinki University of Technology. MattiLehtonen received his Masters and Licenciatedegrees from Helsinki University of Technology,in 1984 and 1989 respectively, and the Doctor ofTechnology degree from Tampere University ofTechnology in 1992. The main activities of Dr.Lehtonen include earth fault problems, harmonicrelated issues and applications of informationtechnology in distribution automation and energymanagement.

    (UNNL /DNHUYL was born in Helsinki on March26, 1945. He received the Master of Sciencedegree from Helsinki University of Technologyin 1969 and the Dr.Tech. degree from TampereUniversity of Technology in 1984. In the 1970she headed the general planning and hydro gen-eration departments in two Finnish utilities. From1976 to 1997 he was an associate professor andprofessor at the Power Engineering Group ofTampere University of Technology. He is nowprofessor at Power Systems Laboratory of Hel-sinki University of Technology.