Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
VOLTAGE LIMIT CONTROL OF MODULAR MULTILEVEL
CONVERTER BASED UNIFIED POWER FLOW
CONTROLLER UNDER UNBALANCED GRID CONDITIONS
SK NAWAAZ 1, B. MADHAVA2
K. SRINIVAS 3
1PG Student, Dept of EEE, SSN Engineering College, Ongole, AP, India.
2Assistant Professor, Dept of EEE, SSN Engineering College, Ongole, AP, India.
3Associate Professor & HOD, Dept of EEE, SSN Engineering College, Ongole, AP, India
Abstract— The modular multilevel converter
(MMC) is being developed as a core technology for
the next generation of high-power, voltage source
converters (VSCs). Voltage fluctuation and power
losses in the distribution line are problems in
distribution networks. The modular multilevel
converter-based unified power flow controller
(MMC-UPFC) is able to operate under unbalanced
grid conditions with symmetric component
decoupling. However, the constraint of the voltage
limit of UPFC is not considered and no protection
schemes are investigated to protect the UPFC from
over modulation under unbalanced grid conditions.
To solve this problem, this project proposes the
cascaded control scheme for MMC-UPFC based on
voltage limit control and symmetric component
decoupling to balance the ac current of the
transmission line.
The Modular Multilevel Converter
(MMC) is an emerging power converter technology
that has caught widespread attention mainly
because of several technical and economic benefits
such as modular realization, easy scalability, low
total harmonic distortion, fail-safe operations etc.
With appropriate transformer connections for
MMC-UPFC, the negative- and zero-sequence
currents are suppressed by the corresponding inner
current loops. Considering the voltage limit of
MMC, the operating ranges of UPFC-MMC under
balanced and unbalanced grid conditions are
investigated in different control strategy methods.
Finally, the final cascaded control structure is
constructed. The simulation results obtained in
MATLAB/SIMULINK are provided to validate the
effectiveness and robust performance of the
proposed control strategies.
I. INTRODUCTION
Environmental constraints limit the
expansion of transmission networks and generation
near load centres. This has a negative influence on
power system voltage stability. Simultaneous
growth in the use of electrical power without a
corresponding increase of transmission capacity
has bought many power systems closer to their
voltage stability limit. Voltage stability is
concerned with the ability of a power system to
maintain acceptable voltages at all buses under
normal conditions and after being subjected to a
disturbance. The assessment of voltage stability has
become more complicated due to the complexity of
power systems. For example, voltages do not
indicate the proximity to voltage collapse points in
heavily compensated systems even in heavy
loading conditions. The main cause of voltage
collapse affecting the power system is faults on the
power system, often resulting from weather
conditions, e.g. lightning, wind, and ice hitting
overhead lines. On underground cables, typically
used in urban areas, insulation problems and the
operation of excavators are the main causes of
voltage interruptions. The conventional voltage
source converter (VSC) based UPFC is limited to
its poor output waveform, and is difficult to extend
due to the limited voltage and current ratings of
switching devices.
In the latter case, the ac currents of
transmission line are not balanced and therefore the
spread of ac fault cannot be inhibited. So far, the
constraints of the voltage limit of UPFC are not
considered and thus no effective protection
schemes are investigated to protect the vulnerable
switches of UPFC from various unbalanced grid
conditions. The general concept of unbalanced grid
conditions includes the following scenarios: ac
voltage unbalance caused by faults, asymmetrical
transmission lines and load imbalance. Instead of
the local control for MMC, the focus of the
analysis on the power flow under unbalanced grid
conditions considering the voltage limit constraint
of UPFC. The novelty of this project is: 1)
choosing appropriate transformer connection
scheme for MMC-UPFC considering the third
order magnetizing currents (TOMC) and zero-
sequence currents (ZSC); 2) investigating the
operating range of MMC-UPFC under the
proposed control scheme by mathematical
derivation and point scanning approaches; 3)
presenting the voltage limit control and
constructing the cascaded control structure to
protect MMC-UPFC from over- modulation or
over-voltage/current. Besides protecting UPFC
from over-modulation, the additional benefit of the
proposed control scheme is obvious: 1) the ac fault
ride-through ability of MMC-UPFC is greatly
enhanced and the spread of ac fault can be
effectively inhibited; 2) MMC-UPFC can operate
with the maximum operating region under
unbalanced grid conditions.
II. SYSTEM MODELING
With the subject to protect MMC-UPFC
from over modulation and over-voltage/current
under unbalanced grid conditions, this project
proposes the cascade control scheme for MMC-
UPFC based on the voltage limit control and
symmetric component control.
Fig. 1. Configuration of MMC-UPFC.
Fig. 1 shows the basic configuration of
MMC-UPFC, which consists of a shunt MMC and
a series one connected back to back. The shunt
MMC usually provides the stiff dc-link voltage and
also controls the shunt reactive power to support
the ac bus voltage u1 . The series one generates one
controllable ac voltage and couples it to the
transmission line through the series transformer, to
regulate the power flow of the line. TBS and
mechanical bypass switch (MBS) are used to
bypass MMC-UPFC temporarily and for a long
time, respectively. In this project, both MMCs
employ conventional half-bridge sub-modules
(HBSM). Since it is already well-known to all, no
details of HBSM are given in this project. The
control strategies in this project are also applicable
to MMC-UPFC with other SM topologies. In the
case of unbalanced grid condition, MMC can be
divided into positive- and negative-sequence
subsystem. In some situation, zero sequence may
exist. In the rotating synchronous frame (RSF), the
positive- and negative-sequence model of MMC is
investigated. The equivalent circuit of MMC-UPFC
is illustrated in Fig. 2. Corresponding to
aforementioned three scenarios of unbalanced grid
conditions, asymmetrical transmission lines can be
represented by unbalanced impedance Zline; load
imbalance can be represented by asymmetric load
impedance ZL, and the asymmetric ZL eventually
causes unbalanced ac bus voltage ur at the
receiving end; when ac fault occurs, ur will also
become unbalanced.
Fig. 2. Equivalent circuit of MMC-UPFC.
To improve performance of UPFC-MMC
under unbalanced grid conditions, the general
control principle is to compensate the unbalanced
components of ur or Zline by regulating use (u12)
coupled from the series MMC, and the control
objective is to obtain balanced ac currents of
transmission line by suppressing the negative- and
zero-sequence currents. In details, the negative
sequence current (NSC) and ZSC can be
suppressed by injecting the corresponding
negative-sequence voltage (NSV) and zero-
sequence voltage (ZSV) into use. In particular, the
circuit of ZSC mainly depends on the connection of
transformers.
A. Control of Shunt and Series MMC
According to Fig. 1, the shunt MMC
adopts the dc voltage control and ac voltage
control, which are identical with the conventional
one, and only positive-sequence control loop is
implemented for the shunt MMC. The series MMC
is responsible for compensating NSV and ZSV in
the transmission line. Therefore, the positive-,
negative and zero-sequence control loops are all
necessary for the series MMC, while only positive-
sequence loop is used for power flow regulation.
As converter currents are identical with ac currents
of transmission line in per unit value, to fully
suppress the NSC, the references of the negative-
sequence and zero-sequence inner-current loops are
directly set as zero.
B. Connection of Transformers
As each primary winding of series
transformer is connected in series with each phase
of transmission line, the main concerns of
transformer connections are the third-order
magnetizing current (TOMC) and ZSC of
fundamental frequency. To provide the flowing
path for TOMC, the secondary windings of series
transformer should be with delta or star-grounding
connection. However, the delta connection will
also provide the flowing path for ZSC of
fundamental frequency and make it impossible to
inhibit ZSC under unbalanced grid conditions. The
only option for the secondary windings of series
transformer is star-grounding connection.
Fig. 3. Zero-sequence equivalent circuit with the
proposed transformer connections.
On the other side, the shunt transformer
should be with delta star grounding connection to
constitute the circuit for TOMC of series
transformer. Fig. 3 illustrates the equivalent zero
sequence circuit with the transformer connections
employed in this project: the secondary windings of
series transformer is of star grounding connection
while the shunt transformer is with delta-star
grounding connection. In Fig. 3, Xm, X1 and X2
represent the magnetizing reactance, leakage
reactance at primary side and secondary side of the
series transformer, respectively; the superscript
denotes the corresponding variables of shunt
transformer; Ra and La represent the equivalent
arm resistance and inductance of MMCs. In this
way, ZSC will flow through the leakage reactance
X1 and X2 of series transformer, the arm resistance
Ra and inductance La of series and shunt MMCs
and the leakage reactance X_1 and X_2 of shunt
transformer, as shown in Fig. 3. The total
impedance of zero-sequence circuit is a dozen
ohms or below for TOMC. Under unbalanced grid
conditions, ZSC of fundamental frequency will be
suppressed by zero-sequence inner-current loop of
series MMC with constant zero reference input.
Besides providing the flowing path for TOMC, the
transformer connections in Fig. 3 bring more
benefits as follows:
1) providing the grounding points at the converter
sides of series and shunt transformers;
2) being able to couple ZSV generated by series
MMC in series with transmission lines;
3) avoiding the fault at the side of series MMC
from disturbing the power flow of transmission line
too much.
On the other hand, ZSC of fundamental
frequency under unbalanced grid conditions can
also get effectively suppressed if the shunt
transformer is grounded through relatively large
impedance. The value of impedance has to be
designed elaborately by the trade-off between
providing flowing path for TOMC and suppressing
ZSC of fundamental frequency. This section will
quantitatively analyze the controllability of power
flow under balanced and unbalanced grid
conditions with MMC-UPFC based on Fig. 1, and
compare the operating regions of power flow in
both cases. The results from mathematical
derivation and point-scanning approaches will
validate each other.
Fig. 4. Schematic of proposed cascade control.
To be noticed, other auxiliary control
modules in the control of series MMC, such as
circulating current suppression and DC voltage
ripple suppression, are not depicted in Fig.4 for the
purpose of simplification.
III. SIMULATION RESULTS
CASE 1: ASYMMETRICAL TRANSMISSION
LINE PARAMETERS:
fig: (a) active and reactive power
fig: (b) ac currents of transmission line.
Fig. 5. Waveforms for the case of asymmetry of
transmission line parameters: (a) active and
reactive power, (b) ac currents of transmission line.
In this section, the asymmetry of
transmission lines is modeled by the parallel layout
of the underground cables. The depth and spacing
of the cables is 1 m and 0.12 m, respectively.
Before UPFC starts operation at 0.8 s, the original
power flow is (175MW,−125MVar) with visible
ripples because of the unbalanced currents, as
shown in Fig. 5(a). After 0.8 s, UPFC starts to
regulate the power flow at its reference (215 MW,
0 MVar). Fig. 5(b) shows the current waveform
before and after UPFC is activated. With the
proposed control, UPFC reduces the unbalance
factor of currents from about 15% before 0.8 s to
0.22% after 0.8 s.
CASE 2: LOAD IMBALANCE:
(a) voltage at receiving end
(b) ac currents of transmission line
Fig.6. Waveforms for the case of load imbalance:
(a) voltage at receiving end, (b) ac currents of
transmission line.
The load imbalance is modeled by the
imbalance of load impedance ZL. Meanwhile, the
cables are laid in triangle to assure of the balance
of transmission impedance Zline. Fig. 6 illustrates
the waveforms of currents and voltages at the
receiving end. Due to load imbalance, the
unbalance factor of voltages at the receiving end
reaches 2.8%, which causes the unbalance factor of
currents up to 73.1% without UPFC. After UPFC
puts into service at 0.8 s, the unbalance factor of
currents reduces to 0.13%.
CASE 3: AC FAULT:
(a) voltage at receiving end
(b) ac currents of transmission line
Fig.7. Waveforms for the case of ac fault: (a)
voltage at receiving end, (b) ac currents of
transmission line.
Following the event in case 2, a remote ac
fault occurs to the receiving end at 1.2 s. Fig. 7
illustrates the waveforms of currents and voltages
at the receiving end. Even though voltages at the
receiving end become unbalanced, ac currents get
through the fault quickly and still keep balanced
with the help of UPFC, as shown in Fig. 7.
CASE 4: SLIGHT AC FAULT:
(a) active and reactive power
(b) ac currents of transmission line
(c) ac voltages of series MMC
Fig.8. Waveforms for the case of slight ac fault: (a)
active and reactive power, (b) ac currents of
transmission line, (c) ac voltages of series MMC.
Before UPFC is activated at 0.8 s, the
power flow of the transmission line is (185 MW,
−128 MVar), as shown in Fig. 8. At 0.8 s, UPFC
starts operation with the reference (150 MW, 0
MVar) within the controllable region. An ac faults
occurs to the receiving end at 1.1 s and lasts for 0.3
s. The unbalance factor of voltages at the receiving
end is 3.4%. In this case, the set power point
becomes out of the controllable region
corresponding to this unbalanced condition. By the
online calculation block, the corresponding original
point is obtained as (240MW, −70 MVar).With the
proposed voltage limit control, UPFC shifts the
power flow from the reference point (150 MW, 0
MVar) to the actual point (168 MW, −14 MVar) on
the boundary of Um. As shown in Fig. 8, the
maximum voltage amplitude among three phases
corresponding to (168 MW, −14 MVar) is 10 kV.
When the fault is cleared at 1.4 s, UPFC regulates
the power to come back to (150 MW, 0 MVar)
quickly and steadily.
CASE 5: SEVERE AC FAULT:
(a) active and reactive power
(b) ac currents of transmission line
(c) ac currents of MMC
(d) ac voltages of series MMC
Fig. 9. Waveforms for the case of severe ac fault:
(a) active and reactive power, (b) ac currents of
transmission line, (c) ac currents of MMC, (d) ac
voltages of series MMC.
With the same initial condition with case
4, the reference power is set to be (350 MW, 0
MVar) which lies out of the controllable region
even under balanced grid condition. The voltage
limit control will reduce the power to the actual
point (320MW, −12 MVar). Meanwhile, the
magnitude of voltages is equal to 10 kV, as shown
in Fig. 9. When a severe ac fault occurs at 1.1 s, the
UPFC is bypassed once the conditional statement
of U−∗ 12 > U− limit is satisfied. The protection
scheme of the transmission line will take action at
1.2 s to clear the fault. After the fault is cleared at
1.3 s, UPFC starts to recover to the pre-fault state
steadily.
IV. CONCLUSION
This project investigates the controllable
regions of power flow under unbalanced grid
conditions in mathematical derivation and point-
scanning methods, respectively. The results from
the two methods are completely consistent and thus
validate each other. The final cascaded control
scheme for series MMC of UPFC is constructed
based on the proposed voltage limit control and
basic symmetric component control. In the
cascaded control scheme, the suppression of NCS
and ZCS is endowed with the first priority over
power flow regulation. With the voltage limit
control, MMC-UPFC can avoid from over-
modulation and maximize its controllability by
operating on the boundary defined by the voltage
limit. The principle of voltage limit control is also
applicable to other applications of VSCs under
unbalanced grid conditions. The simulation result
shows that with the proposed control strategies
MMC-UPFC can effectively operate under
unbalanced grid conditions and exhibit very good
robust controllability. It can be concluded that the
proposed control strategies improves the ac fault
ride-through ability of MMC-UPFC and also can
help to inhibit the spread of ac fault.
REFERENCES
[1] B. Mwinyiwiwa, B. Lv, and B. T. Ooi,
“Multiterminal unified power flow controller,”
IEEE Trans. Power Electron., vol. 15, no. 6, pp.
1088–1093, Nov. 2000.
[2] H. Fujita, H. Akagi, and Y.Watanabe,
“Dynamic control and performance of a unified
power flow controller for stabilizing an AC
transmission system,” IEEE Trans. Power
Electron., vol. 21, no. 4, pp. 1013–1020, Jul. 2006.
[3] A. Lesnicar and R. Marquardt, “An innovative
modular multilevel converter topology suitable for
a wide power range,” in Proc. Power Tech Conf.,
Bologna, Italy, 2003, pp. 3–6.
[4] Q. Tu, Z. Xu, and L. Xu, “Reduced switching-
frequency modulation and circulating current
suppression for modular multilevel converters,”
IEEE Trans. Power Del., vol. 26, no. 3, pp. 2009–
2017, Jul. 2011.
[5] M. Saeedifard and R. Iravani, “Dynamic
performance of a modular multilevel back-to-back
HVDC system,” IEEE Trans. Power Del., vol. 25,
no. 4, pp. 2903–2912, Oct. 2010.
[6] Z. Yuan, S. W. H. de Haan, J. B. Ferreira, and
D. Cvoric, “A facts device: Distributed power-flow
controller (DPFC),” IEEE Trans. Power Electron.,
vol. 25, no. 10, pp. 2564–2572, Oct. 2010.
[7] F. Z. Peng, Y. Liu, S. Yang, S. Zhang, D.
Gunasekaran, and U. Karki, “Transformer-less
unified power-flow controller using the cascade
multilevel inverter,” IEEE Trans. Power Electron.,
vol. 31, no. 8, pp. 2461–5472, Aug. 2016.
[8] S. Yang, Y. Liu, X. Wang, D. Gunasekaran, U.
Karki, and F. Z. Peng, “Modulation and control of
transformer-less UPFC,” IEEE Trans. Power
Electron., vol. 31, no. 2, pp. 1050–1063, Feb. 2016.
[9] J. Yuan, L. Liu, W. Fei, L. Chen, B. Chen, and
B. Chen, “Hybrid electromagnetic unified power
flow controller: A novel flexible and effective
approach to control power flow,” IEEE Trans.
Power Del., Oct. 2016, early access.
[10] A. Rajabi-Ghahnavieh, M. Fotuhi-Firuzabad,
M. Shahidehpour, and R. Feuillet, “UPFC for
enhancing power system reliability,” IEEE Trans.
Power Del., vol. 25, no. 4, pp. 2881–2890, Oct.
2010.