40
8/11/2019 Vol II Price Bid http://slidepdf.com/reader/full/vol-ii-price-bid 1/40  Ahmedabad Municipal Corporation SHORT TENDER DOCUMENT or To Design Engineering Manufacture, Test, Supply, Handling, Installation, Testing & Commissioning of Complete Air Conditioning System , Operating for 5 years and Comprehensive Maintenance Contract for 3 Years at LG Hospital Maninagar , Ahmedabad. TENDER NO : AMC/_______________________/2011 NOTICE NO. : _________________________________ Volume II :- Price Bid PRICE BOQ (1) Last date of Tender Submission :  25st Nov 2011 Up to 02:00 PM By RPAD / Speed post / Hand delivery  (2) Date of Tender Opening (only Technical Bid.) : 25st Nov 2011 at 04:00 PM. NOV ‘2011 

Vol II Price Bid

Embed Size (px)

Citation preview

Page 1: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 1/40

 

Ahmedabad Municipal Corporation

SHORT TENDER DOCUMENT

or

To Design Engineering Manufacture, Test, Supply, Handling, Installation, Testing & Commissioning of

Complete Air Conditioning System , Operating for 5 years and Comprehensive Maintenance Contract for

3 Years at LG Hospital Maninagar , Ahmedabad.

TENDER NO : AMC/_______________________/2011

NOTICE NO. : _________________________________

Volume II :- Price Bid

PRICE BOQ

(1) Last date of Tender Submission :

 

25st Nov 2011 Up to 02:00 PM By RPAD /

Speed post / Hand delivery 

(2) Date of Tender Opening (only Technical Bid.) : 25st Nov 2011 at 04:00 PM.

NOV ‘2011 

Page 2: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 2/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

DOCUMENT : ABSTRACT HVAC SYSTEMOCUMENT : ABSTRACT HVAC SYSTEM

Sl.No DESCRIPTION AMOUNT

1 .0 V OLU ME I - HV AC PLAN T RO OM EQ UIPM EN T B OQ

2.0 VO LUM E II - LO W SID E H VAC BO Q

3 .0 V OLU ME III - LO W SID E O T / STER ILE

4 .0 V OLU ME IV - BO Q FO R V EN TILA TIO N SY STE M

5.0 VOLUME V - BOQ FOR DX SYSTEM

6.0 VO LUM E VI - BO Q FO R BAS SYSTEM

7 .0 V OL UM E V II - B OQ FO R E LE CT RIC AL S YS TE MS

8 .0 V OLU ME VIII - BO Q F OR CIV IL STR UC TU RA L W O RK

9 .0 V OLU ME IX - B OQ FO R O T PAR TITIO N W ORK

10.0

VOLUME - X - AMC CHARGES ( OPERATION AND MAINTANANCE

)

Note: The Total am ount of the above shall be considered for L1 selection.

RS. IN WORDS _________________________________________________________________

GRAND TOTAL ( TO BE CONSIDERED FOR L1 SELECTION )

Signature of Tenderer : Additional Chied Engineer ( Electrical)

 Ahmedabad Municipal Corporation

Name

Company Seal

Date Date

TENDER ABSTRACT 1 OF 39

Page 3: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 3/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -I - BILL OF QUANTITY FOR PLANT ROOM EQUIPMENT

1.0 WATER COOLED HI-EFFICIENCY SCREW CHILLERS

1.1 Supply, Installation, Testing and commissioning & field

performance of self contained water-cooled screw chillers with

semi-hermetic screw compressors ( Twin or Multi Compressor

Chillers Preffered ) ; 415 V/ 3 Phase high efficiency motor with

soft starter microprocessor based control panel; water cooled

condenser & insulated evaporator assembly; operating and

performance parameters and other data shall be as per

enclosed data sheet; Chiller shall support remote

communication on Open Protocols; Chiller shall be rated to

give following capacity 

1.1.1 160 Refrigeration Tons - TR at following duty point :: 6.6 deg C

chilled water outlet temperature and 11.6 Deg C Chilled water

Inlet Temprature

Nos 2

(2 OPERATING )Duty Point : Cooling Water inlet 32 Deg C and Out let 36 Deg

C at 28.7 Deg C Ambient WBT(For Ahmedabad )Refrigerent : R134 or R407Controller - With LCD Touch Screen Control Panel with corded

extention facility to move the controler up to 30 mtr length.

Performance Values should be better then following ::a. IKW/TR at 100% Load < 0.7 KW/TR b. COP > 5.0c. IPLV < 0.51Starter - SOFT STARTER 

1.2 ACCESSORIES

1.2.1 Grooved Pipe Connector Couplings for Chil led Water and

Cooling Water In-Out Nozzle Connections - 1 set per Chiller

Set 2

1.2.2 Acoustic Enclosure for Chiller to l imit the chiller dB less than

specified levels

Set R.O.

1.2.3 BMS Compitable Chil ler Master Controller for integratedoperation of 2 chillers/ 3 Pri pumps/ 3 Sec. Pumps/ 3 CW 

Pumps and 2 towers

Set 1

2.0 PRIMARY CHILLED WATER PUMPING SYSTEM WITH

ACCESSORIES :

2.1 Supply, Installation, Testing and Commissioning of True Back-

pull out type, single suction, Centrifugal Primary Chilled water

pumps with mechanical seal, CI casing and Bronze Impeller -

designed to operate at more than 80% overall efficiency; the

pump shall be factory assembled and dynamically balanced

with 4 Pole hi-efficiency- EFF1 - TEFC IP 55 Induction Motor,

Flexible coupling with Guard, Corrosion resistant painted MS

factory fabricated base frame with necessary vibration isolators

and rubber flexible bellows at suction and discharge nozzles;

pump shall be insulated as specified at site and supplied with

100 mm dial type pressure gauge with SS needle valve andfixtures at suction/disc ports.

2.1.1 Each pump assembly designed to operate for following duty 

point

Nos 3

Chilled water Flow rate = 384 USGPMTotal Dynamic Head = 15 M WC (Shall meet final chiller make

PD)

Pumps shall be checked for Parallel Pumping Operation( 2 working + 1 standby )

REMARK

NIT RATES

IN RS.

TY

TOTAL

AMOUNT

RS.

SR.

NO.

DESCRIPTION UNIT

HVAC TENDER VOL_I_PLANT ROOM 2 OF 39

Page 4: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 4/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -I - BILL OF QUANTITY FOR PLANT ROOM EQUIPMENT

REMARK

NIT RATES

IN RS.

TY

TOTAL

AMOUNT

RS.

SR.

NO.

DESCRIPTION UNIT

bkW values shown in the Power demand sheet are indicative;

vendor to provide selection charts for pumps performance and

motor rating as part of submissionQuoted price shall include cost of vibration isolation and all

other associated accessories as per tender specification & duly 

insulated as per insulat ion specificat ion and covered with

 Aluminum cladding.

3.0 Secondary Variable Speed Chilled Water Pumping System

with accessories

3.1 Supply, Installation, Testing and Commissioning of True Back-

pull out type, End (single) suction, mechanical seal, Centrifugal

type Variable Speed Secondary Chilled Water pumps with CI

casing and Bronze Impeller - designed to operate at more than

80% overall efficiency; the pump shall be with 4P / TEFC IP55

motor / EFF1 / 2900 Rpm factory assembled base frame with

Flexible Coupling and Guard, rubber bellows at

suction/discharge, Corrosion resistant painted factory  

fabricated base frame; pump shall be insulated as specified atsite and supplied with 100 mm dial type pressure gauge with

SS needle valve and fixtures at suction/disc. ortsDesign basis for secondary pumping shall be as per design

specifications enclosed separately 

Motor rating indicated in Power demand sheet are tentative ;

Pumps shall be selected for best ef ficiency point on single

operation for each zone and after calculating actual TDh based

on product specific Water Pressure drops for AHU and

 Accessories at the time of supply 

3.1.1 Chilled water Flow rate = 360 GPM Nos 3Total Dynamic Head = 36 M WC(2 Working + 1 Standby)Supply, Programming, Installation, Testing and Commissioning

of Pump Logic Controller capable of controlling up to 3 Pumps

in parallel housed in IP65 Control Panel compatible for

interface with Pump electrical Panel and Variable frequency 

drive panel - duly internally wired and tested - parallel

pumping software downloaded, along with required DP

transmitters for closed loo control

Set 1

3.1.1.1 Variable Frequency Drives and VFD Panelsa Supply, Installation Testing and Commissioning of Variable

Frequency Drives for Secondary Pump Motors with matching

rating ready to be installed in VFD panel

Set 3

b Panel ready to house the above 3 nos. VFD duly internally  

wired and tested with Bypass arrangements and necessary 

electrical isolators separate for each VFD including its

integration with Pump Motor Panel

Set 1

3.1.1.2 Supply, installation, testing and commissioning of Differential Water Pressure Transmitters with fittings supplied and installed

across selected AHU loads in the field and wired up to Pump

Logic controller for integrated operation of the variable speed

pumping system

Set 2

Quoted price shall include cost of vibration isolation and all

other associated accessories as per tender specification & duly 

Insulated as specified and covered with Aluminum cladding.

HVAC TENDER VOL_I_PLANT ROOM 3 OF 39

Page 5: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 5/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -I - BILL OF QUANTITY FOR PLANT ROOM EQUIPMENT

REMARK

NIT RATES

IN RS.

TY

TOTAL

AMOUNT

RS.

SR.

NO.

DESCRIPTION UNIT

4.0 COOLING WATER PUMPING SYSTEM WITH ACCESSORIES :

4.1 Supply, Installation, Testing and Commissioning of True Back-

pull out type, single suction, Centrifugal Primary Condenser

water pumps with mechanical seal, CI casing and Bronze

Impeller - designed to operate at more than 80% overall

efficiency; the pump shall be factory assembled and

dynamically balanced with 4 Pole hi-efficiency EFF 1 - TEFC IP

55 Induction Motor, Flexible coupling with Guard, Corrosion

resistant painted MS factory fabricated base frame with

necessary vibration isolators and Rubber flexible bellows at

suct ion and discharge nozzles; pump shall be insulated as

specified at site

4.1.1 Each pump assembly designed to operate for following duty 

point

Nos 3

Cooling water Flow rate = 640 USGPMTotal Dynamic Head = 24 M WCPumps shall be checked for Parallel Pumping Operation(2 working + 1 standby)bkW values shown in the Power demand sheet are indicative;

vendor to provide selection charts for pumps performance and

motor rating as part of submission based on product specific

ressure dro s.

5.0 CTI APPROVED FRP INDUCED DRAFT COOLING TOWERS :

Supply, installation, testing and commissioning of FRP Induced

draft counter flow bottle type cooling tower; Tower shall be MS

HDG Frame work, Access ladder & Supports; FRP Casing and

FRP Basin with makeup including Float valve, PVC fills,

Distribution system with PP Nozzles, Axial Flow Direct/Belt drive

Fan with PVC Blades & MS HDG Hub driven by IP55 TEFC 720

RPM vertical flange mount motor suitable for 415±10% V, 50Hz, 3 phase supply; power / control wiring, earthing, drain,

make up, quick fill connection and vibration isolation etc. as

per tender specification.

5.1 100% Eff icient CTI Approved Cooling Tower for designed for

 WBT of 28.7 Deg C , Cooling Water Leaving temp = 32 deg C

at and 36 Deg C Entering Temp at flow rate of 640 USGPM

Nos 2

( 2 working)

5.2 Variable Frequency Drives and VFD Panels for cooling tower

fan motor5.2.1 Supply, Installation Testing and Commissioning of Variable

Frequency Drives for Secondary Pump Motors with matching

rating of 7.5 KW ready to be installed in VFD panel

Set 2

5.2.2 Panel ready to house the above 2 nos. VFD duly internally  

wired and tested with Bypass arrangements and necessary electrical isolators separate for each VFD including its

inte ration with Fan Motor Panel

Set 1

5.2.3 Set of Motor / Motor Drive / Pullies / Belts ( if any ) as a spare

with all required acessories

Set 1

HVAC TENDER VOL_I_PLANT ROOM 4 OF 39

Page 6: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 6/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -I - BILL OF QUANTITY FOR PLANT ROOM EQUIPMENT

REMARK

NIT RATES

IN RS.

TY

TOTAL

AMOUNT

RS.

SR.

NO.

DESCRIPTION UNIT

6.0 EXPANSION TANK WITH ACCESSORIES :

6.1 Supply, installation of instulated pressure type expansion tankof size suitable for expansion provision of water occupying total

pipe volume complete with integral heavy duty rubber

diaphragm, system pressure 125 psig and temperature

difference of 10 deg F

Set R.O.

6.2 Pressurization / Makeup Pumps for 30 USGPM flow rate

coupled with suitable rat ing motor, relief valve, pressure

gauge, cotrol panel, pressure switch, drain pipe, fi tt ings,

valves; Pump shall be sized to creat the required pressure in the

system and complete with check valve, Y strainer, butter fly 

valve at suction/dischagre 25 mm dia.; pump electrical panel

for operation on pressure switch; provide IP 65 panel inclucing

Pressure switch

6.2.1 ( 1 Working + 1 Standby ) Set R.O.

6.3 1500 Ltr Capacity - Supply, installation of Chilled WaterExpansion Tank fabricated from 5mm MS Plate construction -

size shall be suitable for expansion provision of water

occupying total pipe volume complete with float valve & make

up, quick fill, drain and overflow connections; Tank shall be

duly insulated with 50 mm thick TF Quality EPS finished

covered with Aluminium clading.

No 1

6.4 Air Separators

Supply, installation, testing & commissioning of a common air

separator on the return water line located at the pump suction

and suitable for Secondary pump water flow; the separator

shall be complete with high capacity air vent, service valve, non

return valve, isolation butterfly valve for makeup water inlet.

No 1

Capacity suitable for 714 USGPM and 200 mm NB CHW 

Header line

7.0 Documentation in 3 Set Lot 1

7.1 The scope coveres submission of following documents in 3

copies as a part of commissioning and handing over.

7.1.1 Copy of Submitted Tender Document with sign and stamp

7.1.2 Copy of work order and acceptance letter of the same

7.1.3 All shop drags to be approved by consultant.

7.1.4 As built drgs to be furnished in soft and hard form

7.1.5 Technical Detail of all the equipments - High Side and Low side

7.1.6 Test reports showing the capacity proof / O&M manuals / SOPs

/ Warranty Cards to be furnished of all bought out items.

7.1.7 Inspection report of chil lers / AHUS / cooling towers and all

major tender items by client/consultant

7.1.8 Copy of third party validation report for OT

7.1.9 Copy of performanc bank guarantee

HVAC TENDER VOL_I_PLANT ROOM 5 OF 39

Page 7: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 7/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -I - BILL OF QUANTITY FOR PLANT ROOM EQUIPMENT

REMARK

NIT RATES

IN RS.

TY

TOTAL

AMOUNT

RS.

SR.

NO.

DESCRIPTION UNIT

7.1.10 Full company name / Address / Name / Mail ID / Web Address

/ Toll Free no for the after sales service or any break down call.

8.0 Appointment of Project Management Consultant - For the

project duration + 3 Months 

= Total = 8 Months from the

date of contract award

Lot 1

8.1 The contractor has to appoint a Project Management

Consultant Qualified & Experienced with having expertise in the

HVAC Consulting Field for more then 10 years.The PMC shall report directly to AMC and Project Consultant - (

Principal Architect and HVAC Consultant )The prime responsibi li ty of the PMC is to ensure the project

completion in define time line , Site cordination , Design

Cordination with Architect - Consultant & AMC MET Authorities

, Site quality assurance , checking the material & workmaship

receipt w.r.t tender specification, drawing , keep treack record

of all project related communication , keep record of all

documentation starting from tender document to handing over

documentation , Weekly review meeting and review report ,

site progress photo graphs report and comminucation , Day to

day cordination with HVAC Contractor , stricktly follow up with

HVAC contractor for the accepted bar chart site activity , Time

to time cordination and communication with other

agency/consultant like false ceiling / MGPS / Electrical etc ,

 Verification  of site measurement for all the tender quantities ,

Certification of contractors bill, Depute a full day site

supervisior for the above said activity.

Signature of Tenderer : Additional Chied Engineer ( Electrical) Ahmedabad Municipal Corporation

Name

Company Seal

Date Date

GRAND TOTAL FOR HVAC CHILLER PLANT ROOM EQUIPMENT

HVAC TENDER VOL_I_PLANT ROOM 6 OF 39

Page 8: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 8/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -II - HVAC LOW SIDE WORK _ CHILLED WATER SYSTEM

1.0 DOUBLE SKINNED AIR HANDLING UNITS ( Comfort Application ) NOS.

1.1 Supply, Installation, testing, commissioning and field performance of

Double Skinned Sandwiched insulated sectionalized construction

having thermal break profile with Mixing chamber and vibration

isolations Comprising of Fan section with double width double inlet

backward curved centrifugal fan with fix speed IP55/4P TEFC Fan

Motor , Connected with fire resistant f lexible outlet connection,

prefilter section with EU3 / G4 class filters, Cooling coil section with

6R / 4R ( As Mentioned below ) Deep Cooling coils having 13 FPI

aluminum fins and copper tubes, 2 Pass PVC Moisture eliminators

(for floor mounted units only), condensate drain pan duly insulated

with cross l inked polymer, insulated drain piping; complete with

flexible couplings at each coil connection to header, including

temperature & pressure gauges for each AHU inlet outlet header;

floor mounted unit to be installed on Cushy foot type vibrationisolators with 95% vibration isolation efficiency. Rating for the AHUs

shall be as under - Motor selection to suit the below capacity for

each AHU rating by AC Vendor.

 AHU Motor starter shall be in the scope of AHU Supply. The starter

should be equipped with required DC supply as per attached

drawing 1-HVAC-19-20. The DC Voltage shall be as per specif ic

requirement of valve control. Upstream incoming AHU power cable

up to starter panel shall be in electrical contractor's scope and down

stream cable from panel onwards to filed shall be part of AHU SITC

job including terminations. The panel shall be compatible for BMS

system integration.

 Areas located as per Load Summary and with following duty points

1.1.1 6800 CFM / 65 mm WC ESP / 15 TR / 6 Row Deep Coil / - KW  Strip Heater / Ceiling Suspended / 25 mm Double Skin / Tag - AHU

-01

Nos 1

1.1.2 5050 CFM / 65 mm WC ESP / 11 TR / 6 Row Deep Coil / - KW  

Strip Heater / Ceiling Suspended / 25 mm Double Skin / Tag - AHU

-02

Nos 1

1.1.3 2800 CFM / 65 mm WC ESP / 6 TR / 6 Row Deep Coil / - KW Strip

Heater / Roof Floor Mounting / 32 mm Double Skin / Tag - AHU -

13/17/25

Nos. 3

1.1.4 2200 CFM / 65 mm WC ESP / 5.5 TR / 6 Row Deep Coil / - KW  

Strip Heater / Roof Floor Mounting / 50 mm Double Skin / Tag -

 AHU -21

Nos. 1

1.2 Single Loop Digital Controller for AHUs Nos. 6Supply, installation, powering, programming and commissioning of

minimum 8 bit Single Loop Digital PID Controller ( supporting PICV 

Press Ind Cont Valve protocol ) with temperature display, set point

edit facility, supplied with matching RTD sensor and 15 rmt cable

connecting RTD sensor with conduiting ; Controller shall be for

indoor application with Loop Power Supply provision mounted within

IP22 lockable enclosure

Remarknit

Total

Amount Rs.

escriptionr. No.

Unit

Rates in

Rs.

Qty

HVAC TENDER VOL_II_LOW SIDE_CHILLED WATER SYSTEM 7 OF 39

Page 9: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 9/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -II - HVAC LOW SIDE WORK _ CHILLED WATER SYSTEM

Remarknit

Total

Amount Rs.

escriptionr. No.

Unit

Rates in

Rs.

Qty

2.0 DOUBLE SKINNED FAN COIL UNITS

2.1 FCUs to be complete with coil/blower assembly integrated with

room thermostat / pair of 2 ball valve / 1 Pressure Independent

Balancing cum control valve and strainer in inlet line. Please refer

control diagram for understanding. Power shall be available near

FCU by electrical contractor ( Part of Vol VII HVAC Contract ). The

scope also includes the Thermostatic Decorative LCD Desplay Room

Controller with 10 Rmt remote wire and conduite for Fan Coil Units

with built in temperature sensor; On/Off switch, Digital Temp

Display, Set Point Edit and 3 speed switch.

2.1.1 900 CFM each / 2 TR / CHW FCUSets R.O.

2.1.2 1000 CFM each / 2.5 TR / CHW FCUSets R.O.

4.0 CHILLED WATER PIPING :

4.1 Supply, installation, pressure testing, Insulation of MS C Class

Chilled Water Piping laid with roller supports as per details in

drawings insulated with 'X' mm thick (refer schedule below) class O

nitrile rubber covered with silver class ( PVC+Alu+UV Resistance

Face ) ; the pipe shall be applied with rubber adhesive ; pipes shall

be complete with required elbows (short and long), Tees, Reducers,

flanges, fittings as required

Pipes laid with 32 mm thick insulation as under

4.1.1 250 mm NB RMT R.O.

4.1.2 200 mm NB RMT 55

4.1.3 150 mm NB RMT 70

4.1.4 125 mm NB RMT 60

Pipes laid with 25 mm thick insulation as under

4.1.5 100 mm NB RMT 175

4.1.6 80 mm NB RMT 220

4.1.7 65 mm NB RMT 45

4.1.8 50 mm NB RMT 450

4.1.9 40 mm NB RMT 225

4.1.10 32 mm NB RMT 135

4.1.11 25 mm NB RMT 25

4.1.12 19 mm NB RMT R.O.

5.0 CONDNSER COOLING WATER PIPING

5.1 Supply, installation, testing of FRP coated MS C Class Cooling Water

Piping laid between Cooling water pumps, Condenser shell and

cooling towers as per details in drawings; the pipe shall be applied

with bituminous primer and painted to codes; pipes shall be

complete with required elbows (short and long), Tees, Reducers,

flanges, fittings as required

HVAC TENDER VOL_II_LOW SIDE_CHILLED WATER SYSTEM 8 OF 39

Page 10: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 10/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -II - HVAC LOW SIDE WORK _ CHILLED WATER SYSTEM

Remarknit

Total

Amount Rs.

escriptionr. No.

Unit

Rates in

Rs.

Qty

5.1.1 250 mm NB RMT 200

5.1.1 200 mm NB RMT 130

5.1.2 150 mm NB RMT R.O.

5.1.3 80 mm NB RMT 50

5.1.4 50 mm NB RMT 30

6.0 DRAIN PIPING :

6.1 Supply, installation, testing & commissioning of following sizes

insulated GI drain pipes Class C from AHU drain pans to nearest

floor drain and from CHW pump glands to the nearest drain

complete with interconnection, flanges, elbows, tees, nuts, P-trap etc.

The insulation type/finish and thickness should be similar to chilled

water piping insulation.

6.1.1 50 mm NB RMT 150

6.1.2 40 mm NB RMT 85

6.1.3 32 mm NB RMT 85

6.1.4 25 mm NB RMT 25

6.1.5 20 mm NB RMT R.O.

7.0 INSULATED AUTOMATIC BALANCING VALVES :

7.1 150 mm NB ( CHW LINE - CHILLER OUT LET ) Nos 2

7.2 200 mm NB ( CDSW LINE - CHILLER OUT LET ) Nos 2

8.0 INSULATED MANUAL BALANCING VALVES :

8.1 200 mm NB Nos R.O.

8.2 150 mm NB Nos R.O.

8.3 80 mm NB - CHW Tapping Nos R.O.

8.4 65 mm NB - CHW Tapping Nos R.O.

8.5 U TUBE Hg MANOMETER INSTANDERED CONSTRUCTION WITH

REQUIRED FIXTURES AND CALIBRATION CHARTNos 1

9.0 CHILLED/COOLING WATER ISOLATION TYPE MANUAL C.I.

BUTTERFLY VALVES IN PN16 RATING DULY INSULATED WITH

OPERATING LEVER AND GRADUATED DISC ( CHW VALVES IS TO

BE INSULATED ):

9.1 250 mm NB Nos. 3

9.2 200 mm NB Nos. 14

9.3 150 mm NB Nos 16

HVAC TENDER VOL_II_LOW SIDE_CHILLED WATER SYSTEM 9 OF 39

Page 11: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 11/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -II - HVAC LOW SIDE WORK _ CHILLED WATER SYSTEM

Remarknit

Total

Amount Rs.

escriptionr. No.

Unit

Rates in

Rs.

Qty

9.4 125 mm NB Nos R.O.

9.5 100 mm NB Nos 2

9.6 80 mm NB Nos 7

9.7 65 mm NB Nos R.O.

9.8 50 mm NB Nos. 30

9.1 INSULATED CHILLED WATER BALL VALVE WITH GUN METAL

BODY AND SS MOVING PART

9.1.1 40 mm NB Sets 57

9.1.2 32 mm NB Sets 20

9.1.3 25 mm NB Sets 36

9.2 INSULATED CHILLED WATER BALL VALVE WITH Y STRAINER SET

9.2.1 50 mm NB Sets R.O.

9.2.2 40 mm NB Sets R.O.

9.2.3 32 mm NB Sets R.O.

9.2.4 25 mm NB Sets 0

9.3 INSULATED CHILLED WATER( INSULATED )/COOLING WATER CI

POT STRAINER , Y STRAINERS WITH SS MESH FILTER AND NON

RETURN VALVES

9.3.1 200 mm NB Y Strainers for CDSW Pump suction Sets 3

9.3.2 200 mm NB Wafer Type Dual Plate Check Valve for CDSW pumpDischarge

Sets 3

9.3.3 150 mm NB Y Strainers for CDSW Pump suction Sets 6

9.3.4 150 mm NB Wafer Type Dual Plate Check Valve for CDSW pump

DischargeSets 6

9.3.5 250MM NB Pot Strainer Sets 1

9.3.6 80 mm NB Y Strainers for AHU Sets R.O.

9.3.7 65 mm NB Y Strainers for AHU Sets R.O.

9.3.8 50 mm NB Y Strainers for AHU Sets 7

9.3.9 40 mm NB Y Strainers for AHU Sets 13

9.3.10 32 mm NB Y Strainers for AHU Sets 59.4 Automatic Air Purge Valve

9.4.1 15 mm NB Nos 29

10.0 INSULATED CHILLED WATER PRESSURE INDEPENDENT

BALANCING CUM CONTROL VALVE (PIBV) WITH MODULATING

ACTUATOR FOR AIR HANDLING UNITS REGULATED BY

CONTROLLER SUPPLIED VIDE ITEM 1.3 OF BOQ VOL 2

HVAC TENDER VOL_II_LOW SIDE_CHILLED WATER SYSTEM 10 OF 39

Page 12: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 12/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -II - HVAC LOW SIDE WORK _ CHILLED WATER SYSTEM

Remarknit

Total

Amount Rs.

escriptionr. No.

Unit

Rates in

Rs.

Qty

10.1 Pipe sizes are mentioned where the valves are to be installed;

vendor to provide the exact size of the valve based on the PICV cataloge calculated from flow rate analysisSupply, Installation, testing and commissioning of Pressure

independent type 2 way Balancing and modulating Control valves in

a single Unit of Valve. PN16 Rating.DN 15 to DN 32 Brass Body Ext. Threaded DN 40 & DN 50 Cast

Iron Body, Ext. ThreadedDN 65 to DN 250 Cast Iron body, flanged connectionDuly mounted with Modulating actuator IP42/54 Accordingly type

suitable for 24V AC.

Valves to be installed on

10.1.1 125 mm NB Pipe size Nos R.O.

10.1.2 80 mm NB Pipe Size Nos R.O.

10.1.3 65 mm NB Pipe Size Nos R.O.

10.1.4 50 mm NB Pipe Size Nos 9

10.1.5 40 mm NB Pipe Size Nos 12

10.1.6 32 mm NB Pipe Size Nos 9

10.1.7 25 mm NB Pipe Size Nos R.O.

10.1.8 20 mm NB Pipe Size Nos R.O.

(All threaded valves shall be provided with couplings complete as

required for leak proof connections)

11.0 MOTORIZED BUTTER FLY VALVES FOR MACHINE ISOLATION

WITH ON/OFF ACTUATOR - BMS COMPITABLE FOR OPERATION

CONTROL

11.1 150 mm Flanged end INSULATED for CHW inlet/outlet across chiller

shellNos 2

11.2 200 mm Flanged end for CDS water inlet/outlet across Condenser

ShellNos 2

12.0 TEMPERATURE GAUGES FOR CHILLED/COOLING WATER LINE

IN AHUS/CHILLERS WITH THERMOWEL AND FITTINGS

12.1 Degital Desplay type Temp Gauge with CHW/CDSW Pipe MountingNos 8

12.2 Dial type temprature gauge with 4" dial Nos 1

12.3 Dial type Temp Gauge - 4" dial - Master calibrated set Nos 1

13.0 DIAL TYPE PRESSURE GAUGES FOR CHILLED/COOLING WATER

LINE AHUS/CHILLERS / CHW PUMPS/PRESS PUMPS/MAKEUP

PUMPS WITH SS NEEDLE VALVE AND FITTINGS

13.1 Dial type pressure gauge with 4" dial Nos 76

13.2 Dial type pressure gauge with 4" dial - Master Calibrated Set Nos 1

HVAC TENDER VOL_II_LOW SIDE_CHILLED WATER SYSTEM 11 OF 39

Page 13: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 13/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -II - HVAC LOW SIDE WORK _ CHILLED WATER SYSTEM

Remarknit

Total

Amount Rs.

escriptionr. No.

Unit

Rates in

Rs.

Qty

14 Electro Magnatic Flow meter for Chilled Water flow measurementinstalled on header with 8 Dia straight length_200 mm Header with

fixtures

Nos R.O.

15 CHILLED WATER CI CONTROL VALVES WITH MODULATING

 ACTUATOR OPERATING ON 0-10V DC OR 4-20MA SIGNAL

15.1 Pipe sizes are mentioned where the valves are to be installed;

vendor to provide the exact size of the valve based on the Cv value

of the valve offered calculated from Coil Pressure drop and Coil

flow rate for product specific figures

For Pipe size of 

15.1.1 50 mm NB Pipe Size Nos R.O.

15.1.2 40 mm NB Pipe Size Nos R.O.

15.1.3 32 mm NB Pipe Size Nos R.O.

15.1.4 25 mm NB Pipe Size Nos R.O.

16.0 SUPPLY, INSTALLATION, LEAK TESTING AND COMMISSIONING

OF AIR DISTRIBUTION SYSTEM AND DUCTING FOR

FOLLOWING GAUGES AS SPECIFIED

16.1 Supply and installation of GI, Pre fabricated rectangular ducts,

complete with MS flanges and bracing (as specif ied), necessary 

supports using thread rods (as directed) and anchor bolts, supply air

collars, vanes, splitters dampers duly painted of the ducts and as per

specification for Air Conditioned Areas; all sheets shall be supplied

with Mfr Test Certificates with delivery 

16.1.1 1.2 mm Thick GI ducting SQM R.O.

16.1.2 1.0 mm Thick GI ducting SQM R.O.

16.1.3 0.8 mm Thick GI ducting SQM R.O.

16.1.4 0.63 mm Thick GI ducting SQM R.O.

16.2 Supply and installation of Aluminum , site fabricated rectangular

ducts, supported by Mfr Test Certificates, complete with RTV Sealant

joints with necessary supports using thread roads (as directed) and

anchor bolts, supply air collars, vanes, splitters dampers duly 

painting of the ducts and as per specif ication for Air Condit ioned

 Areas. ( For MRI Areas )

16.2.1 1.2 mm Thick GI ducting SQM R.O.

16.2.2 1.0 mm Thick GI ducting SQM R.O.

16.2.3 0.8 mm Thick GI ducting SQM R.O.

16.2.4 0.63 mm Thick GI ducting SQM R.O.

HVAC TENDER VOL_II_LOW SIDE_CHILLED WATER SYSTEM 12 OF 39

Page 14: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 14/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -II - HVAC LOW SIDE WORK _ CHILLED WATER SYSTEM

Remarknit

Total

Amount Rs.

escriptionr. No.

Unit

Rates in

Rs.

Qty

16.3 PRE INSULATED DUCTING SHEET WORK

16.3.1 Supply and Installation of :- 10 mm thick pre-insulated ductingsheets of 4m X 1.2m having a PIR density of 82Kg/CuM with 80

Micron Aluminum facing on both the sides with stucco type finish,

duly Class ‘O’ certified as per BS along with the standard installation

accessories. (Thermal Insulation only)

SQM. R.O.

16.3.2 Supply and Installation of :- 20 mm thick pre-insulated ducting

sheets of 4m X 1.2m having a PIR density of 45Kg/CuM with 80

Micron Aluminum facing on both the sides with stucco type finish,

duly Class ‘O’ certified as per BS along with the standard installation

accessories.(Internal Ducting Not exposed to Sunlight Ducting)

SQM. 350

16.3.3 Supply and Installation of :- 30  mm thick pre-insulated ducting

sheets of 4m X 1.2m having a PIR density of 50Kg/CuM with 80/200

Micron Aluminum facing on each side with stucco type finish, duly

Class ‘O’ certified as per BS along with the standard installationaccessories.(External Ducting not exposed to Sunlight Ducting)

SQM. 250

17.0 SUPPLY INSTALLATION TESTING AND COMMSSIONING OF

DIFFUSERS/ GRILLES AS PER FOLLOWING SCHEDULE

17.1 1000 CFM Rating Jet Diffusers Nos R.O.

17.2 Alu. Powder Coated Supply Air Diffuser with VCD SQM. 10

17.3 Alu. Powder Coated Supply Air Diffuser without VCD SQM. 10

17.4 Alu. Powder Coated Supply Air Grill with VCD SQM. 1

17.5 Alu. Powder Coated Supply Air Grill without VCD SQM. 1

17.6 SS Perforated Supply / Return Air Grill for OT Areas SQM. R.O.

18.0 SUPPLY, INSTALLATION, TESTING, COMMISSIONING OF GI

POWDER COATED DUCT DAMPERS

18.1 G I Dampers shall be with opposed blade aerofoil blades and PVC

gears for smooth operation for volume controlSQM 5

18.2 Fusible Link Type Fire Dampers installed at Wall crossings in SA/ RA 

ducts ( At all wall crossings )SQM 5

19.0 DUCT THERMAL INSULATION

19.1 Thermal insulation of SA ducting internally with ' X ' mm thick Class

O Flame Retardant EPDM nitrile rubber having Thermal Conductivity 

- 0.037 at 20 Deg C & Density - 60 Kg / M3 +/- 10%.

19.1.1 13 mm For Supply air Ducting ( SA duct through F/c loose return)SQM R.O.

19.1.2 19 mm For Supply air Ducting ( SA duct through Non AC Area ) SQM R.O.

20.0 SUPPLY AIR DUCT ACCOUTIC INSULATION ( for Comfort )

HVAC TENDER VOL_II_LOW SIDE_CHILLED WATER SYSTEM 13 OF 39

Page 15: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 15/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -II - HVAC LOW SIDE WORK _ CHILLED WATER SYSTEM

Remarknit

Total

Amount Rs.

escriptionr. No.

Unit

Rates in

Rs.

Qty

20.1 Supply and fixing of acoustic lining inside sheet metal ducts with

13mm / 19 mm thick class O flame retardant sound absorbingaccosound elastrometric nitrile rubber of density 150Kg/cub.mtr and

thermal conductivity of 0.036 W/m k

20.1.1 13 mm SQM 75

20.1.2 19 mm SQM R.O.

21.0 AHU ROOM ACCOUSTIC INSULATION

21.1 Acoustic insulation for plant room using 50mm thick Twiga 300

rigid board stick and GI frame work. Insulation to be covered with

glass fiber cloth & 28 g perforated aluminum sheet.

21.1.1 For Main AHU Rooms SQM 40

22.0 UNDER DECK INSULATION :

22.1 Under deck Insulation with 50 mm thick Fire Retardant Extruded

Polystrene Board having density of 32 Kg / M3 and thermal

conductivity of of 0.028 W/mK or better at 24 Deg C. The material

shall be stuck to slab by G.I. Screw along with washers only. The

Insulation sheets shall be further f ixed with G.I. wires diagonally 

fixed to each sheet.

SQM 2300

23.0 FRESH AIR ARRANGEMENTS FOR AHU ROOMS

23.1 Supply, installation, testing and commissioning of fresh air

arrangements with prefilter for AHU comprising of cowl/bird

screen/wire mesh filter / aerofoil aluminium damper complete with

following cross area.

23.1.1 600 CFM to 1500 CFM Sets 6

24.0 Supply, fabrication, Installation and testing of flexible connectionsconstructed flexible double canvas sleeve in accordance with

approved shop drawings and as per the specifications for each

Packaged & Ductable units. ( CHW AHU - FCU & Dx Idu )

Set 25

25.0 SITC of M.S. Fabrication Work duly painted as per specification( Apx

)Kgs 2500

26.0 PVC DRAIN

26.1 U PVC DRAIN PIPING DULY INSULATED WITH 9 MM NITRILE

RUBBER AND BOPP TAPE OF FOLLOWING SIZE DIA.

26.1.1 25 MM RMT 100

26.1.2 32 MM RMT R.O.

26.1.3 40 MM RMT R.O.26.1.4 50 MM RMT 50

Signature of Tenderer : Additional Chied Engineer ( Electrical) Ahmedabad Municipal Corporation

Name

Company Seal

Date Date

TOTAL FOR LOW SIDE VOLUME II

HVAC TENDER VOL_II_LOW SIDE_CHILLED WATER SYSTEM 14 OF 39

Page 16: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 16/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

Design, Supply, Installation, Testing, Commissioning, Performance

Validation of

1.0 DOUBLE SKINNED AIR HANDLING UNITS (Operation Theaters)

1.1 Supply installation testing and commissioning of Floor Mounted 0.6

mm GI Double Skinned Chilled Water AHU with Al anodized

thermal break frame structure injected with minimum 32 mm thick

40 kg/m3 PUF insulation; GI Panel shall be poweder coated from

both iner and outer side , the AHU shall comprising of: Mixing box

/ Anodized Aluminum Aerofoil Low leakage Fresh / Balancing /

Exhaust Air Damper / Pre-Filter section with EU-4 compliant

Prefilters for Return and Fresh Air / Coil section with ARI 410

compliant Cu Tube / Al finned 6 Row deep -13 FPI CWC Coil /

double skin sandwitch insulated removable SS 304 condensate

drain pan / Fine filter EU 5 / fine filter section with EU 9 compliant

/ Fan section with Hi static best efficiency Plug Fan driven by 

suitable pole Eff-1 TEFC Motor with Drive Package / Al aerofoil SA 

damper/Fire Retardant Canvass connection/Unit mounted on cushy 

foot Vibration isolators; Balance specifications as per tender. Refer

tender AHU Fabrication Scheme Drawing for understanding design

compliance of AHU

Following AHU acessories shall be supplied by AHU manufacturer

along with AHU and not site fabricated by HVAC contractor :

1/2/3/4

1. Diffential pressure switches with anounciation panel across all

filter banks ,

2. Variable Frequency Drive package suitable rating for SA Fan

motor , housed in AHU Starter Panel- IP 55 - 14G MS powdercoated Panel designed and rated to feed Fan Motor / Heaters

including all safeties (short circuit, overload protection) The panel

shall be duly internally wired and tested and provided with

necessary electrical hardware required for remote monitoring -

comprising of 2W/2P Auto manual switch / Potential free contacts

for On/Off Status, Trip Status & On/Off Command Relay for SA,

RA Motors & ReHeaters / additional Bypass status for VFD. Refer

Drawing 1-HVAC-19-20

3. Double Skin Heater Bank Chamber comprising of SS 304 spiral

strip heaters fitted with Porcelene blocks, Safety air stat & access

door for heater rating 2 KW x 3 bank

4.Supply, Installation, calibration and commissioning of Heater

Power controller integrated with above DDC and heater panel for

OT AHU heater power modulation based on return humidity inputin IP55 enclosure with loop power supply; duly internally wired and

tested (shall comprise of 1 AI / 1 AO as minimum)

SITC scope of AHU shall also comprise of suitable size Valve

Manifold comprising of 4 Butter Fly Valve, 1 Pressure Indipendent 2

way Balancing cum Control valve with actuator and strainer with

flenged end connection. The complete manifold shall be insulated

as specified and supply along with AHU from AHU manufacturers

factory.

Refer drawing - 1-HVAC-DET-01

HVAC VOLUME -III - HVAC LOW SIDE WORK FOR OT STERILE AREA

Unit Rates

in Rs.

Remarknit Qty

Total

Amount Rs.

r. No. Description

HVAC TENDER VOL III_ LOW SIDE WORK FOR OT STERILE AREA 15 OF 39

Page 17: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 17/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -III - HVAC LOW SIDE WORK FOR OT STERILE AREA

Unit Rates

in Rs.

Remarknit Qty

Total

Amount Rs.

r. No. Description

Design Factor : EU4/EU5/EU9 Face velocity : 500 FPM ; Cooling

Coil Face: 350 ; SA Fan Disc. 1750 FPM ; CHW EWT:6.6 deg C /

Target ADP: 10.5 deg C AHU with all above specification and acesories compliance with

following ratings

1.1.1 Load 10 TR / D-CFM: 3500 @ 150 mm WC / Fresh Air CFM 750 /

Ex CFM 500 CFM ( Roof Mounted ) / 2kw # 03 Heater Bank   Nos. 12

 AHU-10/11/12/14/15/16/18/19/20/22/23/24

1.1.2 100 % TFA AHU - Load 20 TR / D-CFM: 3500 @ 150 mm WC / /

Ex CFM 3500 CFM ( Roof Mounted ) / Additional Filter F1 at

Exhaust / 2kw # 03 Heater Bank

Nos. R.O.

 AHU - 14

1.1.3 SITC of 3500 CFM Smoke Spill Tube Axial Fan for OT Smoke

Exhaust. The scope includes the starter panel for with fire signal

activation arran ement.

Set 12

2.0 DOUBLE SKINNED AIR HANDLING UNITS ( ICUs Sterile

Corridore )

2.1 Supply installation testing and commissioning of Floor Mounted 0.6

mm GI Double Skinned Chilled Water AHU with Al anodized

thermal break frame structure injected with minimum 32 mm thick

40 kg/m3 PUF insulation; GI Panel shall be poweder coated from

both iner and outer side , the AHU shall comprising of: Mixing box

/ Anodized Aluminum Aerofoil Low leakage Fresh / Balancing /

Exhaust Air Damper / Pre-Filter section with EU-4 compliant

Prefilters for Return and Fresh Air / Coil section with ARI 410

compliant Cu Tube / Al finned 6 Row deep -13 FPI CWC Coil /

double skin sandwitch insulated removable SS 304 condensatedrain pan / Fine filter EU 7 / Fan section with Hi static best

efficiency Plug Fan driven by suitable pole Eff-1 TEFC Motor with

Drive Package / Al aerofoil SA damper/Fire Retardant Canvass

connection/Unit mounted on cushy foot Vibration isolators; Balance

specifications as per tender. Refer tender AHU Fabrication Scheme

Drawing for understanding design compliance of AHU

Following AHU acessories shall be supplied by AHU manufacturer

along with AHU and not site fabricated by HVAC contractor :

1/2/31. Diffential pressure switches with anounciation panel across all

filter banks ,2. Variable Frequency Drive package suitable rating for SA Fan

motor , housed in AHU Starter Panel- IP 55 - 14G MS powder

coated Panel designed and rated to feed Fan Motor / Heaters

including all safeties (short circuit, overload protection) The panelshall be duly internally wired and tested and provided with

necessary electrical hardware required for remote monitoring -

comprising of 2W/2P Auto manual switch / Potential free contacts

for On/Off Status, Trip Status & On/Off Command Relay for SA,

RA Motors & ReHeaters / additional Bypass status for VFD. Refer

Drawing 1-HVAC-19-20

HVAC TENDER VOL III_ LOW SIDE WORK FOR OT STERILE AREA 16 OF 39

Page 18: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 18/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -III - HVAC LOW SIDE WORK FOR OT STERILE AREA

Unit Rates

in Rs.

Remarknit Qty

Total

Amount Rs.

r. No. Description

SITC scope of AHU shall also comprise of suitable size Valve

Manifold comprising of 4 Butter Fly Valve, 1 Pressure Indipendent 2

way Balancing cum Control valve with actuator and strainer withflenged end connection. The complete manifold shall be insulated

as specified and supply along with AHU from AHU manufacturers

factory.

Refer drawing - 1-HVAC-DET-02

Design Factor : EU4/EU7 Face velocity : 500 FPM ; Cooling Coil

Face: 350 ; SA Fan Disc. 1750 FPM ; CHW EWT:6.6 deg C /

Tar et ADP: 10.5 de C AHU with all above specification and acesories compliance with

following ratings

2.1.1 Load 15 TR / D-CFM: 12000 @ 100 mm WC / Fresh Air CFM

1000 / Ex CFM 500 CFM / Roof To Mounted Unit  Nos. 4

 AHU- 3/4/5/6

2.1.2 Load 11 TR / D-CFM: 5300 @ 100 mm WC / Fresh Air CFM 320

/ Ex CFM 150 CFM / Loft MountedNos. 1

 AHU- 7

2.1.3 Load 9 TR / D-CFM: 4200 @ 100 mm WC / Fresh Air CFM 270 /

Ex CFM 150 CFM / Loft MountedNos. 1

 AHU- 8

2.1.4 Load 6 TR / D-CFM: 2750 @ 100 mm WC / Fresh Air CFM 190 /

Ex CFM 100 CFM / Loft MountedNos. 1

 AHU- 9

2.1.5.1 Load 11 TR DX Coil / D-CFM: 3500 @ 100 mm WC / Fresh Air

CFM 750 / Ex CFM 500 CFM / Loft Mounted OT AHU for GF

Minor OT

Nos. 2

Dx OT AHU - Minor OT GF Valve Manifold will not be part of supply in item 2.1.5

2.1.5.2 SITC of Dx Condensing Unit and Control Panel for Dx OT AHU of

Monir OT at Ground Floor

The scope includes the unit starters, thermostats with set point edit,

matching operating range, power and Control Cabling , Electronic

espansion valve etc. Single Point power shall be provided at this

control panel ( Part Of HVAC Contract Vol - VII )

Set of Dx Condensing Unit Rating 11 TR # 01 Nos. - fixed speed

twin scroll com ressor suitable for Minor OT AHU GF  Nos. 2

2.2 Refrigerant piping with hard drawn copper pipes with brazed joints

for liquid and suction lines duly insulated with required thicknessNitrile Rubber covered with Aluminum Foil interconnecting indoor &

outdoor unit with proper supports and accessories such as

refrigerant shutoff valves at compressor and liquid refrigerant

outlet. Metallic foil membrane shall be applied to provide

resistance against breakdown due to UV radiation for exposed

portion of the Rubber Insulation.

Rmt 36

Piping length shall be measured in single line distance between

indoor unit and out door unit ( Irrespective of Number of Ref.

circuits )

HVAC TENDER VOL III_ LOW SIDE WORK FOR OT STERILE AREA 17 OF 39

Page 19: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 19/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -III - HVAC LOW SIDE WORK FOR OT STERILE AREA

Unit Rates

in Rs.

Remarknit Qty

Total

Amount Rs.

r. No. Description

2.3 SITC of Double Skin Heater Bank Chamber comprising of SS 304

spiral strip heaters fitted with Porcelene blocks, Safety air stat &

access door; Chamber shall be installed downstream in-line with AHU dischar e duct

2.3.1 Heater Bank of : 3 Nos. # 3 kW Reheat Nos.   R.O.

2.4 Single Loop Digital Controller for AHUs

Supply, installation, powering, programming and commissioning of

minimum LCD Desplay Single Loop Digital PID Controller (

supporting PICV - Press Ind Cont Valve protocol ) with temperature

display, set point edit facility, supplied with matching RTD sensor

and 15 rmt cable connecting RTD sensor ; Controller shall be for

indoor application with Loop Power Supply provision mounted

within IP22 lockable enclosure

Set 21

3.0 OT AHU Accessories

3.1 Supply, installation testing and validation of Laminar Flow Units

(LFU) comprising of Terminal EU 13 HEPA Filters of 99.997%Efficiency down to 0.3 Micron particle size installed in zero leakage

SS frame with SS perforated plate type SA grille with SS VCD

3.1.1 LFU as above for 3500 CFM each Set   R.O.

LFU Size : 2170 x 2070 mm ( +/- 100mm )

Filter - 99.997 % Eff. . Dn to 0.3 Mic  ( EU-13 - Minipleat HEPA)

610 X 750  ( Filter Size ) # 02 Nos.

610 X 900  ( Filter Size ) # 04 Nos.

3.1.2 TERMINAL HEPA FILTER ( For Minor OT )

3.1.2.1   610 X 610 

( Filter Size )   Set   R.O.

3.1.3   TERMINAL HEPA FILTER BOX  

3.1.3.1   610 X 610  x 150 ( Filter Size )   Set   R.O.

The contractor shall submit the GA drawing with technical  

specification before ordering for the LFU unit.

4.0 SUPPLY, INSTALLATION, LEAK TESTING AND COMMISSIONING

OF AIR DISTRIBUTION AND DUCTING FOR FOLLOWING

GAUGES AS SPECIFIED

( For OT Application )

4.1 Supply and installation of GI, site fabricated rectangular ducts,

complete with soldered joints with necessary supports using thread

roads (as directed) and anchor bolts, supply air collars, vanes,splitters dampers duly painting of the ducts and as per specification

for Air Conditioned Areas.

4.1.1 1.2 mm Thick GI ducting SQM R.O.

4.1.2 1.0 mm Thick GI ducting SQM R.O.

4.1.3 0.8 mm Thick GI ducting SQM   450

4.1.4 0.63 mm Thick GI ducting SQM   1450

HVAC TENDER VOL III_ LOW SIDE WORK FOR OT STERILE AREA 18 OF 39

Page 20: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 20/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -III - HVAC LOW SIDE WORK FOR OT STERILE AREA

Unit Rates

in Rs.

Remarknit Qty

Total

Amount Rs.

r. No. Description

4.2 Supply and installation of GI, site fabricated rectangular ducts,

complete with MS frame structure and necessary supports usingthread roads (as directed) and anchor bolts, supply air collars,

vanes, splitters dampers duly painting of the ducts and as per

specification for Air Conditioned Areas.

4.2.1 1.2 mm Thick GI ducting SQM R.O

4.2.2 1.0 mm Thick GI ducting SQM R.O

4.2.3 0.8 mm Thick GI ducting SQM R.O

4.2.4 0.63 mm Thick GI ducting SQM R.O

4.3 PRE INSULATED DUCTING SHEET WORK

( For Sterile Lobby and ICUs )

4.3.1 Supply and Instal lation of :- 10 mm thick pre-insulated ducting

sheets of 4m X 1.2m having a PIR density of 82Kg/CuM with 80

Micron Aluminum facing on both the sides with stucco type finish,

duly Class ‘O’ certified as per BS along with the standard

installation accessories. (Thermal Insulation only)

SQM. R.O.

4.3.2 Supply and Installation of :- 20 mm thick pre-insulated ducting

sheets of 4m X 1.2m having a PIR density of 45Kg/CuM with 80

Micron Aluminum facing on both the sides with stucco type finish,

duly Class ‘O’ certified as per BS along with the standard

installation accessories.(Internal Ducting Not exposed to Sunlight

Ducting)

SQM.   2950

4.3.3 Supply and Installation of :- 30  mm thick pre-insulated ductingsheets of 4m X 1.2m having a PIR density of 50Kg/CuM with

80/200 Micron Aluminum facing on each side with stucco type

finish, duly Class ‘O’ certified as per BS along with the standard

installation accessories.(External Ducting exposed to Sunlight

Ducting)

SQM.   350

4.3.4 1.0 mm Thick GI Powder coated Factory fabricated front openable

risers

4.3.4.1 610 mm x 150 mm Set   R.O.

5.0 SUPPLY INSTALLATION TESTING AND COMMSSIONING OF

DIFFUSERS/ GRILLES AS PER FOLLOWING SCHEDULE

5.1 SS Perforated Supply / Return Air Grill for OT Areas SQM.   55

5.2 Alu. Powder Coated Supply/ Return Air Grill without VCD SQM. 5

5.3 G I Dampers shall be with opposed blade aerofoil blades and PVC

gears for smooth operation for volume control  SQM. 15

5.4 Alu. Powder Coated Supply Air Diffuser with VCD SQM. 15

5.5 Alu. Powder Coated Return Air Diffuser without VCD SQM. 15

HVAC TENDER VOL III_ LOW SIDE WORK FOR OT STERILE AREA 19 OF 39

Page 21: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 21/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -III - HVAC LOW SIDE WORK FOR OT STERILE AREA

Unit Rates

in Rs.

Remarknit Qty

Total

Amount Rs.

r. No. Description

6.0 DUCT THERMAL INSULATION

6.1 Thermal insulation of SA ducting internally with ' X ' mm thick ClassO Flame Retardant EPDM nitrile rubber having Thermal

Conductivity - 0.037 at 20 Deg C & Density - 60 Kg / M3 +/-

10%.

6.1.1 13 mm - For Supply air Ducting ( SA duct through F/c - loose return

)  SQM R.O.

6.1.2 19 mm - For Supply air Ducting ( SA Duct through Non AC Area )   SQM 1700

6.1.3 CBRI approved UL555 compliant Motorized Fire Dampers complete

with all accessories as specified  SQM 15

6.1.4 Thermal Insulation canvas coating with STARBOND 30-36 with

adhesive and sealant for forming a durable seal against air and

water leaka e for the ex osed ductin .

SQM   1023

7.0 Strip Type Air Heaters

7.1 2 kW rating Finned Strip type Air heaters installed in discharge duct

with porceilene blocks with safety air stat - 2 banks per AHU - 2 kW 

er bank

Set R.O.

8.0 Spare Motors for OT / Sterile AHU

8.1 Supply of Spare Motor 10 kW with Drive Package Nos. R.O.

8.2 Supply of Spare Motor 5.5 kW with Drive Package Nos. R.O.

8.3 Supply of Spare Motor 3.3 kW with Drive Package Nos. R.O.

9.0 Third Party Validation IQ / OQ / PQ documentation as specified

9.1 Third Party Generation & issue of IQ/OQ/PQ documentation for

Operation Theater HVAC System Design Qualification - (for

a roval of consultant common for all Ots & Clean Corridore )

Job 1

10.0 HVAC System Validation

10.1 Submission of Third Party Certified Measuring Equipment

Calibration reports for review/approval of consultant for

e ui ments to be used in Validation exercise

Job 1

10.2 Third Party Validation of HVAC system for Operation theater

complying to ISO14664 in line with approved design qualification

documents and procedure as specified in tender carried out with

above e ui ments Per OT basis

Job 14

Signature of Tenderer : Additional Chied Engineer ( Electrical)

 Ahmedabad Municipal Corporation

Name

Company Seal

Date Date

NOTE : HVAC CONTROL SHALL BE IN THE BMS BOQ PART FOR OT / STERILE CORRIDORE AND ICUS

TOTAL VOLUME - III

HVAC TENDER VOL III_ LOW SIDE WORK FOR OT STERILE AREA 20 OF 39

Page 22: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 22/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

1.0 BASEMENT VENTILATION SYSTEM

( Duct less ventilation System with Jet Dual Speed Fans )Supply, installation, testing, programming and

commissioning

1.1 Car park Ductless Ventilation / Jet fans for Lower Basement

as per attached specifications for normal ventilation

suitable for Normal ventilation and Smoke Extraction

application. The complete fan assembly with its Casing,

impeller & motor (not only the motor or one of the item)

shall be imported from manufacturer and certified as tested

for 250 Deg C for 2 hours operation.

The jet fans as shown in the drawing*. Each fan shall be

complete with dual speed motor. Casing shall be made of

Hot Dipped Galvanized Steel. The Motor shall run on the

electrical ower suitable for 1 Ph/ 50Hz.

1.1.1 Lower Basement dual speed jet fans NO. 18

1.2 Tube Axial fans as specified with GI cowl arrangement at

Exhaust point above ground with GI bird screen for

Exhaust Air for #

1.2.1 900 mm DIA / 17600 CFM / 18 mm WC Static Pressure

each certified as tested for 250 Deg C for 2 hours fire

o eration.

NO. 2

( 1 Normal Mode + 1 Fire Mode )

1.3 Dual Speed Tube Axial fans as specified with GI cowl

arrangement at Exhaust point above ground with GI bird

screen for Exhaust Air for #

1.3.1 900 or 1000mm DIA / 17600 CFM Normal Mode &

35200 CFM Fire Mode / 18 mm WC Static Pressure each

certified as tested for 250 Deg C for 2 hours fire operation.

NO. 3

1.4 GI Site Fabricated ducting work for Tube Axial Fan

connections as specified compiling to IS 655 fabrication

standards.

1.4.1 20G SQM   40

1.4.2 22 G SQM   80

1.4.3 24 G SQM   R.O.

1.5 Supply, programming, installation, testing and

commissioning of Integrated control and electrical

hardware for operation of Jet Fans and Tube Axial Fans in

Normal and CO/Fire Mode com risin of

HVAC VOLUME -IV - BILL OF QUANTITY FOR VENTILATION SYSTEMS

Sr. No. Description Qty

Total

Amount Rs.

nit

Unit Rates

in Rs.

Remark

HVAC TENDER VOL_IV_VENTILATION SYSTEMS 21 OF 39

Page 23: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 23/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -IV - BILL OF QUANTITY FOR VENTILATION SYSTEMS

Sr. No. Description Qty

Total

Amount Rs.

nit

Unit Rates

in Rs.

Remark

1.5.1 Duly internally wired and tested Electrical Power Panel with

feeders and starters suitable for operation of total Jet Fans

and total Tube Axial Fans with necessary accessories /relays / auto-manual provision etc as per above fan

uantit

1.5.1.1 For Lower Basement   SET 1

1.5.2 Control Module housed within the electrical panel

comprising of Programmable logic controller / signal wiring

/ hard wired integration with fan relays of Power panel for

control of 8 TA fans, 30 Jet fans and 8 CO sensors input

si nal

SET 1

1.5.3 Field CO sensors duly calibrated with calibration reports   NO. 4

Note: Fire status signal shall be provided from BMS

System HVAC Scope vol 6

1.5.4 MS Louvered Grill for basement Ventilation Exhaust out let

at elevation level on Ground floor. Louvers shall be 2.5" in

with and shall have 3" clearance between each louveres.

The scope coveres the fabricated support structure and site

spray painting of the louvers and support fabricated

structure.

SQM 12

1.6 Simulation package to execute CFD Analysis (Takeoff price)   Licen

se

1

1.7 Power & Control cabling between Jet Fans and Panel /

Signal & Control Cabling between CO Sensors and Jet Fan

Panel PLC/Power Cabling and Control cabling betweenTAF Panel and TA Fans

LOT 1

1.8 Installation / Testing / Commissioning of the system   LOT 1

1.9 Programming and customization of hardware package   LOT 1

2.0 PLANT ROOM VENTILATION SYSTEM

Supply, installation, testing, programming and

commissionin

2.1 Tube Axial Type fans for plant room as per attached

specifications for normal ventilation .The complete fan

assembly with its Casing, impeller & motor (not only the

motor or one of the item) Complete with starter and

electrical termination of the same

Necessary starter shall be in scope of HVAC Contract.

Power cable will be available up to starter panel. The

starter should be capable to run automatically in case of

fire.

2.1.1 5000 CFM 18 mm TSP Tube Axial Fan ( 1.5 KW Connected

Load ) - HVAC AND ELE ROOM VENTILATION

NO. 2

HVAC TENDER VOL_IV_VENTILATION SYSTEMS 22 OF 39

Page 24: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 24/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -IV - BILL OF QUANTITY FOR VENTILATION SYSTEMS

Sr. No. Description Qty

Total

Amount Rs.

nit

Unit Rates

in Rs.

Remark

3.0 TOILET / CSSD / VENTILATION FANS

3.1 Supply and Installation of Floor Mounted Cabinet TypeCentrifugal Exhaust Air Fan Unit complete with MS zinc

sprayed / powder coated DIDW Centrifugal Impeller Fan

with motor for maximum speed duty point of Specified CFM

and Static pressure , complete with drive package

comprising of V belts and Grooved pulley pair keyed to

motor and fan shafts.

The Fan units shall be designed as per the criteria

mentioned in the specifications and selected so as to

operate in the best efficiency zone; the units shall be

statically and dynamically balanced.

Necessary starter shall be in scope of HVAC Contract.

Power cable will be available up to starter panel. ( Part of

 Volume VII HVAC Job )

3.1.1 4500 CFM / 60 mm TSP SET 1

3.1.2 9800 CFM / 60 mm TSP SET 2

3.1.3 1200 CFM / 60 mm TSP SET 1

3.1.4 17000 CFM / 60 mm TSP SET 1

3.1.5 2500 CFM / 60 mm TSP SET 1

3.1.6 6800 CFM / 60 mm TSP SET 1

3.1.7 5000 CFM / 60 mm TSP SET 1

4.0 SITC OF CABINET TYPE INLINE FAN

4.1 750 CFM / 50 mm ESP NOS 1

4.2 1000 CFM / 50 mm ESP NOS 1

4.3 250 CFM / 50 mm ESP NOS 1

5.0 AIR DISTRUBUTION FOR VENTILATION SYSTEM

5.1 Supply, fabrication and installation of GI air distribution

ducting / supply air grilles as per layouts and quantity 

mentioned below and as s ecified in main tender

5.1.1 20G SQM R.O.

5.1.2 22G SQM 340

5.1.3 24G SQM 1140

5.2 Alu. Powder Coated Supply Air Grill with VCD finished to

match the interiors pre-approved by Architect / Client

before su l

SQM 15

HVAC TENDER VOL_IV_VENTILATION SYSTEMS 23 OF 39

Page 25: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 25/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME -IV - BILL OF QUANTITY FOR VENTILATION SYSTEMS

Sr. No. Description Qty

Total

Amount Rs.

nit

Unit Rates

in Rs.

Remark

5.3 G I Dampers shall be with opposed blade aerofoil blades

and PVC gears for smooth operation for volume control

SQM 5

5.4 Double skin water proof machine canvass connection Set 12

Signature of Tenderer : Additional Chied Engineer ( Electrical) Ahmedabad Municipal Corporation

Name

Company Seal

Date Date

Note : (i) Quantities and Motor Ratings of Tube Axial Fans as well as Jet Fans are indicative; bidder to confirm exact

quantities based on the CFD analysis report, ratings of these items as per their product selection charts prior to

bidding after detailed design calculations – to be submitted as a part of tender submission & (ii) The PLC/DDC

Controller offered for the above control requirements shall have Open Protocol standards to integrate car park

ventilation system with central BMS in future; the offered controller shall support BACNet / LonWorks protocols for

this purpose. Controller supporting protocols other than above shall be provided with suitable Integrator hardware

for seam less integration.

NOTE : HVAC CONTROL SHALL BE IN THE BMS BOQ PART FOR OT / STERILE CORRIDORE AND ICUS

(iii)Quantity of CO sensors shall be as per vendor requirement to maintain average CO ppm level below 100mg at

all times and indicated clearly in the offer

TOTAL FOR VENTILATION SYSTEM

HVAC TENDER VOL_IV_VENTILATION SYSTEMS 24 OF 39

Page 26: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 26/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME - V - BILL OF QUANTITY FOR DX AIR COOLED SPLIT AC SYSTEM

SITC OF DX AIR COOLED SPLIT AC SYSTEM

1.0 CEILING SUSPENDED DUCTABLE SPLIT UNIT

1.1 Supply, Installation, testing & commissioning of MICROPROSSER BASED air

cooled Ductable Split air condit ioning units; each unit shall comprise of

separate Indoor and outdoor unit specified as under:Indoor (fan coil) unit shall be ceiling suspended type comprising of DX coil with

finned copper tubes, centrifugal Fan unit with motor; fan unit shall have proper

insulated and leak proof condensate base connected to drain piping with suitable

trap and laid upto nearest drain point designed to ensure zero leakage; the fan

assembly shall be dynamically balance for low vibration and low noise type

design.

The outdoor (condensing unit) shall be of Corrosion resistant Galvanized powder

coated or equivalent Sheet steel low vibration assembly installed on suitable

vibration isolators and comprising of energy efficient Scroll compressor with

controls such as thermal protector, HP/LP cutouts, Pressure relief valve; the

outdoor unit shall also comprise of finned tube air cooled condenser and

condenser fan unit; the units shall have integral refrigerant copper piping withincompressor and condenser and accessories such as refrigerant shutoff valves at

compressor / compressors and liquid refrigerant outlet if required & filter dryer;

Cooling fans shall have protective metal frame.

Unit Starter panel one for each Split unit rated under item 1.1 and 1.2 – equipped

with necessary metering and protection devices including but not limited to short-

circuit, overload, single phase prevention; The components shall be housed in 14

G or higher powder coated IP 55 enclosure duly internally wired and tested -

Siemens Grey shade exterior finish; the starters shall be selected for vendor's drive

ratings (Bidder to furnish the Starter Panel GA and Wiring diagram along with the

bid)

Cu power cabling between Starters for Compressor motor, condenser fan and

 AHU fan; the scope shall also cover supply and laying of Cu control wiring, 6

SWG G.I wire loop earthing on surface along with other cable as reqd, external

wiring, between AC unit starters, unit & condensing units. The unit shall be

suitable for 415 ± 10 % volts, 50 Hz, 3 phase AC supply and IP55 Protection.

Cabling for Condenser fans, AHU fan, Compressor motors shall be duly laid on

cable tray and tray supports between ceiling unit and condensing unit.

The above specified units shall be supplied as per following schedule installed

at locations as mentioned in the layouts broadly as per following schedule:

1.1.1 3 TR Nominal Capacity Ductable Split Unit SET R.O.

1.1.2 4 TR Nominal Capacity Ductable Split Unit SET R.O.

1.1.3 5.5 TR Nominal Capacity Ductable Split Unit ( Scroll Compressor ) SET 3

1.1.4 8.5 TR Nominal Capacity Ductable Split Unit ( Having Twin Scroll Compressor) SET 1

1.1.5 11 TR Nominal Capacity Ductable Split Unit ( Having Twin Scroll Compressor) SET 1

1.1.6 8.5 TR Nominal Capacity Ductable Split Unit ( Having Twin Scroll Compressor - 6

Row Coil )

SET R.O.

1.2 SITC of 3 Star + Rating Hi Wall Mounted Split AC Unit , Having decorative wall

mounted indoor unit with Cordless remote control ler. The unit shall have

extended 4 years compressor warranty. ( Refrigerent piping rates are required to

be uoted se eratl b contractor

1.2.1 1.5 TR Hi Wall Split AC Unit ( 3 Star Rated Unit ) SET 1

1.2.2 2 TR Hi Wall Split AC Unit ( 3 Star Rated Unit ) SET 29

Unit Rates

in Rs.

r. No. Description Unit Remarkty

Total Amount

Rs.

HVAC TENDER VOL- V_DX SYSTEM 25 OF 39

Page 27: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 27/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME - V - BILL OF QUANTITY FOR DX AIR COOLED SPLIT AC SYSTEM

Unit Rates

in Rs.

r. No. Description Unit Remarkty

Total Amount

Rs.

2.0 Refrigeration Piping, Control Cabling , Insulation Refrigerant Charge of Air

Conditioning Units

Refrigerant copper piping duly insulated with required thickness closed cellelastomeric Nitrile Rubber covered with Aluminum Foil interconnecting indoor &

outdoor unit and accessories such as refrigerant shutoff valves at compressor and

liquid refrigerant outlet. Metallic foil membrane shall be applied to provide

resistance against breakdown due to UV radiation for exposed portion of the

Rubber Insulation.

The refrigerant piping shall be laid with proper supports as required.The said quantities are single line measurement between indoor unit and out door

unit irrespective of number of refrigerant circuit in a ductable or package ac unit

2.1 For 11 TR Ductable Split AC Unit Rmt 15

2.2 For 8.5 TR Ductable Split AC Unit Rmt 15

2.3 For 5.5 TR Ductable Split AC Unit Rmt 45

2.8 For 2 TR High Wall Split AC Unit Rmt 348

2.9 For 1.5 TR High Wall Split AC Unit Rmt 12

SITC OF AIR DISTRIBUTION SYSTEM

3.0 SHEET METAL WORK

3.1 SUPPLY, INSTALLATION, LEAK TESTING AND COMMISSIONING OF AIR

DISTRIBUTION AND DUCTING FOR FOLLOWING GAUGES AS SPECIFIED

Supply and installation of GI, factory fabricated rectangular ducts, complete with

MS flanges and bracing (as specified), necessary supports using thread roads (as

directed) and anchor bolts, supply air collars, vanes, split ters dampers duly 

painting of the ducts and as per specification for Air Conditioned Areas

3.1.1 1.2 mm Thick GI ducting SQM. R.O.

3.1.2 1.0 mm Thick GI ducting SQM. R.O.

3.1.3 0.8 mm Thick GI ducting SQM. R.O.

3.1.4 0.63 mm Thick GI ducting SQM. R.O.

3.2 PRE INSULATED DUCTING SHEET WORK

3.2.1 Supply and Installation of :- 10 mm thick pre-insulated ducting sheets of 4m X 

1.2m having a PIR density of 82Kg/CuM with 80 Micron Aluminum facing on

both the sides with stucco type finish, duly Class ‘O’ certified as per BS along with

the standard installation accessories. Thermal Insulation onl

SQM. R.O.

3.2.2 Supply and Installation of:- 20 mm thick pre-insulated ducting sheets of 4m X 1.2m having a PIR density of 45Kg/CuM with 80 Micron Aluminum facing on

both the sides with stucco type finish, duly Class ‘O’ certified as per BS along with

the standard installation accessories.(Internal Ducting Not exposed to Sunlight

Ductin

SQM. 644

3.2.3 Supply and Installation of :- 30  mm thick pre-insulated ducting sheets of 4m X

1.2m having a PIR density of 50Kg/CuM with 80/200 Micron Aluminum facing

on each side with stucco type finish, duly Class ‘O’ certified as per BS along with

the standard installation accessories.(External Ducting not exposed to Sunlight

Ductin

SQM. R.O.

HVAC TENDER VOL- V_DX SYSTEM 26 OF 39

Page 28: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 28/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME - V - BILL OF QUANTITY FOR DX AIR COOLED SPLIT AC SYSTEM

Unit Rates

in Rs.

r. No. Description Unit Remarkty

Total Amount

Rs.

4.0 CANVAS CONNECTIONS

4.1 Supply, fabrication, Installation and testing of flexible connections constructed

flexible double canvas sleeve in accordance with approved shop drawings and asper the specifications for each Packaged & Ductable units.

SET 5

5.0 SUPPLY INSTALLATION TESTING AND COMMSSIONING OF DIFFUSERS/

GRILLES AS PER FOLLOWING SCHEDULE

5.1 1000 CFM Rating Jet Diffusers SET R.O.

5.2 Alu. Powder Coated Supply Air Diffuser with VCD SQM. 5

5.3 Alu. Powder Coated Supply Air Diffuser without VCD SQM. 5

5.4 Alu. Powder Coated Supply Air Grill with VCD SQM. 1.5

5.5 Alu. Powder Coated Supply Air Grill without VCD SQM. 1.5

6.0 SUPPLY, INSTALLATION, TESTING, COMMISSIONING OF GI POWDER

COATED DUCT DAMPERS

6.1 G I Dampers shall be with opposed blade aerofoil blades and PVC gears for

smooth operation for volume control

SQM. 5

6.2 Fusible Link Type Fire Dampers installed at Wall crossings in SA/ RA ducts ( At all

wall crossings )

SQM. 0.5

7.0 DUCT THERMAL INSULATION

7.1 Thermal insulation of SA ducting internally with ' X ' mm thick Class O Flame

Retardant EPDM nitrile rubber having Thermal Conductivity - 0.037 at 20 Deg C

& Density - 60 Kg / M3 +/- 10%.

7.1.1 13 mm For Supply air Ducting ( SA duct through F/c loose return) SQM. R.O.

7.1.2 19 mm For Supply air Ducting ( SA duct through Non AC Area ) SQM. R.O.

8.0 SUPPLY AIR DUCT ACCOUTIC INSULATION ( for Comfort )

Supply and fixing of acoustic lining inside sheet metal ducts with 13mm / 19 mm

thick class O flame retardant sound absorbing accosound elastrometric nitrile

rubber of density 150Kg/cub.mtr and thermal conductivity of 0.036 W/m k

8.1 Upto first 4 M of SA duct SQM. 55

9.0 PACKAGE AC ROOM ACCOUSTIC INSULATION

9.1 Acoustic insulation for plant room using 50mm thick Twiga 300 rigid board stick

and GI frame work. Insulation to be covered with glass fiber cloth & 28 g

perforated aluminum sheet.

9.1.1 For Main AHU Rooms SQM. R.O.

10.0 UNDER DECK INSULATION :

10.1 Under deck Insulation with 50 mm thick Fire Retardant Extruded Polystrene Board

having density of 32 Kg / M3 and thermal conductivity of of 0.028 W/mK or

better at 24 Deg C. The material shall be stuck to slab by G.I. Screw along with

washers only. The Insulation sheets shall be further fixed with G.I. wires

dia onall fixed to each sheet.

SQM. R.O.

HVAC TENDER VOL- V_DX SYSTEM 27 OF 39

Page 29: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 29/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME - V - BILL OF QUANTITY FOR DX AIR COOLED SPLIT AC SYSTEM

Unit Rates

in Rs.

r. No. Description Unit Remarkty

Total Amount

Rs.

11.0 FRESH AIR ARRANGEMENTS FOR AHU ROOMS

Supply, installation, testing and commissioning of fresh air arrangements with

prefilter for AHU comprising of cowl/bird screen/wire mesh filter complete withfollowing cross area.

11.1 600 CFM to 1500 CFM SET 8

12.0 PVC DRAIN

U PVC DRAIN PIPING DULY INSULATED WITH 9 MM NITRILE RUBBER AND BOPP

TAPE OF FOLLOWING SIZE DIA.

12.1 25 MM RMT 210

12.2 32 MM RMT R.O.

12.3 40 MM RMT 25

12.4 50 MM RMT R.O.

Signature of Tenderer : Additional Chied Engineer ( Electrical) Ahmedabad Municipal Corporation

Name

Company Seal

Date Date

GRAND TOTAL FOR VOL V

HVAC TENDER VOL- V_DX SYSTEM 28 OF 39

Page 30: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 30/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

1.0 BAS System Monitoring Hardwares

1.1 Central Work Station Server/Client with Core 2 Duo Intel processor with

minimum 200Gb HDD, 1 GB RAM, 15" TFT Monitor, DVD Writer, two serial

and one parallel ports, multimedia speakers, infrared mouse; Work station

shall be preloaded with requisite MS Windows Licensed software compatible

with the offered BMS latform

1 No

1.2 600 dpi or better A3 size lazer colour printer R.O. No

1.3 Managable 24 Port Network Switch for integration of IP based DDC with

Front End BAS

2 Nos

1.4 Ethernet Router R/O

2.0 Supply, installation, configuration, programming & customization of BAS

 Development and Runtime Softwares

2.1 Development Version (server version with full function edit facility) unlimitedtags IBMS sof tware support ing LONoverIP / BACNEToverIP with Web

browser as specified with all monitoring/control modules including but not

l imited to full funct ion Report / Trending / Alarms / MIMIC / LAN / WAN

modules

1 UserLicense

2.2 Run time version BMS software for "view only" application 1 License

2.3 Additional email alarm notification module with user capability - 5 User 1 License

2.4 Sof tware customizat ion for providing custmized Report formats / MIMCS /

 Alarm / Trend / History formats to client's satisfaction

1 Job

2.5 Open Protocol Integrators supporting IP compatible for

BACNET/LonWorks/modbus rtu output meeting Vendor's communication

platform

2.5.1 For 2 sets of Chillers 1 No

2.5.2 For Variable Speed Pumping System 1 No

2.5.3 For Variable Speed Cooling Tower Fan System 1 No

2.5.4 For 2 sets of Multifunction Meters 1 No

3.0 DDC Controller and hardware: Supply, installation, testing, commissioning

of

3.1 Onboard IP based Direct Digital controllers as specified with 32 bit

microprocesser supporting either BACNetoverIP/LonoverIP/Bacnet Ms/tp

communication platform, designed for the required IO paramteres(as

specified in this tender)m support ing realtime functions, peer-2-peer

communication and housed in IP 54 MS powder coated panel duly internally 

wired and tested; the DDCs offered shall be with webserver and can be

locall connected to a netbook la to for control and monitorin - one for

3.1.1 DDC System No. 1 for Plant Room as per Plantoom Room IO summary 1 Set

3.1.2 DDC System No. 2 to 13 for Terrace OT AHUs as per IO summary 12 Set

3.1.3 DDC System No. 14 for Minor OT per IO summary 1 Set

4.0 Field Devices duly wired to DDC: supply, installat ion, cal ibrat ion, testing

and commissioning with al l fixtures/accessories/tubing complete as

required

4.1 For Plant Room

Supply, installation, Programming, Configuration,Calibration, Commissioning, of BAS System Hardwares and Customization Of software as

described below

VOLUME VI : BILL OF QUANTITY FOR BUILDING AUTOMATION SYSTEM

Sr. No. Description Unit Qty

Unit Rates in

Rs.

Total Amount

Rs.

HVAC TENDER VOL-VI - BAS SYSTEM 29 of 39

Page 31: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 31/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

Supply, installation, Programming, Configuration,Calibration, Commissioning, of BAS System Hardwares and Customization Of software as

described below

VOLUME VI : BILL OF QUANTITY FOR BUILDING AUTOMATION SYSTEM

Sr. No. Description Unit Qty

Unit Rates in

R

Total Amount

R4.1.1 Pipe mounted Resistance Temperature Detectors for Chilled and Cooling

water inlet out temperatures & header temp with SS thermowells setcomplete

12 Nos

4.1.2 Absolute Pressure water Transmitter for Chiller and Condenser water inlet /

outlet with fixtures

8 Nos

4.1.3 Absolute Pressure water transmitter for pump discharge pressure -

primary/secondary/Cooling water pumps with fixtures

9 Nos

4.1.4 Absolute Pressure water transmitter for pump return header pressure with

fixtures

R.O. Nos

4.1.5 Ultrasonic type clamp on type Flow meter for Chilled Water flow

measurement instal led on header with 10 Dia straight length_200 mm

Header with fixtures. Should be BMS compatible, give total flow and flow

rate and retain last value in the memor in case of ower losss.

1 No

4.1.6 Ambient T+Rh transmitter (wall mount type for outdoor duty) with fixtures 1 No

4.1.7 Water DP switches for CHW / CDS Pumps with fixtures 9 Nos

4.1.8 Butterfly valves with On/Off type actuator (for auto-isolat ion of chi llers)

installed at the outletFor Chiller_150 mm NB size R.O. NosFor Condenser_200 mm NB size R.O. Nos

4.1.9 Digital Energy Meter supporting MODBUS protocol for main HVAC panel R.O. No

a CT/PT hardware for Panel Integration CT - 0-5V, 5% Accuracy R/O Set

4.1.10 Cooling Tower Sump level switch with SS moving and contact parts including

fixtures as per manufacturer

2 Nos

4.1.11 Ambient CO2 Sensor with fixtures R/O

1.1.12 Cooling tower sump water temprature sensor 2 Set

4.2 CHW AHU for OT

4.2.1 Filter & Fan Status Air DP Switch complete with fixtures, tubing, connectors

complete

63 Nos

4.2.2 Air Static Pressure Transmitters 13 No

4.2.3 Duct Mounted Return Air Temperature + Humidity Transmitter with all

fixtures complete

13 Nos

4.2.3.1 AHU Chilled Water Inlet Outlet Sensors with SS Thermowells and fixtures

complete

R/O

4.2.4 2 way pressure independent type auto balancing and control valve withmodulating actuator

4.2.4.1 25 mm NB R/O

4.2.4.2 32 mm NB R/O

4.2.4.3 40 mm NB R/O

4.2.4.4 50 mm NB R/O

4.2.4.5 65 mm NB R/O

HVAC TENDER VOL-VI - BAS SYSTEM 30 of 39

Page 32: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 32/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

Supply, installation, Programming, Configuration,Calibration, Commissioning, of BAS System Hardwares and Customization Of software as

described below

VOLUME VI : BILL OF QUANTITY FOR BUILDING AUTOMATION SYSTEM

Sr. No. Description Unit Qty

Unit Rates in

R

Total Amount

R4.2.4.6 80 mm NB R/O

4.2.5 Duct mounted Air CO2 senors R/O

4.2.6 Selfpowered wall mounted water proof Temp and Rh Display Stations in 6

inch size with backlit facility compatible to be powerd on 230V AC complet

with all accessories

1 Nos

4.3 Spring Return type Fire rated Actuators (for OT Smoke Isolation dampers)

with linkages complete

4.3.1 4 Nm R/O

4.3.2 8 Nm 26 Nos

4.3.3 12 Nm R/O

4.4 Damper Actuators  for Fresh air

4.4.1 4 Nm R/O

4.4.2 8 Nm R/O

4.5 Calibration Work

4.5.1 Calibration of Field devices supplied at site with documentation 1 Lot

4.6 Cabling and Conduits

4.6.1 Copper Flexible Conductor shielded ( Aluminium Mylar with Atc Drain wire

of 0.5 Sq. mm),PVC insulated,PVCSheathed Cable as per IS : 694,with IP 54

 ABS Plastic Junction Box Din rail mounted Elmex Terminals.

Rmt

4.6.1.1 2Cx1.0 sq. mm 1500 Rmt

4.6.1.2 3Cx1.0 sq mm 1000 Rmt

4.6.1.3 4Cx1.0 sq mm 600 Rmt

4.6.1.4 8Cx1.0 sq mm R/O Rmt

4.6.2 Supply and installation of 2 Px 1.5 sq.mm twisted pair individual screened,&

overall Screened PVC insulated,PVC sheathed ,Communication cable

R/O Rmt

4.6.3 Communication Cable CAT - 6A with Jacks,Patch chords,all other

accessories

2000 Rmt

4.6.4 Supply instal lat ion of PVC conduits with al l bends/fi ttings complete for

following size for above cables

4.6.4.1 20 NB 1500 Rmt

4.6.4.2 25 NB 1000 Rmt

4.6.4.3 32 NB R/O Rmt

4.6.5 Supply/laying of GI perforated cable tray

4.6.5.1 100 x 25 150 Rmt

4.6.5.2 200 x 50 R/O Rmt

4.6.5.3 300 x 50 R/O Rmt

HVAC TENDER VOL-VI - BAS SYSTEM 31 of 39

Page 33: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 33/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

Supply, installation, Programming, Configuration,Calibration, Commissioning, of BAS System Hardwares and Customization Of software as

described below

VOLUME VI : BILL OF QUANTITY FOR BUILDING AUTOMATION SYSTEM

Sr. No. Description Unit Qty

Unit Rates in

R

Total Amount

R

4.7 Documentation and Training

4.7.1 Generation of Validation Reports for OT areas prior to handing over 1 Lot

4.7.2 System Operational Training Session to Client - 7 days @ 6 hrs per day 1 Lot

TOTAL

Signature of Tenderer : Additional Chied Engineer ( Electrical) Ahmedabad Municipal Corporation

Name

Company Seal

Date Date

HVAC TENDER VOL-VI - BAS SYSTEM 32 of 39

Page 34: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 34/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

1.0 HVAC PANEL

Supply,Installation, testing and commissioning of Panel Board as per IS ,

Technical Specifications & respective drawings.The unit rate for each item shall include

1) Supply & delivery of the panels at the site.2) Shifting of panels from site store to the suitable location.3) Installation of panel in Electric room or Location suggested by client within

campus including removing packing.4) Earthing all components, frame etc. to a common internal earth bar.5) Supply & fixing all accessories and supporting structure.6) Supply and fixing of M.S. 100 mm. channels for fixing the panels

connection, testing & commissioning.7) The panels shall be compatible to BMS whereever shown in the SLD.8) Checking of Internal connection and wiring, operation of switches, starter,

MCCB, MCB, relays, contactors etc.9) Supply of necessary tools, hardware, testing hardware, testing equipment

etc.10) Electrical contractor shall carry out the insulation test at site & all the

readings shall be submitted in duplicate to the consultant or engineer-in-

charge.

1.1 Supply, installation, testing and commissioning of Ground Floor HVAC

Panel as per the IS, specification and single line diagram No. 9-E-DG-1

No. 1

1.2 Supply, installation, testing and commissioning of First Floor HVAC Panel

as per the IS, specification and single line diagram No. 9-E-DG-2

No. R.O.

1.6 Supply, Installation, Testing and commissioning of 32 A TPN MCB with IP23

Enclosure as per the IS, Specification. Suitable termination arrangement to

be provided to allow for termination of cable size 4Cx16 Sq. mm. Al. XLPE

 Armoured Cable both as incomer and outgoing.

No. 1

1.7 Supply, Installation, Testing and commissioning of 25 A TPN MCB with IP23

Enclosure as per the IS, Specification. Suitable termination arrangement to

be provided to allow for termination of cable size 4Cx16 Sq. mm. Al. XLPE

 Armoured Cable both as incomer and outgoing.

No. 30

1.8 Supply, Installation, Testing and commissioning of Eigth Floor HVAC panel

as per the IS, Specification and Single Line Diagram No. 9-E-DG-6

No. 1

1.9 Supply, Installation, Testing and commissioning of Ninth Floor HVAC panel

as per the IS, Specification and Single Line Diagram No. 9-E-DG-7

No. 1

1.10 Supply, Installation, Testing and commissioning of Tenth Floor HVAC panel

as per the IS, Specification and Single Line Diagram No. 9-E-DG-8

No. 1

1.11 Supply, Installation, Testing and commissioning of Roof Floor HVAC panel

as per the IS, Specification and Single Line Diagram No. 9-E-DG-9

No. 1

1.12 Supply, Installation, Testing and commissioning of Roof Floor Chiller panel

as per the IS, Specification and Single Line Diagram No. 9-E-DG-10

No. 1

VOLUME VII : BILL OF QUANTITY FOR ELECTICAL WORK FOR THE PROPOSED HVAC SYSTEM

Sr. No. Description Unit Qty

Unit Rates

in Rs.

Total

Amount

Rs.

HVAC TENDER VOL-VII-ELECTRICAL DISTRIBUTION 33 of 39

Page 35: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 35/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

VOLUME VII : BILL OF QUANTITY FOR ELECTICAL WORK FOR THE PROPOSED HVAC SYSTEM

Unit Rates

Total

2.0 MEDIUM VOLTAGE CABLES & END TERMINATIONS

MEDIUM VOLTAGE CABLE

2.1 Supply, laying, connection, testing and commissioning of heavy duty  

medium voltage cables as per Specification and IS 7098 PART I XLPE

insulated and outer sheeth of FRLS and inner PVC sheeth stranded AL

conductor unless or otherwise specified. The copper cables shall be

confirming to IS:1554, PVC insulated and sheathed, stranded copper

conductors. The cable shall be laid underground when laid outside the

building. It shall be laid in prepared trench / cable tray / wall clamped /

duct when laid inside the building. The cable shall be laid with RCC Hume

pipe at the entry of the building. The unit rate shall include

The unit rate shall include1) Delivery of the cable at si te.

2) Loading, unloading and delivery of the cable at site store.(If applicable)3) Shifting of cable from site store to place of installation.4) Supply & fixing of cable G I clamps(With GI Screw) ,Nylon Tie, brackets,

supports, route markers etc. where ever required to fix the cables safely.

5) Earthing the glands and armouring with earthing clamp and jumper and

also connecting to common earth bar.6) Excavation, back fill ing and leveling of ground along with supply & laying of

fine sand, protection bricks and other necessary civil material for laying

cables outside the buildin .7) Testing of insulation and continuity of cable and submission of reports to

the client's representative.

2.1.1 3.5 c x 240 sq.mm. AL XLPE Armoured cable (Incomer & CHILLERS) MTR 35

2.1.2 3.5 c x 185 sq.mm. AL XLPE Armoured cable MTR 885

2.1.3 3.5 c x 120 sq. mm. Al. XLPE cable MTR 150

2.1.4 3.5 c x 95 sq. mm. Al. XLPE cable MTR 25

2.1.5 3.5 c x 50 sq. mm. Al. XLPE cable MTR 185

2.1.6 3.5 c x 25 sq. mm. Al. XLPE cable MTR 70

2.1.7 4 c x 16 Sq. mm Al. XLPE Cable MTR 1125

2.1.8 4 c x 10 sq.mm. Al.XLPE cable MTR 925

2.1.9 4 c x 6 sq.mm. Cu.YWY cable MTR 125

2.1.10 4 c x 4 sq.mm. Cu.YWY cable MTR 1320

2.1.11 4 c x 2.5 sq.mm. Cu.YWY cable MTR 290

2.1.12 3 c x 16 sq.mm. Al.XLPE cable MTR 190

2.1.13 3 c x 10 sq.mm. Al.XLPE cable MTR 270

2.1.14 3 c x 6 sq.mm. Cu. YWY cable MTR 80

2.1.15 3 c x 4 sq.mm. Cu. YWY cable MTR 120

2.1.16 3 c x 2.5 sq.mm. Cu. YWY cable MTR 130

HVAC TENDER VOL-VII-ELECTRICAL DISTRIBUTION 34 of 39

Page 36: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 36/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

VOLUME VII : BILL OF QUANTITY FOR ELECTICAL WORK FOR THE PROPOSED HVAC SYSTEM

Unit Rates

Total

2.2 CABLE END TERMINATION AND CONNECTION :

Supply, fixing, connection, testing & commissioning of single compressionbrass cable glands and crimping type Bimetalic lugs / sockets with necessary

tools & equipments as specified in specifications & IS. The glands and lugs /

sockets shall be suitable

2.2.1 3.5 c x 240 sq.mm. AL XLPE Armoured cable (Incomer & CHILLERS) No. 2

2.2.2 3.5 c x 185 sq. mm. Al. XLPE cable No. 16

2.2.3 3.5 c x 95 sq. mm. Al. XLPE cable No. 2

2.2.4 3.5 c x 50 sq. mm. Al. XLPE cable No. 4

2.2.5 3.5 c x 25 sq. mm. Al. XLPE cable No. 2

2.2.6 4 c x 16 Sq. mm Al. XLPE Cable No. 28

2.2.7 4 c x 10 sq.mm. Al.XLPE cable No. 22

2.2.8 4 c x 6 sq.mm. Cu.YWY cable No. 4

2.2.9 4 c x 4 sq.mm. Cu.YWY cable No. 48

2.2.10 4 c x 2.5 sq.mm. Cu.YWY cable No. 10

2.2.11 3 c x 16 sq.mm. Al.XLPE cable No. 6

2.2.12 3 c x 10 sq.mm. Al.XLPE cable No. 18

2.2.13 3 c x 6 sq.mm. Cu. YWY cable No. 4

2.2.14 3 c x 4 sq.mm. Cu. YWY cable No. 12

2.2.15 3 c x 2.5 sq.mm. Cu. YWY cable No. 8

3.0 INTERNAL WIRING - AC DX SPLIT UNITS

3.1 Supply, laying, connection, testing and commissioning of 600V FR PVC Cu.

Flexible wires as per Specification. The rate shall include, all necessory 

accessories, lu s, ferrules etc.

3.1.1 6 Sq.mm. Cu. Flexibles Mts. 7670

3.2 Supply, laying, connection, testing and commissioning of PVC casing

caping, with all necessary bends, clamps, screws,and required accessories

to complete the work.

3.2.2 1 inch wide PVC casing caping Mts 1790

TOTAL FOR VOLUME VII - ELECTRICAL JOB

Signature of Tenderer : Additional Chied Engineer ( Electric Ahmedabad Municipal Corporation

Name

Company Seal

Date Date

HVAC TENDER VOL-VII-ELECTRICAL DISTRIBUTION 35 of 39

Page 37: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 37/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

 SR.NO DESCRIPTION OF ITEM QTY UNIT

UNIT RATE

RS.

AMOUNT

RS.

1Floating Foundation for hvac equipment on roof

providing & laying ordinary cement concrete 1:2:4 (1 cement : 2

coarse sand : 4 graded stone aggregates 20 mm nominal size) and

finishing smooth with curing etc.complete including the cost of form

work but excluding the cost of reinforcement for R.C.C. work. The

same shall be layed on rubber lining of 50mm thickness

1.1 Chiller Footing - 4.1 Mt x 1.8 Mt - 300mm Height 2 Set

1.2 Pri. CHW Pump - 1.5mt x 0.9 Mt - 300mm Height 3 Set

1.3 Sec. CHW Pump - 1.5mt x 0.9 Mt - 300mm Height 3 Set

1.4 Cds. CHW Pump - 1.5mt x 0.9 Mt - 300mm Height 3 Set

1.5 AHUs - 3.7 Mt x 2.1 Mt - 200 mm Height 14 Set

1.6 AHUs - 3.1 Mt x 2.8 Mt - 200 mm Height 4 Set

1.7 AHUs - 3.6 Mt x 2.3 Mt - 200 mm Height 3 Set

( For AHUs the footing shall be as per manifactureres requirement )

2 providing & fixing precast cement concrete blocks(1:2:4) of size

300x300x450 mm as directed by cooling tower dimentional

requirement

2.1 Cooling Tower - 3.5mt x 3.5 Mt - 600mm Height ( Staggered Footing

as per Cooling Tower Requirement )

2 Set

3 Brick work using common burnt clay building bricks having crushing

strength not less than 35 kg/Sq. cm. in foundations and plinth in

cement mortar 1:5 (1 cement : 5 fine sand) (A) Modular

92.1 CuM

3a Half brick masonry in common burnt clay building bricks having

crushing strength not less than 35 kg/sq.cm in cement mortar 1:3(1

cement:3 coarse sand) with 2 No. of 6 mm mild steel round bars

after every three course embedded in cement mortar in foundation &

plinth & all floor height. etc. comp.

739 Smt

3b Providing and laying Mala plaster in two coats with backing coat in

C.M. 1:4 and finishing coat in C.M. 1:3 finished smooth with mala,

watering etc. complete. No extra shall be paid for plaster grooves.

Internal Walls (Min 15 mm thickness)at all hts. 739 Smt

3c 20mm th.sandface cement plaster on walls upto all hts above ground

level consisting of 12mm thk backing coat of C.M.1:3(1 cement :3

sand) & 8mm thk finishing coat of CM(1:1)1 cement :1sand,etc.complete

739 Smt

Fabricated roof covered with polycarbonate sheet

4 Providing and fixing Polycarbonate roof sheets (double layer or two

skin) of approved make, on structural roofing / sky light structures in

shapes as per Architect’s drawing. The rate shall include cost of

scaffolding, screws, nuts, bolts and all necessary fixtures and

fastening etc. complete.

401 Smt

VOLUME VIII : BILL OF QUANTITY FOR CIVIL & FABRICATION WORK

HVAC TENDER DOCUMENT VOL-VIII-CIVIL FABRICATION JOB 36 of 39

Page 38: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 38/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

 SR.NO DESCRIPTION OF ITEM QTY UNIT

UNIT RATE

RS.

AMOUNT

RS.

VOLUME VIII : BILL OF QUANTITY FOR CIVIL & FABRICATION WORK

4a Providing and fixing M.S.hollow structural steel section like SHR, RHS,

tubes etc. or as suggested in contractors 's drawing including of all

labours and materials for all levels Profile

Cutting,threading,drilling, Nut-Bolting, Welding and applying Rust

remover and 1-coats of Zinc Chromate / red lead paint and three or

more coats of synthetic enamel paint of approved shade and

made (“Asian or Tata or" equi.) as directed and specified as directed

by Architect / Clerk-Of-Work. For all levels, lift and leads.

401 Smt

5.a Core cutting in RCC members of any dia R.O. Set

5.b Cut out in rcc slab including handling cutting & removing debris from

site and finising plaster of the cutting edges.

23.34 Smt

6 Making gabda finishing including labour & scaffolding with cement

mortar or(1:5) concrete material (1:2:4) as directed by engineer in

charge.

33 per unit

6a Demolishing of brick work including breaking & clearing debris from

site

15.2 CuM

7 Repainting

7.1 Providing & applying 3 coats of water based 100% acrylic emulsion

paint, waterproof and weather proof, Internal paint Apex or

approved equivalent of desired shade, after thoroughly brushing the

surface to remove all dirt and remaining all loose powdered Walls

1050 Smt

Signature of Tenderer : Additional Chied Engineer ( Electrical)

 Ahmedabad Municipal CorporationName

Company Seal

Date Date

TOTAL FOR VOLUME VIII - CIVIL AND FABRICATION JOB

HVAC TENDER DOCUMENT VOL-VIII-CIVIL FABRICATION JOB 37 of 39

Page 39: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 39/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

1 Providing of G.I. Modular Single Skine flush Cladding 83mm

Thk. With 0.8mm thk. G.I. Sheet finished with powder coated

with 25mm Puff Insulatation. Sq.Mtr. R.O.

( Partition Ht. - 3250mm )

2 Providing of G.I. Powder Coated Flush Door 49 mm thick

with 0.8mm thk. G.I.sheet 4mm Plain glass flush onboth sides fixed with 3M / saint gobin adhesive tape withPuff insulation.

* The Door frame Size Shall be 75 x 53 x 2.75 mm Thk.

1,800.00 x 2100.00 Sq.Mtr. R.O.

3 Providing of G.I. Modular Non Walk-on Ceiling 83mm Thk.

 With 0.8mm thk. G.I. Sheet finished with powder coated &25mm Puff Insulatation

( with all factory made cutouts for Hepa & Lights ) Sq.Mtr. 952

4 Providing of Aluminium Powder Coated Coving wall to wall

& wall to Ceiling R.Mtr. R.O.

5 Providing of G.I. Powder coated Return Air Risers with

Grill ( 550 x 400 )

750.00 x 80.00 Nos. R.O.

6  Automatic Drop Seal ( for Flush doors ) Nos. R.O.

7 Door Accessories ; 

a Door Closer ( Dorma TS-68) STD.Arm. Nos. R.O.

b Door Lock ( Door Set Make ) Nos. R.O.

c S.S. D Type Handle ( 200 mm ) Pair R.O.d S.S. Ball Bearing Hingies LOT R.O.

e View Panel for Flush doors LOT R.O.

f Concealed Flush bolt. LOT R.O.

g Siel for Airtightness LOT 1

h VHB Tape & Sealant Insulation LOT 1

8 Installation Charges : 

a G I Single Skin Flush Partition ( 83mm Thk. ) Sq.mtr. R.O.

b G I Flush Door ( 49mm Thk. ) Sq.mtr. R.O.

c G.I. Non Walk - on Ceiling ( 83mm Thk.) Sq.mtr. 816

d Aluminium Covings R.Mtr. R.O.

TOTAL - 

Signature of Tenderer : Additional Chied Engineer ( Electrical) Ahmedabad Municipal Corporation

Name

Company Seal

Date Date

HVAC VOL IX : BILL OF QUANTITY FOR OT CLEAN ROOM PARTITIONS

Sr. No. Description Qty Unit Rates in Rs.

Total Amount

Rs.

nit

HVAC TENDER VOL_IX - PARTITION 38 of 39

Page 40: Vol II Price Bid

8/11/2019 Vol II Price Bid

http://slidepdf.com/reader/full/vol-ii-price-bid 40/40

PROJECT TITLE : NEW HOSPITAL BUILDING FOR LG HOSPITAL , MANINAGER , AHMEDABAD

PRINCIPAL ARCHITECT : BHAVESH SHAH & PRITI SHAH

MEPF CONSULTANT : SHETH TECHNO CONSULTANTS PTV. LTD.,AHMEDABAD

HVAC VOLUME - X - AMC CHARGES ( FOR THE ENTIRE HVAC SYSTEM - CHW + Dx + VENTILATION ETC )

SR.

NO.DESCRIPTION

COMPREHENSIVE AMC

RS.

OPERATING CONTRACT FOR

HVAC SYSTEM RS.

1.0 FIRST 2 YEAR OF OPERATION & MAINTENANCE

2.0 FOR 1ST YEAR AFTER COMPLETION OF WARRANTY PERIOD

3.0 FOR 2ND YEAR AFTER COMPLETION OF WARRANTY PERIOD

4.0 FOR 3RD YEAR AFTER COMPLETION OF WARRANTY PERIOD

SUB TOTAL FOR 2+ 3 YEARS

Note : In case of Operating Contract - Contractor shall depute 1 Engineer and 3 Technician for full time. ( 1 Engineer for 1 shift - 1

Technician in each shift )

TOTAL

PART OF CONTRACT