Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
Page 1
Version: V1.3 Release date: 2017-10-22
Copyright 2017 DV Vendor ID 310 / 0x0136 Bytes: 01 36 / 0x01 0x36 Device ID 841 / 0x000349 Bytes: 00 03 49 / 0x00 0x3 0x49
Vendor name ifm electronic gmbh Vendor text www.ifm.com Vendor URL http://www.ifm.com/ifmgb/web/io-link-download.htm
Communication
IO-Link revision V1.1 Bit rate COM2 Minimum cycle time 8.00 ms
SIO mode supported Yes
Features
Block parameter setting Yes Data storage Yes
Device version
DV2500 5-segment LED tower, standard, with bracket, without buzzer
DV2510 5-segment LED tower, standard, with bracket, with buzzer
DV2520 5-segment LED tower, standard, without bracket, without buzzer
DV2530 5-segment LED tower, standard, without bracket, with buzzer
Page 2
Process data Total bit length = 48 (output process data) On/Off mode
true = on
false = off
Name Description Data type Bit offset Bit length Value range Gradient Offset Unit NN BooleanT 47 1 (false) inactive
NN BooleanT 46 1 (false) inactive
NN BooleanT 45 1 (false) inactive
NN BooleanT 44 1 (false) inactive
NN BooleanT 43 1 (false) inactive
NN BooleanT 42 1 (false) inactive
NN BooleanT 41 1 (false) inactive
Buzzer Buzzer BooleanT 40 1 (false) inactive (true) active
NN UIntegerT 32 8 0
NN UIntegerT 24 8 0
NN UIntegerT 16 8 0
NN UIntegerT 8 8 0
NN BooleanT 7 1 0
NN BooleanT 6 1 0
NN BooleanT 5 1 0
Segment 5 BooleanT 4 1 (false) inactive (true) active
Segment 4 BooleanT 3 1 (false) inactive (true) active
Segment 3 BooleanT 2 1 (false) inactive (true) active
Segment 2 BooleanT 1 1 (false) inactive (true) active
Segment 1 BooleanT 0 1 (false) inactive (true) active
Page 4
Process data Total bit length = 48 (output process data) RGB mode
Switching off
true = on
false = off
Name Description Data type Bit offset Bit length Value range Gradient Offset Unit NN BooleanT 47 1 (false) inactive
Buzzer style UIntegerT 44 3 0..7
NN BooleanT 43 1 (false) inactive
NN BooleanT 42 1 (false) inactive
NN BooleanT 41 1 (false) inactive
Buzzer Buzzer BooleanT 40 1 (false) inactive (true) active
NN BooleanT 39 1 (false) inactive
Segment 5 appearance UIntegerT 36 3 0...6
NN BooleanT 35 1 (false) inactive
Segment 5 colour UIntegerT 32 3 0..7
NN BooleanT 31 1 (false) inactive
Segment 4 appearance UIntegerT 28 3 0...6
NN BooleanT 27 1 (false) inactive
Segment 4 colour UIntegerT 24 3 0..7
NN BooleanT 23 1 (false) inactive
Segment 3 appearance UIntegerT 20 3 0...6
NN BooleanT 19 1 (false) inactive
Segment 3 colour UIntegerT 16 3 0..7
NN BooleanT 15 1 (false) inactive
Segment 2 appearance UIntegerT 12 3 0...6
NN BooleanT 11 1 (false) inactive
Segment 2 colour UIntegerT 8 3 0..7
NN BooleanT 7 1 (false) inactive
Segment 1 appearance UIntegerT 4 3 0...6
NN BooleanT 3 1 (false) inactive
Segment 1 colour UIntegerT 0 3 0..7
Page 5
Values
Value Colour Appearance Buzzer style
0 Off Continuous
lighting
No sound
1 Blue Flashing slow Rapid intermittent beep
2 Green Flashing med. Rapid Hi Lo
3 Cyan Flashing fast Sweep sound
4 Red Flashing slow Continuous beep sound with cycle ON/OFF
5 Purple Flashing med Rapid intermittent beep with cycle ON/OFF
6 Amber Flashing fast Rapid Hi Lo with cycle ON/OFF
7 White Not used Sweep sound with cycle ON/OFF
Page 6
Process data Total bit length = 48 (output process data) Analogue mode
true = on
false = off
Values
Value Analogue style Buzzer style
0 Not set (all off) No sound
1 Background: Off Indicators: White Direction: From bottom to top
Rapid intermittent beep
2 Background: Off Indicators: White Direction: From top to bottom
Rapid Hi Lo
3 Background: Off Indicators: White Direction: From bottom to top
Sweep sound
Name Description Data type Bit offset Bit length Value range Gradient Offset Unit NN BooleanT 47 1 (false) inactive
Buzzer style UIntegerT 44 3 0..7
NN BooleanT 43 1 (false) inactive
NN BooleanT 42 1 (false) inactive
NN BooleanT 41 1 (false) inactive
Buzzer Buzzer BooleanT 40 1 (false) inactive (true) active
NN UIntegerT 32 8 0
NN UIntegerT 24 8 0
NN UIntegerT 16 8 0
NN BooleanT 15 1 false
NN BooleanT 14 1 false
NN BooleanT 13 1 false
NN BooleanT 12 1 false
UIntegerT 8 4 0..9
UIntegerT 0 8 0..100 0 0 %
Page 7
4 Background: Off Indicators: White Direction: From top to bottom
Continuous beep sound with
cycle ON/OFF
5 Background: green Indicator: blue Direction: From bottom to top
Rapid intermittent beep with
cycle ON/OFF
6 Background: Red Indicator: Blue Direction: From bottom to top
Rapid Hi Lo with cycle
ON/OFF
7 Background: Yellow Indicator: Blue Direction: From bottom to top
Sweep sound with cycle
ON/OFF
8 Background: Off Indicators: White Direction: From bottom to top
Not set (all off)
9 Background: Off Indicators: White Direction: From top to bottom
Not set (all off)
10 Not set (all off) Not set (all off)
11 Not set (all off) Not set (all off)
12 Not set (all off) Not set (all off)
13 Not set (all off) Not set (all off)
14 Not set (all off) Not set (all off)
15 Not set (all off) Not set (all off)
Page 8
Variables
Name Index Subindex Data type Length Access Factory setting Value range Factor Offset Unit
rights
Standard command
2 Sub 0 UIntegerT 8 bits wo (130)
Restore the factory
setting
(240)IO-Link 1.1 system test
command 240, event 8DFE appears
(241)IO-Link 1.1 system test
command 241, event 8DFE disappears
(242)IO-Link 1.1 system test
command 242, event 8DFF appears
(243)IO-Link 1.1 system test
command 243, event 8DFF disappears
Unit locking
12 Sub 0 RecordT 16 bits rw
Data storage bitOffs 1 BooleanT 1 bit (false) (false) open (true) locked
Local user interface bitOffs 3 BooleanT 1 bit (false)
(false) open (true) locked
Name of the manufacturer
16 Sub 0 StringT 48 bytes ro ifm electronic gmbh
Manufacturer text
17 Sub 0 StringT 48 bytes ro www.ifm.com
Product name
18 Sub 0 StringT 32 bytes ro
Page 9
Variables
Name Index Subindex Data type Length Access Factory setting Value range Factor Offset Unit
rights
Product ID
19 Sub 0 StringT 16 bytes ro
Product text
20 Sub 0 StringT 64 bytes ro
Serial number
21 Sub 0 StringT 16 bytes ro
Hardware version
22 Sub 0 StringT 16 bytes ro
Firmware version
23 Sub 0 StringT 16 bytes ro
Application-specific
marking 24 Sub 0 StringT 32 bytes rw ***
Device status
36 Sub 0 intagerT 8 bytes ro (0) Device is OK (1) Maintenance required (2) Outside the specification (3) Function check (4) Fault 5 to 255 (reserved)
Detailed device status
37 Sub 0 ArrayT 21 bytes ro 00 00 00 h
Page 10
Variables
Name Index Subindex Data type Length Access Factory setting Value range Factor Offset Unit
rights
Active events Bit mask for currently active events
545 Sub 0 RecordT 4 bytes ro
Bit_31, bit 31 indicates the assigned active event
bitOffs 31 BooleanT 1 bit (0) noEv (0) noEv (1) 0x8DFF
Bit_30, bit 30 indicates the assigned active event
bitOffs 30 BooleanT 1 bit
(0) noEv (0) noEv
(1) 0x8DFE
Bit_2, bit 2 indicates the assigned active event
bitOffs 2 BooleanT 1 bit
(0) noEv (0) noEv
(1) 0x7710
Bit_1, bit 1 indicates the assigned active event
bitOffs 1 BooleanT 1 bit
(0) noEv (0) noEv
(1) 0x6320
Bit_0, bit 0 indicates the assigned active event
bitOffs 0 BooleanT 1 bit
(0) noEv (0) noEv
(1) 0x5000
Page 11
Variables
Name Index Subindex Data type Length Access Factory setting Value range Factor Offset Unit
rights
Parameter Setting error
Shows the parameter incorrectly set at the time of the download
546 Sub 0 ArrayT 10*32 bits
ro 0 (0) OK (44826624) Operating mode (786432000) On/Off segment colour (786497536) Segment appearance (786563072) Segment intensity (786628608) Buzzer intensity (35717120) BitCoded_ActiveEvents (35717121) BitCoded_ActiveEvents.Bit_0 (35717122) BitCoded_ActiveEvents.Bit_1 (35717123) BitCoded_ActiveEvents.Bit_2 (35717124) BitCoded_ActiveEvents.Bit_30 (35717125) BitCoded_ActiveEvents.Bit_31 (35782656) ParaConfigFaultCollection
Page 12
Variables
Name Index Subindex Data type Length Access Factory setting Value range Factor Offset Unit
rights
Operating mode
684 Sub 0 UIntegerT 1 byte rw 1 (0) - On/Off mode (1) - RGB mode (2) - Analogue mode
On/Off segment colour Colour of the respective segments
12000 Sub 0 UIntegerT 5 bytes rw Seg. 1 = 1 Seg. 2 = 3 Seg. 3 = 2 Seg. 4 = 7 Seg. 5 = 4
(0) - Off (1) - Red (2) - Green (3) - Amber (4) - Blue (5) - Purple (6) - Cyan (7) - White
Segment appearance Indication style
12001 Sub 0 UIntegerT 5 bytes rw Seg. 1 = 0 Seg. 2 = 0 Seg. 3 = 0 Seg. 4 = 0 Seg. 5 = 0
(0) - Continuous lighting (1) - Flashing slow (2) - Flashing med. (3) - Flashing fast (4) - Flashing slow (5) - Flashing med. (6) - Flashing fast
Segment intensity Intensity of the segments
12002 Sub 0 UIntegerT 5 bytes rw Seg. 1 = 75 Seg. 2 = 75 Seg. 3 = 75 Seg. 4 = 75 Seg. 5 = 75
0…100 (0x00 - 0x64)
0 0 %
Buzzer intensity Volume buzzer
12003 Sub 0 UIntegerT 1 byte rw 100 0…100 (0x00 - 0x64)
0 0 %
Page 13
Events
Code Name Type Description
0 d / 0x0000 h No error Notification No error
20480 d / 5000 h Hardware error in the unit Error Replace the unit
25376 d / 6320 h Parameter error Error Check the data sheet and the values.
36350 d / 8D FE h Test event 1 Warning Event appears if index 2 is set to the value 240, event disappears if index 2 is set to the value 241
36351 d / 8D FF h Test event 2 Warning Event appears if index 2 is set to the value 242, event disappears if index 2 is set to the value 243
Error types
Error code Name Description
32768 d / 80 00 h Application error in the device - Access was denied by the device. No detailed information available
no details
32785 d / 80 11 h Index not available Access to a non-existing index
32786 d / 80 12 h Subindex not available Access to a non-existing subindex
32800 d / 80 20 h Service currently not available The parameter cannot be accessed. The device does not allow access in the current mode
32803 d / 80 23 h Access denied Write access to a write protected parameter
32820 d / 80 34 h Index currently not accessible The device does not allow access in the current mode
32816 d / 80 30 h Parameter value outside the Written parameter is outside the admissible value range
permissible range
32819 d / 80 33 h Parameter length too great Written parameter length is greater than permitted
32820 d / 80 34 h Parameter length too small Written parameter length is smaller than permitted
32821 d / 80 35 h Function not available Written command is not supported by the device
32822 d / 80 36 h Function currently not available Written command is not supported by the device in the current mode
32832 d / 80 40 h Invalid parameter set Written individual parameter value conflicts with the other parameter settings
32833 d / 80 41 h Inconsistent parameter set Inconsistencies were detected at the end of the block parameter transfer. The device plausibility check failed
32898 d / 80 82 h Application not ready Access denied because the device is currently not ready