Page 1 Version: V1.0.8 Release date: 2016-05-12 Copyright 2016 DF Vendor ID 310 / 0x0136 Bytes: 01 36 / 0x01 0x36 Device ID 542 / 0x00021E Bytes: 00 02 1E / 0x00 0x02 0x1E Vendor name ifm electronic gmbh Vendor text www.ifm.com Vendor URL http://www.ifm.com/ifmgb/web/io-link-download.htm Communication IO-Link revision V1.1 Bit rate COM2 Minimum cycle time 20.00 ms SIO mode supported NO Features Block parameter setting Yes Data storage Yes Device variant DF2100 Fuse/IO-Link / 24VDC/Module

Version: V1.0.8 Release date: 2016-05-12 - ifm · Version: V1.0.8 Release date: 2016-05-12 ... Extended information Extended 501- Sub 0 UIntegerT 24 bits r 0 channel 1-16 diagnostic

  • Upload
    vudat

  • View
    223

  • Download
    2

Embed Size (px)

Citation preview

Page 1

Version: V1.0.8 Release date: 2016-05-12

Copyright 2016 DF Vendor ID 310 / 0x0136 Bytes: 01 36 / 0x01 0x36 Device ID 542 / 0x00021E Bytes: 00 02 1E / 0x00 0x02 0x1E

Vendor name ifm electronic gmbh Vendor text www.ifm.com Vendor URL http://www.ifm.com/ifmgb/web/io-link-download.htm

Communication

IO-Link revision V1.1 Bit rate COM2 Minimum cycle time 20.00 ms SIO mode supported NO

Features

Block parameter setting Yes Data storage Yes

Device variant

DF2100 Fuse/IO-Link / 24VDC/Module

Page 2

Process Data Total bit length = 216 (Input process data)

Name Description Data type Bit offset Bit length Value range Gradient Offset Unit

Load current F1 Present current channel 1 Unsigned CharacterT 208 8 0 to 255 0.1 0 A

Load current F2 Present current channel 2 Unsigned CharacterT 200 8 0 to 255 0.1 0 A

Load current F3 Present current channel 3 Unsigned CharacterT 192 8 0 to 255 0.1 0 A

Load current F4 Present current channel 4 Unsigned CharacterT 184 8 0 to 255 0.1 0 A

Load current F5 Present current channel 5 Unsigned CharacterT 176 8 0 to 255 0.1 0 A

Load current F6 Present current channel 6 Unsigned CharacterT 168 8 0 to 255 0.1 0 A

Load current F7 Present current channel 7 Unsigned CharacterT 160 8 0 to 255 0.1 0 A

Load current F8 Present current channel 8 Unsigned CharacterT 152 8 0 to 255 0.1 0 A

Load current F9 Present current channel 9 Unsigned CharacterT 144 8 0 to 255 0.1 0 A

Load current F10 Present current channel 10 Unsigned CharacterT 136 8 0 to 255 0.1 0 A

Load current F11 Present current channel 11 Unsigned CharacterT 128 8 0 to 255 0.1 0 A

Load current F12 Present current channel 12 Unsigned CharacterT 120 8 0 to 255 0.1 0 A

Load current F13 Present current channel 13 Unsigned CharacterT 112 8 0 to 255 0.1 0 A

Load current F14 Present current channel 14 Unsigned CharacterT 104 8 0 to 255 0.1 0 A

Load current F15 Present current channel 15 Unsigned CharacterT 96 8 0 to 255 0.1 0 A

Load current F16 Present current channel 16 Unsigned CharacterT 88 8 0 to 255 0.1 0 A

Load output status Current status of the load output per

fuse (channel 1 to 16 bitwise)

Unsigned IntagerT 72 16 (false) inactive (true) active

Load output overload Display of an overload per fuse

(channel 1 to 16 bitwise)

Unsigned IntagerT 56 16 (false) inactive (true) active

Load output short circuit Display of a short circuit per fuse

(channel 1 to 16 bitwise)

Unsigned IntagerT 40 16 (false) inactive (true) active

Load output limit value Display of the achieved limit value

per fuse (channel 1 to 16 bitwise)

Unsigned IntagerT 24 16 (false) inactive (true) active

Status hardware pushbutton Display of whether the channel has

been switched off via the hardware

pushbutton (channel 1 to 16 bitwise)

Unsigned IntagerT 8 16 (false) inactive (true) active

General status byte Display of the undervoltage in bit 0

(all further bytes are reserved)

Unsigned IntagerT 0 8 (false) inactive (true) active

Page 3

Page 4

Process data Total bit length = 32 (Output process data)

false = switch off load output

true = switch on or reset load output

Name Description Data type Bit offset Bit length Value range Gradient Offset Unit Load output reset The corresponding load output

can be reset (channel 1 to 16

bitwise)

Unsigned IntagerT 16 16 (false) inactive (true) active

Load output on/off The corresponding load output

can be switched on and off

(channel 1 to 16 bitwise)

Unsigned IntagerT 0 16 (false) inactive (true) active

Page 5

Variables

Name Description Index Subindex Data type Length Access Default Value range Gradient Offset Unit

bit offset rights

Standard command 2 Sub 0 UIntegerT 8 bits wo (5)

Activation data storage

(130) Restore

factory setting

(240) IO-Link 1.1 system test

Command 240,

event 8DFE appears

(241) IO-Link 1.1 system test

Command 241,

event 8DFE disappears

(242) IO-Link 1.1 system test

Command 242,

event 8DFF appears

(243) IO-Link 1.1 system test

Command 243,

event 8DFF disappears

(255) Command without effect, for

internal use only

Page 6

Variables

Name Description Index Subindex Data type Length Access Default Value range Gradient Offset Unit

bit offset rights

Device access lock

12 Sub 0 RecordT 16 bits rw

Data storage lock bitOffs 1 BooleanT 1 bit (0)

Local user interface lock bitOffs 3 BooleanT 1 bit (0)

Manufacturer name 16 Sub 0 StringT 19 bytes ro ifm electronic

gmbh

Manufacturer text 17 Sub 0 StringT 11 bytes ro www.ifm.com

Product name 18 Sub 0 StringT 6 bytes ro DF2100

Product ID 19 Sub 0 StringT 6 bytes ro DF2100

Product text 20 Sub 0 StringT 29 bytes ro Fuse/IO-Link / 24VDC/Module

Serial number 21 Sub 0 StringT 10 bytes ro

Hardware version 22 Sub 0 StringT 1 byte ro

Firmware version 23 Sub 0 StringT 5 bytes ro

Application-specific mark 24 Sub 0 StringT 32 bytes rw ***

Page 7

Name Description Index Subindex Data type Length Access Default Value range Gradient Offset Unit

bit offset rights

Parameter channel 1- Parameter channel 101- Sub 0 RecordT 16 bits rw

16 116 Nominal current bitOffs 8 UIntagerT 8 bits (2) 2A 1 0 A

Limit value load current bitOffs 0 UIntagerT 8 bits 80

(4) 4A (6) 6A 50 to 100 1 0 %

ELBus controller

Configuration data of the intelligent feeding module DF2100 200 Sub 0 RecordT 8 bits rw 2 (0)

configuration Unfreeze - all

load outputs of the

circuit breakers are switched off and the DF2100 changes to the operating mode "independent operation". (2)

Freeze - all load outputs of the circuit breakers keep their current status and the DF2100 changes to the operating mode "independent operation". (4) Power save activated and unfreeze

(8) Power save activated and freeze

Page 8

Name Description Index Subindex Data type Length Access Default Value range Gradient Offset Unit

bit offset rights

System errors Diagnostic information of the 300 Sub 0 UIntegerT 16 bits ro 0 (0)

intelligent No error

feeding module DF2100 (1)

Hardware error in the

configuration

store

(2)

Checksum in the configuration store New parameters are required.

(16) Full command memory The IO-Link master sends requests faster than they can be processed. (128) ELBus hardware error A possible cause may be a short circuit on the ELBus. (512) Watchdog caused reset. A temporary error has occurred. This error may be caused by strong EMC.

Page 9

Name Description Index Subindex Data type Length Access Default Value range Gradient Offset Unit

bit offset rights

System errors Diagnostic information of the 300 Sub 0 UIntegerT 16 bits w (1024)

intelligent Hardware error.

feeding module Internal test routines

DF2100 detected a

hardware error. Please contact the manufacturer.

Error channel 1-16 Diagnostic messages channel 301 - Sub 0 UIntegerT 8 bits r 0 (0)

316 No error

(1)

Non-supported

device detected.

A

non-supported

circuit breaker has been

integrated

in the system

(2)

No device

present

(144)

The transmitted

device parameters

have been rejected by the

circuit breaker

because they are

outside the

valid

range.

Page 10

Name Description Index Subindex Data type Length Access Default Value range Gradient Offset Unit

bit offset rights

Error channel 1-16 Diagnostic messages channel 301 - Sub 0 UIntegerT 8 bits r (146)

316 Channel blocked

The channel has been

blocked via actuation

of the integrated

pushbutton

and cannot

be switched on

via the

IO-Link master

(147)

Undervoltage

detected.

The operating

voltage is

below the

safe range. (148) Excess temperature (depending on the circuit breaker)

(149)

The device has triggered.

A reset

command must

be sent

(151)

The circuit breaker has

not been

configured

(152)

An internal device

error has

been detected

Page 11

Name Description Index Subindex Data type Length Access Default Value range Gradient Offset Unit

bit offset rights

Error channel 1-16 Diagnostic messages channel 301 - Sub 0 UIntegerT 8 bits r (153)

316 Unknown

command

(154)

ELBus error,

wrong frame length

(155)

Internal ELBus

error detected

(temporary

failure)

This error may

be caused by strong

EMC.

Voltage channel 1-16 Load voltage channel 401- Sub 0 UIntegerT 16 bits r 0 to 3000 0.01 0 V

416

Extended information Extended 501- Sub 0 UIntegerT 24 bits r 0 channel 1-16 diagnostic messages 516

(dynamic info) channel

Error memory bitOffs 16 UIntegerT 8 bits 0 (0)

No error

(1)

No parameters

available

(2)

Parameter memory

error

(4)

Program memory

error

(8)

Data memory

error

(16)

Control unit error

Page 12

Name Description Index Subindex Data type Length Access Default Value range Gradient Offset Unit

bit offset rights

Extended information Extended 501- Sub 0 UIntegerT 24 bits ro 0 channel 1-16 diagnostic messages 516

(dynamic info) channel

Error memory bitOffs 16 UIntegerT 8 bits 0 (32)

A reset has been initiated by

the

watchdog

Triggering counter bitOffs 8 UIntegerT 8 bits 0 0 to 255 1 0

Reason for the triggering bitOffs 0 UIntegerT 8 bits 0 (0)

No reason for

triggering

(1)

Short circuit

(2)

Overload

(4)

Internal

device error

Action channel 1-16 Action commands channel 1 - 16 601- Sub 0 UIntegerT 8 bits w

616

Reset error memory bitOffs 0 UIntegerT 8 bits (115)

Reset triggering counter bitOffs 0 UIntegerT 8 bits (116)

Page 13

Name Description Index Subindex Data type Length Access Default Value range Gradient Offset Unit

bit offset rights

Informations channel Device information channel 701- Sub 0 RecordT 80 bits r

1-16 1-16 716

Type of unit bitOffs 0 UIntegerT 16 bits (0)

No device detected. Either there are no devices, or they are not powered.

(36873)

Fuse/IOLink/1 Channel

(36875)

DF22xx Fuse/IOLink/2 Channels

(36875)

Fuse/IOLink/4 Channels"

Hardware version bitOffs 16 UIntegerT 16 bits

Software version bitOffs 32 UIntegerT 16 bits

Serial number of the bitOffs 48 UIntegerT 32 bits

fuse

Page 14

Events

Code Name Type Description

6145 d / 1801 h F1: device parameters have changed warning F1 trip current changed

6146 d / 1802 h F2: device parameters have changed warning F2 trip current changed

6147 d / 1803 h F3: device parameters have changed warning F3 trip current changed

6148 d / 1804 h F4: device parameters have changed warning F4 trip current changed

6149 d / 1805 h F5: device parameters have changed warning F5 trip current changed

6150 d / 1806 h F6: device parameters have changed warning F6 trip current changed

6151 d / 1807 h F7: device parameters have changed warning F7 trip current changed

6152 d / 1808 h F8: device parameters have changed warning F8 trip current changed

6153 d / 1809 h F9: device parameters have changed warning F9 trip current changed

6154 d / 180A h F10: device parameters have changed warning F10 trip current changed

6155 d / 180B h F11: device parameters have changed warning F11 trip current changed

6156 d / 180C h F12: device parameters have changed warning F12 trip current changed

6157 d / 180D h F13: device parameters have changed warning F13 trip current changed

6158 d / 180E h F14: device parameters have changed warning F14 trip current changed

6159 d / 180F h F15: device parameters have changed warning F15 trip current changed

6160 d / 1810 h F16: device parameters have changed warning F16 trip current changed

6176 d / 1820 h System error warning System Error: extended information available at index 300

6177 d / 1821 h Device error warning Device error F1: extended information available at 301

6178 d / 1822 h Device error warning Device error F2: extended information available at 302

6179 d / 1823 h Device error warning Device error F3: extended information available at 303

6180 d / 1824 h Device error warning Device error F4: extended information available at 304

6181 d / 1825 h Device error warning Device error F5: extended information available at 305

6182 d / 1826 h Device error warning Device error F6: extended information available at 306

Page 15

Code Name Type Description

6183 d / 1827 h Device error warning Device error F7: extended information available at 307

6184 d / 1828 h Device error warning Device error F8: extended information available at 308

6185 d / 1829 h Device error warning Device error F9: extended information available at 309

6186 d / 182A h Device error warning Device error F10: extended information available at 310

6187 d / 182B h Device error warning Device error F11: extended information available at 311

6188 d / 182C h Device error warning Device error F12: extended information available at 312

6189 d / 182D h Device error warning Device error F13: extended information available at 313

6190 d / 182E h Device error warning Device error F14: extended information available at 314

6191 d / 182F h Device error warning Device error F15: extended information available at 315

6192 d / 1830 h Device error warning Device error F16: extended information available at 316

36350 d / 8D FE h Test event 1 warning Event appears if index 2 is set to the value 240, event disappears if index 2 is set to the value 241

36351 d / 8D FF h Test event 2 warning Event appears if index 2 is set to the value 242, event disappears if index 2 is set to the value 243

Error types

Error code Name Description

32768 d / 80 00 h Application error in the device - Access was denied by the device. No detailed information available no details

32785 d / 80 11 h Index not available Access to a non-existing index

32816 d / 80 30 h Parameter value outside the valid range Written parameter is outside the admissible value range

32819 d / 80 33 h Parameter length too great Written parameter length is greater than permitted

32820 d / 80 34 h Parameter length too small Written parameter length is smaller than permitted

32822 d / 80 36 h Function currently not available Written command is not supported by the device in the current mode