155
GE Oil & Gas Vector VII Variable Speed Drive 757KVA - 1515KVA PN: 810207 Revision: 6.8.1 GE imagination at work

Vector VII HHP User Manual 810207 6.8.1

Embed Size (px)

DESCRIPTION

Manual de Variador

Citation preview

  • GE Oil & Gas

    Vector VII

    Variable Speed Drive757KVA - 1515KVA

    PN: 810207 Revision: 6.8.1GE imagination at work

  • 1 Quick Start Guide ............................................................................................................................................................................................................ 62 I want to .............................................................................................................................................................................................................................. 6

    2.1 Activate the normal drive screen .............................................................................................................................................................. 62.2 Activate the status indicator screen ........................................................................................................................................................ 62.3 Adjust the frequency setpoint .................................................................................................................................................................... 72.4 Clear the Fault state ....................................................................................................................................................................................... 72.5 Determine the current rating of this drive ............................................................................................................................................. 72.6 Change one of the parameters in the Linear List ............................................................................................................................... 72.7 Save Data Log, Current Log, and Events files to USB Flash disk ................................................................................................... 72.8 Set drive parameters to their factory default values ........................................................................................................................ 72.9 Adjust the V/F behavior of the drive ........................................................................................................................................................ 72.10 Fine tune the drive output voltage without stopping the drive..................................................................................................... 7

    3 Installation and Setup ................................................................................................................................................................................................... 73.1 Site Installation................................................................................................................................................................................................. 7

    3.1.1 Equipment Inspection...........................................................................................................................................................................73.1.2 Equipment Installation and Requirements...................................................................................................................................83.1.3 Electrical Connections........................................................................................................................................................................10

    3.2 Hardware Connections ...............................................................................................................................................................................113.2.1 Control Terminals.................................................................................................................................................................................113.2.2 External Stop Switches.......................................................................................................................................................................163.2.3 Standby Switch Input..........................................................................................................................................................................163.2.4 Event Switch...........................................................................................................................................................................................163.2.5 Remote Run and Reference...........................................................................................................................................................16

    3.3 Startup Checks ...............................................................................................................................................................................................173.3.1 Pre Power-Up.........................................................................................................................................................................................173.3.2 Pre Run Checks.....................................................................................................................................................................................183.3.3 Drive Start Up........................................................................................................................................................................................19

    3.4 Keypad Conventions ....................................................................................................................................................................................193.4.1 Soft keys....................................................................................................................................................................................................193.4.2 Arrow Keys..............................................................................................................................................................................................203.4.3 Start / Stop...............................................................................................................................................................................................203.4.4 Status Indicator Screen Old Blue Box HMI..................................................................................................................................203.4.5 Status Indicator Screen New HMI..................................................................................................................................................21

    3.5 Configuration ..................................................................................................................................................................................................223.5.1 Drive Mode..............................................................................................................................................................................................223.5.2 Frequency Behavior.............................................................................................................................................................................223.5.3 Alarms and Restarts...........................................................................................................................................................................223.5.4 Motor Direction.....................................................................................................................................................................................22

    4 Screen Descriptions......................................................................................................................................................................................................234.1 Run Status ........................................................................................................................................................................................................234.2 Event Log ..........................................................................................................................................................................................................244.3 Select Screen (Not logged in) ....................................................................................................................................................................254.4 Enter Password ..............................................................................................................................................................................................264.5 Select Screen (Logged in) ...........................................................................................................................................................................274.6 Fault Status ......................................................................................................................................................................................................294.7 Amp Chart ........................................................................................................................................................................................................304.8 Trending ............................................................................................................................................................................................................314.9 History Screen ................................................................................................................................................................................................324.10 Setup Screen ...................................................................................................................................................................................................334.11 Osiris ................................................................................................................................................................................................................344.12 Drive I/O ............................................................................................................................................................................................................354.13 Last Fault ..........................................................................................................................................................................................................364.14 All Monitors ......................................................................................................................................................................................................374.15 Run Info .............................................................................................................................................................................................................414.16 Set Date and Time .........................................................................................................................................................................................424.17 Linear List Menu.............................................................................................................................................................................................43

    4.17.1 Linear List................................................................................................................................................................................................444.18 Operating Mode .............................................................................................................................................................................................45

    4.18.1 Selection Parameter Change..........................................................................................................................................................464.18.2 Operating Mode Frequency Control........................................................................................................................................474.18.3 Operating Mode - Analog Follower...............................................................................................................................................484.18.4 Operating Mode Current Control..............................................................................................................................................504.18.5 Operating Mode Pressure Control...........................................................................................................................................51

    4.19 Alarms Setup ...................................................................................................................................................................................................534.20 Underload Setup ............................................................................................................................................................................................554.21 Start Control ....................................................................................................................................................................................................564.22 Numeric Parameter Change .....................................................................................................................................................................58

  • 4.23 Frequency Setup ............................................................................................................................................................................................594.24 Analog 1 Setup ...............................................................................................................................................................................................604.25 Analog 2 Setup ...............................................................................................................................................................................................624.26 Analog 3 Setup ...............................................................................................................................................................................................634.27 Misc Setup ........................................................................................................................................................................................................654.28 Comm Setup ....................................................................................................................................................................................................664.29 Hard Starting ..................................................................................................................................................................................................684.30 Maintenance Menu .......................................................................................................................................................................................694.31 Startup Control ...............................................................................................................................................................................................704.32 Keypad Test .....................................................................................................................................................................................................72

    5 Parameter Locator .......................................................................................................................................................................................................736 Remote User Interface ................................................................................................................................................................................................75

    6.1 What is the Remote User Interface? ......................................................................................................................................................756.2 Configuration ..................................................................................................................................................................................................756.3 Capabilities ......................................................................................................................................................................................................766.4 V/Hz Factory and Manual Set-up. ...........................................................................................................................................................77

    6.4.1 Factory Default V/Hz and Definition...........................................................................................................................................776.4.2 Selectable 60 Hz V/Hz settings......................................................................................................................................................786.4.3 Selectable 50 Hz V/Hz settings......................................................................................................................................................816.4.4 V/Hz Manual Set-up............................................................................................................................................................................85

    7 SCADA Interface ............................................................................................................................................................................................................867.1 SCADA Interface Port ...................................................................................................................................................................................867.2 SCADA Addresses ..........................................................................................................................................................................................867.3 New HMI Communication Ports Pin Out ..............................................................................................................................................93

    8 Troubleshooting and Maintenance ........................................................................................................................................................................948.1 Main Circuit Test Procedure ......................................................................................................................................................................94

    8.1.1 Test Point Designations..................................................................................................................................................................948.1.2 Main Power Circuit Test and Troubleshooting......................................................................................................................95

    8.2 Drive System Troubleshooting .................................................................................................................................................................988.2.1 Drive Frame PC Board Designations..............................................................................................................................................998.2.2 System Power Checks and Troubleshooting...............................................................................................................................998.2.3 Fan/Heat Exchanger Troubleshooting.....................................................................................................................................1008.2.4 Drive Status / Fault Codes.............................................................................................................................................................100

    8.3 General Maintenance ............................................................................................................................................................................... 1048.3.1 Periodic Inspection NO Power Applied..................................................................................................................................1048.3.2 Periodic Inspection Power Applied (External Only)............................................................................................................105

    Appendix..................................................................................................................................................................................................................................... 1061 Dimensions and Weights ........................................................................................................................................................................................ 1062 Default Parameter Values ....................................................................................................................................................................................... 1083 USB Flash Drive Operation ..................................................................................................................................................................................... 109

    3.1 Save History files ........................................................................................................................................................................................ 1103.2 Save Configuration to USB flash drive ............................................................................................................................................... 1103.3 Save Linear List to USB flash drive ...................................................................................................................................................... 1103.4 Load configuration from a USB flash drive to a Vector VII drive .......................................................................................... 111

    4 Linear List ...................................................................................................................................................................................................................... 1115 Tools Recommended for Maintenance and Repair ....................................................................................................................................... 1516 CE Conformity for drives purchased with CE Option .................................................................................................................................... 152

    6.1 Emergency Stop Function ....................................................................................................................................................................... 152

  • GE Oil & Gas

    GE imagination at work

    Intended UseThis manual applies to the 757, 815, 1010, 1136, 1400 and 1515 models of the GE Oil & Gas Vector VII Variable Speed Drive that are loaded with Firmware revision 6.8.

    General Specifications

    Electrical Specifications:

    Rated Input Voltage: 480 Volt, 3 phase, 60 Hz (+ / - 10% of rated voltage and frequency). Consult factory for other input voltages and frequency ratings. Efficiency: 97% or greater at full load.Output Voltage: 0 Volts to rated input voltageOutput Frequency: 0 Hertz to 120 Hertz.

    Control Specifications:

    Control Method: Sine coded output with optional VSG (Variable Sinewave Generation) technology.Accel / Decel: 0 Seconds to 6,000 seconds.Drive Overload: 110% of drive rating for 60 seconds (Variable Torque).Current Limit: Programmable current limit.

    Control I/O:

    Digital Inputs: 7 Programmable inputs - 24 VDC, 8 mA Sinking or Sourcing Logic.Digital Outputs: 2 Programmable dry contacts rated 250 VAC / 30 VDC @ 1A.

    1 Fault contact - Form C dry contact rated 250 VAC / 30 VDC @ 1A.Analog Inputs: 3 Programmable inputs (10 bit). 2 Input 0 to +10 VDC 20 K Ohms 1 Input 0 to +10 VDC 20 K Ohms or 4 to 20 mA 250 OhmsAnalog Outputs: 2 Programmable outputs (10 bit) 0 to +10 VDC 2 mA.Analog Reference: +15 VDC Source 20 mA. Logic Reference: +24 VDC Source 8 mA.

    Environmental Specifications:

    Ambient Service Temperature: 0C to 50C (32F to 122F) to -40C (-40F) with optional arctic package.Ambient Storage Temperature: -20C to 60C (-4F to 140F)Humidity: 0 to 100%Altitude: Up to 1000 Meters (3300 Feet) without de-rate.Vibration: 9.81m/s2 (1 G) maximum 10 to 20 Hz, 2.0 m/s2 (0.2 G) 20 Hz to 50 Hz.

    Vector, VSG and Osiris are all registered trademarks of GE Oil & Gas ESP, Inc.

  • 5VIIVECTORGeneral Precautions

    DANGER: This drive unit requires and produces potentially lethal voltage levels. Failure to comply with the following may lead to equipment damage, serious personal injury and/or death!!!

    Read and understand this manual in its entirety before installing, operating, or servicing this drive. All warnings, cautions, notes and instructions must be followed. The drive must be installed by qualified personnel only. The drive must be installed following the guidelines in this manual and following all applicable local codes.

    Do not connect or disconnect wiring while power is applied to the drive. Do not remove covers or touch any components while power is on. To avoid the risk of potentially lethal electrical shock, remove and lock-out all incoming power before servicing this drive unit. The internal capacitors

    remain charged even after the power supply is turned off. To prevent electrical shock, wait at least five minutes after removing power and measure the DC bus voltage between the +3 and terminals to confirm safe level of voltage.

    Do not bypass the internal circuit breakers of the drive for any reason. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Replace any protective covers or shields that may have been removed during servicing before operation of the drive. Do not connect or operate this unit with visible damage or missing/removed parts. This unit may start unexpectedly upon application of power. Clear all personnel from the drive and other connected equipment. Secure and/or

    remove any mechanical hazards that may be present with the application of power to this drive This drive contains ESD (ElectroStatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, or

    servicing this unit.

    Arc Flash Warning: There is a potential for Arc Flash Hazard with this equipment. It is strongly recommended that an analysis of incident energy levels and determination of appropriate Personal Protective Equipment be conducted prior to energizing this equipment.

    Danger Warning:A Danger warning symbol is an exclamation mark enclosed in a triangle that precedes the word DANGER. A Danger warning symbol indicates a hazardous situation which, if not avoided, will result in Death or serious injury. Danger warnings in this manual appear in the following manner.

    DANGER Special instructions and descriptions of the associated hazard will be explained in the text following the Danger warning.

    Or for CE marked Applications:

    Electrical Warning:The electrical warning symbol is a lightning bolt mark enclosed in a triangle. The electrical warning symbol is used to indicate locations where hazardous voltage levels are present and conditions may cause serious injury if proper precautions are not followed..

    Or for CE marked Applications:

    Caution Warning:A Caution warning symbol is and exclamation mark enclosed in a triangle that precedes the word CAUTION. A Caution warning symbol indicates a hazardous situation which, if not avoided, will result in minor or moderate injury.

    Or for CE marked Applications:

  • GE Oil & Gas

    GE imagination at work

    1 Quick Start GuideThis section will guide you through drive configuration for a typical ESP installation. It is highly recommended that the user read the entire manual before proceeding with this procedure!

    Step Name Description

    1

    Log on to access drive configuration

    Sections 4.3, 4.4

    From the Run Status screen, press the Menu soft key Use the up and down arrow buttons to select Log In, press the OK soft key. Enter the password and press the OK soft key. Default password is 3333.

    2

    Set Auto Restart and Drive Lockout function

    Section 4.31

    From the Run Status screen, press the Menu soft key From the Select Screen, press the Startup soft key Set Auto Restart to Enable or Disable (Application Dependent) Set Drive Lockout to Unlock before starting the drive

    3

    Set drive mode and related parameters

    Sections 3.6.1, 4.18

    Determine the operating mode for the drive - Current Control, Pressure Control, Frequency Control, and Analog Follower.

    Edit the Drive Mode parameter in the Operating Mode screen as needed. Modify the other parameters in the Operating Mode screen as necessary.

    Use the up and down arrow buttons in the Select Screen to select the Operating Mode screen, press the OK button.

    Use the up and down arrow buttons to select a parameter, press the Edit key to change the selected parameter.

    4Set up alarms

    Section 4.19, 4.20

    Set the motor overload and global restart parameters in the Alarms Setup screen. Set the motor Underload and Underload restart parameters in the Underload Setup

    screen. Select the screen and select / edit parameters as in step 3.

    5

    Set up frequency behavior

    Section 4.23

    Set the V/F curve, motor direction, maximum and minimum frequencies, acceleration and deceleration times, jog setpoint, and lockout frequencies in the Frequency Setup screen.

    Select the screen and select / edit parameters as in step 3.

    6Set up Misc parameters

    Section 4.27

    Configure the Osiris sensor (if available), transformer ratio, customer password, and faults as necessary in the Misc Setup screen.

    Select the screen and select / edit parameters as in step 3.

    7Configure analog inputs

    Section 4.24, 4.25, 4.26

    If required. Use the Analog 1 Setup, Analog 2 and Analog 3 Setup screens. Select the screen and select / edit parameters as in step 3.

    8

    Configure User Selected Parameters

    Section 4.10

    Select parameters to display in the User Selected Parameters section of the Run Status screen using the Setup screen.

    Select the screen and select / edit parameters as in step 3.

    2 I want to..

    2.1 Activate the normal drive screenPress any key. Do NOT press the STOP key unless you want the drive to stop. Refer to Section 3.5.4.

    2.2 Activate the status indicator screenThe status indicator screen is displayed automatically after 5 minutes of keypad inactivity. It can not be activated manually.

  • 7VIIVECTOR2.3 Adjust the frequency setpoint

    Press the Setp soft key on the Run Status screen to activate setpoint change mode. Use the up and down arrow keys to adjust the setpoint as desired. Refer to Section 4.1

    2.4 Clear the Fault statePress the STOP key to attempt to clear the fault state. Some faults require a full power cycle to reset.

    2.5 Determine the current rating of this driveExamine the Drive Max Amps parameter displayed on the All Monitors screen. Refer to Section 4.14

    2.6 Change one of the parameters in the Linear ListPlease discuss this with Engineering. Some of these values are changed automatically when the higher level parameters are changed via the setup screens. Therefore, changes to the parameters in the Linear List must be considered carefully to avoid unexpected results. Refer to Section 4.17

    2.7 Save Data Log, Current Log, and Events files to USB Flash diskSee description of the Save soft key in the History screen. Refer to Section 4.9

    2.8 Set drive parameters to their factory default valuesSelect the Set all parameters to factory defaults. function in Maintenance screen.Note that this function sets both the high level user interface parameters and low level drive parameters to their factory defaults. This function may take several seconds. The drive must be powered off and then back on after this function has completed prior to further drive configuration or use. Refer to Section 4.30

    2.9 Adjust the V/F behavior of the driveThe high level parameter V/F Select in the Frequency Menu allows selection from several standard V/F curves (60 Hz Standard Torque, 60 Hz Medium Torque, 60 Hz High Torque, 50 Hz Standard Torque, 50 Hz Medium Torque, 50 Hz High Torque). Using this selection, along with the Maximum Frequency, should accommodate many, if not all, ESP installations. The V/F behavior can be customized if necessary please contact the GE Oil & Gas controls group at Oklahoma City for advice if such customization is necessary. Refer to section 4.23 and section 7.

    2.10 Fine tune the drive output voltage without stopping the driveAdjust the Voltage Bias parameter in the Frequency Setup screen. Note that the Voltage Bias is applied if the drive is running a maximum frequency. At lower frequencies, the voltage bias is scaled. Also note that the output voltage is limited by the DC bus voltage. Refer to section 4.23 and section 7.

    3 Installation and Setup

    3.1 Site Installation

    3.1.1 Equipment InspectionUpon receiving equipment a thorough inspection for external and internal damage should be conducted before connecting and operating.

  • GE Oil & Gas

    GE imagination at work

    Check the external enclosure for broken welds, hinges, bent corners, doors or bent legs. Check the internal enclosure for loose or broken hardware such as fans, covers or fasteners. Inspect all wire terminations to ensure connections are tight. Inspect the enclosure for any signs of water leakage into the drive. NOTE!!! If the drive is to be used in an ESP application, make sure that the unit is connected to an output

    filter (either internal or an external). NOTE!!! Multi-pulse units require a properly sized and configured phase shift transformer.

    3.1.2 Equipment Installation and RequirementsEquipment Placement The main power service should be located no closer than 100 (30m) from the wellhead. The drive should be placed at least 50 (15m) from the wellhead, to prevent exposure to hazardous and

    explosive gasses, and provide adequate access for well work over equipment. The drive should be placed on a flat level surface; a concrete pad is recommended but not required, The

    VSD should be fastened to the pad through the mounting holes in the enclosure legs. Only use mounting hardware designed for use with the pad material.

    A minimum of 6 of space should be maintained on all four sides of the drive. This will ensure correct airflow across cooling heat sinks and fan intakes, as well as provide easy access for servicing and cable entry.

    Service Requirements Main service amperage is based on drive KVA and motor load calculations. A service disconnect is required between the service transformers and the drive. This should be sized to

    accommodate service amperage. Overhead service drops into disconnects or other equipment must be equipped with a mast mounted

    weather head to prevent rain from entering equipment.

    Grounding and BondingDANGER Correct system grounding and equipment bonding is required to ensure proper operation of equipment during both normal operation and fault conditions. Grounding and bonding conductors provide a path to ground for lethal fault currents and voltages. Failure to correctly ground and bond equipment can lead to equipment damage and personnel injury or death. Refer to Figure 3.1.

    Grounding applies to the main service connection to ground. Service transformer wye-point and enclosures, including the service disconnect switch, must be connected to a common ground conductor and grounding electrodes. (Refer to local electrical authority for approved grounding electrodes and methods in you area) System ground resistance should not exceed 25 Ohms to ground and ideally be between 1-5 Ohms to ground. Ground resistance checks should only be made by qualified electrical inspection agencies.

    Bonding applies to all other electrical equipment and raceways. A bonding conductor must be connected from the main grounding electrodes to all enclosures, junction boxes, buildings, electrical pipes, and the wellhead.

    This equipment provides an internal ground connection for the bonding conductor. This connector is connected to the internal ground bus of the enclosure.

    Generator requirements Generator supplied power systems have the same requirements for grounding and bonding as utility

    supplied systems. Grounding electrodes must be installed and a common bonding conductor connected to all equipment and buildings.

    Use of generators on drives creates other possible operational problems that can be reduced with correct generator sizing and design. Generators must be designed to handle the sub-transient reactance present on VSD applications. When the generator system does not incorporate a wye-point for connection to the system ground, then an isolation transformer is required between the generator and input to the VSD. This provides some protection from floating voltages, and provides a wye-point for connection to the ground

  • 9VIIVECTORsystem.

    Failure to follow the above guidelines will result in poor performance and/or equipment failure. When a generator unit is used for drive input power, it is highly recommended to use a multi-pulse VSD

    (12 Pulse or higher) or the generator should be sized to at least 300% of the VSD rating.

    Figure 3.1 Typical Drive Site Installation Grounding and Bonding

  • GE Oil & Gas

    GE imagination at work

    3.1.3 Electrical ConnectionsMain Circuit Terminal Configuration Input power is applied to the drive circuit breaker MCCB1 terminals L1, L2, L3 (and MCCB2 L11, L21, L31

    terminals in 12 Pulse units). Output power connections are made at the output power block terminals T1, T2, T3. Refer to Figures 3.2 and 3.3 for reference Applicable lug sizes give in Table 3.1

    Drive Model

    Input Conductor 6 Pulse / Phase

    Input Conductor 12 Pulse /Phase

    Output Conductor / Phase Ground LugSize

    PWM VSG

    757 (4x) 1/0 500MCM(4x) 54mm2 - 253mm2(2x) #2 - 600MCM

    (2x) 34mm2 - 304mm2(4x) 1/0 - 750MCM

    (4x) 54mm2 - 380mm2(4x) 1/0 - 750MCM

    (4x) 54mm2 - 380mm2#14 - 2/0

    2.5mm2 - 70mm2

    1010 (4x) 1/0 500MCM (4x)54mm2 - 253mm2(2x) #2 - 600MCM

    (2x) 34mm2 - 304mm2(4x) 1/0 - 750MCM

    (4x) 54mm2 - 380mm2(4x) 1/0 - 750MCM

    (4x) 54mm2 - 380mm2#14 - 2/0

    2.5mm2 - 70mm2

    1136 (6x) 300 600MCM(6x) 152mm2 - 304mm2(3x) 1/0 500MCM

    (3x)54mm2 - 253mm2(8x) 1/0 - 750MCM

    (8x) 54mm2 - 380mm2(8x) 1/0 - 750MCM

    (8x) 54mm2 - 380mm2#6 - 350MCM

    16mm2 - 165mm2

    1515 (6x) 300 600MCM(6x) 152mm2 - 304mm2(4x) 1/0 500MCM

    (4x)54mm2 - 253mm2(8x) 1/0 - 750MCM

    8x) 54mm2 - 380mm2(8x) 1/0 - 750MCM

    (8x) 54mm2 - 380mm2#6 - 350MCM

    16mm2 165mm2

    Table 3.1 Applicable Lug Sizes for Main Circuit Terminals

    Vector VII Recommended Cable Size

    Drive Model Input Conductor 6 Pulse / PhaseL1 L2 L3 Size* (AWG kcmil)Input Conductor 12 Pulse / Phase

    L1 L2 L3 L11 L21 L31 Size* (AWG kcmil)Output Conductor / PhaseT1 T2 T3 Size* (AWG kcmil)

    Cable Temperature Rating and Type Cable Temperature Rating and Type Cable Temperature Rating and Type60 C(140F)TYPETW,UF

    75 C(167F)TYPERHW,

    THHW,THW,

    THWN,XHHW,

    USE,ZW

    60 C(140F)TYPETW,UF

    75 C(167F)TYPERHW,

    THHW,THW,

    THWN,XHHW,

    USE,ZW

    60 C(140F)TYPETW,UF

    75 C(167F)TYPERHW,

    THHW,THW,

    THWN,XHHW,

    USE,ZW

    757Input Rating = 910 Input Rating = 910 Output Rating = 910

    (4x) 500MCM(4x) 240mm2

    (4x) 300MCM (4x) 152mm2

    (2x) 500MCM (2x) 240mm2

    (2x) 300MCM (2x) 152mm2

    (4x) 500MCM (4x) 240mm2

    (4x) 300MCM(4x) 152mm2

    1010Input Rating = 1215 Input Rating =1215 Output Rating =1215

    (4x) 700 MCM (4x) 354mm2

    (4x) 500MCM (4x) 240mm2

    (2x) 700MCM (2x) 354mm2

    (2x) 500MCM (2x) 240mm2

    (4x) 700MCM (4x) 354mm2

    (4x) 500MCM (4x) 240mm2

    1136Input Rating =1336 Input Rating = 1336 Output Rating = 1336

    (6x) 400MCM (6x) 203mm2

    (6x) 300MCM (6x) 152mm2

    (3x) 400MCM (3x) 203mm2

    (3x) 300MCM (3x) 152mm2

    (6x) 400MCM (6x) 203mm2

    (6x) 300MCM (6x) 152mm2

    1515Input Rating = 1822 Input Rating = 1822 Output Rating = 1822

    (6x) 700MCM (6x) 354mm2

    (6x) 500MCM (6x)240mm2

    (3x)700MCM (3x) 354mm2

    (3x) 500MCM (3x) 240mm2

    (6x) 700MCM (6x) 354mm2

    (6x) 500MCM(6x) 240mm2

    Table 3.1.1 Recommeded Cable Sizes*Copper conductors, not more than 3 insulated conductors raterd 0-2000 volts in raceway or cable. Ambient temperature of 30C (86F).*Table 3.1.1 Recommedned cable sizes are calculated to be sized 125% of input/output current rating.

  • 11

    VIIVECTOR

    X1

    X2

    X3

    L1L2L3

    T1

    T2

    T3

    Step Up Transformer

    Vector VII 6P VSD

    H1

    H2

    H3

    INPUTPOWER

    OUTPUT POWER

    TO VENTED J-BOX AND

    MOTOR

    MCCB1

    Figure 3.2 6 Pulse Main Circuit Terminal Configuration

    X1

    X2

    X3

    L1

    L2

    L3

    L1L2L3 T1

    T2

    T3

    Step Up Transformer

    Vector VII 12P VSD

    H1

    H2

    H3

    INPUTPOWER

    OUTPUT POWERTO VENTED J-BOX AND MOTORL1

    L2L3

    Phase ShiftTransformer

    X1

    X2

    X3

    X1X2X3

    Y1Y2Y3

    MCCB1

    MCCB2

    Figure 3.3 12 Pulse Main Circuit Terminal Configuration

    3.2 Hardware Connections

    3.2.1 Control TerminalsIdentifying Control TerminalsDigital and Analog I/O are supported through the control terminals. The Control Terminals (located on the Terminal Card) are mounted on the lower section of the drive chassis. The picture below shows the control terminals.

  • GE Oil & Gas

    GE imagination at work

    Figure 3.4Control Terminal Wire Sizes

    Terminal Possible Wire Sizes AWG (1 Amp Max) Recommended Wire Size AWG

    ALL ( Except E(G) ) Stranded wire: 26 - 16 18

    E(G) 20 - 14 14

    Terminal Designations: Refer to Figure 3.4 and 3.5 for control terminal and HMI terminal diagram.

    Digital InputsTerminal Signal Description Signal level

    9 Remote Run Forward run when CLOSED, stopped when OPEN 24VDC, 8mA10 Not Used - -11 External Fault 1 Fault when OPEN (Programmable) 24VDC, 8mA12 External Fault 2 Fault when OPEN (Programmable) 24VDC, 8mA13 Standby Standby when OPEN (Programmable) 24VDC, 8mA14 Event Programmable 24VDC, 8mA15 Breaker 2 Fault Fault when OPEN (Programmable) 24VDC, 8mA16 Inductor Overheat Fault when OPEN (Programmable) 24VDC, 8mA17 D Common - -

    Analog InputsTerminal Signal Description Signal level

    34 (+ 15VDC) - 15VDC, 8mA44 (- 15VDC) - 15VDC, 8mA36 Analog 3 Analog Input or speed command 0-10 V39 Analog 2 Multi-function Analog input 0-10 V, 4-20mA42 Analog 1 Analog Input or speed command 0-10 V35 Analog Common - -

  • 13

    VIIVECTORDigital Outputs

    Output Contact Ratings 1Amp Max at 250VAC or 30 VDC

    Terminal Signal Description Signal level

    25

    Drive Fault

    25

    52

    23

    Dry Contact

    52

    23

    53

    Drive Running

    53

    57To Fan Relay

    Dry Contact

    57

    50

    Open Collector

    19

    20

    50

    Dry Contact

    19

    20

    Analog Outputs

    Terminal Signal Description Signal level45 Frequency Output Programmable 0-10 VDC48 Current Output Programmable 0-10 VDC46 Analog Common - -

  • GE Oil & Gas

    GE imagination at work

    Digital Inputs

    9

    10

    11

    12

    13

    14

    15

    16

    17

    34

    44

    36

    39

    Remote Run

    Not Used

    External Fault 1

    External Fault 2

    Standby

    Event

    Breaker 2 Fault

    +15 VDC

    - 15 VDC

    Inductor Overheat

    Analog 3

    25

    52

    23

    53

    57

    19

    20

    Digital Outputs

    Analog Inputs

    41

    Drive Fault

    Drive Running

    45

    48

    46

    Frequency Output 0-10 VDC

    Current Output 0-10 VDC

    Analog Common

    Analog Outputs

    47

    COM5

    COM4

    COM3

    COM2

    COM1

    HMI

    RTU/SSU

    RS232

    SCADA

    RESERVED/DEBUG

    D Common

    1 2

    +5V GND

    EXTERNAL USB PORT

    To Fan Relay

    RxTx

    42

    35 Analog Common

    Analog 1

    Analog 2

    51

    58

    38

    29

    TUBE

    FLOW

    50

    Open Collector

    Osiris

    23

    1PCB 6CN

    P/N: 196654 - HMI

    P/N: 196631

    1PCB P/N: 196343

    P/N: 196119 - Keypad Figure 3.5 Control Terminals and HMI Terminal Diagram

  • 15

    VIIVECTORDigital Inputs

    9

    10

    11

    12

    13

    14

    15

    16

    17

    34

    44

    36

    39

    Forward run/stop

    Reverse run/stop

    External Fault 1

    External Fault 2

    Standby

    Event

    Jog

    +15 VDC

    - 15 VDC

    External Fault 3

    VSPDREF

    25

    52

    23

    53

    57

    19

    20

    Digital Outputs

    Analog Inputs

    41

    Drive Fault

    Drive Running

    45

    48

    46

    Frequency Output 0-10 VDC

    Current Output 0-10 VDC

    Analog Common

    Analog Outputs

    47

    R+

    R-

    S+

    S-

    IG

    D Common

    To Fan Relay

    42

    35 Analog Common

    V-AN

    ISPDREF

    51

    58

    38

    29

    TUBE

    FLOW

    50

    Open Collector

    EXTERNAL USB-A PORT

    J3

    1234

    321

    21

    J14

    J22

    J21

    240 VAC Input

    +24 VDC Input

    Ground+24 VDC

    ChassisNeutralLine

    Vector VII Operator Control Panel

    Figure 3.6 Control Terminals and New HMI Terminal Diagram

  • GE Oil & Gas

    GE imagination at work

    3.2.2 External Stop SwitchesThe drive supports up to two external stop switches. When a stop switch is activated, an external fault occurs and the drive stops.

    To connect External Stop Switch 1: 1. Wire a stop switch between 11 and 17.2. Enable External Fault 1 on the Misc Setup screen as Normally Open (N.O.) or Normally Closed (N.C.).

    To connect External Stop Switch 2: 1. Wire a stop switch between 12 and 17.2. Enable External Fault 2 on the Misc Setup screen as Normally Open (N.O.) or Normally Closed (N.C.).

    3.2.3 Standby Switch InputThe drive supports a normally closed external switch that will stop the drive when the switch opens. This can be used to stop the drive in a tank full or lease kill situation. If the Standby switch opens when the drive is running, the drive stops and enters the STANDBY state. An event is created but no fault occurs. The drive will immediately restart when the switch is closed again.

    To connect the Standby Relay:1. Wire the normally closed terminals of the standby relay between 13 and 17.2. Enable the Standby Switch parameter on the Misc Setup screen.

    3.2.4 Event SwitchThe drive supports a switch that logs events when the switch changes states. No fault occurs and the drive does not stop.

    To connect the drive to an event switch.1. Wire the switch to be monitored between 14 and 17.

    3.2.5 Remote Run and ReferenceThe drive supports a 2-wire external run interface along with an analog signal for drive speed control.

    DANGER When operating in 2-wire mode the drive may start automatically upon power up of the unit. Ensure that the Remote Run input is OPEN before powering up a drive set up in 2-wire mode

    To connect the drive to a remote run control and reference (Refer to figure 3.7):1. Install a Normally Open relay contact between terminals 09 and 17. 2. Connect the 0V 10V analog reference signal to terminal block position 36.3. Connect analog ground to terminal block position 35.

    The drive will run when terminal 09 is pulled to the 17 state (i.e. contactor or switch is closed).

  • 17

    VIIVECTORControl

    Terminals9 Remote Run

    17 Signal Common

    34 Analog Input 1(0-10VDC)

    35 Analog Common0-10VDCSpeed Reference

    +-

    Remote Run Switch

    Figure 3.7 Remote Run Operation

    3.3 Startup Checks

    DANGER The following steps require that the system be energized. Only qualified personnel should perform the following procedures.

    3.3.1 Pre Power-Up Remove and lock-out incoming power out before connecting the drive. Ensure that the drive is properly grounded. Do a complete visual inspection, checking for loose or broken wires. Make sure all internal and external fans are free to turn. Perform Main Circuit testing procedure outlined in Section 7.1.2. Connect the service power to the main input circuit breaker of the drive (L1, L2, L3 on 6 Pulse drives (and L11,

    L21, L31 on 12 Pulse drives)). !!!! Note connecting the input power to the output of the drive can cause severe damage to the drive.

    Ensure that the output of the drive is disconnected (T1, T2, T3). Ensure that main drive circuit breaker(s) switch is in the Off position and all remote start signals that may be present are defeated.

    Turn power on at the service disconnect and measure incoming voltage. Check the voltage phase to phase and phase to ground and ensure that the voltages are in range before closing drives circuit breaker. The phase to phase voltage should be 480VAC +/-10% and the phase to ground should be approximately 277VAC +/-10%.

  • GE Oil & Gas

    GE imagination at work

    3.3.2 Pre Run Checks

    DANGER The following steps require that the system be energized. Only qualified personnel should perform the following procedures.

    Drive Power Up Energize main input circuit breaker(s) and verify that the HMI powers up with no fault conditions present. Check the DC Bus level. Measure across +3 and - terminals. Nominal values should be between 650 700

    VDC. In most cases it is wise to reset the drive to its factory default parameter settings before commissioning the

    drive. This should always be done when a drive has been used on a previous application. See Section 4.30 Set All Parameters To Factory Defaults.

    Proceed with no-load checks

    No-Load ChecksNo load checks should be performed to ensure proper operation of the drive before connecting the output of the drive to its load (Step-up Transformer or Motor). Proceed with the following steps.

    Make sure that the drive output connections are disconnected. If they are not, ensure that the incoming power is locked out. Wait at least five minutes after removing power and measure the DC bus voltage to confirm safe level of voltage using volt meter set to read DC volts with the black lead connected to (-) and the red lead connected to (+3). Disconnect the drive output connections.

    From the Run Status screen, use the Setp soft key and the down arrow key to adjust the frequency reference to the minimum frequency.

    Navigate to the Underload Setup screen and set the Underload Current to 0. Set parameter L8-07 in the linear list to 0 (disabled), this will avoid nuisance LF Missing Output Phase

    Faults. Press the Start button. Navigate to the Run Status screen. Check the output voltage. Use the Setp soft key and the up arrow key

    to adjust the frequency reference to the maximum frequency. Check the output voltage. Output voltage should be equal to the incoming voltage at maximum frequency and approximately half of that value at minimum frequency (depending on setup of Voltage/Frequency).

    Press the Stop button. Set parameter L8-07 in the linear list back to 1 (enabled). De-energize the main input circuit breaker and verify the HMI is no longer powered up. Wait at least five minutes after removing power and measure the DC bus voltage between the +3 and

    terminals to confirm safe voltage level. Lock-out incoming power. Re-connect the motor or Transformer leads to output terminal block T1, T2, T3. Make sure that the drive

    output connections are tightly connected before continuing to next step.

  • 19

    VIIVECTOR3.3.3 Drive Start Up

    Once the drive has been set up and checked without the load connected, the drive is ready for startup. Proceed with the following steps.

    Navigate to the Underload Setup screen and set the Underload Current to the desired value. From the Run Status screen, use the Setp soft key and the up / down arrow keys to set the frequency

    reference to the desired operating frequency. Press the Start button on the HMI. With the drive running, check the output voltage and output current to ensure that they are within the

    limits of the given application. If any faults are present refer to Section 9 for troubleshooting.

    3.4 Keypad Conventions

    START STOP

    F5F4F3F2F1

    USB Port

    196783197XXX

    START STOP

    Figure 3.8.2 New HMI Keypad

    3.4.1 Soft keysThe 5 soft keys are located just below the LCD display and are labeled F1 through F5. The function of a soft key is defined by the label in the rectangle on the LCD display just above the key. The function of a soft key varies with the active screen.

  • GE Oil & Gas

    GE imagination at work

    3.4.2 Arrow KeysThe arrow keys are screen dependent but the following rules applyLeft and Right Arrows: If a graph or a chart is displayed, re-draws the chart using older (left arrow) or newer (right arrow) data. In the Linear List, displays the previous (left arrow) or next (right arrow) set of Linear List parameters. In the Enter Password and Date / Time screens, selects the field to the left (left arrow) or the right (right

    arrow) of the currently selected field.

    Up and Down Arrows: In the Run Status screen with the Setp soft key active, the up and down arrows adjust the set point up

    (up arrow) and down (down arrow). The set point applies in the Current Control, Pressure Control, and Frequency Control modes.

    In screens where lists of parameters are displayed, moves the selection to the parameter above (up arrow) or below (down arrow) the currently selected parameter.

    In the Numeric Parameter Entry screen, the Password Entry screen, and the Date / Time Entry screen adjusts the selected (highlighted) value up (up arrow) or down (down arrow).

    3.4.3 Start / StopThe Start and Stop buttons work from all screens. Start will only start the drive if it is in the Ready state. Stop has priority over any other key.

    3.4.4 Status Indicator Screen Old Blue Box HMIThe screen will change to display drive state information that can be seen from a distance whenever the keypad is inactive for 5 minutes. Pressing any key will return the user interface to its normal state. NOTE: Pressing the Stop key at any time whether the screen is in the normal or status indication mode will stop the drive!

    Drive status indicators are as follows: Flashing Red Drive stopped in Fault state. Red Drive stopped in Ready state. Amber Drive stopped in Restart state. Drive will automatically restart but the time to restart

    is greater than 1 minute.

  • 21

    VIIVECTOR Flashing Amber Drive stopped in Restart or Standby state. Drive will automatically restart. If in

    Restart state, the drive will restart in less than 1 minute. If in Standby state, the drive will restart immediately whenever the standby switch closes.

    Green Drive running. Flashing Green Drive running in Alarm state.

    3.4.5 Status Indicator Screen New HMIThere are three high intensity LEDs located just above the screen. These correspond with the following indications as the Old HMI screens.

    Drive State LED IndicatorsStop (Red) Fault (Amber) Run (Green)

    Fault On On OffReady On Off OffRestart (more than 1 minute) On Flash OffRestart (less than 1 minute)Standby

    Flash Flash Off

    Running Off Off OnRunning in Alarm Off Flash On

  • GE Oil & Gas

    GE imagination at work

    3.5 Configuration

    3.5.1 Drive ModeNote: Refer to Section 3.3.1 for locations of control terminal block connections.

    1. From the Run Status screen, select the Menu soft key and then select Log In. Enter the password and select the OK soft key. (refer to Section 3.4 for log in information)

    2. Select the Operating Mode screen and select the OK soft key.3. Select the Drive Mode parameter and press the Edit soft key.4. Select the desired Drive Mode.

    a. Frequency Control Drive output frequency matches Frequency Setpoint.b. Analog Follower Drive speed follows the value of the analog signal (0 10V) connected to terminal

    block connection 36. Note that this mode requires additional wiring.i. Wire the analog input signal (0 10V) to 36 and common to 35.

    c. Current Control In this mode the drive frequency is adjusted to maintain a desired output current. This mode is often used with gassy wells. As the pump encounters gas pockets, the drive current decreases. The drive speeds up and the gas bubbles are cleared from the system.

    d. Pressure Control In this mode the drive frequency is adjusted to maintain a desired intake or exhaust pressure. Note that this mode requires additional wiring.

    i. Wire the pressure sensor signal (0 10V, 4 20mA) to 39 and common to 35.5. Press the OK soft key to accept the change.

    Note: The user interface displays the Select screen if the drive mode has been changed.6. Select the Operating Mode screen and press the OK soft key.7. Select and edit any other parameters associated with the selected drive mode.

    3.5.2 Frequency Behavior

    1. From the Run Status screen, select the Menu soft key. If the Not Logged In Select screen appears, then select Log In, enter the password, and select the OK soft key.

    2. Select the Frequency Setup screen and select the OK soft key.

    3. Select and modify the frequency parameters as desired.

    3.5.3 Alarms and Restarts1. From the Run Status screen, select the Menu soft key. If the Not Logged In Select screen appears, then select Log In, enter the password, and select the OK soft key.3. Select the Alarms Setup screen and select the OK soft key.4. Select and modify the alarms and restart parameters as desired.5. Select the Menu soft key and then select the Underload Setup screen.6. Select and modify the Underload parameters as desired.

    3.5.4 Motor DirectionFrom the Run Status screen, select the Menu soft key. If the Not Logged In Select screen appears, then select Log In, enter the password, and select the OK soft key.Select the Frequency Setup screen and select the OK soft key.Select the Motor Direction parameter and modify as desired. Note that motor direction changes CAN be

  • 23

    VIIVECTORimplemented without stopping the drive. Set the direction as desired. Once the change has been made, press the Start button. Drive will perform a controlled frequency ramp through 0 Hz to the setpoint frequency in the specified motor direction.

    4 Screen Descriptions

    4.1 Run Status

    Function:The Run Status screen is the default screen when the drive is powered up. It displays all data needed to assess the up-to-date state of the drive.

    Field Descriptions:Screen Name: Run Status. This field is the name of the displayed screen.Drive State: Running. This field displays the up-to-date state of the drive. Possible values include Not Ready,

    Ready, Accelerating, Decelerating, Running, Ready Rem(ote), Start Rem(ote), Run Remote, Stop Rem(ote), Forced Stop, Fault, Restart (or RST time to restart), DRIVE OFF, Standby, Standby Remote.

    Drive Serial Number: Serial number of the drive. Drive Mode: Frequency Control. Designates the control mode of the drive. The mode can be changed in the

    Operating Mode screen. Date / Time: Date and time (mm/dd/yyyy hh:mm:ss) Frequency Setpoint: 60.00 Hz. The up-to-date frequency setpoint. This field will not be present in some drive

    control modes.Output Current: 0.2 A. The up-to-date drive output current.Output Frequency: 60.00 Hz. The up-to-date frequency being emitted by the drive.Output Voltage: 230.0 V. The up-to-date voltage being emitted by the drive.Motor Direction Indicator: If the motor is running forward (or set to run forward if drive is currently stopped), the

    direction indicator will show a clockwise semi-circle arrow with an F adornment. If the drive is running in reverse (or set to run in reverse if the drive is currently stopped), the direction indicator will show a counter-clockwise semi-circle arrow with an R adornment.

  • GE Oil & Gas

    GE imagination at work

    User Selected Parameters: Analog A1, Analog A2, Intake Press, Intake Temp, Motor Temp. Up to 5 user selected parameters may be displayed on the run status screen. See the Setup screen for selecting these parameters.

    Graph: Analog A1. Graph displaying 24 hours of graphical data. Graphed parameters include Output Current, Output Voltage, Output Frequency, Analog A1, Analog A2, Intake Pressure, Intake Temperature, and Motor Temperature. Please note that the last 3 parameters require a Osiris downhole tool. Note that red lines in the graph denote data values that are interpolated between actual data values (usually indicates that the drive was powered off).

    Keypad Functions:F1: Graph. Used to select the parameter to be shown on the graph.F2: Setp. Used to activate the setpoint change mode. When activated, the Setp button is displayed in black with

    white text and the up and down arrows can be used to modify the setpoint. Note that the setpoint field is also highlighted when setpoint change mode is activated. Setpoint change mode is automatically cancelled after 45 seconds or can be deactivated by pressing F2 a second time.

    F3: Scale. Modifies the scale of the graph. Scale values cycle 1x, 2x, 4x, 8x, 16x.F4: Events. Activates the Events screen to display the 256 most recent events.F5: Menu. Activates the menu allowing other screens to be accessed.Up Arrow: Increases the setpoint in the Current Control, Pressure Control, and Frequency Control modes (when

    setpoint change mode is active).Down Arrow: Decreases the setpoint in the Current Control, Pressure Control, and Frequency Control modes (when

    setpoint change mode is active).Left Arrow: If graph scale is 1x, draws the graph for the previous day. If graph scale is > 1x, allows scrolling through

    the scaled graph data.Right Arrow: If graph scale is 1x, draws the graph for the next day. If graph scale is > 1x, allows scrolling through the

    scaled graph data.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

    4.2 Event Log

    Function:The Event Log screen displays the last 256 time-stamped events, included drive starts and stops, faults, and parameter changes.

  • 25

    VIIVECTORField Descriptions:

    Screen Name: Event Log. This field is the name of the displayed screen.Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

    Time-stamped Events: List of the last 256 events.

    Keypad Functions:F1: Prev. View older events.F2: Next. View newer events.F3: Not used.F4: Not used.F5: Status. Return to the Run Status Screen.Up Arrow: Not used.Down Arrow: Not used.Left Arrow: Not used.Right Arrow: Not used.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

    4.3 Select Screen (Not logged in)

    Function:The Select Screen allows the user to select and display a different screen. The not logged in version of the select screen prevents non-privileged users from accessing most setup parameters.

    Field Descriptions:Screen Name: Select Screen. This field is the name of the displayed screen.Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

  • GE Oil & Gas

    GE imagination at work

    List of screens that can be selected.

    Keypad Functions:F1: Unlabeled. Activate the Keypad Test screen.F2: Not used. F3: Startup. Activate the Startup Control. Use this screen to enable or disable the drive and to enable or disable

    automatic restarts. F4: Not used.F5: OK. Proceed to the highlighted screen. Note that the Run Status screen is always highlighted by default when

    the Select Screen is drawn.Up Arrow: Move selection up the list.Down Arrow: Move selection down the list.Left Arrow: Not used.Right Arrow: Not used.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

    4.4 Enter Password

  • 27

    VIIVECTORFunction:

    The Enter Password screen allows the user to log in. Once logged in, the user has access to all screens and setup parameters.

    Field Descriptions:Screen Name: Enter Password Screen. This field is the name of the displayed screen.

    Password digits to edit.

    Keypad Functions:F1: OK. Accept the entered password. If the password is correct, the Select Screen (Logged in) will be drawn.F2: CANCEL. Return to the Select Screen.F3: Not used.F4: Not used.F5: Not used.Up Arrow: Increment the highlighted password digit.Down Arrow: Decrement the highlighted password digit.Left Arrow: Select the digit to the left of the currently selected digit.Right Arrow: Select the digit to the right of the currently selected digit.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

    Note that the default password on the drive is 3333. However, the password can be changed in the Misc. Setup screen.

    If the password is forgotten, please contact your local GE Oil & Gas service center.

    4.5 Select Screen (Logged in)

    Function:

  • GE Oil & Gas

    GE imagination at work

    The Select Screen allows the user to select and display a different screen. The Logged in version of the select screen provides access to all screens and setup parameters.

    Field Descriptions:Screen Name: Select Screen. This field is the name of the displayed screen.Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the

    Run Status screen description.

    List of screens that can be selected.

    Use the following screens to configure the drive: Operating Mode Alarms Setup Underload Setup Start Control Frequency Setup Analog 1 Setup Analog 2 Setup Analog 3 Setup Misc Setup Comm Setup Hard Starting Maintenance

    The setup screens are listed together in the right column on this screen.

    Screens in the left column tend to be informational.

    Keypad Functions:F1: Unlabeled. Activate the Keypad Test screen. F2: Not used. F3: Startup. Activate the Startup Control. Use this screen to enable or disable the drive and to enable or disable

    automatic restarts. F4: Not used.F5: OK. Proceed to the highlighted screen. Note that the Run Status screen is always highlighted by default when

    the Select Screen is drawn.Up Arrow: Move selection up the list. Note that at the top of the list the selection will move to the bottom of the list.Down Arrow: Move selection down the list. Note that at the bottom of the list the selection will move to the top of

    the list.Left Arrow: Move selection to the left column.Right Arrow: Move selection to the right column.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

  • 29

    VIIVECTOR4.6 Fault Status

    Function:The Fault Status screen allows the user to determine the state of all drive faults. Note that this screen can be chosen from the Select Screen and is automatically entered when a fault is detected.

    Field Descriptions:Screen Name: Fault Status Screen. This field is the name of the displayed screen.Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

    Any active fault or feature that is not in its OK state is displayed.

    Keypad Functions:F1: Not used.F2: Not used.F3: Not used.F4: Not used.F5: Menu. Return to the Select Screen.Up Arrow: Not used.Down Arrow: Not used.Left Arrow: Not used.Right Arrow: Not used.START: Starts the drive if it is in the Ready state.STOP: Stops the drive if running. If in the fault state, pressing STOP will attempt to clear the faults.

  • GE Oil & Gas

    GE imagination at work

    4.7 Amp Chart

    Function:The Amp Chart screen displays 1 or 7 days worth of current data in the familiar circular format. Current data is taken every 10 seconds. The current log is sized to hold 7 days of current data.

    Field Descriptions:Screen Name: Amp Chart. This field is the name of the displayed screen.Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

    Outer Ring: 10 A. Displays the current associated with the outer circle of the amp chart. Resolution: 1 A. Displays the current resolution (current difference between adjacent lines) of the amp chart.Date: 12/01/2008. The day associated with the amp chart. On a 7 day amp chart the date displayed is for the

    newest displayed data.Output Current: 0.0 A. Displays the up-to-date drive output current.

    Keypad Functions: F1: Today. Draws the amp chart associated with todays date.F2: Not used.F3: 1/7 Day. Toggles the amp chart between a 1 day and a 7 day scale.F4: Not used.F5: Menu. Return to the Select Screen.Up Arrow: Not used.Down Arrow: Not used.Left Arrow: Draw the amp chart associated with the preceding day.Right Arrow: Draw the amp chart associated with the following day.START: Starts the drive if it is in the Ready state.STOP: Stops the drive if running.

  • 31

    VIIVECTOR4.8 Trending

    Function:The Trending screen displays graphs containing 5 days worth of data. Graph data is taken from the Data log and is sized to hold 35 days worth of data (with data taken every 5 minutes).

    Field Descriptions:Screen Name: Trending. This field is the name of the displayed screen.Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

    Graph: Output Frequency (Hz). Graph displaying 5 days of graphical data. Graphed parameters include Output Current, Output Voltage, Output Frequency, Analog A1, Analog A2, Intake Pressure, Intake Temperature, and Motor Temperature. Please note that the last 3 parameters require a Osiris downhole tool. Note that red lines in the graph denote data values that are interpolated between actual data values.

    Statistics: Min Value, Max Value, Average, RMS. Values calculated from the 5 days of data from the data log.

    Keypad Functions:F1: Graph. Used to select the parameter to be shown on the graph.F2: Not used.F3: Scale. Modifies the scale of the graph. Scale values cycle 1x, 2x, 4x, 8x, 16x.F4: Not used.F5: Menu. Activates the menu allowing other screens to be accessed.Up Arrow: Not used.Down Arrow: Not used.Left Arrow: If graph scale is 1x, draws the graph for the previous 5 day period. If graph scale is > 1x, allows scrolling

    through the scaled graph data.Right Arrow: If graph scale is 1x, draws the graph for the next 5 day period. If graph scale is > 1x, allows scrolling

    through the scaled graph data.START: Starts the drive if it is in the Ready state.STOP: Stops the drive if running.

  • GE Oil & Gas

    GE imagination at work

    4.9 History Screen

    Function:The History screen displays logged performance data.

    Field Descriptions:Screen Name: History Screen. This field is the name of the displayed screen.Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

    Time-stamped History Entries: The data log is circular log sized to store the last 35 days of data. Data is captured every 5 minutes.

    Keypad Functions:F1: Prev. View older logged data.F2: Next. View newer logged data.F3: Set. View a different set of data. Currently there are 4 sets of data. The first set is shown. The other sets

    include more drive parameters and parameters retrieved from a Osiris downhole tool.F4: Save. Save the Data Log, the Event Log, the Current Data (used for the Amp Chart), and the drive configuration

    to a USB Flash drive. This device must be placed in the drives USB port for 10 seconds prior to activating the function. All files saved will be saved with the drives programmed serial number and the date the data was retrieved.

    F5: Menu. Return to the Select screen.Up Arrow: Not used.Down Arrow: Not used.Left Arrow: Not used.Right Arrow: Not used.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.Note: To save history data, refer to Appendix 3.1

  • 33

    VIIVECTOR4.10 Setup Screen

    Function:The Setup screen allows any user (no login required) to modify the parameters on this screen.

    Field Descriptions:Screen Name: Setup. This field is the name of the displayed screen.Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

    Language: Allows the user to change between English and SpanishDate Format: Allows the user to choose between mm/dd/yyyy (default), dd/mm/yyyy, and dd-Mmm-yyyy (01-Jan-

    2010) as the format the date will be displayed.Local/Remote: Parameter that determines if control of the drive (Start / Stop and Frequency Reference) is under

    control of the drive user interface or a remote 2-wire host. Remote should not be used if the drive is in Analog Follower Mode.

    Control Location: Gives the user the ability to control the drive from Keypad, SCADA or both.Drive Output: Set to Disabled to inhibit the drives response to all start commands.User Selected 1 5: The parameters selected in these fields are displayed on the Run Status screen.Parameter Description: Local Control / Remote Control Provides user with information concerning the selected

    (highlighted) parameter.

    General Help: Use Up and Down arrows General help information on how to use this screen. Note that some parameters may not be changed when the drive is running. The General Help will state that the drive must be stopped when such a parameter is selected and the drive is running.

    Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

  • GE Oil & Gas

    GE imagination at work

    Keypad Functions:F1: Edit. Edit the selected (highlighted) parameter.F2: Not used.F3: Not used.F4: Not used.F5: Menu. Return to the Select screen.Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom of

    list).Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to top

    of list.Left Arrow: Not used.Right Arrow: Not used.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

    4.11 Osiris

    jFunction:

    The Osiris screen reports the current state of the Osiris interface.

    Field Descriptions:Screen Name: Osiris. This field is the name of the displayed screen.Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run Status

    screen description.

    Osiris Data: Displays the state of the Osiris data:Disabled - Interface disabled

    Osiris Fault Relay: Displays the state of the Osiris fault relay.OK - Data is valid, Bad - Osiris unit is reporting loss of sync. When the data state is disabled or bad, all Osiris readings are set to 0.

    Osiris Comms: Displays the communication efficiency of the communications link with the Osiris. 100% indicates all messages to the Osiris are successful.

    Osiris Sensor Values Intake Press, Intake Temp, Motor Temp, Discharge Pressure, Vibration, Leakage Current,

  • 35

    VIIVECTORUphole Voltage, and Osiris Duty Cycle are displayed in their appropriate units

    Osiris State: Displays the value of the Osiris fault detection state machine. Values include Initializing, OK, Fault, and Restart. Note that this parameter stays in the Init state if the Osiris interface is disabled.

    Keypad Functions:F1: Not used.F2: Not used.F3: Not used.F4: Not used.F5: Menu. Return to the Select screen.Up Arrow: Not used.Down Arrow: Not used. Left Arrow: Not used.Right Arrow: Not used.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

    4.12 Drive I/O

    Function:The Drive I/O screen allows the operator to easily determine the state of all the drive I/O.

    Field Descriptions:Screen Name: Drive I/O. This field is the name of the displayed screen.Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

    9 - 16: Drive digital inputs. These values will be 0 or 1 if the input is not used or if its function is disabled. If the function associated with the input is enabled (i.e. in the example, external fault 1, standby, and Breaker 2 detection features are enabled on the Misc Setup screen), more descriptive text will be displayed (OK, FAULT, RUN, STANDBY).

    19,20: Drive digital outputs.Analog 1, Analog 2, Analog 3: Drive analog inputs. The values are scaled as programmed in the Analog 1 Setup,

    Analog 2 Setup and Analog 3 Setup screens.

    General Help: Press Menu soft key General help information on how to use this screen.

  • GE Oil & Gas

    GE imagination at work

    Keypad Functions:F1: Not used.F2: Not used.F3: Not used.F4: Not used.F5: Menu. Return to the Select screen.Up Arrow: Not used.Down Arrow: Not used.Left Arrow: Not used.Right Arrow: Not used.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

    4.13 Last Fault

    Function:The Last Fault screen allows the operator the ability to easily view the drive condition when the last fault occurred.

    Field Descriptions:Screen Name: Last Fault. This field is the name of the displayed screen.Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

    Parameter Values: Values of key parameters when the drive last faulted. Selecting the fault code parameter will bring up a window that explains the fault code. Selecting a bitmap parameter (one displayed in hexadecimal format) will bring up a window that describes the meaning of all set bits.

    General Help: Press Menu soft key General help information on how to use this screen.

    Keypad Functions:F1: Not used.F2: Not used.F3: Not used.

  • 37

    VIIVECTORF4: Not used.F5: Menu. Return to the Select screen.Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom of

    list).Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to top

    of list.Left Arrow: Not used.Right Arrow: Not used.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

    4.14 All Monitors

    Function:The All Monitors screen displays a variety of parameters that may be useful for troubleshooting problems in the field.

    Field Descriptions:Screen Name: All Monitors. This field is the name of the displayed screen.Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.Drive Monitor Registers: Most of the parameters displayed are directly from the underlying drive. See table below

    for explanation of bitmapped (displayed in hexadecimal) registers. UI S/W Rev: Displays the revision of the User Interface software. Serial Number: Displays the drive serial number. Drive Comms: Displays the quality of the communications with the drive over the last 30 seconds.Osiris Comms: Displays the quality of the communications with the Osiris Surface Unit (always set to 100% if the

    Osiris is disabled in the Misc Setup screen).Cabinet Temp: Displays internal drive temp from the power module heat sink.UI S/W Rev: Displays the revision of the User Interface software. O/S Build: Displays the date of the Windows CE version installed on the HMI.

  • GE Oil & Gas

    GE imagination at work

    General Help: Press Menu soft key General help information on how to use this screen.

    Note: You may use the up and down arrow keys to select monitor values. Selecting the fault code parameter will bring up a window that explains the fault code. Selecting a bitmap parameter (one displayed in hexadecimal format) will bring up a window that describes the meaning of all set bits.

    Drive StatusBit 0 Denotes 1 Denotes0 Drive Stopped Drive Running1 Forward Operation Reverse Operation2 Drive Startup in Progress Drive Startup Completed3 No Fault Fault4 No Data Setting Error Data Setting Error5 Digital Output 1 is OFF Digital Output 1 is ON6 Digital Output 2 is OFF Digital Output 2 is ON

    7 F Not Used Not Used

    Fault Details

    Bit 0 Denotes 1 Denotes0 No Error Over current or Ground Fault Error1 No Error Main Circuit Overvoltage2 No Error Drive Overload3 No Error Drive Overheat4 Not Used Not Used5 No Error Fuse Blown6 No Error PI Feedback Reference Lost7 No Error External Error8 No Error Hardware Error9 No Error Motor Overload or OvertorqueA No Error Underload FaultB No Error Main Circuit UndervoltageC No Error Main Circuit Undervoltage, Control Power

    Supply Error, Inrush Prevention Circuit Error, or Power Loss

    D No Error Missing Output PhaseE No Error ModBus Comm ErrorF HMI Connected HMI Disconnected

    Drive Fault Code

  • 39

    VIIVECTORCurrent Fault exhibited by drive.(There are a few codes that are not included in the Fault Details bitmapped list above.)0 No Fault 25 DEV Speed Deviation

    1 PUF DC Bus Fuse Open 26 OVL Enhanced O-load2 UV1 DC Bus Undervolt 27 PF Input Phase Loss3 UV2 Ctl PS Undervolt 28 LF Output Phase Loss4 UV3 MC Answerback 29 OH3 Motor Overheat 15 SC Short Circuit 30 OPR HMI Disconnect6 GF Ground Fault 31 ERR EEPROM R/W Err7 OC Over current 32 OH4 Motor Overheat 28 OV DC Bus Overvolt 33 CE Serial Com Err9 OH Heatsink Overtemp 34 BUS Option Com Err10 OH1 Heatsink Max Temp 35 E-15 SI-F/G Com Err11 OL1 Motor Overload 36 E-10 SI-F/G CPU Down12 OL2 Inverter Overload 37 CF Out of Control13 OL3 Overtorque 1 38 SVE Zero Servo Fault14 OL4 Overtorque 2 39 EF0 Opt External Fault15 RR DynBrk Transistor 40 FBL Feedback Loss16 RH DynBrk Resistor 41 LL3 Loss of Load17 EF3 External Fault 1 42 UL4 Undertorq Det 218 EF4 External Fault 2 43 UNBC - Unbalanced Current19 EF5 Fault Not Enabled 44 ULF Underload20 EF6 Fault Not Enabled 45 A1-HI Terminal A1 High21 EF7 Breaker 2 Fault 46 A1-LO Terminal A1 Low22 EF8 Filter Overheat 47 A2-HI Terminal A2 High23 FAN Cooling Fan Error 48 A2-LO Terminal A2 Low24 OS Overspeed Detect

    Data Link Status

    Bit 0 Denotes 1 Denotes0 Not Writing Data Writing Data

    1 2 Not Used Not Used3 No Range Error Upper or Lower Limit Errors4 No Integrity Error Data Integrity Error

    5 F Not Used Not Used

    Digital Inputs

    Bit 0 Denotes 1 Denotes0 Input 9 OFF Input 9 ON1 Input 9 OFF Input 10 ON2 Input 9 OFF Input 11 ON3 Input 9 OFF Input 12 ON4 Input 9 OFF Input 13 ON5 Input 9 OFF Input 14 ON6 Input 9 OFF Input 16 ON

    7 - F Not Used Not Used

    Drive Status 2

    Bit 0 Denotes 1 Denotes0 Drive Stopped Drive Running1 Drive not at Zero Speed Drive at Zero Speed

  • GE Oil & Gas

    GE imagination at work

    2 Drive Freq does not match internal speed Drive Freq matches internal speed3 Drive is not at Setpoint (accelerating) Drive is at Setpoint4 Freq Detect 1 Not Active Freq Detect 1 Active5 Freq Detect 2 Not Active Freq Detect 2 Active6 Drive Startup in Progress Drive Startup Complete7 No Low Voltage Detected Low Voltage Detected8 Drive Output Baseblock is Not Active Drive Output Baseblock is Active9 Freq Reference Mode is Communicating Freq Ref Mode is Not CommunicatingA Run Command Mode is Communicating Run Cmd Mode is Not CommunicatingB Overtorque is Not Detected Overtorque is DetectedC Frequency Reference OK Frequency Reference LostD Retrying is Not in Progress Retrying in ProgressE No Error ErrorF ModBus Comm Timeout is Not Detected ModBus Comm Timeout Detected

    Digital Output Status

    Bit 0 Denotes 1 Denotes0 Digital Output 1 OFF Digital Output 1 ON1 Digital Output 2 OFF Digital Output 2 ON

    2 F Not Used Not Used

    Communication Error

    Bit 0 Denotes 1 Denotes0 No Error CRC Error1 No Error Invalid Data Length2 Not Used Not Used3 No Error Parity Error4 No Error Overrun Error5 No Error Framing Error6 No Error Timeout

    7 F Not Used Not Used

    Keypad Functions:F1: Not used.F2: Not used.F3: Not used.F4: Not used.F5: Menu. Return to the Select screen.Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom of

    list).Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to top

    of list.Left Arrow: Not used.Right Arrow: Not used.START: Starts the drive if it is in the Ready state.STOP: Stops the drive.

  • 41

    VIIVECTOR4.15 Run Info

    Function:Displays current running information

    Field Descriptions:Screen Name: Run Info. This field is the name of the displayed screen.Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run

    Status screen description.

    Keypad Functions:F1: Not used.F2: Not used.F3: Not used.F4: Not used.F5: MenuUp Arrow: Not usedDown Arrow: Not usedLeft Arrow: Not usedRight Arrow: Not usedSTART: Starts the drive if it is in the Ready state.STOP: Stops the drive.

  • GE Oil & Gas

    GE imagination at work

    4.16 Set Date and Time

    Function:The Set Date and Time screen allows the user to adjust the date and time on the drives real-time clock.

    Field Descriptions:Screen Name: Set Date and Time Screen. This field is the name of the displayed screen.

    Date and Time fields to edit. (mm/dd/yyyy hh:mm 24 hour display)

    Note: Selectable date format is adjusted on the Setup Screen.

    Keypad Functions:F1: OK. Acce