VCWA202 Controls Providing Flexibility

Embed Size (px)

Citation preview

  • 8/13/2019 VCWA202 Controls Providing Flexibility

    1/7districtenergy.danfoss.com

    Controls providing exibility for the customerincrease comfort and save energyHalldor Kristjansson, Danfoss A/SPublished in HOT| COOL I/2008, DBDH (www.dbdh.dk)

    Technical paper

    MAKING MODERN LIVING POSSIBLE

  • 8/13/2019 VCWA202 Controls Providing Flexibility

    2/7

    2 Danfoss District Energy

    One of the main advantages of thedistrict heating system is its excellentexibility in utilising waste heat andCHP, as well as most kinds of primaryenergy sources. It is relatively easy to

    replace one fuel type with a new one,in case of fuel shortage, or for thepurpose of reduction of fuel costs andenvironmental straining.Another kind of exibility is involvedwith the consumer end of the DHsystem. The heat supplied from the DHsystem to the consumer should matchthe heat demand of the individualconsumer as much as possible. Anydifference between the consumer heatdemand and the heat supplied makesup an energy-saving potential. Theenergy savings can be obtained bymeans of local control equipment(temperature and balancing controls).In theory, it may be possible to designa constant ow heating system withperfect radiator dimensions in a blockof ats. In reality, it is not possible toavoid overheating without localautomatic controls, for the followingreasons: the ows can not be balanced;the dh temperatures are not precise;the insulation effect of a room differfrom preconditions; the wind one dayis from the south and the nex t dayfrom the north; the heat balance is

    inuenced by elec trical installationsand persons in the room; the residentsdiffer in their preferences about indoortemperature (Fig. 1), etc. For instance,elderly people and parents to babies

    may choose higher indoortemperatures, whereas lowertemperatures are preferred inbedrooms.

    In case of heating systems withoutlocal controls, it is necessary tooverheat one part of the building toensure that all residents in anotherpart of the building get sufficient heat.

    This results in huge energy lossesrelated to high indoor temperatures,the so called open window losses

    Author(s)

    Halldor Kristjansson ,Application Consultant, Danfoss A/SDanfoss District Heating, Nordborg, Denmark,+45 7488 2962 [email protected]

    Increasing energy prices, together with more demands for comfortlead to further development of DH consumerend technologies. This development involves better controlling and metering possibilitiesfor the individual consumer, so unnecessary heat supplied to theconsumer is not wasted. Maximum individualisation of the heat supplyis becoming more feasible than ever. In the case of blocks of ats, this

    brings about thermostatic radiator valves and a district heating unit forthe individual ats, the at station. And blocks of ats include a hugeenergy-saving potential, as they traditionally make up a big part of theDH consumers in most cities. In the former Eastern bloc countries, theyconstitute the majority of consumers.

    FIGURE 1: In theory, it may be possible to adjust the heat supply to the heatdemand without local controls but not in reality. The gure showsthe room heat supply, but the same principle applies to the hottap water supply.

    TECHNICAL PAPERControls providing flexibility

    for the customer increasecomfort and save energy

    Individual demand and xed supply in a block of ats

    Various demand preferences by residents (example)

    Actual supply without local controls (example)

    Indoor temperaturescalehot

    20C

    cold

  • 8/13/2019 VCWA202 Controls Providing Flexibility

    3/7

    3Danfoss District Energy

    (Fig. 2). This design was chosen inmany Eastern regions in times with lowfuel prices. In later periods ofrecession, the heat supply was limited,leaving some of the residents with verycold rooms. In this case, an evendispersion of the scarce heat wouldhave improved the average comfortlevel considerably.Comfort level is an important factorinvolved with energy consumption.Economic growth results in increaseddemands of comfort, which in case ofnon-controlled systems leads toa rapidly increasing heat consumption(Fig. 3). The saving potential of local automatic

    controls would be underestimated,if the rst sight savings were notadjusted according to thedevelopment (left side of Fig. 3). Thecorrect reference basis is what the heatconsumption of the obsolete systemwould have been in the future. Theseconditions, together with increasingenergy prices, can make investment inlocal automatic controls far morefeasible than at rst sight. The most common examples ofincreasing comfort demands are the

    available higher indoor temperatures,elongated heating seasons, more airventilation, and a stable suitable hottap water temperature. The literatureincludes extensive formulas for, forinstance, how indoor comfort dependson indoor air temperature, draught,radiation, humidity, air dust andchemical composition. The purpose of automatic controlequipment is to t the heat supply tothe individual consumer demands,with a minimum of losses. It isimportant to distinguish betweendifferent levels of individualisation ofthe control (Fig. 4). The traditionalEastern regional designs are found inthe left side of the gure, while thebest control quality is found in theright side of the gure. This design involves thermostaticvalves on all radiators and a substationwith a heat meter for every at, the socalled Flat Stations. This design allowseach family to optimise the indoorcomfort and hot tap water preparationwith the heat cost from time to time,providing maximum energy savings(Fig. 5).

    FIGURE 2: Individual needs for heat should be met with individual controls.Otherwise, either comfort, heat, or both, are lost. Note that several parameter alternatives exist on both axes.

    FIGURE 3: Within unregulated systems, economic growth results in a substantialincrease in heat consumption and an increased saving potentialthrough local automatic controls. The leftmost side of the gureindicates a tempting underestimation of the nal savings potential.

    The demand - Supply difference is an energy saving potential - but comfort is involved

    Parameters involvedwith heat consumption: - heat demand, - room temperature, - hot tap water temperature, - htw. circulation temperature, etc.

    Parameters involved withindividual situation: - room number, - house, - at, - individual (person), - hour of day, - lenght of heat season preferred - shower and tapping equipment - energy price - family economy, etc.

    1 2 3 4 5

    Heat supply,surplus

    Heat losses(cost)

    Heat supply,shortage

    Comfortlosses (cost)

    Heat supply,local controls

    Heat savings

    Example:Net heatdemand

    Increase in saving potential caused by growth

    Annualenergy

    consumption

    Saving potential of

    controls

    Final Simple

    year 0 later time [years]

    Heating system withoutany automatic controlsinside building

    Economicalgrowth increasesenergy demand

    Heating system withlocal automatic controls

    Good times withopen window regulation

    25C

    Hard times

    25C a

    b

    c

    Technical Paper Controls providing flexibility

  • 8/13/2019 VCWA202 Controls Providing Flexibility

    4/7

    4 Danfoss District Energy

    Evaluation of the energy-savingpotential of local automatic controlsonly becomes credible when alsoconsidering the comfort level. Energysaving data have to be cleaned fordifferences in comfort level. If thecomfort level were not considered, themost efficient energy savings would beobtained by simply turning off theheat! No controls needed! But as far asthe future brings increasing demandsfor comfort as well as energy savings,a maximum individualisation ofcontrols is the most relevant issue.Another important effect of the atstation design is that the authoritiesrelatively quickly can obtain optimalenergy savings by raising the energyprice during energy crises. It should bekept in mind that building distributionsystems are normally constructed forthe purpose of lasting several decades,while energy crises can occur withinunexpectedly. This is especiallyrelevant for many european countrieswhich rely on imported primaryenergy. The third important effect of the atstation system design is thatinstallations are maintained, as their

    condition inuence the consumers billdirectly. Experience shows that jointlyowned substations hidden in cellarsare poorly maintained, causingunnecessary losses and too highreturn temperature in the DH pipenetwork.As for the riser pipe system, thebasement is lled with hot tap waterand room heating pipes connected toseveral riser pipe pairs drilled upthrough the oor and ceilings of ats(Fig. 6). According to the literature, the

    HTW system heat losses are biggerthan the net heat for preparing theHTW.As for the at station system, thebasement only includes DH pipesconnected to one DH riser pipe pairin each staircase.All HTW and room heating pipes areplaced inside the ats, usually behindnice-looking skirting boards.(Hydraulic separation and/or a mainheat meter in the basement is still anoption, if required).As for the riser pipe system, the HTWand circulation pipes are kept hot all

    FIGURE 4: There are several levels of individualisation of control equipment.They heavily inuence both the energy consumption and thecomfort level.

    the time, causing considerable pipeheat losses, and, by the way, the risk ofhygienic problems may be increased(Fig. 7). Only 20 30 % of the HTW andcirculation pipe heat losses is utilisedfor room heating, the rest are nallosses.As for at station systems, the HTWpipes are mostly idle, and mostfamilies would not utilise a circulationpipe, or only shortly according toa timer function. Even if the totallength of pipes is slightly larger in caseof at station systems, the heat lossesare lower due to operation time of thedifferent parts of the system (Fig. 8).And as for investment, it is more

    convenient to lay horizontal pipesinside ats than to drill riser pipesthrough concrete oors. The piping makes it possible to makeindividual adjustments of the roomheating season. A resident on the topoor would typically prefer the longestheating season. In riser pipe systems,this would keep all risers hot for anextra 500 hours. In case of at stationsystems, this makes no difference. Anexample of energy savings related toindividualisaton and comfort demand.According to measurements of a few

    groups of houses in Denmark between1991 and 2005, individual billingresulted in savings of 15 30 %. Savings

    Individualisation of controls in blocks of atsFew alternatives in basic designs

    1 2 3 4 65

    1 2 3

    R

    N

    N

    N

    N

    N

    N

    R

    N

    N

    N

    N

    N

    R

    R

    R

    R

    R

    R

    R

    R

    RR

    R

    Basic control level 1 better 2 better 3 better 4

    better 5

    best 6.

    Basic control level Better Best

    R

    R

    R

    R

    R

    R

    R

    R

    R

    R

    Room heat part

    Hot tap water part

    SubstationBuilding block Flat station ( HTW HEX, heat meter, etc.)

    DH pipe (f. & return)HTW pipe (& circ)

    N : No automatic controlsR: Automatic controls, room heat R: Automatic controls, HTW

    N

    N

    N

    N

    N

    Technical Paper Controls providing flexibility

  • 8/13/2019 VCWA202 Controls Providing Flexibility

    5/7

    5Danfoss District Energy

    of 15 %, out of an energy cost ofEUR 1,000 per year, would generateEUR 1,500 for the consumer over thenext ten years, provided that energyprices are xed. But energy prices willprobably not stay constant for long - asit is with the demand for comfort inmany countries. The at station design principle is animportant opportunity for energysaving activities in the near future.

    FIGURE 6: Principal geometrics and operation modes in case of two basic designs of heat supply system.

    FIGURE 5: The increasing demand for both comfort and energy savings urge theindividualisation of automatic controls. The most reliable energysavings are achieved in a system where the individual consumer isallowed to optimise comfort and energy cost (system D).

    Energy consumptioninuenced by comfort level and control individualisation level

    Energy consumption(annual cost for consumer)

    Authority - or consumer

    demand for energy savings

    Consumer demand for better comfort Comfort level

    (average, revenue for customer)

    I n d i v i d

    u a l i s

    a t i o

    n -

    l e v e l o

    f c o n t r o

    l s

    15 C

    25 C

    A. Heating system without any automatic controlsinside building

    B. Automatic controlsin block basement

    C . + thermostatic valves on radiators

    D. + + at stationwith hot water preparation, energy meter, individual billing

    Open window -regulation

    Hard times

    A B C D

    13

    5

    (2)

    (4)

    Piping of two basic designs in a block of flats

    Riser pipe system Flat station system

    (If required)

    Station

    Heat meter

    Sink, shower, etc.

    Radiator HTW / circ CW

    DH or RH Hot all day (winter only)Hot few hours / day (all year)

    Hot all day (all year)

    Technical Paper Controls providing flexibility

  • 8/13/2019 VCWA202 Controls Providing Flexibility

    6/7

    6 Danfoss District Energy

    FIGURE 8: Comparison of pipe lengths and pipe heat losses for a riser pipe system and a at station system. Operation time indifferent parts of the system strongly inuence the nal heat losses. The example concerns a four-storey buildingwith ats of 120 m 2 each.

    FIGURE 7: The Flat Station System decreases the risk of hygiene problems in the hottap water, as it is prepared immediately before consumption,in a one-way ow. In riser systems, the water may ow in a loop fordays, through or past pipes with inexpedient temperatures.

    Hygiene risk from basic design of hot tap water system

    Riser pipe system Flat station system

    Hot tapwater 55 C

    Cold water 10 C

    Fresh hot tap water 50 C

    Cold water

    Riser pipes

    ??C

    HTW circulation

    Pipe lenght (m / at)

    Gross pipe losses(w.av. / at)

    Net pipe losses (nal)(kWh /y / at)

    HTWater living

    HTWater basem

    RmHeat living

    RmHeat basem

    DH living

    DH basemRiser pipe

    system

    Flat stationsystem

    Riser pipe

    system

    Flat stationsystem

    Riser pipe

    system

    Flat stationsystem

    Technical Paper Controls providing flexibility

  • 8/13/2019 VCWA202 Controls Providing Flexibility

    7/7

    VF.CW.A2.02 Produced by Danfoss A/S, DH-SM/PL 09/2011

    More information Find more information on Danfoss District Energy products and applicationson our homepage: www.districtenergy.danfoss.com

    Technical Paper Controls providing flexibility