VASCO technical specifications
VASCO 209 214 406 409 414 418 425 430
Input Voltage 1 x 230 VAC +/- 15% 3 x 380460 VAC +/- 15%
Frequency 48-62 Hz
Raccomended
Circuit breaker
Type C
20 A 25 A 10 A 16 A 20 25 32 40
Raccomended
Residual Current
Device
Pulse Sensitive RCD AC/DC sensitive RCD
Output Max Voltage 1 x V in 3 x Vin 1 x Vin 3 x Vin 3 x Vin
7/23/2019 VASCO Tech Spec Rev0
2/7
Frequency 0 -300 Hz
Current 9 A 7 A 9 A 11 A 6 A 9 A 14 A 18 A 25 A 30 A
Typical motor
power [P2]
1.1 kW 1.5 kW 1.1 kW 3 kW 2.2 kW 4 kW 5.5 kW 7.5 kW 11 kW 15 kW
Overload
Capacity101 % for 10 min , 110% for 1 min
Dimensions 180x180x225 mm 260x260x180 mm
Ambient
Conditions
Operating
Temperature
0 - 40C (104 F)
Max Altitude 1000 m
Humidity 95% max, non condening
Enclosure Material Die-casted Allumium, Stainless Steel AISI 304, PA, PE, PVC
Protection
DegreeIP55, NEMA 4 (Indoor only)
EMC
(EN55011)
with internal
filterClass A (industrial environment)
7/23/2019 VASCO Tech Spec Rev0
3/7
with external
filterClass B (domestic environment)
Certifications CE
Cooling Forced air
Protections Overvoltage, Undervoltage, Overload inverter, Motor Overcurrent, No load, Dry running, Overtemperature, Sensor alarm
Mounting Motor onboard Fixed on motor fan cover by 4 inox straps. VASCO is cooled by motor fan.
Wall mounted Fixed to the wall by special supports. Fans powered and controlled by VASCO.
Display 2 x 16 characters backlit display
Keypad start, stop, up, down, enter
Software Languages Italian, English, Spanish, Deutsch, French, Polish
Parameters
menInstaller and Advanced
Passwords
Programming
protections
Yes, 2 user changeable passwords
Multiple
pumps
DOL pumps
cascade relayOne inverter controlling a pump + 1 or 2 alternating starting DOL pumps
7/23/2019 VASCO Tech Spec Rev0
4/7
operation
Variable speed
pumps cascade
serial
Up to 8 inverters, each one controlling a pump, connected by RS485
Alternance Yes. Starting priority based on effective pump running hours.
Slave inverter
replacementYes. when a slave invert goes off-line another inverter can take its place.
Master
ReplacementYes. when master inverter goes off.line, first slave inverter can take its place.
Autorestart Yes, settable as ON or OFF
Max motor
frequencyYes.
Min motor
frequencyYes.
Ramps accelerationSettable ramp from 0 to minimum motor frequency.
Settable ramp minimum motor frequency to maximum motor frequency.
deleration
Settable ramp from maximum motor frequency to minimum motor frequency.
Settable ramp from minimum motor frequency to 0 Hz.
Autoadjusting Yes. Based on max inverter current.
7/23/2019 VASCO Tech Spec Rev0
5/7
max motor
frequency.
PI Control Yes. Direct / Inverse.
Setpoint
controlDigital by software or analog by 4-20 mA or 0-10 V trimmer
No flow
stopping
detection
By software, based on minimum frequency
Dry running
protection
Software Yes, based on P.F.
Float switch Yes.
Analog inputs 2 inputs 4-20 mA + 2 inputs 4-20 mA / 0-10V (settable by jumper)
Digital inputs 4 inputs N.0 or N.C (settable by software)
Relays Alarm Yes. N.O. or N.C. 12 VDC, 250 VAC, 5 A
Motor Run Yes. N.O. or N.C. 12 VDC, 250 VAC, 5 A
D.O.L. 1 pump Yes. N.O. or N.C. 12 VDC, 250 VAC, 5 A
7/23/2019 VASCO Tech Spec Rev0
6/7
D.O.L. 2 pump Yes. N.O. or N.C. 12 VDC, 250 VAC, 5 A
Connectable
sensors2 sensors 4-20 mA
Sensors
voltage
supply
15 VDC
Auxiliary
power supply15 VDC, max 100 mA
PWM Settable as 2.5, 4, 6, 8, 10 kHz
Sensors
switchingYes, by digital input
Control
ModesConstant Value
Constant value
with 2 valuesSwitchable by digital input
Fix speed
Fix speed with 2
valuesSwitchable by digital input
7/23/2019 VASCO Tech Spec Rev0
7/7
External
FrequencyBy 4-20 mA or 0-10 V trimmer
Sensors
differenceYes. digitally made
V/f control V/f curve settable from linear to quadratic
Stand-by
hours timerYes
Running
hours timerYes
Alarms
hystoryYes, last 5 alarms