Variable Air VolumeVAV Systems
Jeff Wotnosky
Trane Sales Engineer
Raleigh, North Carolina
This presentation can be used to re-introduce rooftop VAV systems
to technical customers, and to introduce Trane’s new “Rooftop VAV
Systems” application manual (lit number SYS-APM007-EN):
http://tranenetlax1/GrpApplicationsEngineering/Home/Appl_man/SYS-APM007-EN.pdf
Notes to the presenter:
Some slides in this presentation include animation. The script
under the animated slides includes a cue word (CLICK) to instruct
the presenter when to press the space bar, or click the mouse, in
order to activate the next step of the animation.
Special notes to the presenter are in red. Further reference
information is listed at the bottom of some slides.
The most up-to-date version of this preso can be found at:
http://tranenetlax1/GrpApplicationsEngineering/Home/PowerPointPresos.htm
File Name - Page * Version: 9/00
VAV systems
Why(/Not) design VAV systems
What buildings utilize VAV
Changeover Bypass ( Varitrac)
True VAV ( Varitrane)
Single Zone VAV
System control considerations
Leed and VAV
Questions?
So how does a Trane EarthWise rooftop VAV system help if the
building is going for LEED certification?
File Name - Page * Version: 9/00
What is Variable Air Volume(VAV)
?
Yesterday we spoke about VariTrac. Today we will be changing gears
and discussing VariTrane
File Name - Page * Version: 9/00
VAV System
VAV
terminal
units
supply
ductwork
return
ductwork
supply-air
diffusers
A rooftop VAV system consists of a packaged rooftop air conditioner
that can serve multiple, individually-controlled zones.
Conventional practice is to use a standard-efficiency rooftop unit
with air-cooled condensing and gas heat. The system is typically
designed to deliver 55°F, and often has an airside
economizer.
Each zone has a VAV terminal unit that is controlled to maintain
the desired temperature in that zone. Interior zones typically use
cooing-only VAV terminals, while VAV reheat boxes are typically
used for the perimeter zones and for some conference rooms.
A building automation system is often included to startup and
shutdown the system based on a time-of-day schedule, but the level
of optimization is usually minimal.
File Name - Page * Version: 9/00
Characterstics of VAV systems
Vary the air volume as load requires
Yesterday we spoke about VariTrac. Today we will be changing gears
and discussing VariTrane
File Name - Page * Version: 9/00
Why use VAV?
Provides multiple zones of comfort
Life cycle cost will be less than other HVAC Systems trying to
accomplish similar comfort levels
Load diversity
Smaller equipment ( lower AC unit first cost compared to Constant
Volume)
Less supply air ( less energy consumption)
Able to adapt to changes in building use
Go to black board and draw diagram showing pressure dependent, then
pressure independent.
File Name - Page * Version: 9/00
Why Not ??
Controls, equipment, commissioning
Increased maintenance cost
Terminal units might be located in occupied space
Go to black board and draw diagram showing pressure dependent, then
pressure independent.
File Name - Page * Version: 9/00
Common places to use VAV systems
Commercial/Medical Office buildings
Schools ( all levels)
Houses of worship
Conference Centers
Yesterday we spoke about VariTrac. Today we will be changing gears
and discussing VariTrane
File Name - Page * Version: 9/00
VAV System Types
Changeover Bypass (Varitrac)
“True VAV” (Varitrane)
Single Zone VAV
Yesterday we spoke about VariTrac. Today we will be changing gears
and discussing VariTrane
File Name - Page * Version: 9/00
VariTrac Changeover / Bypass System
File Name - Page * Version: 9/00
Cost Effective way to zone Standard packaged Rooftop units or Split
Systems
Often Driven by Light Commercial contractors:
Used to “Package Rooftop Equipment”
Desire somewhat simple installations and want to get on and off the
job quickly.
Want to get a little more flexibility than their typical
applications
What is VariTrac?
Pressure dependent - does not read flow - control is dependent on
pressure in the duct.
File Name - Page * Version: 9/00
Changeover/Bypass VAV System Layout
SA
Like a typical VAV system, a changeover/bypass system contains an
airflow modulation device for each individually controlled space.
This VariTrac damper modulates supply airflow in response to the
space load. However, instead of modulating the central supply fan,
this system supplies constant primary airflow. Any unneeded air is
diverted to the return airstream, allowing individual comfort
control of the spaces.
At part load conditions, when more of the primary air bypasses the
space, the mixture of previously conditioned primary air and
recirculated return air cuts energy use at the cooling and heating
equipment. This explains the use of the term “bypass” in the name
of this system. However, due to the fan providing a constant
airflow, no fan energy savings is realized at part load
conditions.
The term “changeover” refers to how this system handles the
building’s cooling and heating requirements. The central air
handler can provide either cooled or heated primary air to the
space terminal units and it makes this decision by periodically
“polling” the spaces. Since it can only provide heating or cooling
at a given time, this system is best applied to smaller buildings
with a minimal number of incidences where heating is required in
some spaces and cooling is simultaneously required in others.
File Name - Page * Version: 9/00
Where would you use VariTrac?
Ideal candidates for VariTrac Systems are:
one-story office buildings, clinics, movie theaters, strip malls,
light manufacturing centers.
Examples are offices within a church, school, or manufacturing
facility seeking individual (zoned) temperature control.
Popular in restaurants. Gives VAV or zone control at an affordable
price.
File Name - Page * Version: 9/00
Light Commerical RTU
File Name - Page * Version: 9/00
Light Commercial Split System
File Name - Page * Version: 9/00
VariTrac Changeover Bypass System
Odyssey Split System (ReliaTel)
VaiTrac or VariTrane
Units with reheat
Cooling only standard
Remote reheat control
Round or Rectangular
Pressure Dependent System (damper position control- no direct CFM
measurement)
Up to 1.75” system pressure
VariTrac Dampers
The current system uses three direct wired (non-communicating)
components, the bypass damper, the supply air temperature sensor,
and the duct air pressure sensor.
The new system uses a communicating bypass assembly that combines
these three functions into one device that resides on theCOM 4 bus
with the zone dampers and Voyager RTU. The damper information, duct
pressure, and supply air temperature are communicated back to the
new CCP via the bus.
The new assembly eliminates the option for velocity and is
available only configured as a static pressure sensor.
In retrofit jobs (where an existing CCP is replaced by a new CCP),
the existing bypass damper, duct pressure sensor, and supply air
temperature sensor must also be replaced by a communicating bypass
damper assembly.
File Name - Page * Version: 9/00
Central Control Panel
Simple PC interface with Windows™ based software
Interfaces with Main AHU via 2H/2C Control
Scheduling
How is changeover achieved?
CCP polls UCM’s
On a minimum calls for changeover the CCP will disable heat or cool
and enable heat or cool
CCP then communicates to UCM’s new control mode and UCM’s control
to different setpoints
File Name - Page * Version: 9/00
True VAV System – (Varitrane)
VAV
terminal
units
supply
ductwork
return
ductwork
supply-air
diffusers
A rooftop VAV system consists of a packaged rooftop air conditioner
that can serve multiple, individually-controlled zones.
Conventional practice is to use a standard-efficiency rooftop unit
with air-cooled condensing and gas heat. The system is typically
designed to deliver 55°F, and often has an airside
economizer.
Each zone has a VAV terminal unit that is controlled to maintain
the desired temperature in that zone. Interior zones typically use
cooing-only VAV terminals, while VAV reheat boxes are typically
used for the perimeter zones and for some conference rooms.
A building automation system is often included to startup and
shutdown the system based on a time-of-day schedule, but the level
of optimization is usually minimal.
File Name - Page * Version: 9/00
True Variable-Air-Volume System
supply
fan
cooling
coil
thermostat
VAV
box
PA
SA
A variable-air-volume (VAV) system delivers the primary air at a
constant temperature and varies the airflow to maintain the
required space temperature at all load conditions.
All VAV units have a controller attached to them and are designed
to control temperature in the space… applications beyond “zone
temperature control”, should be discussed with product
support.
File Name - Page * Version: 9/00
VAV Terminal Units
2. Go into each type individually and explain their features.
File Name - Page * Version: 9/00
VCCF
No auxiliary heat
Air valve modulates open or closed to deliver primary air. Always
trying to satisfy zone temperature.
This VAV terminal unit is typically used for those zones that
require year-round cooling, like the interior zones of a building.
It is the most common and basic type of single-duct VAV terminal
unit.
Go over Model #
VCCF
primary
air
supply
air
VAV Terminal Units
A VAV terminal unit is a sheet-metal assembly installed upstream of
its respective space diffusers. The unit consists of an
air-modulation device, control hardware and, depending on the
system application, possibly a heating coil, a filter, and a small
terminal mixing fan.
Modulating the airflow to each individual space is accomplished
using a temperature-controlled mechanical device that varies the
airflow resistance in the supply duct to that space. The rotating
blade damper changes airflow resistance by rotating the damper into
the air stream, restricting the size of the air passage to the
space. It is very cost-effective and flexible. Typically, either a
pneumatic or electric controller can be used to adjust the
damper.
An understanding of the common VAV terminal unit types is important
to understanding VAV systems.
File Name - Page * Version: 9/00
VCWF
Hot Water Coils
TOPSS always selects the smallest coil that meets capacity.
Model #
VCWF
primary
air
supply
air
VCEF
Interlocking door disconnect
Heater line fuse
Element removal through control enclosure
Electric heat units now (beginning in 2Q07) have the ability to
remove the elements without disturbing downstream ductwork. This is
handy if the heater elements fail for some reason…
File Name - Page * Version: 9/00
Terminal Reheat System
EA
PA
OA
RA
supply
fan
cooling
coil
reheat
coil
thermostat
SA
The terminal reheat system uses a central air handler and cooling
coil to deliver cool primary air to all the spaces. Each space has
its own heating coil to temper the air to satisfy its load.
File Name - Page * Version: 9/00
parallel,
Fan-Powered VAV
Similarly, fan-powered terminal units can be used in perimeter
spaces that require seasonal cooling and heating.
In the heating mode, the parallel, fan-powered unit turns on its
small fan as the first stage of heating. Doing so allows it to
temper the supply air with the heat of the building and lights that
is carried by the return air rather than using “new” energy. When
activated, the small fan also increases airflow to the space,
improving the mixing of supply and space air to prevent
stagnation.
Series, fan-powered terminal units may also be used in this manner.
They offer the added advantage of supplying constant airflow to the
space in both cooling and heating modes.
File Name - Page * Version: 9/00
Parallel, Fan-Powered
primary air
plenum
air
A parallel, fan-powered terminal unit consists of a primary airflow
modulation device and a small, integral, constant-volume fan
packaged to provide parallel airflow paths.
File Name - Page * Version: 9/00
Parallel Fan-Powered VAV
cool primary air
from rooftop unit
warm air recirculated
from ceiling plenum
(second stage of heat)
Heat generated by light fixtures warms the air in the ceiling
plenum. Fan-powered VAV boxes use this warm air from the plenum as
a form of energy recovery.
In a parallel, fan-powered VAV box, primary airflow is reduced as
the cooling load decreases. When the box reaches its minimum
airflow setting, CLICK the small fan activates to draw warm air
from the ceiling plenum and mix it with cool primary air from the
rooftop unit. CLICK If more heat is required, the heating coil can
be activated.
Parallel, fan-powered VAV boxes can save energy because they use
warm air from the ceiling as the first stage of heating. This
delays the need to use new energy by activating the heating
coil.
And, since the terminal fan only operates when the zone needs heat,
these boxes use much less fan energy than series fan-powered boxes,
in which the terminal fan runs whenever the zone is occupied.
[Further information: SYS-APM007-EN, pp. 28-31]
File Name - Page * Version: 9/00
supply
air
primary air
A series, fan-powered terminal unit consists of an airflow
modulation device and a small, constant-volume fan, packaged so
that their airflow paths are in series. The terminal unit fan
operates continuously whenever the space is occupied. The fan draws
air from either the primary air stream or the plenum, based on the
thermostat in the space. This results in a constant volume of
supply air delivered to the space at all times.
File Name - Page * Version: 9/00
Parallel vs. Series
Intermittent fan
Fan only runs in the heat mode (Variable Volume to the space)
Fan is the first stage of heat
Fan CFM < Max Cooling
Most energy efficient design
Continuous fan
Fan runs continuously in the occupied mode (constant volume to the
space)
Fan CFM = Max Cooling
Smaller main supply fan?
fan-powered VAV
series FPVAV with ECM
This chart shows the impact of using parallel versus series
fan-powered units in the same example office building. The “base
case” uses single-duct, VAV reheat terminal units. Parallel
fan-powered VAV reduced the overall HVAC energy use in each of the
three locations, with the biggest impact in the heating-dominated
climate of Minneapolis.
CLICK Series fan-powered VAV terminals—even when they are equipped
with ECMs (electrically-commutated motors)—actually increased HVAC
energy use in Atlanta and Los Angeles. For the building in
Minneapolis, series fan-powered VAV reduced energy use compared to
VAV reheat, but still used more energy than parallel fan-powered
VAV.
File Name - Page * Version: 9/00
Fan Powered Units: Cooling Only
Plenum Air provides “free” reheat from lights, etc.
Parallel units (only when fan energized)
Series (increases as air valve closes)
Cooling only (no reheat) - fan is only heat source.
File Name - Page * Version: 9/00
Fan Powered Units: Cooling with Hot Water Reheat
Model VPWF/LPWF (Parallel)
Model VSWF, LSWF (Series)
Coil Offerings
1 Row
2 Row
2. 1 & 2 row coils
Different mounting options
Water coils can have a pressure drop which impacts system
efficiency and fan airflow. Parallel units are MOST efficient when
the water coil is mounted on the plenum inlet. Why would that
be?
File Name - Page * Version: 9/00
Fan Powered Units: Cooling with Electric Reheat
Model VPEF / LPEF(Parallel)
Discharge mounted
UL listed
Pressure drop through electric heaters is negligible. That is why
the heater is located ONLY on the unit discharge.
File Name - Page * Version: 9/00
Fan Powered Units: Electric Heater Options
8 different voltages
2 stages of heat (plus the fan as stage 1)
Interlocking door disconnect
Heater line fuse
Air flow switch
File Name - Page * Version: 9/00
Differences between VariTrac and VariTrane
VariTrac
Simpler System Control
Up to 24 zones
Very Flexible System Control (more complex sequences)
Larger Variable Volume AHU/RTU equipment (up to 130 Tons)
Up to 120+ zones
Pressure Independent
Go to black board and draw diagram showing pressure dependent, then
pressure independent.
File Name - Page * Version: 9/00
VAV System Types
Single Zone VAV
Yesterday we spoke about VariTrac. Today we will be changing gears
and discussing VariTrane
File Name - Page * Version: 9/00
Single Zone VAV
AHU is your VAV Box !!
Yesterday we spoke about VariTrac. Today we will be changing gears
and discussing VariTrane
File Name - Page * Version: 9/00
Application for Single Zone VAV
Large areas ( conference rooms, assembly halls…)
Control air flow off room sensor
Yesterday we spoke about VariTrac. Today we will be changing gears
and discussing VariTrane
File Name - Page * Version: 9/00
Controls
Analog - commonly ordered in error - needs DDC
In the last 20 years pneumatics have gone from 90 to 80% to less
than 20% with the introduction of DDC.
File Name - Page * Version: 9/00
Unit Controls
No- controls- field installation of others controllers- about 5%
(ENON)
Factory Installation of others Controls- about 20% (FM0*)
DDC Controls - around 70% (DD**)
Trane DDC (Communicates to a Trane-Trane-Trane System)
Trane LonTalk DDC (designed to talk a language which is not
proprietary to Trane)
Analog - commonly ordered in error - needs DDC
In the last 20 years pneumatics have gone from 90 to 80% to less
than 20% with the introduction of DDC.
File Name - Page * Version: 9/00
VAV systems
Optimal start and optimal stop
Fan-pressure optimization
Supply-air-temperature reset
File Name - Page * Version: 9/00
occupied hours
Optimal Start
6 AM
mid
mid
system
on
system
off
occupied
heating
setpoint
unoccupied
heating
setpoint
optimal
start
In many applications, a simple time clock or time-of-day schedule
is used to start and stop the HVAC system.
CLICK During the unoccupied hours, the system is shut off and the
temperature is allowed to drift away from the occupied setpoint.
The time at which the system starts in the morning is typically set
to ensure that the indoor temperature reaches occupied setpoint on
either the coldest or warmest morning of the year. The result is
that, for most days, the system starts much earlier than it needs
to. This increases the number of system operating hours and
increases energy use.
An alternative approach is a strategy called “optimal start.” A
building automation system is used to determine the length of time
required to bring each zone from its current temperature to the
occupied setpoint temperature.
CLICK Then, the system waits as long as possible before starting,
so that the temperature in each zone reaches occupied setpoint just
in time for occupancy.
This reduces the number of hours that the system needs to operate,
and saves energy by avoiding the need to maintain the indoor
temperature at occupied setpoint even though the building is still
unoccupied.
[Further information: SYS-APM007-EN (pp. 129-130) and BAS-APG003-EN
(pp. 128-131)]
File Name - Page * Version: 9/00
occupied hours
Optimal Stop
6 AM
occupied
setpoint
A related strategy is “optimal stop”. As I mentioned, at the end of
the occupied period the system is shut off and the temperature is
allowed to drift away from the occupied setpoint. The building
occupants, however, may not mind if the zone temperature drifts
just a few degrees before they leave for the day.
Optimal stop uses the same building automation system to determine
how early the heating and cooling can be shut off for each zone,
CLICK so that the indoor temperature drifts only a few degrees from
occupied setpoint. The supply fan continues to operate, and outdoor
air is still provided to the building for ventilation. Only cooling
and heating are turned off.
The optimal stop strategy also reduces the number of hours that the
system needs to operate, saving energy by allowing indoor
temperatures to drift early.
[Further information: SYS-APM007-EN (pp. 130-131) and BAS-APG003-EN
(pp. 131-133)]
File Name - Page * Version: 9/00
communicating BAS
VAV boxes
P
In a VAV system, as the cooling loads in the zones change, the VAV
boxes modulate to vary airflow supplied to those zones. This causes
the pressure inside the supply ductwork to change. The rooftop unit
modulates the supply fan to maintain a certain static pressure in
the ductwork. In most systems, this pressure sensor is located
about two-thirds of the distance down the main supply duct. But
when no zone is at design airflow, the system is generating more
static pressure than required because all the dampers are partially
closed.
When communicating controllers are used on the VAV boxes, its
possible to optimize this control function to provide just enough
pressure in the duct, and minimize fan energy consumption.
Each VAV box controller knows the current position of its damper.
The BAS continually polls these individual box controllers, looking
for the one with the most-open damper. If all dampers are somewhat
closed, the fan’s static-pressure setpoint can be reset
lower.
The result is that the supply fan generates only enough static
pressure to push the required quantity of air through this
“critical” VAV box. Same airflow, just less pressure.
[Further information: SYS-APM007-EN (pp. 131-133) and BAS-APG003-EN
(pp. 153-156)]
File Name - Page * Version: 9/00
surge
This concept, which Trane calls fan-pressure optimization, has
several benefits.
First is that it reduces supply fan energy use. CLICK At part-load
conditions, the supply fan operates at a lower static pressure and,
therefore, uses less energy.
Second, because the supply fan doesn’t need to generate as much
pressure, it typically generates less noise. And, with lower
pressures in the ductwork, the dampers in the VAV boxes will be
more open, resulting in less noise generated at the boxes.
A third benefit is the reduced risk of fan surge. By allowing the
fan to operate at lower pressures when delivering reduced airflows,
the fan operating point is kept further away from the surge
region.
The fourth benefit is the ability to have the pressure sensor
factory-installed and tested at the outlet of the fan inside the
rooftop unit.
File Name - Page * Version: 9/00
ASHRAE Standard 62.1-2004
in response to:
(ventilation reset)
The 2004 version of ASHRAE Standard 62 now explicitly permits
dynamic reset of outdoor airflow as operating conditions
change.
The standard lists examples, including these two:
You can reset intake airflow in response to variations in zone
population, which is often referred to as “demand-controlled
ventilation.” DCV is commonly implemented using carbon dioxide
(CO2) sensors, occupancy sensors, or time-of-day schedules.
In addition, you can reset intake airflow based on variations in
ventilation efficiency, which Trane refers to as “ventilation
reset.”
The goal of each of these strategies is to bring in only the
minimum amount of outdoor air needed for the current operating
conditions. In most applications, reducing the outdoor airflow will
save energy.
File Name - Page * Version: 9/00
ventilation optimization
elevators
vestibule
corridor
mech
room
BAS
CO2
CO2
OCC
OCC
AHU
TOD
TOD
For a VAV system, the best approach often combines several
demand-controlled ventilation strategies at the zone level, using
each where it best fits; and then couple these with ventilation
reset at the system level.
CLICK With this strategy, CO2 sensors are installed only in those
zones that are densely occupied and experience widely varying
population. In this example, sensors are installed only in the
conference room and the lounge. These are good candidates for CO2
sensors, and provide the biggest bang for the buck.
CLICK However, zones that are less densely-occupied or have a
population that varies only a little are probably better suited for
occupancy sensors. In this example, each of the private offices has
an occupancy sensor to indicate when it is unoccupied, which then
lowers the ventilation requirement for that zone. Occupancy sensors
are relatively inexpensive, don’t need to be calibrated, and are
already used in many zones to control the lights.
CLICK Finally, zones that are sparsely populated or have
predictable occupancy patterns may be best controlled using a
time-of-day schedule in the building automation system. This
schedule can either indicate when the zone would be normally
occupied, or may even be used to vary the zone’s ventilation
requirement based on anticipated population.
[Further information: SYS-APM007-EN (pp. 136-139) and BAS-APG003-EN
(pp. 157-179)]
File Name - Page * Version: 9/00
ventilation optimization
DDC/VAV terminals
rooftop unit
with controls
communicating BAS
CO2
TOD
TOD
These various zone-level DCV strategies are used to reset the
ventilation requirement for their respective zones for any given
hour. In addition, the flow sensor on each VAV terminal
continuously monitors primary airflow being delivered to the
zone.
CLICK This zone-level control is then tied together using
ventilation reset at the system level. The BAS periodically gathers
this data from all the VAV terminals and solves the ventilation
reset equations (from ASHRAE 62) to determine how much outdoor air
must be brought in at the rooftop unit to satisfy all of the zones
served.
CLICK Finally, the BAS sends this calculated outdoor airflow
setpoint to the rooftop unit, which modulates a flow-measuring
outdoor-air damper to maintain this new setpoint.
File Name - Page * Version: 9/00
rooftop VAV system
HVAC Energy Savings
% of base
optimized controls
conventional system
The results show that there is potential to save energy in rooftop
VAV systems through the use of optimized controls.
The blue column to the left for each city is the conventional
system, and the green column to the right is the optimized system.
The Y axis is overall HVAC energy consumption, shown as a
percentage of the base case.
The optimized controls reduced HVAC energy use by 24% for the
building in Atlanta, by 19% in Los Angeles, and by 27% in
Minneapolis.
File Name - Page * Version: 9/00
Trane Control Systems Architecture
VAV systems
Sustaining Performance
Centralized alarming, diagnostics, trending
Features like centralized alarms or diagnostic messages alert the
building operator or outside service contractor, and even help them
pinpoint the cause of a problem. This allows them to respond to
problems faster.
With remote communications and remote access, these messages can be
transmitted, even allowing problems to be fixed before people
return to work on Monday morning.
File Name - Page * Version: 9/00
VAV systems
Sustaining Performance
Building operations, energy management, commissioning,
validation
Various facility management services can help you operate your
facility more efficiently. In addition to the standard energy
management features available in Tracer Summit, add-on packages and
software products are also available.
Computerized maintenance management systems schedule preventive
maintenance, issue and track work orders, and manage
maintenance-related purchasing and inventory. By integrating these
tools with the building automation system, work orders can be
automatically “triggered.”
Tools like Tracer Summit Energy Services can allow you, or a
service provider, to use data to spot anomalies or unusual
conditions, and take corrective action to reduce energy costs
before they become too big of a drain on the business.
[Further information: BAS-SLM015-EN]
VAV systems
Sustaining Performance
Periodic commissioning and calibration exercises the different
components of the system, testing them to make sure that they
continue to work as intended.
For example, the system can direct the VAV boxes to step through
various tests to make sure the flow sensor is calibrated, and that
the damper, heating valve, and terminal fan all operating
properly.
This avoids wasting energy and assures that the system is able to
provide occupant comfort.
[Further information: BAS-APG003-EN (pp. 145-152)]
File Name - Page * Version: 9/00
VAV systems
Sustaining Performance
for flexibility
A wireless zone sensor can be easily placed in the best location to
provide comfort. This might be on a cubicle wall, a concrete or
brick wall, or some other difficult-to-wire location.
In addition, a wireless sensor is easy and inexpensive to move when
the layout or use of the zone changes.
Or if the planned location of the sensor turns out to be a bad
spot, it can be easily moved until the right location is
found.
[Further information: BAS-SLM023-EN]
EA credit 1: Optimize Energy Performance
TRACE 700
Ventilation optimization
CO2 sensors only in densely-occupied zones
Traq dampers in IntelliPak rooftop unit
Certainly, one of the key goals of an EarthWise system is to save
energy, so it helps achieve points under EA credit 1. Because this
credit typically requires whole-building energy simulation, tools
like TRACE 700 can help.
In addition, Trane’s new IntelliPak II rooftop unit is the most
efficient in the marketplace, with a full-load EER of 9.7.
CLICK Tracer Summit’s ventilation optimization strategy can help
achieve EQ credit 1, by installing CO2 sensors only in the
densely-occupied zones, and then using Traq outdoor airflow
measurement dampers in the Trane IntelliPak rooftop unit.
[EA credit 4: Enhanced Refrigerant Management – Some sizes of
IntelliPak I units can achieve this point with R-407c, but some
sizes cannot. Some sizes of IntelliPak II units (with R-410a), can
achieve this point, but many cannot.]
File Name - Page * Version: 9/00
Summary
Why(/Not) design VAV systems
What buildings utilize VAV
Changeover Bypass ( Varitrac)
True VAV ( Varitrane)
Single Zone VAV
System control considerations
Leed and VAV
So how does a Trane EarthWise rooftop VAV system help if the
building is going for LEED certification?
File Name - Page * Version: 9/00
VAV systems
QUESTIONS ??
So how does a Trane EarthWise rooftop VAV system help if the
building is going for LEED certification?
File Name - Page * Version: 9/00
VAV systems
THANK YOU