2
Discharge depth 100% Discharge depth 50% Number of Cycles (time) Capacity (%) Discharge depth 30% 1 Discharge current: 0.2CA ( Final Voltage 1.7 V/cell) 2 Charge current: 0.1CA 3 Ambient temperature: (68° to 77°F) 0 0 20 40 60 80 100 120 200 400 600 800 1,000 1,200 CYCLE LIFE vs DISCHARGE DEPTH 1 3C 2C 1C 0.6C 2 3 5 10 20 30 60 2 3 5 10 20 30 0.25C 0.17C 0.09C 0.05C Discharge Time min h Terminal Voltage (V) 13 12 11 10 9.0 8.0 0 DISCHARGE CHARACTERISTICS 0 20 40 60 80 100 11.5 12.0 12.5 13.0 13.5 6.8 6.6 6.4 6.2 6.0 5.8 Residual Capacity (%) Ambient Temperature 77°F (25°) Open Circuit Voltage (V) CAPACITY CHART 0 2 4 6 8 10 12 14 16 18 20 100 80 60 40 0 40°C (104°F) 30°C (86°F) 20°C (68°F) 5°C (41°F) Storage Period (months) Percentage of Nominal Capacity “C” No supplementary charge required (Car- ry out supplementary charge before use if 100% capacity is required.) Supplementary charge required before use. This supplementary charge will help to re- cover the capacity and should be made as early as possible. Supplementary charge may often fail to re- cover the capacity. The battery should never be left standing until this state is reached. Supplementary charge and storage guidelines STORAGE GRAPH DISCHARGING CURRENT AND FINAL DISCHARGE VOLTAGE 0.2C > A 1.75 0.2C (A) < 0.5C 1.70 0.5C (A) < 1.0C 1.55 A 1.0C 1.30 Charge Voltage (V/Cell) Applications Optimum Temp. Compensation Required Set Allowable Max. Charge Max. Ripple Temp. Range Outside Optimum Temp. Range Point Range Current (A) Time Current Cycle 0°C–40°C Under 5°C +5mV/°C/Cell 2.45 2.40–2.50 0.3C Est. 12–24 Hrs. 0.1 x C20 32°F–104°F Over 35°C –5mV/°C/Cell Standby (Float) 0°C–40°C Under 5°C +3.3mV/°C/Cell 2.275 2.25–2.30 0.3C Continuous 0.05 x C20 32°F–104°F Over 35°C –3.3mV/°C/Cell Valve Regulated Sealed Lead Acid Battery Characteristics Platinum Power UPS Cabinets, Telco & Open Racks Discharging Current (A) Final Discharge Voltage (V/cell) OPTIMUM TEMPERATURE RANGES F C Discharge –15° ~ 122° –20° ~ 50° Charge –15° ~ 104° –20° ~ 40° Storage –15° ~ 104° –20° ~ 40° Revised 11/2006 CABINET FEATURES Constant Power Up to 161.5KW (5 mins.,1.75 FV) 2 weeks lead time Fast Acting fuses & UL listed, High Flex THHW cables Seismic Zone 4 certified 10 GA cold rolled steel (cabinet body & rails) 16 GA galvanized steel (battery trays) Powder coat, oven baked for chip and corrosion resistance Adjustable rails for multiple battery configurations and future upgrades Pre-wired cabinets to fit up to 40 large (group 31T) batteries Optional circuit breaker and charger options Full turnkey solutions — sized, configured, drop-shipped Charging Always charge batteries in an open, well ventilated area. Do not charge batteries near equipment that may produce sparks. Do not charge near an open flame. Do not use smoking materials in battery charging area. Electrolysis may cause hydrogen and oxygen to be released toward the end of a charging cycle or in the event the battery is overcharged. The combination of hydrogen and oxygen can result in an explosion if a spark or flame is introduced. Handling Never place or dispose of the battery near or in a fire. Never short the terminals. Never operate the battery in a air-tight container. Never unassemble the battery. Never clean the ABS battery cases with organic solvents. CSB batteries contain diluted sulfuric acid and in the event of contact to the skin or clothing, the exposed areas should be flushed generously with water and the victim should seek medical attention. 1-800 number manned 24 hours for any chemical emergency by Chemtrec (800-424-9300). California Proposition 65 labeling available. Charging and Handling Precautions TELCO RACK FEATURES: Standard 19" and 23" racks Seismic Zone 4 certified options Tier height flexibility Chargers, fuses and circuit breakers protection options Pre-wired racks to fit up to 16 Full turnkey solutions — sized, configured, drop-shipped OPEN RACK FEATURES: Open Racks (RxTx series) 2 weeks lead time Seismic Zone 4 certified options Tier height flexibility Acid-resistant paint for improved protection and endurance Chargers, fuses and circuit breakers protection options Pre-wired racks to fit up to 40 large (group 31T) batteries Full turnkey solutions – sized, configured, drop-shipped TELCO RACK UPS CABINETS Front Access 12V VRLA Batteries Long Life 2V Modular Systems Extreme Environment & Long Life 12V VRLA Batteries CSB Model Standard Nominal Nominal Capacity Length Width Height Ht. Over Term. Weight Number Terminal Voltage 20 HR Rate in mm in mm in mm in mm lb. kg. XTR SERIES (Extreme Environment + Long Life) XTR1272 F2 12 7.7 5.94 151.0 2.56 65.0 3.70 94.0 3.94 100.0 6.2 2.8 CSB Model Standard Nominal Nominal Capacity Length Width Height Ht. Over Term. Weight Number Terminal Voltage 10 HR Rate in mm in mm in mm in mm lb. kg. MSJ SERIES MSJ150 Flag or Recessed 2 150 4.2 106.0 6.69 170.0 12.99 330.0 14.37 365.0 28.6 13.0 MSJ200 Flag or Recessed 2 200 4.2 106.0 6.69 170.0 12.99 330.0 14.37 365.0 33.0 15.0 MSJ260 Flag or Recessed 2 260 4.2 106.0 6.69 170.0 12.99 330.0 14.27 365.0 38.5 17.5 MSJ300 Flag or Recessed 2 300 5.9 150.0 6.69 170.0 12.99 330.0 14.37 365.0 46.2 21.0 MSJ350 Flag or Recessed 2 350 5.9 150.0 6.69 170.0 12.99 330.0 14.37 365.0 49.0 22.3 MSJ400 Flag or Recessed 2 400 6.6 171.0 9.48 241.0 12.99 330.0 14.37 365.0 61.6 28.0 MSJ500 Flag or Recessed 2 500 6.6 171.0 9.48 241.0 12.99 330.0 14.37 365.0 77.0 35.0 MSJ650 Flag or Recessed 2 650 6.6 171.0 12.08 307.0 12.99 330.0 14.37 365.0 102.1 46.4 MSJ800 Flag or Recessed 2 800 6.6 171.0 12.08 307.0 12.99 330.0 14.37 365.0 118.4 53.7 MSJ1000 Flag or Recessed 2 1000 6.6 171.0 18.54 471.0 12.99 330.0 14.37 365.0 154.0 70.0 MU SERIES MU1000 Recessed 2 1000 11.9 303.0 6.8 172.0 19.1 486.0 19.6 497.0 145.2 66.0 MU1500 Recessed 2 1500 17.2 437.0 6.8 172.0 19.1 486.0 19.6 497.0 211.2 96.0 CSB Model Standard Nominal Nominal Capacity Length Width Height Ht. Over Term. Weight Number Terminal Voltage 8 HR Rate in mm in mm in mm in mm lb. kg. TPL SERIES (Front Access + Long Life)* TPL121000 M6 12 100 20.10 511.0 4.33 110.0 10.00 254.0 10.12 257.1 79.2 36.0 TPL121250 M6 12 125 21.90 557.0 4.90 124.8 12.60 320.0 12.72 320.0 117.0 53.0 TPL121500 M6 12 150 21.90 557.0 4.90 124.8 12.60 320.0 12.72 320.0 123.0 56.0 TPL121900* M6 12 190 21.90 557.0 4.90 124.8 12.60 320.0 12.72 320.0 140.8 64.0 MU 1000 MSJ SERIES MSJ 500 MSJ 500 MSJ 300 MSJ 300 *to be introduced in 2007 CSB Battery Technologies, Inc. 2901 White Settlement Road, Fort Worth, Texas 76107 USA Phone: 817/244-7777 • Toll Free: 800/3CSB/USA • Fax: 817/244-4445 www.csb-battery.com • E-mail: [email protected], [email protected]

Valve Regulated Sealed Platinum Power UPS Cabinets, …informaticstt.com/docs/GENERAL CATALOG (FINAL VERSION).pdf · ( Final Voltage 1.7 V/cell) 2 Charge current: 0.1CA 3 Ambient

  • Upload
    lytu

  • View
    218

  • Download
    4

Embed Size (px)

Citation preview

Page 1: Valve Regulated Sealed Platinum Power UPS Cabinets, …informaticstt.com/docs/GENERAL CATALOG (FINAL VERSION).pdf · ( Final Voltage 1.7 V/cell) 2 Charge current: 0.1CA 3 Ambient

Discharge depth 100% Discharge depth 50%

Number of Cycles (time)

Capaci

ty (

%)

Discharge depth 30%

1 Discharge current: 0.2CA ( Final Voltage 1.7 V/cell)2 Charge current: 0.1CA3 Ambient temperature: (68° to 77°F)

00

20

40

60

80

100

120

200 400 600 800 1,000 1,200

CYCLE LIFE vs DISCHARGE DEPTH

1

3C 2C 1C

0.6C

2 3 5 10 20 30 60 2 3 5 10 20 30

0.25C0.17C 0.09C 0.05C

Discharge Timemin h

Ter

min

al V

olt

age

(V)

13

12

11

10

9.0

8.0

0

DISCHARGE CHARACTERISTICS

0 20 40 60 80 100

11.5

12.0

12.5

13.0

13.56.8

6.6

6.4

6.2

6.0

5.8

Residual Capacity (%)

Ambient Temperature 77°F (25°)

Op

en C

ircu

it V

olt

age

(V)

CAPACITY CHART

0 2 4 6 8 10 12 14 16 18 20

100

80

60

40

0

40°C(104°F)

30°C(86°F)

20°C(68°F)

5°C(41°F)

Storage Period (months)

Per

cen

tag

e o

f N

om

inal

Cap

acit

y “C

” No supplementary charge required (Car-ry out supplementarycharge before use if100% capacity isrequired.)

Supplementary chargerequired before use.This supplementarycharge will help to re-cover the capacity andshould be made as early as possible.

Supplementary chargemay often fail to re-cover the capacity.The battery shouldnever be left standinguntil this state isreached.

Supplementary chargeand storage guidelines

STORAGE GRAPH DISCHARGING CURRENT AND FINALDISCHARGE VOLTAGE

0.2C > A 1.75

0.2C ≤ (A) < 0.5C 1.70

0.5C ≤ (A) < 1.0C 1.55

A ≥ 1.0C 1.30

Charge Voltage (V/Cell)

Applications Optimum Temp. Compensation Required Set Allowable Max. Charge Max. RippleTemp. Range Outside Optimum Temp. Range Point Range Current (A) Time Current

Cycle0°C–40°C Under 5°C +5mV/°C/Cell

2.45 2.40–2.50 0.3C Est. 12–24 Hrs. 0.1 x C2032°F–104°F Over 35°C –5mV/°C/Cell

Standby (Float)0°C–40°C Under 5°C +3.3mV/°C/Cell

2.275 2.25–2.30 0.3C Continuous 0.05 x C2032°F–104°F Over 35°C –3.3mV/°C/Cell

Valve Regulated SealedLead Acid Battery Characteristics

Platinum Power UPS Cabinets, Telco & Open Racks

Discharging Current (A)

Final Discharge Voltage (V/cell)

OPTIMUM TEMPERATURE RANGES

F C

Discharge –15° ~ 122° –20° ~ 50°

Charge –15° ~ 104° –20° ~ 40°

Storage –15° ~ 104° –20° ~ 40°

Revised 11/2006

CABINET FEATURES■ Constant Power Up to 161.5KW

(5 mins.,1.75 FV)■ 2 weeks lead time■ Fast Acting fuses & UL listed, High

Flex THHW cables■ Seismic Zone 4 certified■ 10 GA cold rolled steel (cabinet body &

rails)■ 16 GA galvanized steel (battery trays)■ Powder coat, oven baked for chip and

corrosion resistance■ Adjustable rails for multiple battery

configurations and future upgrades■ Pre-wired cabinets to fit up to 40 large

(group 31T) batteries■ Optional circuit breaker and charger

options■ Full turnkey solutions — sized,

configured, drop-shipped

Charging• Always charge batteries in an open, well ventilated

area.• Do not charge batteries near equipment that may

produce sparks.• Do not charge near an open flame.• Do not use smoking materials in battery charging

area.• Electrolysis may cause hydrogen and oxygen to be

released toward the end of a charging cycle or in theevent the battery is overcharged. The combination ofhydrogen and oxygen can result in an explosion if aspark or flame is introduced.

Handling• Never place or dispose of the battery near or in a fire.• Never short the terminals.• Never operate the battery in a air-tight container.• Never unassemble the battery.• Never clean the ABS battery cases with organic

solvents.• CSB batteries contain diluted sulfuric acid and in the

event of contact to the skin or clothing, the exposedareas should be flushed generously with water andthe victim should seek medical attention.

• 1-800 number manned 24 hours for any chemicalemergency by Chemtrec (800-424-9300).

• California Proposition 65 labeling available.

Charging and Handling Precautions

TELCO RACK FEATURES:■ Standard 19"

and 23" racks■ Seismic Zone 4

certified options■ Tier height

flexibility■ Chargers, fuses

and circuitbreakersprotection options

■ Pre-wired racks to fit up to 16

■ Full turnkeysolutions —sized, configured,drop-shipped

OPEN RACK FEATURES:■ Open Racks (RxTx series)■ 2 weeks lead time■ Seismic Zone 4 certified

options■ Tier height flexibility■ Acid-resistant paint for

improved protection andendurance

■ Chargers, fuses and circuitbreakers protection options

■ Pre-wired racks to fit up to 40large (group 31T) batteries

■ Full turnkey solutions – sized, configured, drop-shipped

TELCO RACK

UPS CABINETS

Front Access 12V VRLA Batteries

Long Life 2V Modular Systems

Extreme Environment & Long Life 12V VRLA BatteriesCSB Model Standard Nominal Nominal Capacity Length Width Height Ht. Over Term. Weight

Number Terminal Voltage 20 HR Rate in mm in mm in mm in mm lb. kg.

XTR SERIES (Extreme Environment + Long Life)

XTR1272 F2 12 7.7 5.94 151.0 2.56 65.0 3.70 94.0 3.94 100.0 6.2 2.8

CSB Model Standard Nominal Nominal Capacity Length Width Height Ht. Over Term. WeightNumber Terminal Voltage 10 HR Rate in mm in mm in mm in mm lb. kg.

MSJ SERIESMSJ150 Flag or Recessed 2 150 4.2 106.0 6.69 170.0 12.99 330.0 14.37 365.0 28.6 13.0

MSJ200 Flag or Recessed 2 200 4.2 106.0 6.69 170.0 12.99 330.0 14.37 365.0 33.0 15.0

MSJ260 Flag or Recessed 2 260 4.2 106.0 6.69 170.0 12.99 330.0 14.27 365.0 38.5 17.5

MSJ300 Flag or Recessed 2 300 5.9 150.0 6.69 170.0 12.99 330.0 14.37 365.0 46.2 21.0

MSJ350 Flag or Recessed 2 350 5.9 150.0 6.69 170.0 12.99 330.0 14.37 365.0 49.0 22.3

MSJ400 Flag or Recessed 2 400 6.6 171.0 9.48 241.0 12.99 330.0 14.37 365.0 61.6 28.0

MSJ500 Flag or Recessed 2 500 6.6 171.0 9.48 241.0 12.99 330.0 14.37 365.0 77.0 35.0

MSJ650 Flag or Recessed 2 650 6.6 171.0 12.08 307.0 12.99 330.0 14.37 365.0 102.1 46.4

MSJ800 Flag or Recessed 2 800 6.6 171.0 12.08 307.0 12.99 330.0 14.37 365.0 118.4 53.7

MSJ1000 Flag or Recessed 2 1000 6.6 171.0 18.54 471.0 12.99 330.0 14.37 365.0 154.0 70.0

MU SERIES

MU1000 Recessed 2 1000 11.9 303.0 6.8 172.0 19.1 486.0 19.6 497.0 145.2 66.0

MU1500 Recessed 2 1500 17.2 437.0 6.8 172.0 19.1 486.0 19.6 497.0 211.2 96.0

CSB Model Standard Nominal Nominal Capacity Length Width Height Ht. Over Term. WeightNumber Terminal Voltage 8 HR Rate in mm in mm in mm in mm lb. kg.

TPL SERIES (Front Access + Long Life)*

TPL121000 M6 12 100 20.10 511.0 4.33 110.0 10.00 254.0 10.12 257.1 79.2 36.0

TPL121250 M6 12 125 21.90 557.0 4.90 124.8 12.60 320.0 12.72 320.0 117.0 53.0

TPL121500 M6 12 150 21.90 557.0 4.90 124.8 12.60 320.0 12.72 320.0 123.0 56.0

TPL121900* M6 12 190 21.90 557.0 4.90 124.8 12.60 320.0 12.72 320.0 140.8 64.0

MU 1000

MSJ SERIES

MSJ 500 MSJ 500

MSJ 300 MSJ 300

*to be introduced in 2007

CSB Battery Technologies, Inc.2901 White Settlement Road, Fort Worth, Texas 76107 USA

Phone: 817/244-7777 • Toll Free: 800/3CSB/USA • Fax: 817/244-4445

www.csb-battery.com • E-mail: [email protected], [email protected]

Page 2: Valve Regulated Sealed Platinum Power UPS Cabinets, …informaticstt.com/docs/GENERAL CATALOG (FINAL VERSION).pdf · ( Final Voltage 1.7 V/cell) 2 Charge current: 0.1CA 3 Ambient

• A worldwide leader in VRLA battery products

• Over 30 years manufacturing experience

• Joint venture with Shin Kobe Electric Machinery Co., Ltd. (Hitachi Group)

• Worldwide distribution

• 2, 6, 12 and 24-Volt VRLA batteries

• #1 worldwide supplier to the micro UPS industry

About CSB

CSB is committed to preserving our environment andtogether we can make a difference. Our labeling includes:

• 1-800 number (1- 800-Re-use-pb) affixed to all batteries marketed in the United States for disposal instructions and locations.

• Universal recycle symbol.

• European nonwaste disposal symbol.

• Consumer information indicating the elementcontained within the battery along withdisposal warning.

• Web address located on battery to provideworldwide recycle information.

Recycling

CSB Model Matrix

CSB offers a wide range of valve regulated lead acid

(VRLA) batteries. If what you need is a long service life,

an extended cycle life, and/or a high rate of discharge,

CSB can fulfill your needs. With manufacturing facilities in

Taiwan and China, and strategically located warehousing

facilities, CSB Battery Technologies is here to serve your

production and supply needs now and in the future.

CSB Batteries

Top CoverTerminal

Cover

Container

Safety Valve

Cast OnStrap(COS)

NegativePlate

AGM Retainer

PositivePlate

Pb

RECYCLE

LEAD

RETURN

RechargeableProvides hundreds to thousands of recharge cycles (basedon depth of discharge)

Computerized Charge/Discharge SystemThe patented CCDS system is fully automated and performs 100% two-cycle testing. Each battery is individuallymonitored. Delivers 100% capacity first cycle.

Extended Float LifeBatteries are designed for 3–5 years, 5–8 years, 10 years and 20 years under JIS and Eurobat standards.

CertificationsCSB manufactured batteries offer UL recognized componentsunder UL 924 CSB file number MH14533. TL9000:R3.0Certified. ISO 9001:2000 Certified. ISO 14001:1994 Certified.

Full Particle In Case and Tank FormationDeliver tighter battery-to-battery tolerances for critical applications.

Immobilized ElectrolyteNon-spillable, usable in any position, should not be chargedin an inverted position.

Maintenance FreeNo addition of electrolyte during service life due torecombination technology.

Superior Shelf LifeBattery can be stored in excess of 12 months at 20°C.

TransportationAll batteries have been determined to be in compliancewith D.O.T. Hazardous Material Regulations, theInternational Civil Aeronautics Organization (ICAO), andthe International Air Transport Association (IATA)Packing Instruction 806 and Special Provision A67, andtherefore are exempt from all other requirements of theregulations and classified as a non-spillable battery.CSB batteries are categorized by D.O.T. requirements49 CFR Part 173.159 as electric storage batteries wet,non-spillable, and are therefore exempt from D.O.T.requirements set forth in the above Title. All batteriesmeet FAA standards for air transportation.

Features and Benefits

Specifications are subject to change without notice.UL#14533

Watt rating based on watts/battery @ 15 minutes @ 25°C F.V. 1.67 volts/cell.

Battery Series Application Design Factor Float LifePrefix Suggestion Description Design (25°C)

GP Emergency Lighting, Security, UPS General Purpose 3–5 Years

GH Emergency Lighting, Security, UPS General Purpose 3–5 Years

HC Emergency Lighting, Security, UPS Recessed Terminals 3–5 Years

HR UPS High Rate 3–5 Years

HRL <100 watts UPS High Rate, Long Life 5–8 Years

HRL >100 watts Telecom, UPS High Rate, Long Life 10 Years

GPL < 40 amps Emergency Lighting, Security, UPS General Purpose, Long Life 5–8 Years

GPL >=40 amps Telecom, UPS General Purpose, Long Life 10 Years

EVX Wheelchairs, Scooters, EVs, UPS, Solar High Cycling Applications 5–8 Years

EVH Wheelchairs, Scooters, EVs, UPS, Solar Extended Runtime, High Cycling Applications 5–8 Years

XTR Telecom, UPS Extreme Conditions, Long Life 8 Years

TPL Telecom, UPS Front Access Terminals 10 Years

MU Telecom, UPS 2 Volt Cells 20 Years

MSJ Telecom, UPS 2 Volt Cells 20 Years

Specifications are subject to change without notice.UL#14533

• TL9000:R3.0 certified

• ISO 9001:2000 certified

• ISO 14001:1994 certified

• NEBS Level 3 certified

• Innovative technologies

TERMINALSB1 Nut/Bolt .220 Hole

B2 Nut/Bolt .710 Hole

B3 Nut/Bolt .220 Hole

B4 Nut/Bolt .260 Hole

B5 Nut/Bolt .230 Hole

C1 Recessed Polarized

F1 .187 x .032 Faston

F2 .250 x .032 Faston

M5 Thread Insert& 5 mm Bolt

M6 Thread Insert& 6mm Bolt

Terminals

(0.59)15

(0.7

1)18

(0.3

)7.

5

(0.7

1)ø5

.5

(0.2)5

(0.1

4)

3.46

(0.0

8)

2

12 (0.47)

60

1.5(0.06)(016)

4

(0.10)2.5

ø6.5(0.26) (0.28)

18 (0.71)

18 (

0.71

)

8(0

.31)

7

6.35 (0.25)

3.2 (0.13)

0.8

(0.0

3)(0

.19)

4.75

(0.31)7.95

3.4 (0.13)

0.8

(0.0

3)(0

.25)

6.35

M5

12 (0.47)

5(0

.20)

5.5

(0.2

2)

2 (0.08)

B1 Nut & Bolt B2 (M5) Nut & Bolt B3 Nut & Bolt B4 (M6) Nut & Bolt

F1 Faston Tab 187 F2 Faston Tab 250 M5 Thread Insert/Bolt

M6

M6 Thread Insert/Bolt14.1

1.5

1.5

11.5

7.78

8.137

4.75

20.5

11.5

11.1

12

6

1.7

2.93.4 5.35

4.38

14.1

1.5

1.5

11.5

8.13

108.66.35

20.5

C1 Recessed Polarized

(0.2)5

16.7(0.65)

ø6(0.25)

19(0

.74)

6.8

(0.2

6)

B5 Nut and Bolt

CSB Model Standard Nominal Nominal Capacity Length Width Height Ht. Over Term. Weight Flame Retardant Number Terminal Voltage 20 HR Rate in mm in mm in mm in mm lb. kg. Casing

GH “PRISM’ SERIES (General Purpose)

GH613 F1 6 1.3 3.82 97 0.95 24 2.05 52 2.32 59 0.66 0.30 N/A

GH633 F1 6 3.3 5.28 134 1.34 34 2.36 60 2.64 67 1.52 0.69 N/A

GH645 F1 6 4.5 2.76 70 0.96 47 3.98 101 4.21 107 1.85 0.84 N/A

GH660S Spring 6 6 2.68 68 1.85 68 3.82 97 4.53 115 2.07 0.94 N/A

GH672 F1 6 7.2 5.95 151 1.34 34 3.70 94 3.94 100 2.95 1.34 N/A

GH685 F1 6 8.5 3.86 98 1.69 56 4.65 118 4.65 118 3.52 1.60 N/A

GH6120 F1 6 12 5.95 151 2.21 50 3.70 94 3.94 100 4.52 2.05 N/A

GH6130WLF Wire Lead 6 12 4.21 107 1.97 70 5.51 140 5.51 140 4.79 2.18 N/A

GH1207 Wire Lead 12 0.7 3.78 96 0.98 25 2.44 62 2.44 62 0.93 0.42 N/A

GH1213 F1 12 1.3 3.82 97 1.69 43 2.05 52 2.22 57 1.28 0.55 N/A

GH1222 F1 12 2.2 7.01 178 1.69 35 2.36 60 2.64 67 2.09 0.95 N/A

GH1222SLM F1 12 2.2 5.91 150 0.81 20.5 3.52 89.5 3.52 89.5 1.54 0.70 N/A

GH1234 F1 12 3.4 5.28 134 1.38 67 2.36 60 2.64 67 3.02 1.37 N/A

GH1250 F1 12 5 3.54 90 2.64 70 3.98 101 4.21 107 4.04 1.83 N/A

GH1270 F1 12 7 5.94 151 2.56 65 3.70 94 3.94 100 5.67 2.58 N/A

GH12500 12 50 9.60 245 5.30 135 8.15 207 9.18 233 39.80 18.05 N/A

CSB Model Standard Nominal Nominal Capacity Length Width Height Ht. Over Term. Weight Flame RetardantNumber Terminal Voltage 20 HR Rate in mm in mm in mm in mm lb. kg. Casing

GP SERIES (General Purpose) GP645 F1 or F2 6 4.5 2.76 70 1.89 48 4.02 102 4.25 108 1.8 .82 Optional

GP672 F1 or F2 6 7.2 5.94 151 1.34 34 3.70 94 3.94 100 2.90 1.31 Optional

GP6120 F1 or F2 6 12 5.94 151 1.97 50 3.70 94 3.94 100 4.43 2.01 Optional

GP1222 F1 12 2.2 7.01 178 1.34 34 2.36 60 2.60 66 2.1 .92 Optional

GP1245 F1 or F2 12 4.5 3.65 92.8 2.75 69.9 4.02 102 4.25 108 3.62 1.64 Optional

GP1272 F1 or F2 12 7.2 5.94 151 2.56 65 3.70 94 3.94 100 5.67 2.58 Optional

GP12120 F1 or F2 12 12 5.94 151 3.85 98 3.70 94 3.94 100 8.86 4.02 Optional

GP12170 B1 or B3 12 17 7.13 181 3.00 76.2 6.50 165.5 6.57 167 13.0 5.9 Optional

GP12200 M5 12 20 7.13 181 3.00 76.2 6.29 160 6.57 167 14.4 6.5 Optional

GP12260 B1 or B3 12 26 6.54 166 6.89 175 4.8 122 4.92 125 20.4 9.25 Optional

GP12340 B5 12 34 7.70 195.6 5.12 130 6.09 154.8 7.02 178 27.3 12.6 Optional

GP12400 B2 12 40 7.76 197 6.50 165 6.63 168.5 6.69 170 32.7 14.8 Optional

GP12650 B4 12 65 13.75 349.4 6.53 166 6.79 172.5 6.85 174 48.6 22 Optional

GP24150 B3 24 15 7.12 181 5.84 148.4 6.57 167 6.57 167 27.8 12.4 Optional

HC SERIES (High Rate), Watt rating based on watts/cell @ 15 min. rate @ 25°C F.V. 1.67 volt/cell

HC1217W C1 12 4.5 5.50 139.7 1.89 48 4.02 102 4.07 103.5 3.82 1.73 N/A

HC1221W C1 12 5.1 5.50 139.7 1.89 48 4.02 102 4.07 103.5 4.40 2.0 N/A

HC1228W C1 12 8.2 5.50 139.7 1.89 48 4.96 126 5.00 127.5 5.73 2.6 N/A

HR SERIES (High Rate Discharge), Watt rating based on watts/cell @ 15 min. rate @ 25°C F.V. 1.67 volt/cell

HR1221WF2 F2 12 5.1 3.54 90 2.76 70 4.01 101.8 4.17 106 4.4 2.0 Optional

HR1224WF2F1 F2F1 12 6.4 5.94 151 2.01 51 3.70 94 3.87 98.3 4.63 2.1 Optional

HR1234WF2 F2 12 9 5.94 151 2.56 65 3.70 94 3.94 100 5.73 2.6 Optional

HR1251WF2 F2 12 13.5 5.94 151 3.85 98 3.70 94 3.94 100 9.26 4.2 Optional

HR12120W M5 12 30 6.53 166 4.92 125 6.55 166.5 6.89 175 23.6 10.7 Standard

GPL SERIES (Standard High Rate + Long Life)

GPL672 F2 6 7.2 5.94 151 1.34 34 3.70 94 3.94 100 3.02 1.37 Optional

GPL1272F2 F2 12 7.2 5.94 151 2.56 65 3.70 94 3.94 100 5.83 2.65 Standard

GPL12400 B2 12 40 7.76 197 6.50 165 6.34 161 6.69 170 31.9 14.5 Optional

GPL12520 B4 12 52 8.98 228 5.45 138.4 7.92 201.3 8.63 219.3 39.38 17.9 Optional

GPL12750 M6 12 75 10.28 261 6.64 168.5 8.26 209.7 8.37 212.7 57.2 26.0 Optional

GPL12880 M6 12 88 12.15 308.7 6.66 169 8.26 209.8 8.38 212.8 66.1 30.0 Optional

GPL121000 M6 12 100 13.46 342 6.69 170 8.39 213.1 8.51 216.2 77.2 35.0 Optional

HRL SERIES (High Rate Discharge + Long Life), Watt rating based on watts/cell @ 15 min. rate @ 25°C F.V. 1.67 volt/cell

HRL634WF2 F2 6 9 5.94 151 1.34 34 3.70 94 3.87 98.3 2.9 1.34 Optional

HRL1210WF2 F2 12 2.3 7.01 178.0 1.34 34.0 2.52 64 2.76 70.0 2.67 1.2 Standard

HRL1223WF2 F2 12 5.75 3.54 90.0 2.76 70.0 4.01 101.8 4.17 106.0 4.62 2.0 Standard

HRL1234WF2 F2 12 9 5.94 151 2.56 65 3.70 94 3.87 98 5.95 2.7 Standard

HRL1280W M5 12 23 7.13 181 3.0 76.2 6.29 160 6.57 167 14.5 6.6 Optional

HRL12110W M5 12 28 6.53 166 4.92 125 6.55 166.5 6.89 175 21.78 9.9 Standard

HRL12150W M6 12 37 7.7 195 5.12 130 6.28 159.5 6.42 163 26.46 12 Standard

HRL12200W M6 12 52 8.97 228 5.45 138.4 8.06 204.8 8.16 207.3 38.72 17.6 Standard

HRL12280W M6 12 75 10.28 261 6.64 168.5 8.31 211 8.43 214.2 59.6 27.1 Standard

HRL12330W M6 12 88 12.15 308.7 6.66 169.0 8.32 211 8.44 214.3 69.5 31.6 Standard

HRL12390W M6 12 100 13.46 342.0 6.69 170.0 8.45 214.6 8.57 217.6 78.1 35.5 Standard

HRL12500W M6 12 134 13.5 343 6.69 170 10.81 274.7 10.93 277.7 100.54 45.7 Standard

EVX SERIES (Cycle Application)

EVX1272F2 F2 12 7.2 5.94 151 2.56 65 3.70 94 3.94 100 5.73 2.6 Optional

EVX12120F2 F2 12 12 5.94 151 3.85 98.0 3.70 94 3.94 100 9.26 4.2 Optional

EVX12170 B1 or B3 12 17 7.13 181 3.0 76.2 6.51 165.5 6.57 167 13.4 6.1 Optional

EVX12200 M5 12 20 7.13 181 3.0 76.2 6.29 160 6.57 167 14.77 6.7 Optional

EVX12260 B1 or B3 12 26 6.54 166 6.89 175 4.80 122 4.92 125 20.8 9.46 Optional

EVX12300 M5 12 30 6.53 166 4.92 125 6.55 166.5 6.89 175 22.9 10.4 Optional

EVX12340 B5 12 34 7.70 195.6 5.12 130 6.09 154.8 7.03 178.3 25.8 11.74 Optional

EVX12400 B2 12 40 7.76 197 6.50 165 6.63 168.5 6.69 170 32.1 14.6 Optional

EVX12520 B4 12 52 9.76 248 5.45 138.4 7.93 201.3 8.63 219.3 39.38 17.9 Optional

EVX12750 B5 12 75 10.83 275 6.63 168.5 8.31 211.2 9.18 233.2 58.96 26.8 Optional

EVX121000 B5 12 100 20.2 511.6 6.9 175.2 6.79 172.5 6.85 174 78.1 35.5 Optional

EVH SERIES (Extended Runtime Cycle Application)

EVH12150 F2 12 15 5.94 151 3.86 98 3.7 94 4.02 102 9.9 4.5 Optional

EVH12220 M5 12 22 7.13 181 3.0 76.2 6.26 159 6.57 167 14.7 6.7 Optional

EVH12390 B5 12 39 7.7 195.6 5.12 130 6.09 154.8 7.02 178.3 25.3 11.5 Optional