VALVE&,HYDRANT»I:VI:SI:ON
DIVISION OF MUELLER CO.
JAMES JONES MODEL J4060ER FIRE HYDRANT
[IONES I Fire Hydrant-3 Nozzle Cast or Ductile IronForm 12740 - 4/11
Hydrant DescriptionPART # NOZZLE CONFIG.
J4060AR 41/2" X 2 '/2" x 21/2"J4060BR 4" x 2 1/2" X 21/2"J4060CR 4" x 21/2" X 2 1/2"
J4060DR 4" x 21/2" X 21/2"J4060ER 4 1/2"x 21/2" X 2 J /2"
Product Features• Meels or Exceeds ANSI/AWWA C503
• Individual Stem Operation• Limited Number of Intemal Parts
• Nozzle Threads Conform 10 NFPA1963. NH/NST• Removable Nozzle Design
• Available in a Variety of Bolt Hole Patterns• Low Zinc Silicon Bronze Stems
• Heavy Duty Disc Holder• Product Rated up to 200 PSI(1379 kPa). Hydrostatically Tested
at 400 PSt(2758 kPa)• a-Ring Construction in Stem Insert• Epoxy Coated Interior Meets AWWA C5S0 and NSF61• Plastic Caps Available• 10-year Limited warranty• 5" Storz Pumper Nozzle Available
Eou>-t:oa.Eoo'-Q)
Parfs List10 PART NAME MATERIAL1 Hydrant Body Cast or Duclile Iron2 Nozzle Insets Copper Alloy UNSC836003 Hose Caps Cast Iron4 Hydrant Stem S~icon BronzeQ)
:::lE@o-cQ)
5 Stem Locknut Copper Alloy UNSC836006 Beveled Hydrant Disc BUNA-N
NOTE:200 PSI(1379 kPa) -Cast IronHydrantRated at17SPSI
(1207kpa~I~~~~~~~~~,l(
~©INl~4CNO
lCOO{AWWA200l'SI
7 Hydrant Disc Locknut Copper Alloy UNSC83600Copper Alloy UNSC836008 Stem Insert
9 Pent Nut Copper Alloy UNSC8360010 Pent Nut Retainer Copper Alloy UNSC8360011 Hydrant Disc Holder Copper Alloy UNSC83600'-o
E12 NOllie Gasket Neoprene13 a-Rings BUNA-N
1-- 11.15" (283mm) REF -I Zinc Coaled Steel14 Chain
(Mueller Ca.)FM ~ 200 PSt RAliNG
® 200 PSI RATING
INT&ANATIONAL DIVIS'ON
Mueller International Division. 633 Chestnut St. Suite 1200 . Chattanooga, TN 37450 . 423·209-4814 . FAX 423-209-4850
Form: J4060 9-24-2012
09.50·(241nvn)
26.25"(667mm)
.---!
Dimensions 1-0(0(-------
[IONES I Fire Hydrant-3 Nozzle Cast or Ductile Iron
23.12"(587nvn)
19.28"(49OmmJ
14.40(366mmJ
I~ 1l.lS"{283mm) ---.._DIA. REf •
60'/-$-.,
/""" I " 6x 0.75" (19mm)/ . " EQUALLY SPACED
\,~(------
6 x 0.875" (22mmJEQUAII.Y SPACED
09.33"(237mmJ
8 x 0.875" (22mm)EQUALLY SPACED
(Mueller ea.1INTERNATIONAL DIVISION
Mueller International Division. 633 Chestnut St. Suite 1200 Chattanooga, TN 37450 423·209·4814. FAX 423-209-4850
..---!
Form: J4060 9-24·2012
! .>
-NIJ I EiJ·-j~2rj';';20:;'12_.-
t£\I RELEASE FlJl: COSTA RICA
26.25
23.12
8x07/8"EQUALLY SPACED
11I-- I EO 344119-20-12 REVISED IT£MS u, 9. 2i AND 23
I1-- -+-- _1--(-1-++1
I
SECTION A-A
1l,~~t~1Q)n~~
~@$[P~~
JJ©~~~~@•~~
1
d=
19.28
14.40
A I 11.1~ DIA I AI REF. tMAINTENANCE NOTES:
1. OPERATE HYDRANT AT LEAST ONCE EVERY 6 MONTHS.2. VISUALLY INSPECT FOR LEAKS.
SECTION AZ-AZ
SSY - HOLDER AND DISC 2-11213 2127~50n12 rl34C59 :INSERT 4-112 LONG LENGTH25 I ~ 20-55 SET SCRE'oI 114-20 - 3/4
NSERT 2-112 MEDIUM LENGTHIT 1-134-5724 I 2 20-54 SET SCRE'oI 114-20 - 5/1623Tl r134~5 iiNSERT 2-112 SHORT LENG192345 ASKET 4-1/2 (REF ASSY 23 565) o221 2 90272 ASKET 2-112 (RtFlISsY-2:FS63) 9 2-12-6=93 ~TEM 4'211 2 ;30-21 -HOOK - STEEL 8 1126=99 [STEM 2-112nT3 120-26 SC nfS::'-N3 -RmG
16-254 NUT - STEM19 1 3 6 2- 115-242 -RfNGUT - OPERATING181 3 121-4 5 3 115-192 -RING
r6~f617 1 3 OCKNUT - STEM 4 194572 -RING16-1-]: ~ IOZZLE INSERT - 4-1/2' 'oilS3C,S6 ¥--CAP AND RING 4-1/2rST2 2l34- !OZZLE INSERT - 2-112' "'I SET SCREV3CC5b1 Y-C,- CAP AND RING 2-1/2
fDRANT BODY - DOCTILE fRllN14 1 ~ 7-501 SSY - HOLDER-ANnrst4-1I2 lIT 134-202ITEMIQTY ITEMIQTYI PART NO DESCRIPTIONPART NO DESCRIPTION
JAMES JONES CD.tOI[' •••.~~\ ..•••.~~CA. ••••••• ~J4060 ER
4~rit.'f'..;ieu:,tt~
~~;:"~;:~~~I!::~~ :::.J~:r
(Mueller Ca.)INTeRNA,'TIONAL DIVISION
GENERALVVARRANTVMueller Co. warrants its products to be free of defects in workmanship and material undernormal use and service and when used for the purposes and under the conditions for whichthey are intended, for a period of one year from the date of shipment.
Obligation under this warranty is limited, at Mueller's option; to adjust, repair or replace, F.O.B.point of manufacture, the defective product. Purchaser must immediately notify Mueller Co. inwriting of the claimed defect. Mueller shall have the right to inspect said product and purchasershall, if requested, return the defective product to Mueller Co. with transportation prepaid.Purchaser shall assume all responsibility and expense for removal and reinstallation and freightcharges in connection with the foregoing remedy. Mueller Co. shall not be liable for indirect,special, incidental or consequential damage or penalties and does not assume any liability ofpurchaser to others, or to anyone for injury to persons or property. This warranty is in lieu of allother warranties, expressed and implied including the warranty of merchantability.
Any claims or shortages or damages must be in writing within ten days after receipt ofshipment. Buyer shall note loss or damage on truck shipments by providing a delivery receiptsigned by the driver.
Mueller Co.Chattanooga, Tennessee USwww.muellercompany.com
1~Nick Peyton - VP, International & Gas Sales8/15/2012
REVISED 09·2009
Form:J4060 9-24-2012
FMAPPROVAL~pprovaIS·
NOT to be distributed outside ofFMApprovals and its affiliates except by CUSTOMER.
.~1(·1/I1n.·1' £If ,hc.' FM Gtoba! GrollI'
APPROVAL REPORT
WET BARREL FIRE HYDRANTMODEL J4040 AND J4060(MODIFICATION)
Prepared for:
James Jones CompanyDivision of Mueller Company20 Thurber Blvd.Smithfield, RI 02917
Project 10. 3034369Class: 1511Approval Date: September 19, 2008
Authorized by: ~,f~Richard B. Dunne, Group Manager, Hydraulics
FM Approvals1151 Boston-Providence TurnpikeP.O. Box 9102Norwood, MA 02062
Page 1 of4
Form: J4060 9-24-2012
FMAPPROVALFM APPROVALS
3034369
WET BARREL FIRE HYDRANTMODEL J4040 AND J4060 WITH A MODIFICATION
from
JAMES JONES COMPANYDIVISION OF MUELLER COMPANY
20 Thurber Blvd.Smithfield, RI 02917
I INTRODUCTION
1.1 James Jones Company, A Division of Mueller Company, requested an Approval of their J4040 andJ4060 Wet Barrel Fire Hydrants with a modification. The modification is the availability of a 5 inchStorz threadless pumper nozzle.
1.2 This Report may be freely reproduced only in its entirety and without modification.
1.3 Standards
Title Class Number DateFire Hydrants (Wet Barrel Type) for
1511 November, 1990Private Fire Services
1.4 Listing:
The listing for the Model J4040 and J4060 Wet Barrel Fire Hydrants with the modification discussedin this Report will continue to be listed in Chapter One of the Fire Protection section of the FMApproval Guide, an online resource ofFM Approvals, under the heading "Wet Barrel Hydrants" asfollows:
James Jones Co 4127 Temple City Blvd, EI Monte, California 91731, USA
Model J4040 and J4060 Wet Barrel Fire Hydrants
Product Rating RemarksJ4040 200 psi, (1380 kPa) a,bJ4060 200 psi, (1380 kPa) a,b
a) Two 2-112inch (64 mm) hose outlets and a 4 or 4-112inch (102 or 104 mm) pumper nozzleb) Available with a 5 inch Storz Threadless Pumper Nozzle
Page 2 of4
Form:J4060 9-24-2012
FMAPPROVALFM APPROVALS
3034369
II DESCRIPTION
2.1 Modification
The only change between the currently FM Approved J4040 and J4060 Wet Barrel Hydrantsdiscussed in this Report and those discussed in previous Approval Reports for these products shownbelow is the addition of a 5 inch Storz pumper nozzle.
Project Identification Number Date of ReportOB5A4.AH 03-26-1997
3004245 05-06-19993011286 11-09-20013015277 10-13-2004
2.2 Rated Working Pressure
The rated working pressure of the Model J4040 and J4060 Wet Barrel Fire Hydrant discussed in thisReport shall be 200 psi (1380 kPa).
m EXAMINATIONS AND TESTS
3.1 This examination was limited to a desk review.
3.2 Hydrostatic testing of the hydrants with the 5 inch Storz threadless pumper nozzle was not deemednecessary due to the similarities between those tested under U.S. Pipe Valve and Hydrant P.1.3033323, and that submitted for this examination. Mueller Company allowed FM Approvalspermission to use the data obtained in P.1. 3033323, in making this determination.
3.3 Because the internal diameter of the 5 inch threadless Storz nozzle is greater than the currentlyApproved 4 inch threaded nozzles discussed in the projects shown above, no friction loss testing wasdeemed necessary.
IV MARKING
The following information appears on the apparatus identified in Section 1.5 and meets Standardrequirements:
Manufacturer's nameThe model designations, J4040 or J4060The nominal device sizeThe year of manufactureThe rated working pressureThe word "Open" in close proximity to the hydrants opening nutThe FM Approvals Certification mark.
V REMARKS
Installation shall comply with the latest edition of the manufacturer's installation instructions and bein accordance with the applicable FM Global Property Loss Prevention Data Sheets.
Page 3 of4
Form: J4060 9-24-2012
FM APPROVALFM APPROVALS
3034369
VI FACILITIESANDPROCEDURESAUDIT
The manufacturing site at 956 Industrial Blvd. Albertville, AL. 35950, is subject to follow-up auditinspections. The facilities and quality control procedures in place have been found to be satisfactory tomanufacture product identical to that examined and tested as described in this report.
VII MANUFACTURERSRESPONSmILITIES
Documentation considered critical to this Approval is on file at FM Approvals and listed in theDocumentation File, Section VIII of this report. No changes of any nature shall be implementedunless notice of the proposed change has been given and written authorization obtained from FMApprovals. The Approved Product Revision Report, Form 797, shall be forwarded to FM Approvalsas notice of proposed changes.
VIII DOCUMENTATION
The following drawings describes the 5 inch threadless Storz pumper nozzle and are filed under P.I.OB5A4.AH.
Drawlna No. DescriptionIssue5" Machining, Nozzle (Jones) Quick
Disconnect240675 D
IX CONCLUSION
The James Jones Model J4040 and J4060 Wet Barrel Hydrants with the 5 inch Storz threadlessnozzle described in section 2.1 of this Report meet FM Approval requirements, at a workingpressure of200 psi (1380 kPa.) Since a duly signed Master Agreement is on file, Approval iseffective as of the date ofthis signed Approval Report.
EXAMINATION BY: Robert J. Masinda
PROJECT DATA RECORD: Filed under P.I. 3034369, dated September 22,2008
ORIGINAL TEST DATA: Filed under P.I. OB5A4.AH, dated March 26,1997
REPORT BY: REPORT REVIEWED BY:
Robert J. MasindaAssociate EngineerHydraulics
Technical Team ManagerHydraulics
Page 4 of4
Form: J4060 9-24-2012
HBOR.EX3821 - Hydrant"> Page 1 of 1
UL CERTIFICATION
-® ONLINE CERTIFICATIONS DIRECTORY
HBOR.EX3822Hydrants
Pago HOUpT
Hydrants
JAMES JONES co II C, SUB OF MUEllER co1470 S VINTAGE AVE
ONTARIO, CA 91761 USA
EX 3322
Wetb ancl desion:
Hose Outlet Pumper Outlet Rated PressureMod", In. In. (p5ig)
)4001 (1) 2-1/2 (1) 4 150
J4005* (1) 2-1/2 (1) 4 150
)4040 (1) 2-1/2 (l) 4 or 4-1/2 175
J404001+ (1) 2-1/2 (1) 4 or 4-1/2 200
)4043 (l) 2-1/2 (1) 4 or 4-112 175
)4060 (2) 2-1/2 (1) 4 or 4-1/2 175
)406001+ (1) 2-1/2 (1) 4 or 4-1/2 200
The Models )40'40, J404S and J4060 4-1/2 10. bas:", valve hydrants t:an utilize an optiof':lsl 4 or 5 In. tfueadless(<julCk dlsconned}ncwe,
*Models J4008 and J4048 an! supplied ~.•.ith a 2-1J2 in. dome cap.
+Models )404001 and ]406001 provided with ductilE iron barrel.
I as Updat •••d on 2003-10-23
Print this page Notice of Disclaimer
Copvnght ~) 2011 Undel"/riters labol'atclI'ies lnc,®
The appearance of a comp.any's name or product in this database- does not in itself assure that products so Identtfied have been manefaeturedunder UL's Follow-Up Service, Only those products bearing the V Mark should be considered to be Usted and covered under UL's Fotlow-UpService, Always look for the Mark on the product.
ULpermits the reprcducbon or the material contained in the Online Certification Directory subject to the rollo\-,ing conditions: 1. The GuideInrormation, Designs andlol' Listings (files) must be presented in their entirety and in a non-misle3ding manner, without any manipul a 'on of thedata (or drawings). 2. The statement "Reprinted from the Online CErtifications Directory ••../ith perrrusstcn from Underwriters Lebcratcrses tee," mustappear adjacent to the extracted material. In addition. the reprinted rnatertal must Include a copYl;ght notice in the fonowing fermat r "Copyright '?")2011 Underwriters Labcratcrtes Inc,@tt
I -re c ce 1111 t ' 0'1';: JI. ~I • n ;t.'.ll~ nr e c r ·;1 _,11. t /,1, u .~I!··, I 1:;:>1'1', r':\ t c rt ...•1 ,J ••• n e ot e c g c
http: ' database. ul. com czi-bin XYV 't<!111plate US EXT 1FRA.ME 'shO\\yag:e .html'lname= _.. 10'28.2011
Form: J4060 9-24-2012