PARAMETERS FOR SINAMICS V20 VFD FOR SOLAR APPLICATION USING EXTERNAL PUSH BUTTON
DO THE QUICK COMMISSIONING FOR MOTOR DATA.
FOR THIS FOLLOW THE BELOW STEPS:
PARAMETER DISCRIPTION FACTORY DEFAULT
DEFAULT FOR cn006
REMARKS
P0010 COMMISSIONING PARAMETER
0 1 QUICK COMMISSIONING
P0304 RATED MOTOR VOLTAGE (V)
400 CHANGE AS PER MOTOR
ENTER THE MOTOR OPERATING VOLTAGE
P0305 RATED MOTOR CURRENT (A)
1.86 CHANGE AS PER MOTOR
ENTER THE MOTOR OPERATING CURRENT
P0307 RATED MOTOR POWER (KW)
0.75 CHANGE AS PER MOTOR
ENTER THE MOTOR KW
P0308 RATED MOTOR COS PI 0 CHANGE AS PER MOTOR
ENTER COS PI OF MOTOR
P0310 RATED MOTOR FREQUENCY
50 50 MOTOR FREQUENCY
P0311 RATED MOTOR SPEED (RPM)
1395 CHANGE AS PER MOTOR
ENTER MOTOR RPM
P0700 SELECTION OF COMMAND SOURCE
1 2 TERMINAL AS COMMAND SOURCE
P0731 FUNCTION OF DIGITAL OUTPUT 1
52.3 52.3 INVERTER FAULT ACTIVE
P0732 FUNCTION OF DIGITAL OUTPUT 1
52.7 52.2 INVERTER RUNNING
P1080 MINIMUM FREQUENCY 0 50 ENTER FREQUENCY AS MAXIMUM
P1082 MAXIMUM FREQUENCY
50 50 ENTER MAXIMUM FREQUENCY
P1120 RAMP UP TIME 10 20 RAMP UP TIME
P1121 RAMP DOWN TIME 10 20 RAMP DOWN TIME
PARAMETERS FOR SINAMICS V20 VFD FOR SOLAR APPLICATION USING EXTERNAL PUSH BUTTON
THE ABOVE STEPS ENDS THE QUICK COMMISSIONIG.
SELECT THE CONNECTION MACRO –cn006 BY PRESSING ‘M’ BUTTON ON VFD FOR >2S.
BY DOING SO DEFAULT SETINGS WILL GET SAVED
AFTER QUICK COMMISSIONIG CHANGE THE FOLLOWING PARAMETERS FOR THE SOLAR APPLICATION.
P3900 END OF QUICK COMMISSIONING
0 3 END QUICK COMMISSIONING ONLY FOR MOTOR DATA
PARAMETER DISCRIPTION FACTORY DEFAULT
DEFAULT FOR cn006
REMARKS
P0700 SELECTION OF COMMAND SOURCE
1 2 TERMINAL AS COMMAND SOURCE
P1000 SELECTION OF FREQUENCY
1 1 BOP/MOP
P0701 FUNCTION OF DIGITAL INPUT 1
0 2 OFF1/HOLD
P0702 FUNCTION OF DIGITAL INPUT 2
0 1 ON PULSE
P0727 SELECTION OF 2/3-WIRE METHOD
0 3 3-WIRE ONPULSE+OFF1/HOLD+REVERSE
P0731 FUNCTION OF DIGITAL OUTPUT 1
52.3 52.2 INVERTER RUNNING
P0732 FUNCTION OF DIGITAL OUTPUT 1
52.7 52.3 INVERTER FAULT ACTIVE
PARAMETER DISCRIPTION FACTORY DEFAULT
DEFAULT FOR cn006
REMARKS
PARAMETERS FOR SINAMICS V20 VFD FOR SOLAR APPLICATION USING EXTERNAL PUSH BUTTON
FOR RESTING THE DRIVE TO FACTORY SETTINGS :
SET P0010 : 30 AND P0970 : 1
THIS WILL MAKE THE FACTORY DEFAULT.
P1200 FLYING START 0 4 FLYING START ALWAYS ACTIVE
P1210 AUTOMATIC RESTART 1 6 RESTART AFTER MAINS BROWN- /BLACKOUT OR FAULT, P1211 ENABLED
P1240 CONFIGURATION OF VDC CONTROLLER
1 2 KINETIC BUFFERING (VDC_MIN CONTROLLER) ENABLED
P1245 SWITCH ON LEVEL KINETIC BUFFERING (%)
76 68 SWI TCH ON LEVEL (%)