PARAMETERS FOR SINAMICS V20 VFD FOR SOLAR APPLICATION USING EXTERNAL PUSH BUTTON DO THE QUICK COMMISSIONING FOR MOTOR DATA. FOR THIS FOLLOW THE BELOW STEPS: PARAMETER DISCRIPTION FACTOR Y DEFAUL T DEFAULT FOR cn006 REMARKS P0010 COMMISSIONING PARAMETER 0 1 QUICK COMMISSIONING P0304 RATED MOTOR VOLTAGE (V) 400 CHANGE AS PER MOTOR ENTER THE MOTOR OPERATING VOLTAGE P0305 RATED MOTOR CURRENT (A) 1.86 CHANGE AS PER MOTOR ENTER THE MOTOR OPERATING CURRENT P0307 RATED MOTOR POWER (KW) 0.75 CHANGE AS PER MOTOR ENTER THE MOTOR KW P0308 RATED MOTOR COS PI 0 CHANGE AS PER MOTOR ENTER COS PI OF MOTOR P0310 RATED MOTOR FREQUENCY 50 50 MOTOR FREQUENCY P0311 RATED MOTOR SPEED (RPM) 1395 CHANGE AS PER MOTOR ENTER MOTOR RPM P0700 SELECTION OF COMMAND SOURCE 1 2 TERMINAL AS COMMAND SOURCE P0731 FUNCTION OF DIGITAL OUTPUT 1 52.3 52.3 INVERTER FAULT ACTIVE P0732 FUNCTION OF DIGITAL OUTPUT 1 52.7 52.2 INVERTER RUNNING P1080 MINIMUM FREQUENCY 0 50 ENTER FREQUENCY AS MAXIMUM P1082 MAXIMUM FREQUENCY 50 50 ENTER MAXIMUM FREQUENCY P1120 RAMP UP TIME 10 20 RAMP UP TIME P1121 RAMP DOWN TIME 10 20 RAMP DOWN TIME

v20 Vfd Setting for Solar Application With External p.b

Embed Size (px)

DESCRIPTION

seimens vfd

Citation preview

Page 1: v20 Vfd Setting for Solar Application With External p.b

PARAMETERS FOR SINAMICS V20 VFD FOR SOLAR APPLICATION USING EXTERNAL PUSH BUTTON

DO THE QUICK COMMISSIONING FOR MOTOR DATA.

FOR THIS FOLLOW THE BELOW STEPS:

PARAMETER DISCRIPTION FACTORY DEFAULT

DEFAULT FOR cn006

REMARKS

P0010 COMMISSIONING PARAMETER

0 1 QUICK COMMISSIONING

P0304 RATED MOTOR VOLTAGE (V)

400 CHANGE AS PER MOTOR

ENTER THE MOTOR OPERATING VOLTAGE

P0305 RATED MOTOR CURRENT (A)

1.86 CHANGE AS PER MOTOR

ENTER THE MOTOR OPERATING CURRENT

P0307 RATED MOTOR POWER (KW)

0.75 CHANGE AS PER MOTOR

ENTER THE MOTOR KW

P0308 RATED MOTOR COS PI 0 CHANGE AS PER MOTOR

ENTER COS PI OF MOTOR

P0310 RATED MOTOR FREQUENCY

50 50 MOTOR FREQUENCY

P0311 RATED MOTOR SPEED (RPM)

1395 CHANGE AS PER MOTOR

ENTER MOTOR RPM

P0700 SELECTION OF COMMAND SOURCE

1 2 TERMINAL AS COMMAND SOURCE

P0731 FUNCTION OF DIGITAL OUTPUT 1

52.3 52.3 INVERTER FAULT ACTIVE

P0732 FUNCTION OF DIGITAL OUTPUT 1

52.7 52.2 INVERTER RUNNING

P1080 MINIMUM FREQUENCY 0 50 ENTER FREQUENCY AS MAXIMUM

P1082 MAXIMUM FREQUENCY

50 50 ENTER MAXIMUM FREQUENCY

P1120 RAMP UP TIME 10 20 RAMP UP TIME

P1121 RAMP DOWN TIME 10 20 RAMP DOWN TIME

Page 2: v20 Vfd Setting for Solar Application With External p.b

PARAMETERS FOR SINAMICS V20 VFD FOR SOLAR APPLICATION USING EXTERNAL PUSH BUTTON

THE ABOVE STEPS ENDS THE QUICK COMMISSIONIG.

SELECT THE CONNECTION MACRO –cn006 BY PRESSING ‘M’ BUTTON ON VFD FOR >2S.

BY DOING SO DEFAULT SETINGS WILL GET SAVED

AFTER QUICK COMMISSIONIG CHANGE THE FOLLOWING PARAMETERS FOR THE SOLAR APPLICATION.

P3900 END OF QUICK COMMISSIONING

0 3 END QUICK COMMISSIONING ONLY FOR MOTOR DATA

PARAMETER DISCRIPTION FACTORY DEFAULT

DEFAULT FOR cn006

REMARKS

P0700 SELECTION OF COMMAND SOURCE

1 2 TERMINAL AS COMMAND SOURCE

P1000 SELECTION OF FREQUENCY

1 1 BOP/MOP

P0701 FUNCTION OF DIGITAL INPUT 1

0 2 OFF1/HOLD

P0702 FUNCTION OF DIGITAL INPUT 2

0 1 ON PULSE

P0727 SELECTION OF 2/3-WIRE METHOD

0 3 3-WIRE ONPULSE+OFF1/HOLD+REVERSE

P0731 FUNCTION OF DIGITAL OUTPUT 1

52.3 52.2 INVERTER RUNNING

P0732 FUNCTION OF DIGITAL OUTPUT 1

52.7 52.3 INVERTER FAULT ACTIVE

PARAMETER DISCRIPTION FACTORY DEFAULT

DEFAULT FOR cn006

REMARKS

Page 3: v20 Vfd Setting for Solar Application With External p.b

PARAMETERS FOR SINAMICS V20 VFD FOR SOLAR APPLICATION USING EXTERNAL PUSH BUTTON

FOR RESTING THE DRIVE TO FACTORY SETTINGS :

SET P0010 : 30 AND P0970 : 1

THIS WILL MAKE THE FACTORY DEFAULT.

P1200 FLYING START 0 4 FLYING START ALWAYS ACTIVE

P1210 AUTOMATIC RESTART 1 6 RESTART AFTER MAINS BROWN- /BLACKOUT OR FAULT, P1211 ENABLED

P1240 CONFIGURATION OF VDC CONTROLLER

1 2 KINETIC BUFFERING (VDC_MIN CONTROLLER) ENABLED

P1245 SWITCH ON LEVEL KINETIC BUFFERING (%)

76 68 SWI TCH ON LEVEL (%)