UTAdvanced UP55AProgram Controller

Parameter Maps and Lists

TI 05P02C41-01EN©Copyright July. 20111st Edition July. 2011

Page 1 / 25

Page 2: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

UTAdvanced UP55AIntroduction

Brief Description of Sheets

This sheet provides a brief description of the following sheets entitled "Names and Functions of Display Parts,""Operation and Program Parameter Map," "Setup Parameter Map," "List of Parameters," "Program Data Sheet,"and "Example."

"Names and Functions of Display Parts"This sheet describes the names and functions of display parts, function of parameter display level, meaning ofparameter map symbol and numeric value, parameter display transition and setup operation, and display symbollist.

"Operation Map (SGL_PRO)"This sheet describes the operation parameter map, which can be used as an operation guide.

"Setup Map (SGL_PRO)"This sheet describes the setup parameter map, which can be used as an operation guide.

"List of Parameters (SGL_PRO)"This sheet describes the setting range and initial value of operation parameters and setup parameters. There is acolumn for user settings.

"Program Data Sheet"This sheet can be used for recording the setting value or creating the program pattern.

"Example"This sheet describes an example of simply program pattern.

Parameters in the sheets are displayed when the control mode is set to single loop control (CTLM=SGL) and theparameter display level is set to professional setting mode (LEVL=PRO). Some parameters are not displayedaccording to model and suffix codes. For details, refer to the User's Manual.

Operation and Program Parameters: Parameters for setting the functions necessary for the operationand Parameters for creating the program pattern.Setup Parameters: Parameters for setting the basic functions of the controller.

NoticeThe contents of this manual are subject to change without notice as a result of continuing improvements to theinstrument’s performance and functions.

Page 2 / 25

Page 3: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

UTAdvanced UP55ANames and Functions of Display Parts

UP55A Display Parts

No. in figure

(1)

(2)

(3)

(4)

(5)

(6)

(7)

(8)

(9)

(10)

(11)

(12)

(13)

Name

PV display(white or red)

Group display (patternnumber)(green)Symbol display (orange)

Data display (orange)

Bar-graph display (event,alarm)(orange)

Event indicator (orange)

Key navigation indicator(green)

Parameter display levelindicator(green)

Program monitor (green)

Status indicator (green andred)

Security indicator (red)

Displays a parameter setpoint and menu symbol.

Displays the event status and the segment position in the Operation Display. (Defaultvalues: Time event status, Alarm status)Displays control output value (OUT) and measured input value (PV).The data to be displayed can be set by the parameter.

Lit when the PV events occur.Event displays can be set by the parameter.

Lit or blinks when the Up/Down or Left/Right arrow key operation is possible.

Displays PV. Displays an error code if an error occurs.Displays the scrolling guide in the Menu Display and Parameter Setting Display when theguide display ON/OFF is set to ON.

Description

1 to 30 represent pattern numbers in the Operation Display.Displays a group number (1 to 8 or R) and terminal area (E1 to E4) in the ParameterSetting Display.Displays a parameter symbol.

Displays the setting conditions of the parameter display level function. Parameter display level EASY PRO Easy setting mode Lit Unlit Standard setting mode Unlit Unlit Professional setting mode Unlit Lit

Displays the status of increment, constancy, and decrement of the program setpoint. : Lit when a program setpoint is increasing. : Lit when a program setpoint is constant. : Lit when a program setpoint is decreasing.

Displays the operating conditions and control status. Display Description HLD Lit when in remote mode (HOLD). CAS Lit when in cascade mode (CAS). PRG Lit when in program operation mode (PRG). Lit while the Starting time of program operation (S.TM) is available. RST Lit when in reset mode (RST). MAN Lit when in manual mode (MAN). Blinks during auto-tuning.

Lit if a password is set. The setup parameter settings are locked.

Ladder operation indicator(green)

Loop 2 indicator (LP2 lamp)(green)

Lit while the ladder program operation is executed.

Lit when the control mode is Cascade control.In the Operation Display, the LP2 lamp is lit while the Loop-2 data is displayed on Setpointdisplay. In the Parameter Setting Display, the LP2 lamp indicates the loop of displayedmenu symbol or parameter symbol. The LP2 lamp is lit while the Loop-2 menu symbol orparameter symbol is displayed.

Page 3 / 25

Page 4: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

UP55A Key Parts

No. in figure

(1)

(2)

(3)

(4)

(5)

Name

DISPLAY key

Hold down the key for 3 seconds to move to the Operation Parameter Setting Display.Hold down the key and the Left arrow key simultaneously for 3 seconds to move to theSetup Parameter Setting Display.Press the key in the Parameter Setting Display to return to the Menu Display. Press the keyonce to cancel the parameter setting (setpoint is blinking).

SET/ENTER keyPress the key in the Menu Display to move to the Parameter Setting Display of the Menu.Press the key in the Parameter Setting Display to transfer to the parametersetting mode (setpoint is blinking), and the parameter can be changed. Press the keyduring parameter setting mode to register the setpoint.Up/Down/Left/Right arrow keysPress the Left/Right arrow keys in the Menu Display to switch the Displays.Press the Up/Down/Left/Right arrow keys in the Parameter Setting Display to switch theDisplays.Press the Up/Down arrow keys during parameter setting mode (setpoint is blinking) tochange a setpoint.Press the Left/Right arrow keys during parameter setting mode (setpoint is blinking) tomove between digits according to the parameter.

DescriptionUsed to switch the Operation Displays.Press the key in the Operation Display to switch the provided Operation Displays.Press the key in the Menu Display or Parameter Setting Display to return to the OperationDisplay.

PARAMETER key

SET/ENTER keyUp/Down/ Left/Right arrowkeys

Light-loader interface

RUN keyRST keyMODE keyPTN key

It is the communication interface to the adapter cable when setting and storing parametersvia PC. The LL50A Parameter Setting Software (sold separately) is required.

PTN key: Press the RUN key for 1 second while an operation display is shown starts thecontroller.RST key: Press the RST key for 1 second while an operation display is shown stops thecontroller.MODE key: Presents a display for switching between the HOLD, ADVANCE, PROG, RESET,LOCAL, REMOTE and AUTO/MAN. In order to change the operation mode, press theSET/ENTER key while the setpoint is blinking.PTN key: A program pattern number can be selected during the operation except theprogram pattern operation. (The program pattern number displayed on the Group displayblinks.) When the PTN key is pressed while the program pattern number is blinking, theblinking stops. Users can assign functions to the key using parameters.

Page 4 / 25

Page 5: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

Brief Description of Parameter Map

The control prevents unintentional change of the function.The parameter display level is just a function to hide the display so the set function works.

Changing of parameter display levelThe parameters to be displayed can be controlled by changing the setting value for setup parameter LEVL.

Setting value

EASY EASY Symbol Corresponding parameters are displayedin all modes.

STD Symbol Symbol

PRO PRO Symbol Symbol SymbolCorresponding parameters are displayed only in Professional setting mode.

Meaning of Parameter Symbol and Numeric ValueNumeric Value Symbol Symbol

↑ ↑ ↑

Group/Segment ↑ LP2: Program pattern-2 retransmission

  Parameter symbolGroup E1: indicates the parameter in E1-terminal area

E2: indicates the parameter in E2-terminal areaE3: indicates the parameter in E3-terminal areaE4: indicates the parameter in E4-terminal area1 to 8, R: indicate the group numbers

Display may be controlled according to the setting value of the setup parameter and operation status.

Parameter Display Transition and Setup OperationTo move to the Operation Parameter Setting Display

To move to the Setup Parameter Setting Display

To move to the Operation Display

<Operation for Setting>

Corresponding parameters are displayed only in Standard setting mode and Professional setting mode.Parameter display level indicators "EASY" and "PRO" are unlit in Standard setting mode.

If you cannot remember how to carry out an operation during setting, press the DISPLAY key once. This brings you to thedisplay (Operation Display) that appears at power-on.

The parameter display level is a function to control the parameters to be displayed. The factory setting isLEVL=STD.

Parameter Display Level

To select the parameter setting displayed as the initial value, press the Down arrow key to move to the next parameter.

To change and set the parameter setting, press the SET/ENTER key to start the setpoint blinking. The blinking state allowsyou to make changes (setting mode). Use the Up/Down/Left/Right arrow keys to change the setpoint. Press theSET/ENTER key to register the setting.

Press the keyfor 3 seconds.

+ Press the keyfor 3 seconds.

Page 5 / 25

Page 6: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

The following operating procedure describes an example of setting alarm setpoint (A1)

1. Hold down the PARAMETER key for 3 seconds in the Operation Display to call up the [MODE] Menu Display.

2. Press the Right arrow key to display the [AL] Menu Display.

3. Press the SET/ENTER key to display the [A1] Parameter Setting Display.

4. Press the SET/ENTER key to blink the setpoint.

5. Press the Up or Down arrow key to change the setpoint.

6. Press the SET/ENTER key to register the setpoint (the setpoint stops blinking).

This completes the setting procedure.

How to Cancel Parameter SettingTo cancel parameter setting when a parameter is being set (setpoint is blinking), press the PARAMETER key once

7. Press the PARAMETER key once to return to the Menu Display. Press the DISPLAY key once to return tothe Operation Display.

(Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Rightarrow keys to move between digits.)

Page 6 / 25

Page 7: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

How to Set Parameter Setpoint

Numeric Value Setting

Selection Data Setting

Time (minute.second) Setting

Page 7 / 25

Page 8: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

List of Display Symbols

Figure (common to all display area)

PV display (14 segments): Alphabet

Symbol display and Data display (11 segments): Alphabet

Group display (7 segments): Alphabet

PV display (14 segments): Symbol

The following shows the parameter symbols, menu symbols, alphanumeric of guide, and symbols which aredisplayed on the UP55A.

Page 8 / 25

Page 9: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

UTAdvanced UP55AOperation and Program Parameter Map * This parameter map is for the case that the control mode (CTLM) is set to single loop control (SGL). Some parameters are not displayed according to model and suffix codes. For details, refer to the User's Manual.

OperationMode

SELECTParameter

ProgramPatternSetting

LocalSetting

ProgramEditing

AlarmSetpointSetting

SP-relatedSetting

AlarmFunctionSetting

PV-relatedSetting

PID Setting TuningZone

ControlP

Parameter

(END) MODE CS PROG LOC EDIT AL SPS ALRM PVS PID TUNE ZONE PPAR

HOLD CS10 PTNO. LSP ALL.S A1 RMS EHY1 BS 1 P 8 P R P SC RP1 P01ADV CS11 LSP LP2 PTN.S A2 RFL EHY2 FL 1 I 8 I R I AT.TY RP2 P02

MODE CS12 L.PID USE.S A3 RT EHY3 END 1 D 8 D R D AT.OH RP3 P03A.M CS13 SEGNO. L.TY1 CPY.S A4 RBS EHY4 1 OH 8 OH R OH AT.OL RP4 P04

PTNO. CS14 L.EV1 CPY.D A5 SPT EHY5 1 OL 8 OL R OL AT.BS RP5 P05SST CS15 L.TY2 CLR.P A6 S.TM EHY6 1 MR 8 MR R MR GW RP6 P06

P.FWD CS16 SSP 1 TSP 99 TSP L.EV2 END A7 PNC EHY7 1 HYS 8 HYS R HYS GG RP7 P07AT CS17 SSP LP2 1 TSP LP2 99 TSP LP2 L.TY3 A8 END EHY8 1 HY.UP 8 HY.UP R HY.UP AR RHY P08

PID CS18 STC 1 TIME 99 TIME L.EV3 END AL1 1 HY.LO 8 HY.LO R HY.LO OPR RDV P09END CS19 WT.SW1 1 TM.RT 99 TM.RT L.TY4 AL2 1 DR ······ 8 DR ··· R DR OLMT END P10

END WZ.UP1 1 S.PID 99 S.PID L.EV4 AL3 1 Pc 8 Pc R Pc MPON ENDWZ.LO1 1 JC 99 JC L.TY5 AL4 1 Ic 8 Ic R Ic MPO1WT.TM1 1 PV.TY1 99 PV.TY1 L.EV5 AL5 1 Dc 8 Dc R Dc MPO2WT.SW2 1 PV.EV1 99 PV.EV1 L.TY6 AL6 1 OHc 8 OHc R OHc MPO3WZ.UP2 1 … 99 … L.EV6 AL7 1 OLc 8 OLc R OLc MPO4WZ.LO2 1 PV.TY8 ······ 99 PV.TY8 L.TY7 AL8 1 HYSc 8 HYSc R HYSc MPO5WT.TM2 1 PV.EV8 99 PV.EV8 L.EV7 VT1 1 DB 8 DB R DB END

… 1 TME1 99 TME1 L.TY8 VT2 1 PO 8 PO R POWT.SW5 1 T.ON1 99 T.ON1 L.EV8 VT3 1 POc 8 POc R POcWZ.UP5 1 T.OF1 99 T.OF1 END VT4 END END ENDWZ.LO5 1 … 99 … VT5WT.TM5 1 TME16 99 TME16 VT6R.CYCL 1 T.ON16 99 T.ON16 VT7R.STRT 1 T.OF16 99 T.OF16 VT8R.END END END HY1END HY2

HY3HY4HY5HY6HY7

Symbol Corresponding parameters are displayedin all modes. HY8 1 PYS1 2 PYS2 3 PYS3 4 PYS4 END (MODE)DYN1DYN2

Symbol DYN3 1 PYS 2 PYS 3 PYS 4 PYSDYN4 1 A1 2 A1 3 A1 4 A1DYN5 1 B1 2 B1 3 B1 4 B1

Symbol Corresponding parameters are displayed only in Professional setting mode. DYN6 1 A2 2 A2 3 A2 4 A2DYN7 1 B2 2 B2 3 B2 4 B2DYN8 1 A3 2 A3 3 A3 4 A3DYF1 1 B3 2 B3 3 B3 4 B3DYF2 1 A4 2 A4 3 A4 4 A4DYF3 1 B4 2 B4 3 B4 4 B4

Numeric Value Symbol Symbol DYF4 1 A5 2 A5 3 A5 4 A5↑ ↑ ↑ DYF5 1 B5 2 B5 3 B5 4 B5

Group/Segment ↑ LP2: Program pattern-2 retransmission DYF6 1 A6 2 A6 3 A6 4 A6  Parameter symbol DYF7 1 B6 2 B6 3 B6 4 B6

DYF8 1 A7 2 A7 3 A7 4 A7AMD 1 B7 2 B7 3 B7 4 B7

To move to the Setup Parameter Setting Display END 1 A8 2 A8 3 A8 4 A81 B8 2 B8 3 B8 4 B81 A9 2 A9 3 A9 4 A91 B9 2 B9 3 B9 4 B9

To move to the Operation Parameter Setting Display 1 A10 2 A10 3 A10 4 A101 B10 2 B10 3 B10 4 B101 A11 2 A11 3 A11 4 A111 B11 2 B11 3 B11 4 B111 PMD 2 PMD 3 PMD 4 PMD

END END END END

Display may be controlled according to the setting value of the setup parameter andoperation status.

10-segmentLinearizer-4

Setting

Corresponding parameters are displayed only in Standard setting mode and Professional settingmode. Parameter display level indicators "EASY" and "PRO" are unlit in Standard setting mode.

OperationDisplay

10-segmentLinearizer-1

Setting

10-segmentLinearizer-2

Setting

10-segmentLinearizer-3

Setting

The parameter in PROG is displayed in the PV Display.

1 to 30

1 to 990

Press the keyfor 3 seconds.

+ Press the keyfor 3 seconds.

If you cannot remember how to carry out an operation duringsetting, press the DISPLAY key once. This brings you to the display(Operation Display) that appears at power-on

CS menu is displayed when the SELECTparameter has been registered.

Parameters for settingthe functions necessaryfor the operation.

SET/ENTER key

Press the keyfor 3 seconds.

Page 9 / 25

Page 10: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

UTAdvanced UP55ASetup Parameter Map * This parameter map is for the case that the control mode (CTLM) is set to single loop control (SGL). Some parameters are not displayed according to model and suffix codes. For details, refer to the User's Manual.

PASS

ControlFunctionSetting

PV InputSetting

RSP Setting

AIN2 Aux.AnalogInput

Setting

AIN4 Aux.AnalogInput

Setting

InputRange/SP

LimiterSetting

OutputSetting

HeaterBreak Alarm

Setting

RS-485Communication Setting

(E3 terminalarea)

RS-485Communication Setting

(E4 terminalarea)

EthernetCommunication Setting

PROFIBUS-DP

Communication Setting

DeviceNetCommunication Setting

CC-LinkCommunication Setting

Key ActionSetting

DisplayFunctionSetting

SELECTDisplaySetting

(END) CTL PV E1 RSP E2 AIN2 E4 AIN4 MPV OUT HBA E3 R485 E4 R485 E3 ETHR E3 PROF E3 DNET E3 CC-L KEY DISP CSEL

CTLM IN E1 IN E2 IN E4 IN P.UNI OT HB1.S E3 PSL E4 PSL E3 HSR E3 BR E3 BR E3 BR RUN PCMD CS1CNT UNIT E1 UNIT E2 UNIT E4 UNIT P.DP CT HB2.S E3 BPS E4 BPS E3 BPS E3 ADR E3 ADR E3 ADR RST PCH CS2ALG RH E1 RH E2 RH E4 RH P.RH CTc HB1 E3 PRI E4 PRI E3 PRI E3 BPS E3 BPS E3 BPS PTN PCL CS3

ALNO. RL E1 RL E2 RL E4 RL P.RL V.AT HB2 E3 STP E4 STP E3 IP1 E3 FILE E3 FILE E3 FILE MODE PTSL CS4ZON SDP E1 SDP E2 SDP E4 SDP SPH V.RS CT1.T E3 DLN E4 DLN E3 IP2 E3 SCAN E3 SCAN E3 SCAN END BAR1 CS5

SEG.T SH E1 SH E2 SH E4 SH SPL V.L CT2.T E3 ADR E4 ADR E3 IP3 END END END BAR2 CS10TMU SL E1 SL E2 SL E4 SL END V.H HDN1 E3 RP.T E4 RP.T E3 IP4 BDV CS11

PT2.G BSL E1 BSL E2 BSL E4 BSL TR.T HDN2 END END E3 SM1 EV1 CS12SMP RJC E1 RJC E2 A.BS E4 A.BS V.MOD HDF1 E3 SM2 EV2 CS13END ERJC E1 ERJC E2 A.FL E4 A.FL RTS HDF2 E3 SM3 EV3 CS14

A.BS E1 RTD.S E2 A.SR E4 A.SR RTH HB1.D E3 SM4 EV4 CS15A.FL E1 A.BS E2 A.LC E4 A.LC RTL HB2.D E3 DG1 EV5 CS16A.SR E1 A.FL E2 DI6.D E4 DI6.D O1RS END E3 DG2 EV6 CS17A.LC E1 A.SR END END O1RH E3 DG3 EV7 CS18END E1 A.LC O1RL E3 DG4 EV8 CS19

E1 DI6.D O2RS E3 PRT PV.D ENDEND O2RH E3 IPAR SP.D

O2RL E3 1.IP1 STS.DOU.H E3 1.IP2 SPDOU.L E3 1.IP3 GUID

Symbol Corresponding parameters are displayedin all modes. OU2.H E3 1.IP4 HOMEOU2.L E3 2.IP1 ECORET.H E3 2.IP2 BRI

Symbol RET.L E3 2.IP3 B.PVWOU.A E3 2.IP4 B.PVR

OU2.A E3 ESW B.SPSymbol Corresponding parameters are displayed only in Professional setting mode. RET.A END B.BAR

END B.STSD.CYC

Numeric Value Symbol Symbol OP.JP↑ ↑ ↑ MLSD

Group/Segment ↑ LP2: Program pattern-2 retransmission END  Parameter symbol

Key LockSetting

Menu LockSetting

DI FunctionRegistration

DI FunctionNumbering

DI1-DI3ContactType

Setting

DI Setting(E1 terminal

area)

DI Setting(E2 terminal

area)

DI Setting(E3 terminal

area)

DI Setting(E4 terminal

area)

AL1-AL3Function

Registration

DO Setting(E1 terminal

area)

DO Setting(E2 terminal

area)

DO Setting(E3 terminal

area)

DO Setting(E4 terminal

area)I/O Display

SystemSetting

InitializationError andVersion

Confirmation

ParameterDisplayLevel

KLOC MLOC DI.SL DI.NU DI.D E1 DI.D E2 DI.D E3 DI.D E4 DI.D ALM E1 DO E2 DO E3 DO E4 DO I/O SYS INIT VER LVL END (CTL)

U.SP CTL PRG PT.B0 DI1.D E1 DI1.D E2 DI1.D E3 DI1.D E4 DI1.D AL1.S E1 DO1.S E2 DO1.S E3 DO1.S E4 DO1.S KEY R.MD U.DEF PA.ER LEVLU.SP LP2 PV RST PT.B1 DI2.D E1 DI2.D E2 DI2.D E3 DI2.D E4 DI2.D AL2.S E1 DO2.S E2 DO2.S E3 DO2.S E4 DO2.S X000 R.TM F.DEF OP.ER

U.TSP E1 RSP LOC PT.B2 DI3.D E1 DI3.D E2 DI3.D E3 DI3.D E4 DI3.D AL3.S E1 DO3.S E2 DO3.S E3 DO3.S E4 DO3.S E1 X100 EPO P.DEF AD1.EU.TSP LP2 E2 AIN2 REM PT.B3 END E1 DI4.D E2 DI4.D E3 DI4.D E4 DI4.D OR.S E1 DO4.S E2 DO4.S E3 DO4.S E4 DO4.S E2 X200 C.GRN END AD2.EU.TM E4 AIN4 P/R PT.B4 E1 DI5.D E2 DI5.D E3 DI5.D E4 DI5.D OR2.S E1 DO5.S E2 DO5.S E3 DO5.S E4 DO5.S E3 X300 FREQ PV1.EU.OUT MPV P/H PT.B5 END END END END AL1.D E1 DO1.D E2 DO1.D E3 DO1.D E4 DO1.D E4 X400 QSM PV2.E LP2

U.OUT LP2 MPV LP2 P/L PN.B0 AL2.D E1 DO2.D E2 DO2.D E3 DO2.D E4 DO2.D Y000 LANG LA.ERU.HCO OUT HOLD PN.B1 AL3.D E1 DO3.D E2 DO3.D E3 DO3.D E4 DO3.D E1 Y100 PASS MCUU.VP HBA ADV PN.B2 OR.D E1 DO4.D E2 DO4.D E3 DO4.D E4 DO4.D E2 Y200 SMEC DCUU.MV E3 R485 WAIT PN.B3 OR2.D E1 DO5.D E2 DO5.D E3 DO5.D E4 DO5.D E3 Y300 END E1 ECU1U.PID E4 R485 S.HLD MP.B0 END END END END END E4 Y400 E2 ECU2U.PID LP2 E3 ETHR A/M MP.B1 END E3 ECU3U.SEG E3 PROF AT MP.B2 E4 ECU4U.RCY E3 DNET LAT PT.BC PARAU.PTN E3 CC-L LCD PN.BC H.VERU.AL KEY PVRW MP.BC SER1U.AL LP2 DISP MG1 END SER2U.HC CSEL MG2 LVL E3 MAC1U.PV1 KLOC MG3 MODE E3 MAC2U.PV2 LP2 DI.SL MG4 CS E3 MAC3U.PV DI.NU END PROG END

U.RSP DI.D LOCU.AI2 E1 DI.D EDITU.AI4 E2 DI.D AL

COM.W E3 DI.D SPSDATA E4 DI.D ALRMRUN ALM PVSRST E1 DO PIDPTN E2 DO TUNE

MODE E3 DO ZONEEND E4 DO PPAR

I/O 1 PYS1SYS 2 PYS2INIT 3 PYS3VER 4 PYS4

END

Corresponding parameters are displayed only in Standard setting mode and Professional settingmode.Parameter display level indicators "EASY" and "PRO" are unlit in Standard setting mode

OperationDisplay

Displayed when a password has been

Parameters for settingthe basic functions of thecontroller

If you cannot remember how to carry out an operation duringsetting, press the DISPLAY key once. This brings you to the display(Operation Display) that appears at power-on.

SET/ENTER key

SET/ENTER key

+ Press the keyfor 3 seconds.

Page 10 / 25

Page 11: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

UTAdvanced UP55AList of ParametersOperation and Program ParametersOperation Mode

Menu Symbol Name Display level Setting range Initial value User setting

MODE HOLD Pause/cancel release of program operation EASYON: PauseOFF: Cancel release (Program operation restart)Display during program operation.

OFF

ADV Advance of segment EASYOFF: -Display during program operation.Set as “ADV = ON” to advance from the current segment to the next segment.

OFF

MODE Operation mode EASY

RESET: Stop of program operationPROG: Start of program operationLOCAL: Start of local-mode operationREM: Start of remote-mode operation

RESET

A.M AUTO/MAN switch EASY AUTO: Automatic modeMAN: Manual mode

MAN

PTNO. Program pattern number selection EASY 0: Not select program pattern1 to 30

0

SST Start-of-program segment number EASY1 to 99The setting value returns to “1” when the program operation (PROG) changesinto RESET, LOCAL, or REM.

1

P.FWD Fast-forwarding of program operation EASY

1: Normal, 2: Twice, 5: Five times, 10: Ten times, 20: Twenty times* Use this function when checking the program pattern setting. Only Segmenttime and Time event can be faster.* The operation returns to the normal speed after fast-forwarding.

1

AT Auto-tuning switch EASY

OFF: Disable1 to 8: Perform auto-tuning. Tuning result is stored in the specified numberedPID.R: Tuning result is stored in the PID for reference deviation.

OFF

PID PID number EASY The PID group number being selected is displayed. (display only)1 to 8, R: PID group for reference deviation

1

SELECT Parameter

Menu Symbol Name Display level Setting range Initial value User settingCS CS10 SELECT parameter 10 EASY -

CS11 SELECT parameter 11 EASY -CS12 SELECT parameter 12 EASY -CS13 SELECT parameter 13 EASY -CS14 SELECT parameter 14 EASY -CS15 SELECT parameter 15 EASY -CS16 SELECT parameter 16 EASY -CS17 SELECT parameter 17 EASY -CS18 SELECT parameter 18 EASY -CS19 SELECT parameter 19 EASY -

Program Pattern SettingProgram pattern-2

retransmission(PT2.G=ON)

Menu Symbol Name Display level Setting range Initial value User setting User setting

PROG>SEGNO.

SSP Starting target setpoint EASY 0.0 to 100.0% of PV input range (EU)(Setting range: P.RL to P.RH)

P.RLSeeSheet"ProgramData Sheet"

SeeSheet"ProgramData Sheet"

STC Start code EASY

SSP: Program operation begins with the starting target setpoint.RAMP: Ramp-prioritized PV startTIME: Time-prioritized PV startLSP: Local-mode startRSP: Remote-mode start* STC=TIME cannot be selected when the parameter SEG.T is TM.RT.

SSPSeeSheet"ProgramData Sheet"

WT.SW1 Wait function ON/OFF 1 STD OFF: DisableON: Enable

OFFSeeSheet"ProgramData Sheet"

WZ.UP1 Upper-side wait zone 1 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WZ.LO1 Lower-side wait zone 1 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WT.TM1 Wait time 1 STD

OFF: No function0.00 to 999.59 (“hour.minute” or “minute.second”)* Available only for the wait time at the segment switching.* Use the parameter TMU to set the time unit. (Common in the instrument.)

OFFSeeSheet"ProgramData Sheet"

WT.SW2 Wait function ON/OFF 2 STD Same as SW1. OFFSeeSheet"ProgramData Sheet"

WZ.UP2 Upper-side wait zone 2 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WZ.LO2 Lower-side wait zone 2 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WT.TM2 Wait time 2 STD Same as TM1. OFFSeeSheet"ProgramData Sheet"

WT.SW3 Wait function ON/OFF 3 STD Same as SW1. OFFSeeSheet"ProgramData Sheet"

WZ.UP3 Upper-side wait zone 3 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WZ.LO3 Lower-side wait zone 3 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WT.TM3 Wait time 3 STD Same as TM1. OFFSeeSheet"ProgramData Sheet"

WT.SW4 Wait function ON/OFF 4 STD Same as SW1. OFFSeeSheet"ProgramData Sheet"

WZ.UP4 Upper-side wait zone 4 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WZ.LO4 Lower-side wait zone 4 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WT.TM4 Wait time 4 STD Same as TM1. OFFSeeSheet"ProgramData Sheet"

WT.SW5 Wait function ON/OFF 5 STD Same as SW1. OFFSeeSheet"ProgramData Sheet"

WZ.UP5 Upper-side wait zone 5 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WZ.LO5 Lower-side wait zone 5 STD 0.5% of PV input rangeSeeSheet"ProgramData Sheet"

WT.TM5 Wait time 5 STD Same as TM1. OFFSeeSheet"ProgramData Sheet"

R.CYCL Number of repeat cycles STD 0 to 999, CONT (The controller indefinitely repeats the segment specified bythe R.STRT and R.END parameters.)

0SeeSheet"ProgramData Sheet"

R.STRT Repeat cycle start segment number STD 1SeeSheet"ProgramData Sheet"

R.END Repeat cycle end segment number STD 1SeeSheet"ProgramData Sheet"

When the program pattern-2 retransmission is selected (PT2.G=ON), the second loop is also displayed for the parameter SSP. (LP2 lamp is lit.)

* This parameter lists are for the case that the control mode (CTLM) is set to single loop control (SGL). Someparameters are not displayed according to model and suffix codes. For details, refer to the User's Manual.

Same as WZ.UP1 and WZ.LO1.

Same as WZ.UP1 and WZ.LO1.

1 to 991 ≤ R.STRT ≤ R.END ≤ 99

Setting range of a registered parameter.See User's Manual.

0.0 to 10.0% of PV input range (EU)

Same as WZ.UP1 and WZ.LO1.

Same as WZ.UP1 and WZ.LO1.

Page 11 / 25

Page 12: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

Program Pattern SettingProgram pattern-2

retransmission(PT2.G=ON)

Menu Symbol Name Display level Setting range Initial value User setting User setting

PROG>PTNO.

TSP Final target setpoint EASY 0.0 to 100.0% of PV input range (EU)(Setting range: P.RL to P.RH)

P.RLSeeSheet"ProgramData Sheet"

SeeSheet"ProgramData Sheet"

TIME Segment time setting EASY

-: Unregistered0.00 to 999.59 (“hour.minute” or “minute.second”)* Setting available for the parameter SEG.T=TIME.* Use the parameter TMU to set the time unit. (Common in the instrument.)* If the setting is 0.00, TSP changes in stepwise after one control period.

-SeeSheet"ProgramData Sheet"

TM.RT Segment ramp-rate setting EASY

-: UnregisteredRamp: 0.0 to 100.0% of PV input range span (EUS) / 1 hour or 1 minuteSoak: 0.00 to 999.59 (“hour.minute” or “minute.second”)* Setting available for the parameter SEG.T=TM.RT.* Use the parameter TMU to set the time unit. (Common in the instrument.)Per 1 hour: TMU=HH.MM,Per 1 minute: TMU=MM.SS* If it is set to 0.0% of the input range span, or the segment time 0.00, theprogram moves to the next segment after one control period.

-SeeSheet"ProgramData Sheet"

S.PID Segment PID number selection EASY 1 to 8* PID number can be set when the parameter “ZON = 0.”

1SeeSheet"ProgramData Sheet"

JC Junction code STD

CONT: Switching for continuationHOLD: Hold-on switching (the controller holds the end-of-segment setpointwhen the segment is completed, to perform control).LOCAL: Local-mode switching (the controller switches to a local setpoint whenthe segment is completed).REM: Remote-mode switching (the controller switches to a remote setpointwhen the segment is completed).W.SW1 to W.SW5: Wait during switching between segments.W.IV1 to W.IV5: Wait within a segment interval.W.SL1 to W.SL5: Segment switching (the controller switches to a local setpointwhen the segment is completed after release.) (5 groups)W.SR1 to W.SR5: Segment switching (the controller switches to a remotesetpoint when the segment is completed after release.) (5 groups)PLK.1 to PLK.30: Linked to patterns 1 to 30.INS.: Allows a segment to be added to the end of a specified segment.DEL.: Allows a specified segment to be deleted.

CONTSeeSheet"ProgramData Sheet"

PV.TY1~

PV.TY8 PV event-1 to -8 type STD

OFF: Disable(Energized)1: PV high limit,2: PV low limit,3: SP high limit,4: SP low limit,5: Deviation high limit,6: Deviation low limit,7: Deviation high and low limits,8: Deviation within high and low limits,9: Target SP high limit,10: Target SP low limit,11: Target SP deviation high limit,12: Target SP deviation low limit,13: Target SP deviation high and low limits,14: Target SP deviation within high and low limits,15: OUT high limit,16: OUT low limit,17: Cooling-side OUT high limit,18: Cooling-side OUT low limit* Add 100 for "de-energized". For example, when the PV high limit is de-energized, the setting is 101.

OFFSeeSheet"ProgramData Sheet"

PV.EV1~

PV.EV8 PV event-1 to -8 setpoint STD

Set a display value of setpoint of PV alarm, SP alarm, deviation alarm, oroutput alarm.-19999 to 30000 (Set a value within the input range.)Decimal point position depends on the input type.

0SeeSheet"ProgramData Sheet"

TME1~TME16 Start condition of time event 1 to 16 STD ON: Start ON stateOFF: Start OFF state

OFFSeeSheet"ProgramData Sheet"

T.ON1~T.ON16 On time of time event 1 to 16 STD -SeeSheet"ProgramData Sheet"

T.OF1~T.OF16 Off time of time event 1 to 16 STD -SeeSheet"ProgramData Sheet"

Local SettingProgram pattern-2

retransmission(PT2.G=ON)

Menu Symbol Name Display level Setting range Initial value User setting User setting

LOC LSP Local target setpoint EASY 0.0 to 100.0% of PV input range (EU)(Setting range: P.RL to P.RH)

P.RL

L.PID PID number selection for local mode operation EASY

Set a PID group number to use.1 to 8* Available only for the L.PID when ZON = 0 or 5.* If set to “Local PID selection,” local PID is selected irrespective of theoperation modes.

1

L.TY1 Local event-1 type STD

OFF: Disable(Energized)1: PV high limit,2: PV low limit,3: SP high limit,4: SP low limit,5: Deviation high limit,6: Deviation low limit,7: Deviation high and low limits,8: Deviation within high and low limits,9: Target SP high limit,10: Target SP low limit,11: Target SP deviation high limit,12: Target SP deviation low limit,13: Target SP deviation high and low limits,14: Target SP deviation within high and low limits,15: OUT high limit,16: OUT low limit,17: Cooling-side OUT high limit,18: Cooling-side OUT low limit* Add 100 for "de-energized". For example, when the PV high limit is de-energized, the setting is 101.

OFF

L.EV1 Local event-1 setpoint STD

Set a display value of setpoint of PV alarm, SP alarm, deviation alarm, oroutput alarm.-19999 to 30000 (Set a value within the input range.)Decimal point position depends on the input type

0

L.TY2 Local event-2 type STD Same as L.TY1 OFFL.EV2 Local event-2 setpoint STD Same as L.EV1 0L.TY3 Local event-3 type STD Same as L.TY1 OFFL.EV3 Local event-3 setpoint STD Same as L.EV1 0L.TY4 Local event-4 type STD Same as L.TY1 OFFL.EV4 Local event-4 setpoint STD Same as L.EV1 0L.TY5 Local event-5 type STD Same as L.TY1 OFFL.EV5 Local event-5 setpoint STD Same as L.EV1 0L.TY6 Local event-6 type STD Same as L.TY1 OFFL.EV6 Local event-6 setpoint STD Same as L.EV1 0L.TY7 Local event-7 type STD Same as L.TY1 OFFL.EV7 Local event-7 setpoint STD Same as L.EV1 0L.TY8 Local event-8 type STD Same as L.TY1 OFFL.EV8 Local event-8 setpoint STD Same as L.EV1 0

Program Editing

Menu Symbol Name Display level Setting range Initial value User settingEDIT ALL.S Number of remaining unused segments PRO 0 to 300 (Display only) 300

PTN.S Pattern number designation for comfirmingnumber of segments

PRO Specify the numbers of program pattern to display in parameter USE.S.1 to 30

0

USE.S Number of segments within a pattern PRO

Can be displayed when the parameter number specify in parameter PTN.S.(Display only)0: disable1 to 99

-

CPY.S Source-of-copying pattern number designation PRO Specify the number of the sourceof-copying program pattern. (1 to 30) 0

CPY.D Target-of-copying pattern number designation PRO Specify the target-of-copying program pattern. (1 to 30) 0

CLR.P Program pattern clearance PRO Specify the number of the program pattern to be cleared. (1 to 30) 0

Alarm Setpoint Setting

Menu Symbol Name Display level Setting range Initial value User settingAL A1 Alarm-1 setpoint EASY 0

A2 Alarm-2 setpoint EASY 0A3 Alarm-3 setpoint EASY 0A4 Alarm-4 setpoint EASY 0A5 Alarm-5 setpoint EASY 0A6 Alarm-6 setpoint EASY 0A7 Alarm-7 setpoint EASY 0A8 Alarm-8 setpoint EASY 0

These alarms work irrespective of the operation mode.Set a display value of setpoint of PV alarm, SP alarm, deviation alarm, outputalarm, or velocity alarm.-19999 to 30000 (Set a value within the input range.)Decimal point position depends on the input type.

-: Unregistered0.01 to 999.59 (“hour.minute” or “minute.second”)* Available only within the segment time.* OFF when the operation mode is changed to the mode except the programoperation.* Use the parameter TMU to set the time unit. (Common in the instrument.)

Page 12 / 25

Page 13: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

SP-related Setting

Menu Symbol Name Display level Setting range Initial value User setting

SPS RMS Remote input method STD RSP: Via remote (aux. analog) inputCOM: Via communication

RSP

RFL Remote input filter STD OFF, 1 to 120 s OFF

RT Remote input ratio STD 0.001 to 9.999 1.000

RBS Remote input bias STD -100.0 to 100.0% of PV input range span (EUS) 0.0 % of PV input rangespan

SPT SP tracking selection STDOFF, ONTracking is performed when the mode changes from Program or Remote toLocal. (The local setpoint keeps track of the remote setpoint.)

OFF

S.TM Starting time of program operation STD 0.00 to 999.59 (“hour.minute” or “minute.second” (common use of instrument)* Use the parameter TMU to set the time unit.

0.00

PNC Program pattern number clearance STD

OFF: Not cleared.ON: Cleared. (Set the program No. before restart program operation)* The controller resets (clears) the program pattern number on the operatingdisplay to “0” at the end of program operation.

OFF

Alarm Function Setting

Menu Symbol Name Display level Setting range Initial value User settingALRM EHY1 Event-1 hysteresis STD 0.5%

EHY2 Event-2 hysteresis STD 0.5%EHY3 Event-3 hysteresis STD 0.5%EHY4 Event-4 hysteresis STD 0.5%EHY5 Event-5 hysteresis STD 0.5%EHY6 Event-6 hysteresis STD 0.5%EHY7 Event-7 hysteresis STD 0.5%EHY8 Event-8 hysteresis STD 0.5%

AL1 Alarm-1 type EASY

PV high limit (01)Without Standby action (0)Energized (0)Latch action (0)

AL2 Alarm-2 type EASY

PV low limit (02)Without Standby action (0)Energized (0)Latch action (0)

AL3 Alarm-3 type EASY

PV high limit (01)Without Standby action (0)Energized (0)Latch action (0)

AL4 Alarm-4 type EASY

PV low limit (02)Without Standby action (0)Energized (0)Latch action (0)

AL5 Alarm-5 type EASY

PV high limit (01)Without Standby action (0)Energized (0)Latch action (0)

AL6 Alarm-6 type EASY

PV low limit (02)Without Standby action (0)Energized (0)Latch action (0)

AL7 Alarm-7 type EASY

PV high limit (01)Without Standby action (0)Energized (0)Latch action (0)

AL8 Alarm-8 type EASY

PV low limit (02)Without Standby action (0)Energized (0)Latch action (0)

VT1 PV velocity alarm time setpoint 1 EASY 1.00VT2 PV velocity alarm time setpoint 2 EASY 1.00VT3 PV velocity alarm time setpoint 3 EASY 1.00VT4 PV velocity alarm time setpoint 4 EASY 1.00VT5 PV velocity alarm time setpoint 5 EASY 1.00VT6 PV velocity alarm time setpoint 6 EASY 1.00VT7 PV velocity alarm time setpoint 7 EASY 1.00VT8 PV velocity alarm time setpoint 8 EASY 1.00HY1 Alarm-1 hysteresis EASY 10HY2 Alarm-2 hysteresis EASY 10HY3 Alarm-3 hysteresis EASY 10HY4 Alarm-4 hysteresis EASY 10HY5 Alarm-5 hysteresis EASY 10HY6 Alarm-6 hysteresis EASY 10HY7 Alarm-7 hysteresis EASY 10HY8 Alarm-8 hysteresis EASY 10DYN1 Alarm-1 On-delay timer STD 0.00DYN2 Alarm-2 On-delay timer STD 0.00DYN3 Alarm-3 On-delay timer STD 0.00DYN4 Alarm-4 On-delay timer STD 0.00DYN5 Alarm-5 On-delay timer STD 0.00DYN6 Alarm-6 On-delay timer STD 0.00DYN7 Alarm-7 On-delay timer STD 0.00DYN8 Alarm-8 On-delay timer STD 0.00DYF1 Alarm-1 Off-delay timer PRO 0.00DYF2 Alarm-2 Off-delay timer PRO 0.00DYF3 Alarm-3 Off-delay timer PRO 0.00DYF4 Alarm-4 Off-delay timer PRO 0.00DYF5 Alarm-5 Off-delay timer PRO 0.00DYF6 Alarm-6 Off-delay timer PRO 0.00DYF7 Alarm-7 Off-delay timer PRO 0.00DYF8 Alarm-8 Off-delay timer PRO 0.00

AMD Alarm mode STD0: Always active1: Not active in RESET mode2: Not active in RESET or MAN mode

0

PV-related Setting

Menu Symbol Name Display level Setting range Initial value User setting

PVS BS PV input bias EASY -100.0 to 100.0% of PV input range span (EUS) 0.0 % of PV input rangespan

FL PV input filter EASY OFF, 1 to 120 s OFF

The hysteresis setpoint of PV event or Local event is set to the parcentage of0.0 to 100.0%.The setting value (%) is for the PV input range span or output span.

These alarms work irrespective of the operation mode.Set a 5-digit value in the following order.[Alarm type: 2 digits (see below)] + [Without (0) or With (1) Stand-by action]+ [Energized (0) or De-energized (1)] + [Latch action (0/1/2/3/4)]

Alarm type: 2 digits00: Disable01: PV high limit02: PV low limit03: SP high limit04: SP low limit05: Deviation high limit06: Deviation low limit07: Deviation high and low limits08: Deviation within high and low limits09: Target SP high limit10: Target SP low limit11: Target SP deviation high limit12: Target SP deviation low limit13: Target SP deviation high and low limits14: Target SP deviation within high and low limits15: OUT high limit16: OUT low limit17: Cooling-side OUT high limit18: Cooling-side OUT low limit19: Analog input PV high limit20: Analog input PV low limit21: Analog input RSP high limit22: Analog input RSP low limit23: Analog input AIN2 high limit24: Analog input AIN2 low limit25: Analog input AIN4 high limit26: Analog input AIN4 low limit27: Feedback input high limit28: Feedback input low limit29: PV velocity30: Fault diagnosis31: FAIL

0.01 to 99.59 (minute.second)

Set a display value of setpoint of hysteresis.-19999 to 30000 (Set a value within the input range.)Decimal point position depends on the input type.When the decimal point position for the input type is set to "1", the initialvalue of the hysteresis is "1.0".

0.00 to 99.59 (minute.second)

0.00 to 99.59 (minute.second)

Page 13 / 25

Page 14: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

PID Setting Group 1(S.PID=1)

Group 2(S.PID=2)

Group 3(S.PID=3)

Group 4(S.PID=4)

Group 5(S.PID=5)

Group 6(S.PID=6)

Group 7(S.PID=7)

Group 8(S.PID=8)

Menu Symbol Name Display level Setting range Initial value User setting User setting User setting User setting User setting User setting User setting User setting

PID PProportional bandHeating-side proportional band (inHeating/cooling control)

EASY0.0 to 999.9%When 0.0% is set, it operates as 0.1%.Heating-side ON/OFF control applies when 0.0% in Heating/cooling control

5.0%

IIntegral timeHeating-side integral time (in Heating/coolingcontrol)

EASYOFF: Disable1 to 6000 s 240 s

DDerivative timeHeating-side derivative time (in Heating/coolingcontrol)

EASYOFF: Disable1 to 6000 s 60 s

OHControl output high limitHeating-side control output high limit (inHeating/cooling control)

EASY-4.9 to 105.0%, (OL<OH)In Heating/cooling control: 0.1 to 105.0% (OL<OH) 100.0%

OLControl output low limitHeating-side control output low limit (inHeating/cooling control)

EASY-5.0 to 104.9%, (OL<OH), SD:Tight shutIn Heating/cooling control: 0.0 to 104.9% (OL<OH) 0.0%

MR Manual reset EASYEnabled when integral time is OFF.The manual reset value equals the output value when PV = SP.-5.0 to 105.0%

50.0%

HYS

Hysteresis (in ON/OFF control, or Positionproportional control)Heating-side ON/OFF control hysteresis (inHeating/cooling control)

EASYIn ON/OFF control: 0.0 to 100.0% of PV input range span (EUS)In Heating/cooling control or Position proportional control: 0.0 to 100.0%

In ON/OFF control: 0.5 %of PV input range spanIn Heating/cooling controlor Position proportionalcontrol: 0.5 %

HY.UP Upper-side hysteresis (in ON/OFF control) EASY 0.5 % of PV input rangespan

HY.LO Lower-side hysteresis (in ON/OFF control) EASY 0.5 % of PV input rangespan

DR Direct/reverse action switch STD RVS: Reverse action, DIR: Direct action RVS

Pc Cooling-side proportional band EASY 0.0 to 999.9%(Cooling-side ON/OFF control applies when 0.0% in Heating/cooling control)

5.0%

Ic Cooling-side integral time EASY OFF: Disable1 to 6000 s

240 s

Dc Cooling-side derivative time EASY OFF: Disable1 to 6000 s

60 s

OHc Cooling-side control output high limit EASY 0.1 to 105.0%, (OLc<OHc) 100.0%OLc Cooling-side control output low limit EASY 0.0 to 104.9%, (OLc<OHc) 0.0%HYSc Cooling-side ON/OFF control hysteresis EASY 0.0 to 100.0% 0.5%

DB Output dead band (in Heating/cooling controlor Position proportional control)

EASY In Heating/cooling control: -100.0 to 50.0%In Position proportional control: 1.0 to 10.0%

3.0%

POPreset outputHeating-side preset output (in Heating/coolingcontrol)

EASY-5.0 to 105.0%In RESET mode, fixed control output can be generated. In Positionproportional control, Valve opening can be set.

0.0%

POc Cooling-side preset output EASY -5.0 to 105.0%In RESET mode, cooling-side fixed control output can be generated.

0.0%

Tuning

Menu Symbol Name Display level Setting range Initial value User setting

TUNE SC Super function EASY

OFF: Disable1: Overshoot suppressing function (normal mode)2: Hunting suppressing function (stable mode)Enables to answer the wider characteristic changes compared with responsemode.3: Hunting suppressing function (response mode)Enables quick follow-up and short converging time of PV for the changed SP.4: Overshoot suppressing function (strong suppressing mode)Note: Setpoints 2 and 3 must be used in PID control or PI control.Disabled in the following controls:1) ON/OFF control, 2) PD control, 3) P control, 4) Heating/cooling control.Do not use the function for the control processes with response such as flowor pressure control.

OFF

AT.TY Auto-tuning type STD 0: Normal1: Stability

0

AT.OH Output high limit in auto-tuning PRO 100.0%AT.OL Output low limit in auto-tuning PRO 0.0%

AT.BS SP bias in autotuning PRO -100.0 to 100.0% of PV input range span (EUS) 0.0% of PV input rangespan

GW Non-linear control gap width PRO OFF, 0.0%+1digit to 50.0% of PV input range span (EUS) OFFGG Non-linear control gain PRO 0.001 to 1.000 1.000

AR Anti-reset windup (excess integrationprevention)

STD AUTO, 50.0 to 200.0% AUTO

OPR Output velocity limiter STD OFF: Disable0.1 to 100.0%/s

OFF

OLMT Output limiter switch PRO OFF: Disable output limiter in MAN modeON: Enable output limiter in MAN mode

ON

MPON Manual preset output number selection STD

OFF: Hold the control output in AUTO mode (bumpless)1: Use manual preset output 1 (output bump)2: Use manual preset output 2 (output bump)3: Use manual preset output 3 (output bump)4: Use manual preset output 4 (output bump)5: Use manual preset output 5 (output bump)

OFF

MPO1 Manual preset output 1 STD 0.0%MPO2 Manual preset output 2 STD 0.0%MPO3 Manual preset output 3 STD 0.0%MPO4 Manual preset output 4 STD 0.0%MPO5 Manual preset output 5 STD 0.0%

Zone Control

Menu Symbol Name Display level Setting range Initial value User settingZONE RP1 Reference point 1 STD 100.0 % of PV input range

RP2 Reference point 2 STD 100.0 % of PV input rangeRP3 Reference point 3 STD 100.0 % of PV input rangeRP4 Reference point 4 STD 100.0 % of PV input rangeRP5 Reference point 5 STD 100.0 % of PV input rangeRP6 Reference point 6 STD 100.0 % of PV input rangeRP7 Reference point 7 STD 100.0 % of PV input range

RHY Zone PID switching hysteresis STD 0.0 to 10.0% of PV input range span (EUS)* Hysteresis can be set for switching at a reference point.

0.5 % of PV input rangespan

RDV Reference deviation STD

OFF: Disable0.0 + 1 digit to 100.0% of PV input range span (EUS)* Set a deviation from SP. The PID for reference deviation is used if there is alarger deviation than the preset reference deviation.

OFF

P Parameter

Menu Symbol Name Display level Setting range Initial value User settingPPAR P01 P01 Parameter STD 0

P02 P02 Parameter STD 0P03 P03 Parameter STD 0P04 P04 Parameter STD 0P05 P05 Parameter STD 0P06 P06 Parameter STD 0P07 P07 Parameter STD 0P08 P08 Parameter STD 0P09 P09 Parameter STD 0P10 P10 Parameter STD 0

0.0 to 100.0% of PV input range span (EUS)

-5.0 to 105.0% (Disabled in Heating/cooling control)

-5.0 to 105.0%* However, output is limited to the output high limit and low limit.

0.0 to 100.0% of PV input range (EU)(RP1 ≤ RP2 ≤ RP3 ≤ RP4 ≤ RP5 ≤ RP6 ≤ RP7)* Set reference points at which switching is carried out between groups of PIDconstants according to the given temperature zone.

-19999 to 30000 (Set a decimal point position using LL50A Parameter SettingSoftware.)

Page 14 / 25

Page 15: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

10-segment Linearizer-1 Setting

Menu Symbol Name Display level Setting range Initial value User setting

PYS1 PYS 10-segment linearizer-1 selection STD

OFF: DisablePV: PV analog inputRSP: RSP analog inputAIN2: AIN2 analog inputAIN4: AIN4 analog inputPVIN: PV inputOUT: OUT analog outputOUT2: OUT2 analog outputRET: RET analog output

PV(CTLM: SGL)

A1 10-segment linearizer-1 input 1 STD 0.0%B1 10-segment linearizer-1 output 1 STD 0.0%A2 10-segment linearizer-1 input 2 STD 0.0%B2 10-segment linearizer-1 output 2 STD 0.0%A3 10-segment linearizer-1 input 3 STD 0.0%B3 10-segment linearizer-1 output 3 STD 0.0%A4 10-segment linearizer-1 input 4 STD 0.0%B4 10-segment linearizer-1 output 4 STD 0.0%A5 10-segment linearizer-1 input 5 STD 0.0%B5 10-segment linearizer-1 output 5 STD 0.0%A6 10-segment linearizer-1 input 6 STD 0.0%B6 10-segment linearizer-1 output 6 STD 0.0%A7 10-segment linearizer-1 input 7 STD 0.0%B7 10-segment linearizer-1 output 7 STD 0.0%A8 10-segment linearizer-1 input 8 STD 0.0%B8 10-segment linearizer-1 output 8 STD 0.0%A9 10-segment linearizer-1 input 9 STD 0.0%B9 10-segment linearizer-1 output 9 STD 0.0%A10 10-segment linearizer-1 input 10 STD 0.0%B10 10-segment linearizer-1 output 10 STD 0.0%A11 10-segment linearizer-1 input 11 STD 0.0%B11 10-segment linearizer-1 output 11 STD 0.0%

PMD 10-segment linearizer mode STD 0: 10-segment linearizer bias1: 10-segment linearizer approximation

0

10-segment Linearizer-2 Setting

Menu Symbol Name Display level Setting range Initial value User setting

PYS2 PYS 10-segment linearizer-2 selection STD

OFF: DisablePV: PV analog inputRSP: RSP analog inputAIN2: AIN2 analog inputAIN4: AIN4 analog inputPVIN: PV inputOUT: OUT analog outputOUT2: OUT2 analog outputRET: RET analog output

OFF

A1 10-segment linearizer-2 input 1 STD 0.0%B1 10-segment linearizer-2 output 1 STD 0.0%A2 10-segment linearizer-2 input 2 STD 0.0%B2 10-segment linearizer-2 output 2 STD 0.0%A3 10-segment linearizer-2 input 3 STD 0.0%B3 10-segment linearizer-2 output 3 STD 0.0%A4 10-segment linearizer-2 input 4 STD 0.0%B4 10-segment linearizer-2 output 4 STD 0.0%A5 10-segment linearizer-2 input 5 STD 0.0%B5 10-segment linearizer-2 output 5 STD 0.0%A6 10-segment linearizer-2 input 6 STD 0.0%B6 10-segment linearizer-2 output 6 STD 0.0%A7 10-segment linearizer-2 input 7 STD 0.0%B7 10-segment linearizer-2 output 7 STD 0.0%A8 10-segment linearizer-2 input 8 STD 0.0%B8 10-segment linearizer-2 output 8 STD 0.0%A9 10-segment linearizer-2 input 9 STD 0.0%B9 10-segment linearizer-2 output 9 STD 0.0%A10 10-segment linearizer-2 input 10 STD 0.0%B10 10-segment linearizer-2 output 10 STD 0.0%A11 10-segment linearizer-2 input 11 STD 0.0%B11 10-segment linearizer-2 output 11 STD 0.0%

PMD 10-segment linearizer-2 mode STD 0: 10-segment linearizer bias1: 10-segment linearizer approximation

0

10-segment Linearizer-3 Setting

Menu Symbol Name Display level Setting range Initial value User setting

PYS3 PYS 10-segment linearizer-3 selection PRO

OFF: DisablePV: PV analog inputRSP: RSP analog inputAIN2: AIN2 analog inputAIN4: AIN4 analog inputPVIN: PV inputOUT: OUT analog outputOUT2: OUT2 analog outputRET: RET analog output

OFF

A1 10-segment linearizer-3 input 1 PRO 0.0%B1 10-segment linearizer-3 output 1 PRO 0.0%A2 10-segment linearizer-3 input 2 PRO 0.0%B2 10-segment linearizer-3 output 2 PRO 0.0%A3 10-segment linearizer-3 input 3 PRO 0.0%B3 10-segment linearizer-3 output 3 PRO 0.0%A4 10-segment linearizer-3 input 4 PRO 0.0%B4 10-segment linearizer-3 output 4 PRO 0.0%A5 10-segment linearizer-3 input 5 PRO 0.0%B5 10-segment linearizer-3 output 5 PRO 0.0%A6 10-segment linearizer-3 input 6 PRO 0.0%B6 10-segment linearizer-3 output 6 PRO 0.0%A7 10-segment linearizer-3 input 7 PRO 0.0%B7 10-segment linearizer-3 output 7 PRO 0.0%A8 10-segment linearizer-3 input 8 PRO 0.0%B8 10-segment linearizer-3 output 8 PRO 0.0%A9 10-segment linearizer-3 input 9 PRO 0.0%B9 10-segment linearizer-3 output 9 PRO 0.0%A10 10-segment linearizer-3 input 10 PRO 0.0%B10 10-segment linearizer-3 output 10 PRO 0.0%A11 10-segment linearizer-3 input 11 PRO 0.0%B11 10-segment linearizer-3 output 11 PRO 0.0%

PMD 10-segment linearizer-3 mode PRO 0: 10-segment linearizer bias1: 10-segment linearizer approximation

0

10-segment Linearizer-4 Setting

Menu Symbol Name Display level Setting range Initial value User setting

PYS4 PYS 10-segment linearizer-4 selection PRO

OFF: DisablePV: PV analog inputRSP: RSP analog inputAIN2: AIN2 analog inputAIN4: AIN4 analog inputPVIN: PV inputOUT: OUT analog outputOUT2: OUT2 analog outputRET: RET analog output

OFF

A1 10-segment linearizer-4 input 1 PRO 0.0%B1 10-segment linearizer-4 output 1 PRO 0.0%A2 10-segment linearizer-4 input 2 PRO 0.0%B2 10-segment linearizer-4 output 2 PRO 0.0%A3 10-segment linearizer-4 input 3 PRO 0.0%B3 10-segment linearizer-4 output 3 PRO 0.0%A4 10-segment linearizer-4 input 4 PRO 0.0%B4 10-segment linearizer-4 output 4 PRO 0.0%A5 10-segment linearizer-4 input 5 PRO 0.0%B5 10-segment linearizer-4 output 5 PRO 0.0%A6 10-segment linearizer-4 input 6 PRO 0.0%B6 10-segment linearizer-4 output 6 PRO 0.0%A7 10-segment linearizer-4 input 7 PRO 0.0%B7 10-segment linearizer-4 output 7 PRO 0.0%A8 10-segment linearizer-4 input 8 PRO 0.0%B8 10-segment linearizer-4 output 8 PRO 0.0%A9 10-segment linearizer-4 input 9 PRO 0.0%B9 10-segment linearizer-4 output 9 PRO 0.0%A10 10-segment linearizer-4 input 10 PRO 0.0%B10 10-segment linearizer-4 output 10 PRO 0.0%A11 10-segment linearizer-4 input 11 PRO 0.0%B11 10-segment linearizer-4 output 11 PRO 0.0%

PMD 10-segment linearizer-4 mode PRO 0: 10-segment linearizer bias1: 10-segment linearizer approximation

0

10-segment linearizer input-66.7 to 105.0% of input range (EU)Output linearizer: -5.0 to 105.0%

10-segment linearizer output10-segment linearizer bias: -66.7 to 105.0% of input range span (EUS)10-segment linearizer approximation: -66.7 to 105.0% of input range (EU)Output linearizer: -5.0 to 105.0%

10-segment linearizer input-66.7 to 105.0% of input range (EU)Output linearizer: -5.0 to 105.0%

10-segment linearizer output10-segment linearizer bias: -66.7 to 105.0% of input range span (EUS)10-segment linearizer approximation: -66.7 to 105.0% of input range (EU)Output linearizer: -5.0 to 105.0%

10-segment linearizer input-66.7 to 105.0% of input range (EU)Output linearizer: -5.0 to 105.0%

10-segment linearizer output10-segment linearizer bias: -66.7 to 105.0% of input range span (EUS)10-segment linearizer approximation: -66.7 to 105.0% of input range (EU)Output linearizer: -5.0 to 105.0%

10-segment linearizer input-66.7 to 105.0% of input range (EU)Output linearizer: -5.0 to 105.0%

10-segment linearizer output10-segment linearizer bias: -66.7 to 105.0% of input range span (EUS)10-segment linearizer approximation: -66.7 to 105.0% of input range (EU)Output linearizer: -5.0 to 105.0%

Page 15 / 25

Page 16: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

Setup ParametersControl Function Setting

Menu Symbol Name Display level Setting range Initial value User setting

CTL CTLM Control mode STD

SGL: Single-loop controlCAS1: Cascade primary-loop controlCAS: Cascade controlPVSW: Loop control with PV switchingPVSEL: Loop control with PV autoselector* When using the ladder program, the control mode cannot be changed.

SGL

CNT Control type EASY

PID: PID controlONOF: ON/OFF control (1 point of hysteresis)ONOF2: ON/OFF control (2 points of hysteresis)H/C: Heating/cooling control

Standard type: PIDHeating/cooling type: H/C

ALG PID control mode PRO 0: Standard PID control mode1: Fixed-point control mode

0

ALNO. Number of alarms PRO 1 to 8 4

ZON Zone PID selection STD

0: Segment PID selection1: Zone PID selection (selection by PV)2: Zone PID selection (selection by target SP)4: Zone PID selection (selection by SP)5: Local PID selection* If set to “Segment PID selection,” allows PID constants to be selected foreach segments.* If set to “Zone PID selection,” automatically selects PID constants accordingto the range set in the Reference point.* If set to “Local PID selection,” local PID is selected irrespective of theoperation modes.

1

SEG.T Segment setting method EASYTIME: Segment time settingTM.RT: Segment ramp-rate settingNote: A change of setting deletes a program pattern.

TIME

TMU Program time unit EASY HH.MM: hour.minuteMM.SS: minute.second

HH.MM

PT2.G Program pattern-2 retransmission STD

OFF: Not used.ON: used.* The controller can serve as a program pattern generator.* Retransmission output types (RTS, O1RS, or O2RS) need to be set to SP2.

OFF

SMP Input sampling period (control period) STD 100: 100 ms200: 200 ms

200

PV Input Setting

Menu Symbol Name Display level Setting range Initial value User setting

PV IN PV input type EASY

OFF: DisableK1: -270.0 to 1370.0 (ºC) / -450.0 to 2500.0 (ºF)K2: -270.0 to 1000.0 (ºC) / -450.0 to 2300.0 (ºF)K3: -200.0 to 500.0 (ºC) / -200.0 to 1000.0 (ºF)J: -200.0 to 1200.0 (ºC) / -300.0 to 2300.0 (ºF)T1: -270.0 to 400.0 (ºC) / -450.0 to 750.0 (ºF)T2: 0.0 to 400.0 (ºC) / -200.0 to 750.0 (ºF)B: 0.0 to 1800.0 (ºC) / 32 to 3300 (ºF)S: 0.0 to 1700.0 (ºC) / 32 to 3100 (ºF)R: 0.0 to 1700.0 (ºC) / 32 to 3100 (ºF)N: -200.0 to 1300.0 (ºC) / -300.0 to 2400.0 (ºF)E: -270.0 to 1000.0 (ºC) / -450.0 to 1800.0 (ºF)L: -200.0 to 900.0 (ºC) / -300.0 to 1600.0 (ºF)U1: -200.0 to 400.0 (ºC) / -300.0 to 750.0 (ºF)U2: 0.0 to 400.0 (ºC) / -200.0 to 1000.0 (ºF)W: 0.0 to 2300.0 (ºC) / 32 to 4200 (ºF)PL2: 0.0 to 1390.0 (ºC) / 32.0 to 2500.0 (ºF)P2040: 0.0 to 1900.0 (ºC) / 32 to 3400 (ºF)WRE: 0.0 to 2000.0 (ºC) / 32 to 3600 (ºF)JPT1: -200.0 to 500.0 (ºC) / -300.0 to 1000.0 (ºF)JPT2: -150.00 to 150.00 (ºC) / -200.0 to 300.0 (ºF)PT1: -200.0 to 850.0 (ºC) / -300.0 to 1560.0 (ºF)PT2: -200.0 to 500.0 (ºC) / -300.0 to 1000.0 (ºF)PT3: -150.00 to 150.00 (ºC) / -200.0 to 300.0 (ºF)0.4-2V: 0.400 to 2.000 V1-5V: 1.000 to 5.000 V4-20: 4.00 to 20.00 mA0-2V: 0.000 to 2.000 V0-10V: 0.00 to 10.00 V0-20: 0.00 to 20.00 mA-1020: -10.00 to 20.00 mV0-100: 0.0 to 100.0 mVNote: W: W-5% Re/W-26% Re (Hoskins Mfg. Co.), ASTM E988 WRE: W97Re3-W75Re25

OFF

UNIT PV input unit EASY

-: No unitC: Degree Celsius-: No unit--: No unit---: No unitF: Degree Fahrenheit

C

RH Maximum value of PV input range EASY Depends on the input type

RL Minimum value of PV input range EASY Depends on the input type

SDP PV input scale decimal point position EASY

0: No decimal place1: One decimal place2: Two decimal places3: Three decimal places4: Four decimal places

Depends on the input type

SH Maximum value of PV input scale EASY Depends on the input typeSL Minimum value of PV input scale EASY Depends on the input type

BSL PV input burnout action STDOFF: DisableUP: UpscaleDOWN: Downscale

Depends on the input type

RJC PV input reference junction compensation PRO OFF: RJC OFFON: RJC ON

ON

ERJC PV input external RJC setpoint PRO -10.0 to 60.0 (°C) 0.0

A.BS PV analog input bias STD -100.0 to 100.0% of PV input range span (EUS) 0.0 % of PV input rangespan

A.FL PV analog input filter STD OFF, 1 to 120 s OFF

A.SR PV analog input square root extraction PROOFF: No square root extraction.1: Compute the square root. (The slope equals “1.”)2: Compute the square root. (The slope equals “0.”)

OFF

A.LC PV analog input low signal cutoff PRO 0.0 to 5.0% 1.0%

RSP Setting

Menu Symbol Name Display level Setting range Initial value User setting

RSP IN RSP remote input type EASY

0.4-2V: 0.400 to 2.000 V1-5V: 1.000 to 5.000 V0-2V: 0.000 to 2.000 V0-10V: 0.00 to 10.00 V0-125: 0.000 to 1.250 VFor option /DR, RSP remote input type is same as PV input type.

1-5V

UNIT RSP remote input unit EASY

-: No unitC: Degree Celsius-: No unit--: No unit---: No unitF: Degree Fahrenheit

C

RH Maximum value of RSP remote input range EASY Depends on the input type

RL Minimum value of RSP remote input range EASY Depends on the input type

SDP RSP remote input scale decimal point position EASY

0: No decimal place1: One decimal place2: Two decimal places3: Three decimal places4: Four decimal places

Depends on the input type

SH Maximum value of RSP remote input scale EASY Depends on the input typeSL Minimum value of RSP remote input scale EASY Depends on the input type

BSL RSP remote input burnout action STDOFF: DisableUP: UpscaleDOWN: Downscale

Depends on the input type

RJC RSP remote input reference junctioncompensation (for /DR option)

PRO OFF: RJC OFFON: RJC ON

ON

ERJC RSP remote input external RJC setpoint (for/DR option)

PRO -10.0 to 60.0 (°C) 0.0

RTD.S RTD wiring system STD 3-W: 3-wire system, 4-W: 4-wire system 3-W

A.BS RSP aux. analog input bias PRO -100.0 to 100.0% of RSP input range span (EUS) 0.0 % of RSP input rangespan

A.FL RSP aux. analog input filter PRO OFF, 1 to 120 s OFF

A.SR RSP aux. analog input square root extraction PROOFF: No square root extraction.1: Compute the square root. (The slope equals “1.”)2: Compute the square root. (The slope equals “0.”)

OFF

A.LC RSP aux. analog input low signal cutoff PRO 0.0 to 5.0% 1.0%

DI6.D DI16 contact type PRO 0: The assigned function is enabled when the contact is closed.1: The assigned function is enabled when the contact is opened.

0

When each parameter is displayed, the terminal area (E1) is displayed on Group display.

-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000

Depends on the input type.- For temperature input -Set the temperature range that is actually controlled. (RL<RH)- For voltage / current input -Set the range of a voltage / current signal that is applied.The scale across which the voltage / current signal is actually controlled shouldbe set using the maximum value of input scale (SH) and minimum value ofinput scale (SL).(Input is always 0% when RL = RH.)

Depends on the input type.- For temperature input (with /DR option) -Set the temperature range that is actually controlled. (RL<RH)- For voltage / current (with /DR option) input -Set the range of a voltage / current signal that is applied.The scale across which the voltage / current signal is actually controlled shouldbe set using the maximum value of input scale (SH) and minimum value ofinput scale (SL).(Input is always 0% when RL = RH.)

-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000

Page 16 / 25

Page 17: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

AIN2 Aux. Analog Input Setting

Menu Symbol Name Display level Setting range Initial value User setting

AIN2 IN AIN2 aux. analog input type EASY

0.4-2V: 0.400 to 2.000 V1-5V: 1.000 to 5.000 V0-2V: 0.000 to 2.000 V0-10V: 0.00 to 10.00 V0-125: 0.000 to 1.250 V

1-5V

UNIT AIN2 aux. analog input unit EASY

-: No unitC: Degree Celsius-: No unit--: No unit---: No unitF: Degree Fahrenheit

C

RHMaximum value of AIN2 aux. analog inputrange EASY Depends on the input type

RL Minimum value of AIN2 aux. analog input range EASY Depends on the input type

SDPAIN2 aux. analog input scale decimal pointposition EASY

0: No decimal place1: One decimal place2: Two decimal places3: Three decimal places4: Four decimal places

Depends on the input type

SH Maximum value of AIN2 aux. analog input scale EASY Depends on the input typeSL Minimum value of AIN2 aux. analog input scale EASY Depends on the input type

BSL AIN2 aux. analog input burnout action STDOFF: DisableUP: UpscaleDOWN: Downscale

Depends on the input type

A.BS AIN2 aux. analog input bias PRO -100.0 to 100.0% of AIN2 input range span (EUS) 0.0 % of AIN2 input rangespan

A.FL AIN2 aux. analog input filter PRO OFF, 1 to 120 s OFF

A.SR AIN2 aux. analog input square root extraction PROOFF: No square root extraction.1: Compute the square root. (The slope equals “1.”)2: Compute the square root. (The slope equals “0.”)

OFF

A.LC AIN2 aux. analog input low signal cutoff PRO 0.0 to 5.0% 1.0%

DI6.D DI26 contact type PRO 0: The assigned function is enabled when the contact is closed.1: The assigned function is enabled when the contact is opened.

0

When each parameter is displayed, the terminal area (E2) is displayed on Group display.

AIN4 Aux. Analog Input Setting

Menu Symbol Name Display level Setting range Initial value User setting

AIN4 IN AIN4 aux. analog input type EASY

0.4-2V: 0.400 to 2.000 V1-5V: 1.000 to 5.000 V0-2V: 0.000 to 2.000 V0-10V: 0.00 to 10.00 V0-125: 0.000 to 1.250 V

1-5V

UNIT AIN4 aux. analog input unit EASY

-: No unitC: Degree Celsius-: No unit--: No unit---: No unitF: Degree Fahrenheit

C

RHMaximum value of AIN4 aux. analog inputrange EASY Depends on the input type

RL Minimum value of AIN4 aux. analog input range EASY Depends on the input type

SDPAIN4 aux. analog input scale decimal pointposition EASY

0: No decimal place1: One decimal place2: Two decimal places3: Three decimal places4: Four decimal places

Depends on the input type

SH Maximum value of AIN4 aux. analog input scale EASY Depends on the input typeSL Minimum value of AIN4 aux. analog input scale EASY Depends on the input type

BSL AIN4 aux. analog input burnout action STDOFF: DisableUP: UpscaleDOWN: Downscale

Depends on the input type

A.BS AIN4 aux. analog input bias PRO -100.0 to 100.0% of AIN4 input range span (EUS) 0.0 % of AIN4 input rangespan

A.FL AIN4 aux. analog input filter PRO OFF, 1 to 120 s OFF

A.SR AIN4 aux. analog input square root extraction PROOFF: No square root extraction.1: Compute the square root. (The slope equals “1.”)2: Compute the square root. (The slope equals “0.”)

OFF

A.LC AIN4 aux. analog input low signal cutoff PRO 0.0 to 5.0% 1.0%

DI6.D DI46 contact type PRO 0: The assigned function is enabled when the contact is closed.1: The assigned function is enabled when the contact is opened.

0

When each parameter is displayed, the terminal area (E4) is displayed on Group display.

Input Range/SP Limiter Setting

Menu Symbol Name Display level Setting range Initial value User setting

MPV P.UNI Control PV input unit STD

-: No unitC: Degree Celsius-: No unit--: No unit---: No unitF: Degree Fahrenheit

Same as PV input unit

P.DP Control PV input decimal point position STD

0: No decimal place1: One decimal place2: Two decimal places3: Three decimal places4: Four decimal places

Depends on the input type

P.RH Maximum value of control PV input range STD Depends on the input typeP.RL Minimum value of control PV input range STD Depends on the input type

SPH SP high limit STD 100.0 % of PV input range

SPL SP low limit STD 0.0 % of PV input range

Depends on the input type.Set the range of a voltage signal that is applied.The scale across which the voltage signal is actually controlled should be setusing the maximum value of input scale (SH) and minimum value of inputscale (SL).(Input is always 0% when RL = RH.)

-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000

Depends on the input type.Set the range of a voltage signal that is applied.The scale across which the voltage signal is actually controlled should be setusing the maximum value of input scale (SH) and minimum value of inputscale (SL).(Input is always 0% when RL = RH.)

-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000

-19999 to 30000, (P.RL<P.RH), | P.RH - P.RL | ≤ 30000

0.0 to 100.0% of PV input range (EU), (SPL<SPH)Place limits on the program setpoints or the local setpoints when the controlleris in program operation.* Places the limit on the program setpoint, local setpoint, or remote setpointduring program operation.* When LP2 lamp is on, SPH and SPL limit the program setpoint for programpattern 2 retransmission.

Page 17 / 25

Page 18: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

Output Setting

Menu Symbol Name Display level Setting range Initial value User setting

OUT OT Output type selection EASY

Control output or Heating-side control output (Lower two digits)00: OFF01: OUT terminals (voltage pulse)02: OUT terminals (current)03: OUT terminals (relay/triac)04: OUT2 terminals (voltage pulse)05: OUT2 terminals (current)06: OUT2 terminals (relay/triac)Cooling-side control output (Upper two digits)00: OFF01: OUT terminals (voltage pulse)02: OUT terminals (current)03: OUT terminals (relay/triac)04: OUT2 terminals (voltage pulse)05: OUT2 terminals (current)06: OUT2 terminals (relay/triac)

Standard type: 00.03Heating/cooling type: 06.03

CTControl output cycle timeHeating-side control output cycle time (inHeating/cooling control)

EASY 30.0 s

CTc Cooling-side control output cycle time EASY 30.0 s

V.AT Automatic valve position adjustment EASY OFF: Stop automatic adjustmentON: Start automatic adjustment

OFF

V.RS Valve position setting reset EASY Setting V.RS to ON resets the valve adjustment settings and causes theindication “V.RS” to blink.

OFF

V.L Fully-closed valve position setting EASYPressing the SET/ENTER key with valve position set to the fullyclosed positionby Down arrow key causes the adjusted value to be stored. When V.Ladjustment is complete, V.L stops blinking.

-

V.H Fully-open valve position setting EASYPressing the SET/ENTER key with valve position set to the fullyopened positionby Up arrow key causes the adjusted value to be stored. When V.H adjustmentis complete, V.H stops blinking.

-

TR.T Valve traveling time STD 5 to 300 s 60 s

V.MOD Valve adjusting mode STD

0: Valve position feedback type1: Valve position feedback type(moves to the estimating type if a feedback input error or break occurs.)2: Valve position estimating type

0

RTS Retransmission output type of RET EASY

OFF: DisablePV1: PVSP1: SPOUT1: OUT (Valve opening: 0 to 100 % in Position proportional control)LPS: 15 V DC loop power supplyPV2: Loop-2 PVSP2: Loop-2 SPOUT2: Loop-2 OUTTSP1: Target SPHOUT1: Heating-side OUTCOUT1: Cooling-side OUTMV1: Position proportional output internal computed value)TSP2: Loop-2 target SPHOUT2: Loop-2 heating-side OUTCOUT2: Loop-2 cooling-side OUTMV2: Loop-2 position proportional output (internal computed value)PV: PV terminals analog inputRSP: RSP terminals analog inputAIN2: AIN2 terminals analog inputAIN4: AIN4 terminals analog input

Loop-2 setting values are unavailable in Single-loop control.

PV1

RTH Maximum value of retransmission output scaleof RET

STD 100 % of PV input range

RTL Minimum value of retransmission output scaleof RET

STD 0 % of PV input range

O1RS Retransmission output type of OUT currentoutput

STD Same as RTS OFF

O1RH Maximum value of retransmission output scaleof OUT current output

STD -

O1RL Minimum value of retransmission output scaleof OUT current output

STD -

O2RS Retransmission output type of OUT2 currentoutput

STD Same as RTS OFF

O2RH Maximum value of retransmission output scaleof OUT2 current output

STD -

O2RL Minimum value of retransmission output scaleof OUT2 current output

STD -

OU.H 100% segmental point of OUT current output PRO 100.0%OU.L 0% segmental point of OUT current output PRO 0.0%OU2.H 100% segmental point of OUT2 current output PRO 100.0%OU2.L 0% segmental point of OUT2 current output PRO 0.0%RET.H 100% segmental point of RET current output PRO 100.0%RET.L 0% segmental point of RET current output PRO 0.0%

OU.A OUT current output range STD 4-20

OU2.A OUT2 current output range STD 4-20

RET.A RET current output range STD 4-20

Heater Break Alarm Setting

Menu Symbol Name Display level Setting range Initial value User settingHBA HB1.S Heater break alarm-1 function selection EASY 1

HB2.S Heater break alarm-2 function selection EASY 1HB1 Heater break alarm-1 current setpoint EASY OFFHB2 Heater break alarm-2 current setpoint EASY OFFCT1.T CT1 coil winding number ratio EASY 800CT2.T CT2 coil winding number ratio EASY 800HDN1 Heater break alarm-1 Ondelay timer STD 0.00HDN2 Heater break alarm-2 Ondelay timer STD 0.00HDF1 Heater break alarm-1 Offdelay timer PRO 0.00HDF2 Heater break alarm-2 Offdelay timer PRO 0.00HB1.D Heater break alarm-1 contact type PRO CLSHB2.D Heater break alarm-2 contact type PRO CLS

RS-485 Communication Setting (E3 terminalarea)

(E4 terminalarea)

Menu Symbol Name Display level Setting range Initial value User setting User setting

R485 PSL Protocol selection EASY

PCL: PC link communicationPCLSM: PC link communication (with checksum)LADR: Ladder communicationCO-M: Coordinated master stationMBASC: Modbus (ASCII)MBRTU: Modbus (RTU)CO-S2: Coordinated slave station (Loop-2 mode)P-P: Peer-to-peer communication

MBRTU

BPS Baud rate EASY

600: 600 bps1200: 1200 bps2400: 2400 bps4800: 4800 bps9600: 9600 bps19200: 19.2k bps38400: 38.4k bps (except for communication of E4 terminal area)

19200

PRI Parity EASYNONE: NoneEVEN: EvenODD: Odd

EVEN

STP Stop bit EASY 1: 1 bit, 2: 2 bits 1DLN Data length EASY 7: 7 bits, 8: 8 bits 8ADR Address EASY 1 to 99 1RP.T Minimum response time PRO 0 to 10 (x10ms) 0

0.5 to 1000.0 s

When RTS = PV1, SP1, PV2, SP2, TSP1, TSP2, PV, RSP, AIN2, or AIN4,RTL + 1 digit to 30000-19999 to RTH - 1 digitDecimal point position:When RTS=PV1, SP1, or TSP1, decimal point position is same as that of PVinput.When RTS=PV2, SP2, or TSP2, decimal point position is same as that of RSPinput.When RTS=PV, decimal point position is same as that of PV input scale.When RTS=RSP, decimal point position is same as that of RSP input scale.When RTS=AIN2, decimal point position is same as that of AIN2 scale.When RTS=AIN4, decimal point position is same as that of AIN4 scale.

When O1RS = PV1, SP1, PV2, SP2, TSP1, TSP2, PV, RSP, AIN2, or AIN4,O1RL + 1 digit to 30000-19999 to O1RH - 1 digitDecimal point position:When O1RS=PV1, SP1, or TSP1, decimal point position is same as that of PVinput.When O1RS =PV2, SP2, or TSP2, decimal point position is same as that of RSPinput.When O1RS =PV, decimal point position is same as that of PV input scale.When O1RS =RSP, decimal point position is same as that of RSP input scale.When O1RS =AIN2, decimal point position is same as that of AIN2 scale.When O1RS =AIN4, decimal point position is same as that of AIN4 scale.

When O2RS = PV1, SP1, PV2, SP2, TSP1, TSP2, PV, RSP, AIN2, or AIN4,O2RL + 1 digit to 30000-19999 to O2RH - 1 digitDecimal point position:When O2RS=PV1, SP1, or TSP1, decimal point position is same as that of PVinput.When O2RS =PV2, SP2, or TSP2, decimal point position is same as that of RSPinput.When O2RS =PV, decimal point position is same as that of PV input scale.When O2RS =RSP, decimal point position is same as that of RSP input scale.When O2RS =AIN2, decimal point position is same as that of AIN2 scale.When O2RS =AIN4, decimal point position is same as that of AIN4 scale.

-100.0 to 200.0%

4-20: 4 to 20 mA0-20: 0 to 20 mA20-4: 20 to 4 mA20-0: 20 to 0 mA

0: Heater current measurement1: Heater break alarm

OFF, 0.1 to 300.0 Arms

1 to 3300

0.00 to 99.59 (minute.second)

CLS: When the event occurs, the contact is closed.OPN: When the event occurs, the contact is opened.

Page 18 / 25

Page 19: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

Ethernet Communication Setting

Menu Symbol Name Display level Setting range Initial value User settingETHR HSR High-speed response mode EASY OFF, 1 to 8 1

BPS Baud rate EASY9600: 9600 bps19200: 19.2k bps38400: 38.4k bps

38400

PRI Parity EASYNONE: NoneEVEN: EvenODD: Odd

EVEN

IP1 IP address 1 EASY 0 to 255 192IP2 IP address 2 EASY 0 to 255 168IP3 IP address 3 EASY 0 to 255 1IP4 IP address 4 EASY 0 to 255 1SM1 Subnet mask 1 EASY 0 to 255 255SM2 Subnet mask 2 EASY 0 to 255 255SM3 Subnet mask 3 EASY 0 to 255 255SM4 Subnet mask 4 EASY 0 to 255 0DG1 Default gateway 1 EASY 0 to 255 0DG2 Default gateway 2 EASY 0 to 255 0DG3 Default gateway 3 EASY 0 to 255 0DG4 Default gateway 4 EASY 0 to 255 0PRT Port number EASY 502, 1024 to 65535 502

IPAR IP access restriction EASY OFF: Disable, ON: Enable OFF

1.IP1 Permitted IP address 1-1 EASY 0 to 255 2551.IP2 Permitted IP address 1-2 EASY 0 to 255 2551.IP3 Permitted IP address 1-3 EASY 0 to 255 2551.IP4 Permitted IP address 1-4 EASY 0 to 255 2552.IP1 Permitted IP address 2-1 EASY 0 to 255 2552.IP2 Permitted IP address 2-2 EASY 0 to 255 2552.IP3 Permitted IP address 2-3 EASY 0 to 255 2552.IP4 Permitted IP address 2-4 EASY 0 to 255 255

ESW Ethernet setting switch EASY

OFF, ONSetting this parameter to “ON” enables the Ethernet communication parametersettings.* The parameter ESW automatically returns to “OFF” after “ON” is set.

OFF

When each parameter is displayed, the terminal area (E3) is displayed on Group display.

PROFIBUS-DP Communication Setting

Menu Symbol Name Display level Setting range Initial value User setting

PROF BR Baud rate EASY

9.6K: 9.6k bps19.2K: 19.2k bps93.75K: 93.75k bps187.5K: 187.5k bps0.5M: 0.5M bps1.5M: 1.5M bps3M: 3M bps6M: 6M bps12M: 12M bpsAUTO45.45K: 45.45k bps

AUTO

ADR Address EASY 0 to 125 3

BPS Baud rate EASY9600: 9600 bps19200: 19.2k bps38400: 38.4k bps

38400

FILE Profile number EASY 0, 11 to 15 0

SCAN Automatic rescan time PRO

OFF1M: 1 minute10M: 10 minutes30M: 30 minutes60M: 60 minutes

OFF

When each parameter is displayed, the terminal area (E3) is displayed on Group display.

DeviceNet Communication Setting

Menu Symbol Name Display level Setting range Initial value User setting

DNET BR Baud rate EASY125K: 125k bps250K: 250k bps500K: 500k bps

125K

ADR Address EASY 0 to 63 63

BPS Baud rate EASY9600: 9600 bps19200: 19.2k bps38400: 38.4k bps

38400

FILE Profile number EASY 0, 11 to 15 0

SCAN Automatic rescan time PRO

OFF1M: 1 minute10M: 10 minutes30M: 30 minutes60M: 60 minutes

OFF

When each parameter is displayed, the terminal area (E3) is displayed on Group display.

CC-Link Communication Setting

Menu Symbol Name Display level Setting range Initial value User setting

CC-L BR Baud rate EASY

156K: 156k bps625K: 625k bps2.5M: 2.5M bps5M: 5M bps10M: 10M bps

10M

ADR Address EASY 1 to 64 1

BPS Baud rate EASY9600: 9600 bps19200: 19.2k bps38400: 38.4k bps

38400

FILE Profile number EASY 0, 11 to 15(0, 11: Ver.1.10) (12 to 15: Ver.2.00)

0

SCAN Automatic rescan time PRO

OFF1M: 1 minute10M: 10 minutes30M: 30 minutes60M: 60 minutes

OFF

When each parameter is displayed, the terminal area (E3) is displayed on Group display.

Key Action Setting

Menu Symbol Name Display level Setting range Initial value User setting

KEY RUN RUN key action setting RPO PROG

RST RST key action setting PRO RESET

PTN PTN key action setting PRO PTN

MODE MODE key action setting PRO MODE

OFF: DisablePROG: Switch to PROG (Start of program operation)RESET: Switch to RESET (Stop of program operation)LOCAL: Switch to LOCAL(LSP) (Start of local-mode operation)REM: Switch to REMOTEP/R: PROG/RESET SwitchP/H: PROG/HOLD SwitchP/L: PROG/LOCAL(LSP) SwitchL/C: LOCAL(LSP)/CAS switchHLD: Switch to HOLD (Start of hold-mode operation)ADV: Advance of segmentA/M1: Loop-1 AUTO/MAN switchA/M2: Loop-2 AUTO/MAN switchPRG1: Switch to PROG1 (Start of program-1 operation)PRG2: Switch to PROG2 (Start of program-2 operation)AT: Auto-tuningLTUP: LCD brightness UPLTDN: LCD brightness DOWNBRI: Adjust LCD brightnessLCD: LCD backlight ON/OFF switchLAT: Latch releasePID: PID tuning switchPTN: Program pattern number switchMODE: Operation mode

Page 19 / 25

Page 20: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

Display Function Setting

Menu Symbol Name Display level Setting range Initial value User setting

DISP PCMD Active color PV display switch EASY

0: Fixed in white1: Fixed in red2: Link to alarm 1 (Alarm OFF: white, Alarm ON: red)3: Link to alarm 1 (Alarm OFF: red, Alarm ON: white)4: Link to alarm 1 or 2 (Alarm OFF: white, Alarm ON: red)5: Link to alarm 1 or 2 (Alarm OFF: red, Alarm ON: white)6: PV limit (Within range: white, Out of range: red)7: PV limit (Within range: red, Out of range: white)8: SP deviation (Within deviation: white, Out of deviation: red)9: SP deviation (Within deviation: red, Out of deviation: white)10: Link to DI (ON: red, OFF: white)

0

PCH PV color change high limit EASY 0

PCL PV color change low limit EASY 0

PTSL Program display pattern selection STD PTN: Pattern displaySK.RP: Ramp and soak display

PTN

BAR1 Upper bar-graph display registration STD 23

BAR2 Lower bar-graph display registration STD 0

BDV Bar-graph deviation display band STD 0.0 to 100.0% of PV input range span (EUS) 10.0 % of PV input rangespan

EV1 EV1 display condition registration PRO 4785

EV2 EV2 display condition registration PRO 4786

EV3 EV3 display condition registration PRO 4787

EV4 EV4 display condition registration PRO 4789

EV5 EV5 display condition registration PRO 4790

EV6 EV6 display condition registration PRO 4791

EV7 EV7 display condition registration PRO 4793

EV8 EV8 display condition registration PRO 4794

PV.D PV display area ON/OFF PRO ONSP.D Setpoint display area ON/OFF PRO ONSTS.D Status display area ON/OFF PRO ONSPD Scroll speed PRO (Slow) 1 to 8 (Quick) 4

GUID Guide display ON/OFF STD OFF: NondisplayON: Display

ON

HOME Home Operation Display setting PRO

SP1: SP DisplaySP2: Loop-2 SP DisplayOUT1: OUT DisplayOUT2: Loop-2 OUT DisplayHCO: Heating/cooling OUT DisplayVP: Valve Position DisplayMV: Position Proportional Computation Output DisplayPID1: PID Number DisplayPID2: Loop-2 PID Number DisplayHC1: Heater Break Alarm-1 Current DisplayHC2: Heater Break Alarm-2 Current DisplayPV1: PV2/PV1 DisplayPV2: PV1/PV2 DisplayPV: PV Analog Input DisplayRSP: RSP Analog Input DisplayAIN2: AIN2 Analog Input DisplayAIN4: AIN4 Analog Input DisplayCS1 to CS5: SELECT Display 1 to 5TSP1: TSP DisplayTSP2: Loop-2 TSP DisplayR.TIM: Remaining Segment-tim DisplaySEG.N: Segment Number DispalyR.CYC: Remaining Repetition DisplayPTN: Program Pattern DisplayAL5.8.1: Alarm-5 to -8 Status DisplayAL5.8.2: Loop-2 Alarm-5 to -8 Status Display

SP1

ECO Economy mode STD

OFF: Disable1: Economy mode ON (All indications except PV display OFF)2: Economy mode ON (All indications OFF)3: Brightness 10 % (All indications)

OFF

BRI Brightness EASY (Dark) 1 to 5 (Bright) 3

B.PVW White brightness adjustment of PV display PRO Adjusts the white brightness of PV display.(Dark) -4 to 4 (Bright)

0

B.PVR Red brightness adjustment of PV display PRO Adjusts the red brightness of PV display.(Dark) -4 to 4 (Bright)

0

B.SP Brightness adjustment of Setpoint display PRO Adjusts the brightness of SP display.(Dark) -4 to 4 (Bright)

0

B.BAR Brightness adjustment of Bargraph display PRO Adjusts the brightness of Bargraph display.(Dark) -4 to 4 (Bright)

0

B.STS Brightness adjustment of Status indicator PRO Adjusts the brightness of Status indicator.(Dark) -4 to 4 (Bright)

0

D.CYC Display update cycle PRO

1: 100 ms2: 200 ms3: 500 ms4: 1 s5: 2 s

2

OP.JP Autoreturn to operation display PROAutomatically returned to the Operation Display when there has been nokeystroke operation for 5 minutes.OFF, ON

ON

MLSD Least significant digital mask of PV display STD OFF: With least significant digitON: Without least significant digit

OFF

Set a display value when in PV limit or SP deviation.-19999 to 30000 (Set a value within the input range.)Decimal point position depends on the input type.

0: Disable1: OUT, Heating-side OUT, Internal value in Position proportional control2: Cooling-side OUT3: PV4: SP5: Deviation6: Loop-2 OUT, Loop-2 heatingside OUT7: Loop-2 cooling-side OUT8: Loop-2 PV9: Loop-2 SP10: Loop-2 deviation11 to 16: Disable17: Feedback input (valve opening)18: PV terminals analog input19: RSP terminals analog input20: AIN2 terminals analog input21: AIN4 terminals analog input22: Segment progress23: Time event and alarm status

Setting range: 4001 to 6304OFF: Disable4785: Link to PV event-1/local event-1 (Lit when the event occurs)4786: Link to PV event-2/local event-2 (Lit when the event occurs)4787: Link to PV event-3/local event-3 (Lit when the event occurs)4789: Link to PV event-4/local event-4 (Lit when the event occurs)4790: Link to PV event-5/local event-5 (Lit when the event occurs)4791: Link to PV event-6/local event-6 (Lit when the event occurs)4793: Link to PV event-7/local event-7 (Lit when the event occurs)4794: Link to PV event-8/local event-8 (Lit when the event occurs)4817: Link to time event-1 (Lit when the event occurs)4818: Link to time event-2 (Lit when the event occurs)4819: Link to time event-3 (Lit when the event occurs)4821: Link to time event-4 (Lit when the event occurs)4822: Link to time event-5 (Lit when the event occurs)4823: Link to time event-6 (Lit when the event occurs)4825: Link to time event-7 (Lit when the event occurs)4826: Link to time event-8 (Lit when the event occurs)4833: Link to time event-9 (Lit when the event occurs)4834: Link to time event-10 (Lit when the event occurs)4835: Link to time event-11 (Lit when the event occurs)4837: Link to time event-12 (Lit when the event occurs)4838: Link to time event-13 (Lit when the event occurs)4839: Link to time event-14 (Lit when the event occurs)4841: Link to time event-15 (Lit when the event occurs)4842: Link to time event-16 (Lit when the event occurs)4321: Link to alarm-1 (Lit when the alarm occurs)4322: Link to alarm-2 (Lit when the alarm occurs)4323: Link to alarm-3 (Lit when the alarm occurs)4325: Link to alarm-4 (Lit when the alarm occurs)4326: Link to alarm-5 (Lit when the alarm occurs)4327: Link to alarm-6 (Lit when the alarm occurs)4329: Link to alarm-7 (Lit when the alarm occurs)4330: Link to alarm-8 (Lit when the alarm occurs)4529: Heater break alarm 1 (Lit when the alarm occurs)4530: Heater break alarm 2 (Lit when the alarm occurs)5025 to 5027: Link to DI1-DI3 (Lit when the contact is closed)5041 to 5046: Link to DI11-DI16 (E1-terminal area) (Lit when the contact is closed)5057 to 5062: Link to DI21-DI26 (E2-terminal area) (Lit when the contact is closed)5073 to 5077: Link to DI31-DI35 (E3-terminal area) (Lit when the contact is closed)5089 to 5094: Link to DI41-DI46 (E4-terminal area) (Lit when the contact is closed)5153 to 5155: Link to AL1-AL3 (Lit when the contact is closed)5169 to 5173: Link to DO11-DO15 (E1-terminal area) (Lit when the contact is closed)5185 to 5189: Link to DO21-DO25 (E2-terminal area) (Lit when the contact is closed)5201 to 5205: Link to DO31-DO35 (E3-terminal area) (Lit when the contact is closed)5217 to 5221: Link to DO41-DO45 (E4-terminal area) (Lit when the contact is closed)* For other functions, see the UTAdvanced Series Communication Interface User’s Manual.

OFF: Nondisplay, ON: Display

Page 20 / 25

Page 21: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

SELECT Display Setting

Menu Symbol Name Display level Setting range Initial value User setting

CSEL CS1 SELECT Display-1 registration STD OFF

CS2 SELECT Display-2 registration STD OFF

CS3 SELECT Display-3 registration STD OFF

CS4 SELECT Display-4 registration STD OFF

CS5 SELECT Display-5 registration STD OFF

CS10 SELECT parameter-10 registration PRO OFF

CS11 SELECT parameter-11 registration PRO OFF

CS12 SELECT parameter-12 registration PRO OFF

CS13 SELECT parameter-13 registration PRO OFF

CS14 SELECT parameter-14 registration PRO OFF

CS15 SELECT parameter-15 registration PRO OFF

CS16 SELECT parameter-16 registration PRO OFF

CS17 SELECT parameter-17 registration PRO OFF

CS18 SELECT parameter-18 registration PRO OFF

CS19 SELECT parameter-19 registration PRO OFF

Key Lock SettingProgram pattern-2

retransmission(PT2.G=ON)

Menu Symbol Name Display level Setting range Initial value User setting User settingKLOC U.SP SP Display lock PRO OFF

U.TSP TSP Display lock PRO OFFU.TM Remaining Segment-tim Display lock PRO OFF

U.OUT OUT Display lock PRO OFF(Cascade control: ON)

U.HCO Heating/cooling OUT Display lock PRO OFFU.VP Valve Position Display lock PRO OFF

U.MV Position Proportional Computation OutputDisplay lock

PRO ON

U.PID PID Number Display lock PRO ONU.SEG Segment Number Display lock PRO OFFU.RCY Remaining Repetition Display lock PRO OFFU.PTN Program Pattern Display lock PRO OFFU.AL Alarm-5 to -8 Status Display lock PRO OFFU.HC Heater Break Alarm Current Value Display lock PRO OFFU.PV1 PV2/PV1 Display lock PRO OFFU.PV2 PV1/PV2 Display lock PRO OFF

U.PV PV Analog Input Display lock PRO

ON(Loop control with PVswitching and Loop controlwith PV autoselector: OFF)

U.RSP RSP Analog Input Display lock PRO

ON(Loop control with PVswitching and Loop controlwith PV autoselector: OFF)

U.AI2 AIN2 Analog Input Display lock PROON(Loop control with PV auto-selector: OFF)

U.AI4 AIN4 Analog Input Display lock PROON(Loop control with PV auto-selector: OFF)

COM.W Communication write enable/disable STD OFF: Enable, ON: Disable OFF

DATA Front panel parameter data key lock STD OFFRUN Front panel RUN key lock STD OFFRST Front panel RST key lock STD OFFPTN Front panel PTN key lock STD OFFMODE Front panel MODE key lock STD OFF

Menu Lock Setting

Menu Symbol Name Display level Setting range Initial value User settingMLOC CTL [CTL] menu lock PRO OFF

PV [PV] menu lock PRO OFFRSP [RSP] menu lock PRO OFFAIN2 [AIN2] menu lock PRO OFFAIN4 [AIN4] menu lock PRO OFFMPV [MPV] menu lock PRO OFFOUT [OUT] menu lock PRO OFFHBA [HBA] menu lock PRO OFFR485 [R485] menu lock PRO OFFETHR [ETHR] menu lock PRO OFFPROF [PROF] menu lock PRO OFFDNET [DNET] menu lock PRO OFFCC-L [CC-L] menu lock PRO OFFKEY [KEY] menu lock PRO OFFDISP [DISP] menu lock PRO OFFCSEL [CSEL] menu lock PRO OFFKLOC [KLOC] menu lock PRO OFFDI.SL [DI.SL] menu lock PRO OFFDI.NU [DI.NU] menu lock PRO OFFDI.D [DI.D] menu lock PRO OFFALM [ALM] menu lock PRO OFFDO [DO] menu lock PRO OFFI/O [I/O] menu lock PRO OFFSYS [SYS] menu lock PRO OFFINIT [INIT] menu lock PRO OFFVER [VER] menu lock PRO OFFLVL [LVL] menu lock PRO OFFMODE [MODE] menu lock PRO OFFCS [CS] menu lock PRO OFFPROG [PROG] menu lock PRO OFFLOC [LOC] menu lock PRO OFFEDIT [EDIT] menu lock PRO OFFAL [AL] menu lock PRO OFFSPS [SPS] menu lock PRO OFFALRM [ALRM] menu lock PRO OFFPVS [PVS] menu lock PRO OFFPID [PID] menu lock PRO OFFTUNE [TUNE] menu lock PRO OFFZONE [ZONE] menu lock PRO OFFPPAR [PPAR] menu lock PRO OFFPYS1 [PYS1] menu lock PRO OFFPYS2 [PYS2] menu lock PRO OFFPYS3 [PYS3] menu lock PRO OFFPYS4 [PYS4] menu lock PRO OFF

When each parameter is displayed, the terminal area (E1 to E4) is displayed on Group display.• Parameter: RSP, AIN2, AIN4, R485, ETHR, PROF, DNET, CC-L, DI.D, DO

DI Function Registration

Menu Symbol Name Display level Setting range Initial value User settingDI.SL PRG Switch to PROG (Start of program operation) STD 5025

RST Switch to RESET (Stop of program operation) STD 5026

LOC Switch to LOCAL(LSP) (Start of local-modeoperation)

STD 5027

REM Switch to REMOTE STD 5046P/R PROG/RESET Switch STD OFFP/H PROG/HOLD Switch STD OFFP/L PROG/LOCAL(LSP) Switch STD OFFHOLD Switch to HOLD (Start of hold-mode operation) STD OFFADV Advance of segment STD OFFWAIT Wait ON/OFF switch STD OFF

S.HLD Switch to HOLD for synchronized programoperation

PRO OFF

A/M AUTO/MAN switch STD OFFAT Auto-tuning START/STOP switch STD OFFLAT Latch release STD OFFLCD LCD backlight ON/OFF switch STD OFFPVRW PV red/white switch STD OFFMG1 Message display interruption 1 PRO OFFMG2 Message display interruption 2 PRO OFFMG3 Message display interruption 3 PRO OFFMG4 Message display interruption 4 PRO OFF

OFF, 2201 to 5000For the D register number, see the UTAdvanced Series CommunicationInterface User’s Manual

Main registration parameters- Group 1 (S.PID=1)Control output high limit (OH): 3004, Control output low limit (OL): 3005,Cooling-side control output high limit (OHc): 3016,Cooling-side control output low limit (OLc): 3017- Group 2 (S.PID=2)Control output high limit (OH): 3054, Control output low limit (OL): 3055,Cooling-side control output high limit (OHc): 3066,Cooling-side control output low limit (OLc): 3067- Group 3 (S.PID=3)Control output high limit (OH): 3104, Control output low limit (OL): 3105,Cooling-side control output high limit (OHc): 3116,Cooling-side control output low limit (OLc): 3117- Group 4 (S.PID=4)Control output high limit (OH): 3154, Control output low limit (OL): 3155,Cooling-side control output high limit (OHc):3166, Cooling-side control output low limit (OLc): 3167

Alarm-1 setpoint (A1): 2351, Alarm-2 setpoint (A2): 2352,Alarm-3 setpoint (A3): 2353, Alarm-4 setpoint (A4): 2354,Alarm-5 setpoint (A5): 2355, Alarm-6 setpoint (A6): 2356,Alarm-7 setpoint (A7): 2357, Alarm-8 setpoint (A8): 2358

OFF: DisplayON: Nondisplay

OFF: UnlockON: Lock

OFF: DisplayON: Nondisplay

OFF: DisplayON: Nondisplay

Set an I relay number of contact input.Set “OFF” to disable the function.

Standard terminals DI1: 5025, DI2: 5026, DI3: 5027E1-terminal area DI11: 5041, DI12: 5042, DI13: 5043, DI14: 5044, DI15: 5045, DI16: 5046E2 -terminal area DI21: 5057, DI22: 5058, DI23: 5059, DI24: 5060, DI25: 5061, DI26: 5062E3-terminal area DI31: 5073, DI32: 5074, DI33: 5075, DI34: 5076, DI35: 5077E4-terminal area DI41: 5089, DI42: 5090, DI43: 5091, DI44: 5092, DI45: 5093, DI46: 5094

Page 21 / 25

Page 22: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

DI Function Numbering

Menu Symbol Name Display level Setting range Initial value User settingDI.NU PT.B0 Bit-0 of Program pattern number EASY 5089

PT.B1 Bit-1 of Program pattern number EASY 5090PT.B2 Bit-2 of Program pattern number EASY 5091PT.B3 Bit-3 of Program pattern number EASY 5092PT.B4 Bit-4 of Program pattern number EASY 5093PT.B5 Bit-5 of Program pattern number EASY OFFPN.B0 Bit-0 of PID number STD OFFPN.B1 Bit-1 of PID number STD OFFPN.B2 Bit-2 of PID number STD OFFPN.B3 Bit-3 of PID number STD OFFMP.B0 Bit-0 of manual preset output number STD OFFMP.B1 Bit-1 of manual preset output number STD OFFMP.B2 Bit-2 of manual preset output number STD OFF

PT.BCBit changing method of program patternnumber PRO

0: Status switch 11: Status switch 22: BCD switch

0

PN.BC Bit changing method of PID number PRO 0

MP.BC Bit changing method of manual preset outputnumber

PRO 0

DI1-DI3 Contact Type Setting

Menu Symbol Name Display level Setting range Initial value User settingDI.D DI1.D DI1 contact type PRO 0

DI2.D DI2 contact type PRO 0DI3.D DI3 contact type PRO 0

DI Setting (E1 terminal area)(DI11-DI15)

(E2 terminal area)(DI21-DI25)

(E3 terminal area)(DI31-DI35)

(E4 terminal area)(DI41-DI45)

Menu Symbol Name Display level Setting range Initial value User setting User setting User setting User settingDI.D DI1.D DIn1 contact type PRO 0

DI2.D DIn2 contact type PRO 0DI3.D DIn3 contact type PRO 0DI4.D DIn4 contact type PRO 0DI5.D DIn5 contact type PRO 0

n: Terminal area number (1 to 4)

AL1-AL3 Function Registration

Menu Symbol Name Display level Setting range Initial value User setting

ALM AL1.S AL1 function selection STD 4801

AL2.S AL2 function selection STD 4802

AL3.S AL3 function selection STD 4803

OR.S OUT relay function selection STD OFF

OR2.S OUT2 relay function selection STD OFF

AL1.D AL1 contact type PRO 0AL2.D AL2 contact type PRO 0AL3.D AL3 contact type PRO 0OR.D OUT relay contact type PRO 0OR2.D OUT2 relay contact type PRO 0

DO Setting (E1 terminal area)(DO11-DO15)

(E2 terminal area)(DO21-DO25)

(E3 terminal area)(DO31-DO35)

(E4 terminal area)(DO41-DO45)

Menu Symbol Name Display level Setting range Initial value User setting User setting User setting User setting

DO DO1.S DOn1 function selection STD See left

DO2.S DOn2 function selection STD See left

DO3.S DOn3 function selection STD See left

DO4.S DOn4 function selection STD See left

DO5.S DOn5 function selection STD See left

DO1.D DOn1 contact type PRO 0DO2.D DOn2 contact type PRO 0DO3.D DOn3 contact type PRO 0DO4.D DOn4 contact type PRO 0DO5.D DOn5 contact type PRO 0

n: Terminal area number (1 to 4)

I/O Display

Menu Symbol Name Display level Setting rangeI/O KEY Key status PRO

X000 DI1-DI3 status (equipped as standard) PROX100 DI11-DI16 status (E1-terminal area) PROX200 DI21-DI26 status (E2-terminal area) PROX300 DI31-DI35 status (E3-terminal area) PROX400 DI41-DI46 status (E4-terminal area) PROY000 AL1-AL3 status (equipped as standard) PROY100 DO11-DO15 status (E1-terminal area) PROY200 DO21-DO25 status (E2-terminal area) PROY300 DO31-DO35 status (E3-terminal area) PROY400 DO41-DO45 status (E4-terminal area) PRO

System Setting

Menu Symbol Name Display level Setting range Initial value User setting

SYS R.MD Restart mode STD

CONT: Continue action set before power failure.MAN: Start from MAN.RESET: Start from AUTO and RESET. The preset output value is outputted.* Set how the controller should recover from a power failure of 5 seconds ormore.

CONT

R.TM Restart timer STD0 to 10 s* Set time between power on and the instant where controller startscomputation.

0

EPO Input error preset output STD

0: Preset output1: 0% output2: 100% output* Set preset output value when the input burnout or ADC error occurs. Manualoutput is prioritized when the input burnout occurs in MAN.

0

C.GRN Response as GREEN Series PRO

OFF: Works as UP55A in communication of device information response orbroadcasting.ON: Works as GREEN Series in communication of device information responseor broadcasting.

OFF

FREQ Power frequency EASY AUTO, 60: 60 Hz, 50: 50 Hz AUTO

QSM Quick setting mode EASY OFF: DisableON: Enable

ON

LANG Guide display language EASY

ENG: EnglishFRA: FrenchGER: GermanSPA: Spanish

Depends on the Model andSuffix Codes

PASS Password setting EASY 0 (No password) to 65535Once a password is set, you can no longer choose not to set a password.

0

SMEC Sampling period error counter PRO 0 to 65535 (display only) 0 when power is turned on.

Initialization

Menu Symbol Name Display level Setting range Initial value User settingINIT U.DEF Initialization to user default value PRO 12345: Initialization, automatically returned to "0" after initialization. 0

F.DEF Initialization to factory default value PRO -12345: Initialization, automatically returned to "0" after initialization. 0

P.DEF Clearing all program pattern data PRO 13579: Initialization, automatically returned to "0" after initialization.* Data all deletions in menu [PROG]

0

Set an I relay number of contact input.Set “OFF” to disable the function.

Standard terminals DI1: 5025, DI2: 5026, DI3: 5027E1-terminal area DI11: 5041, DI12: 5042, DI13: 5043, DI14: 5044, DI15: 5045, DI16: 5046E2 -terminal area DI21: 5057, DI22: 5058, DI23: 5059, DI24: 5060, DI25: 5061, DI26: 5062E3-terminal area DI31: 5073, DI32: 5074, DI33: 5075, DI34: 5076, DI35: 5077E4-terminal area DI41: 5089, DI42: 5090, DI43: 5091, DI44: 5092, DI45: 5093, DI46: 5094

0: Status switch 11: Status switch 2

0: The assigned function is enabled when the contact input is closed.1: The assigned function is enabled when the contact input is opened.

0: The assigned function is enabled when the contact input is closed.1: The assigned function is enabled when the contact input is opened.

Set an I relay number.Setting range: 4001 to 6304No function: OFFPV event 1: 4801, PV event 2: 4802,PV event 3: 4803, PV event 4: 4805,PV event 5: 4806, PV event 6: 4807,PV event 7: 4809, PV event 8: 4810,Time event 1: 4817, Time event 2: 4818,Time event 3: 4819, Time event 4: 4821,Time event 5: 4822, Time event 6: 4823,Time event 7: 4825, Time event 8: 4826,Time event 9: 4833, Time event 10: 4834,Time event 11: 4835, Time event 12: 4837,Time event 13: 4838, Time event 14: 4839,Time event 15: 4841, Time event 16: 4842,Alarm 1: 4353, Alarm 2: 4354, Alarm 3: 4355, Alarm 4: 4357,Alarm 5: 4358, Alarm 6: 4359, Alarm 7: 4361, Alarm 8: 4362,AUTO (ON ) / MAN (OFF) status: 4177,Program RESET status: 4181, Program RUN status: 4182,Local operation status: 4183,Remote operation status: 4185,HOLD mode status: 4189,Program advance status: 4187,Pattern end signal (1 second): 4265,Pattern end signal (3 seconds): 4266,Pattern end signal (5 seconds): 4267,Wait end signal (1 second) : 4257,Wait end signal (3 seconds) : 4258,Wait end signal (5 seconds) : 4259,Output tracking (ON) switching signal: 4186,FAIL (Normally ON) output: 4256

Read onlySee User's Manual.

0: When the event of assigned function occurs, the contact output is closed.1: When the event of assigned function occurs, the contact output is opened.

0: When the event of assigned function occurs, the contact output is closed.1: When the event of assigned function occurs, the contact output is opened.

Same as AL1.S.

DO11=4805, DO12=4806, DO13=4807, DO14=4809, DO15=4810,DO21=4817, DO22=4818, DO23=4819, DO24=4821, DO25=4822,DO31=4823, DO32=4825, DO33=4826, DO34=4833, DO35=4834,DO41=OFF, DO42=OFF, DO43=OFF, DO44=OFF, DO45=OFF

0: When the event of assigned function occurs, the contact output is closed.1: When the event of assigned function occurs, the contact output is opened.

Page 22 / 25

Page 23: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

Error and Version Confirmation

Menu Symbol Name Display level Setting rangeVER PA.ER Parameter error status EASY

OP.ER Option error status EASYAD1.E A/D converter error status 1 EASYAD2.E A/D converter error status 2 EASYPV1.E Loop-1 PV input error status EASYPV2.E Loop-2 PV input error status EASYLA.ER Ladder error status EASYMCU MCU version EASYDCU DCU version EASYECU1 ECU-1 version EASYECU2 ECU-2 version EASYECU3 ECU-3 version EASYECU4 ECU-4 version EASYPARA Parameter version EASYH.VER Product version EASYSER1 Serial number 1 EASYSER2 Serial number 2 EASYMAC1 MAC address 1 EASYMAC2 MAC address 2 EASYMAC3 MAC address 3 EASY

When the following parameters are displayed, the terminal area (E1 to E4) is displayed on Group display.• Parameter: ECU1, ECU2, ECU3, ECU4, MAC1, MAC2 and MAC3

Parameter Display Level

Menu Symbol Name Display level Setting range Initial value User setting

LVL LEVL Parameter display level EASYEASY: Easy setting modeSTD: Standard setting modePRO: Professional setting mode

STD

Read onlySee User's Manual

Page 23 / 25

Page 24: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

UTAdvanced UP55AProgram Pattern Setup Charts

CAUTION

You can register max. 99 program segments with the UP55A controller. Create as many copies of the chart as necessary.

System name Maximum value of PV input range / Maximum value of PV input scale ( )Program No. Unit (      )Program nameModelSerial No. A program pattern can be drawn in the right table.

Minimum value of PV input range / Minimum value of PV input scale ( )

Parameter symbol User settings Parameter symbol Parameter nameTMU 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20SEG.T TSP Final target setpointZON TSP Final target setpoint for Program pattern-2 retransmissionPT2.G TIME Segment time setting

TM.RT Segment ramp-rate settingS.PID Segment PID number selectionJC Junction codePV.TY1 PV event-1 typePV.EV1 PV event-1 setpoint

Parameter symbol User settings PV.TY2 PV event-2 typeSSP PV.EV2 PV event-2 setpointSSP PV.TY3 PV event-3 typeSTC PV.EV3 PV event-3 setpointWT.SW1 PV.TY4 PV event-4 typeWZ.UP1 PV.EV4 PV event-4 setpointWZ.LO1 PV.TY5 PV event-5 typeWT.TM1 PV.EV5 PV event-5 setpointWT.SW2 PV.TY6 PV event-6 typeWZ.UP2 PV.EV6 PV event-6 setpointWZ.LO2 PV.TY7 PV event-7 typeWT.TM2 PV.EV7 PV event-7 setpointWT.SW3 PV.TY8 PV event-8 typeWZ.UP3 PV.EV8 PV event-8 setpointWZ.LO3 TME1 Start condition of time event 1WT.TM3 T.ON1 On time of time event 1WT.SW4 T.OF1 Off time of time event 1WZ.UP4 TME2 Start condition of time event 2WZ.LO4 T.ON2 On time of time event 2WT.TM4 T.OF2 Off time of time event 2WT.SW5 TME3 Start condition of time event 3WZ.UP5 T.ON3 On time of time event 3WZ.LO5 T.OF3 Off time of time event 3WT.TM5 TME4 Start condition of time event 4R.CYCL T.ON4 On time of time event 4R.STRT T.OF4 Off time of time event 4R.END TME5 Start condition of time event 5

T.ON5 On time of time event 5T.OF5 Off time of time event 5TME6 Start condition of time event 6T.ON6 On time of time event 6T.OF6 Off time of time event 6TME7 Start condition of time event 7T.ON7 On time of time event 7T.OF7 Off time of time event 7TME8 Start condition of time event 8T.ON8 On time of time event 8T.OF8 Off time of time event 8TME9 Start condition of time event 9T.ON9 On time of time event 9T.OF9 Off time of time event 9TME10 Start condition of time event 10T.ON10 On time of time event 10T.OF10 Off time of time event 10TME11 Start condition of time event 11T.ON11 On time of time event 11T.OF11 Off time of time event 11TME12 Start condition of time event 12T.ON12 On time of time event 12T.OF12 Off time of time event 12TME13 Start condition of time event 13T.ON13 On time of time event 13T.OF13 Off time of time event 13TME14 Start condition of time event 14T.ON14 On time of time event 14T.OF14 Off time of time event 14TME15 Start condition of time event 15T.ON15 On time of time event 15T.OF15 Off time of time event 15TME16 Start condition of time event 16T.ON16 On time of time event 16T.OF16 Off time of time event 16

Parameter nameProgram time unitSegment setting method

The following parameters are necessary to be set before programming.Note that the program is deleted if TMU or SEG.T is changed after creatingprograms.

Zone PID selectionProgram pattern-2 retransmission

Parameter nameStarting target setpoint

The following parameters are common parameters for the programpattern specified.

Starting target setpoint (for program pattern-2 retransmission)Start codeWait function ON/OFF 1Upper-side wait zone 1Lower-side wait zone 1Wait time 1Wait function ON/OFF 2Upper-side wait zone 2Lower-side wait zone 2Wait time 2Wait function ON/OFF 3Upper-side wait zone 3

Upper-side wait zone 5

Lower-side wait zone 3Wait time 3Wait function ON/OFF 4Upper-side wait zone 4

Note that the program patterns are all deleted if the settings change after creating program patterns.Be sure to check the PV input range, Program time unit (TMU), and Segment setting method (SEG.T) before creating.

Segments

Repeat cycle end segment number

Lower-side wait zone 5Wait time 5Number of repeat cyclesRepeat cycle start segment number

Lower-side wait zone 4Wait time 4Wait function ON/OFF 5

Page 24 / 25

Page 25: UTAdvanced UP55A Program Controller Parameter … UP55A Introduction Brief Description of Sheets This sheet provides a brief description of the following sheets entitled "Names and

UTAdvanced UP55AProgram Pattern Setup Charts

CAUTION

You can register max. 99 program segments with the UP55A controller. Create as many copies of the chart as necessary.

System name Maximum value of PV input range / Maximum value of PV input scale (250.0)Program No. Unit (°C)Program nameModelSerial No. A program pattern can be drawn in the right table.

Minimum value of PV input range / Minimum value of PV input scale (0.0)

Parameter symbol User settings Parameter symbol Parameter nameTMU HH.MM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20SEG.T TIME TSP Final target setpoint 100.0 100.0 200.0 200.0 50.0 50.0ZON 0 TSP Final target setpoint for Program pattern-2 retransmissionPT2.G OFF TIME Segment time setting 0.50 0.30 1.00 0.30 0.50 0.30

TM.RT Segment ramp-rate settingS.PID Segment PID number selection 1 2 3 4 5 6JC Junction code CONT CONT CONT CONT CONT CONTPV.TY1 PV event-1 type 5 1 5 1 6 2PV.EV1 PV event-1 setpoint 5.0 110.0 5.0 210.0 5.0 10.0

Parameter symbol User settings PV.TY2 PV event-2 typeSSP 50.0 PV.EV2 PV event-2 setpointSSP PV.TY3 PV event-3 typeSTC SSP PV.EV3 PV event-3 setpointWT.SW1 PV.TY4 PV event-4 typeWZ.UP1 PV.EV4 PV event-4 setpointWZ.LO1 PV.TY5 PV event-5 typeWT.TM1 PV.EV5 PV event-5 setpointWT.SW2 PV.TY6 PV event-6 typeWZ.UP2 PV.EV6 PV event-6 setpointWZ.LO2 PV.TY7 PV event-7 typeWT.TM2 PV.EV7 PV event-7 setpointWT.SW3 PV.TY8 PV event-8 typeWZ.UP3 PV.EV8 PV event-8 setpointWZ.LO3 TME1 Start condition of time event 1 OFF OFF ON OFF ON OFFWT.TM3 T.ON1 On time of time event 1 0.25WT.SW4 T.OF1 Off time of time event 1 0.20 0.20WZ.UP4 TME2 Start condition of time event 2 OFF ON OFF ON OFF ONWZ.LO4 T.ON2 On time of time event 2WT.TM4 T.OF2 Off time of time event 2WT.SW5 TME3 Start condition of time event 3WZ.UP5 T.ON3 On time of time event 3WZ.LO5 T.OF3 Off time of time event 3WT.TM5 TME4 Start condition of time event 4R.CYCL T.ON4 On time of time event 4R.STRT T.OF4 Off time of time event 4R.END TME5 Start condition of time event 5

T.ON5 On time of time event 5T.OF5 Off time of time event 5TME6 Start condition of time event 6T.ON6 On time of time event 6T.OF6 Off time of time event 6TME7 Start condition of time event 7T.ON7 On time of time event 7T.OF7 Off time of time event 7TME8 Start condition of time event 8T.ON8 On time of time event 8T.OF8 Off time of time event 8TME9 Start condition of time event 9T.ON9 On time of time event 9T.OF9 Off time of time event 9TME10 Start condition of time event 10T.ON10 On time of time event 10T.OF10 Off time of time event 10TME11 Start condition of time event 11T.ON11 On time of time event 11T.OF11 Off time of time event 11TME12 Start condition of time event 12T.ON12 On time of time event 12T.OF12 Off time of time event 12TME13 Start condition of time event 13T.ON13 On time of time event 13T.OF13 Off time of time event 13TME14 Start condition of time event 14T.ON14 On time of time event 14T.OF14 Off time of time event 14TME15 Start condition of time event 15T.ON15 On time of time event 15T.OF15 Off time of time event 15TME16 Start condition of time event 16T.ON16 On time of time event 16T.OF16 Off time of time event 16

The following parameters are common parameters for the program patternspecified.

*********************

Program time unitSegment setting methodZone PID selection

UP55A

Parameter name

The following parameters are necessary to be set before programming.Note that the program is deleted if TMU or SEG.T is changed after creatingprograms.

Lower-side wait zone 1Wait time 1

Parameter nameStarting target setpointStarting target setpoint (for program pattern-2 retransmission)Start code

Upper-side wait zone 5

Wait function ON/OFF 4Upper-side wait zone 4Lower-side wait zone 4Wait time 4

Upper-side wait zone 2

Segments

Program pattern-2 retransmission

Wait function ON/OFF 5

Wait function ON/OFF 3Upper-side wait zone 3

Lower-side wait zone 2Wait time 2

Wait function ON/OFF 1Upper-side wait zone 1

Note that the program patterns are all deleted if the settings change after creating program patterns.Be sure to check the PV input range, Program time unit (TMU), and Segment setting method (SEG.T) before creating.

Repeat cycle end segment number

Number of repeat cyclesRepeat cycle start segment number

Lower-side wait zone 5Wait time 5

Lower-side wait zone 3Wait time 3

Wait function ON/OFF 2

The programming example given here demonstrates how to do the tasks outlined below.

1) Program the controller to start program operation at 50.0°C and raise the temperature up to 100.0°C in 50 minutes.2) When the temperature reaches 100.0°C, keep it at this level for 30 minutes.3) Raise the temperature up to 200.0°C in 60 minutes.4) When the temperature reaches 200.0°C, keep it at this level for 30 minutes.5) Lower the temperature to 50.0°C in 50 minutes.6) When the temperature reaches 50.0°C, keep it at this level for 30 minutes.

PV input ranges are following:Maximum value of PV input range: 250.0°CMinimum value of PV input range: 0.0°CPV input unit: C

Zone PID selection (ZON): Segment PID selection (0)Segment setting method (SEG.T): Segment time setting (TIME)Program time unit (TMU): hour.minute (HH.MM)

Page 25 / 25