IM 05P01D81-11EN page 1/6 Contents 1. Safety Precautions 2. Model and Suffix Codes 3. How to Install 4. Hardware Specifications 5. How to Connect Wires 6. Terminal Wiring Diagrams 7. Setup Procedure 8. Operations 9. Troubleshooting Introduction Thank you for purchasing the UT35A/MDL, UT32A/MDL Controller. (The UT35A and UT32A with option /MDL have no display.) This operation guide describes the installing, wirings, setup flow, and troubleshooting of the UT35A/MDL and UT32A/MDL. The guide should be provided to the end user of this product. Be sure to read this operation guide before using the product in order to ensure correct operation. For details of each function, refer to the electronic manual. Before using the product, refer to the table of Model and Suffix Codes to make sure that the delivered product is consistent with the model and suffix codes you ordered. Also make sure that the following items are included in the package. • Controller (the model you ordered) .........................................................x1 • Unit Label (L4502VZ) ..............................................................................x1 • Tag Label (L4502VE) ..............................................................................x1 (Only when ordered.) • Operation Guide (this document) ............................................................x3 (A3 size) (Installation and Wiring, Initial Settings, Operations, and Parameters) l Target Readers This guide is intended for the following personnel; • Engineers responsible for installation, wiring, and maintenance of the equipment. • Personnel responsible for normal daily operation of the equipment. 1. Safety Precautions The following symbol is used on the instrument. It indicates the possibility of injury to the user or damage to the instrument, and signifies that the user must refer to the operation guide or user’s manual for special instructions. The same symbol is used in the operation guide and user’s manual on pages that the user needs to refer to, together with the term “WARNING” or “CAUTION.” WARNING Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences. CAUTION Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre- cautions that should be taken to prevent such occurrences. AC AC/DC The equipment wholly protected by double insulation or reinforced insulation. Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important information required to operate the instrument. Warning and Disclaimer (1) YOKOGAWA makes no warranties regarding the product except those stated in the WARRANTY that is provided separately. (2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to any person or entity for any loss or damage, direct or indirect, arising from the use of the product or from any unpredictable defect of the product. Safety, Protection, and Modification of the Product (1) In order to protect the system controlled by this product and the product itself, and to ensure safe operation, observe the safety precautions described in the operation guide. Use of the instrument in a manner not prescribed herein may compromise the product's functions and the protection features inherent in the device. We assume no liability for safety, or responsibility for the product's quality, performance or functionality should users fail to observe these instructions when operating the product. (2) Installation of protection and/or safety circuits with respect to a lightning protector; protective equipment for the system controlled by the product and the product itself; foolproof or fail-safe design of a process or line using the system controlled by the product or the product itself; and/or the design and installation of other protective and safety circuits are to be appropriately implemented as the customer deems necessary. (3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts or consumables. (4) This product is not designed or manufactured to be used in critical applications that directly affect or threaten human lives. Such applications include nuclear power equipment, devices using radioactivity, railway facilities, aviation equipment, air navigation facilities, aviation facilities, and medical equipment. If so used, it is the user’s responsibility to include in the system additional equipment and devices that ensure personnel safety. (5) Modification of the product is strictly prohibited. (6) This product is intended to be handled by skilled/trained personnel for electric devices. (7) This product is UL Recognized Component. In order to comply with UL standards, end-products are necessary to be designed by those who have knowledge of the requirements. WARNING l Power Supply Ensure that the instrument’s supply voltage matches the voltage of the power supply before turning ON the power. l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H 2 S, SO X , etc.) for extended periods of time may cause a failure. l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself. l Damage to the Protective Construction Operation of the instrument in a manner not specified in the operation guide may damage its protective construction. CAUTION This instrument is an EMC class A product. In a domestic environ- ment this product may cause radio interference in which case the user needs to take adequate measures. 2. Model and Suffix Codes UT35A/MDL «Standard Code Model» Model Suffix code Option code Description UT35A /MDL (Required) Digital Indicating Controller (Power supply: 100-240 V AC) (provided with retransmission output or 15 V DC loop power supply, 2 DIs, and 3 DOs) (*3) Type 1: Basic control -0 Standard type -2 Heating/cooling type Type 2: Functions 0 None 2 5 additional DIs, 5 additional DOs Type 3: Open networks 0 None 1 RS-485 communication (Max.38.4 kbps, 2-wire/4-wire) 2 Ethernet communication (with serial gateway function) 3 CC-Link communication (with Modbus master function) 4 PROFIBUS-DP communication (with Modbus master function) 5 DeviceNet communication (with Modbus master function) Fixed code -1 Temperature unit: deg C & deg F Case color 1 Black (Light charcoal gray) Fixed code -00 Always "-00" (for Standard Code Model) Option codes /MDL (Required) Mount on DIN rail (without the display parts and keys) (*1) /LP 24 V DC loop power supply (*1) /DC Power supply 24 V AC/DC /CT Coating (*2) /CV Terminal cover *1: When /MDL option and /LP option is combined, only “0” can be specified for Type 2 code. *2: When the /CT option is specified, the UT35A does not conform to the safety standards (UL and CSA) and CE marking (Products with /CT option are not intended for EEA-market). *3: UT35A has a panel mount type (without option /MDL). Please see the Operation Guide (IM 05P01D31-11EN). UT32A/MDL «Standard Code Model» Model Suffix code Option code Description UT32A /MDL (Required) Digital Indicating Controller (Power supply: 100-240 V AC) (provided with retransmission output or 15 V DC loop power supply, 2 DIs, and 3 DOs) (*6) Type 1: Basic control (*7) -0 Standard type -2 Heating/cooling type Type 2: Functions 0 None 1 RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) (*1) Type 3: Open networks 0 None 3 CC-Link communication (with Modbus master function) Fixed code -1 Temperature unit: deg C & deg F Case color 1 Black (Light charcoal gray) Fixed code -00 Always "-00" (for Standard Code Model) Option codes /MDL (Required) Mount on DIN rail (without the display parts and keys) (*2) (*3) /LP 24 V DC loop power supply (*3) /HA Heater break alarm (*4) /DC Power supply 24 V AC/DC /CT Coating (*5) /CV Terminal cover *1: When /LP option is specified, the RS-485 communication of the type 2 code “1” is 2-wire system. *2: The /MDL option is specified, the model and suffix codes are follows: UT32A-010-11-00/x/MDL UT32A-003-11-00/x/MDL UT32A-210-11-00/x/MDL *3: When /MDL option and /LP option is combined, “3” can not be specified for Type 3 code. *4: The /HA option can be specified only in the combination of Type2 code “1” and Type 3 code “0.” *5: When the /CT option is specified, the UT32A does not conform to the safety standards (UL and CSA) and CE marking (Products with /CT option are not intended for EEA-market). *6: UT32A has a panel mount type (without option /MDL). Please see the Operation Guide (IM 05P01D31-11EN). *7: UT32A has also a Dual-loop type model; for information, see Manuals in Section-6. Accessories (sold separately) The following is an accessory sold separately. • LL50A Parameter Setting Software Model Suffix code Description LL50A -00 Parameter Setting Software • External Precision Resistor Model Suffix code Description X010 See the General Specifications (*) Resistance Module *: Necessary to input the current signal to the voltage input terminal. • Terminal Cover For UT35A: Model UTAP001; For UT32A: Model UTAP002 • Manuals Note: Manuals can be downloaded from a website. URL: http://www.yokogawa.com/ns/ut/im/ • Brackets Part number: L4502TP (2 pcs for upper and lower sides) • Wall mount bracket For UT32A/MDL: Model UTAP005 3. How to Install Installation Location The instrument should be installed in indoor locations meeting the following conditions: • Instrumented enclosure This instrument is designed to be mounted in an instrumented enclosure. Mount the instrument in a location where its terminals will not inadvertently be touched. Be sure to mount the instrument in an enclosure with a door. • Well ventilated locations Mount the instrument in well ventilated locations to prevent the instrument’s inter- nal temperature from rising. However, make sure that the terminal portions are not exposed to wind. Exposure to wind may cause the temperature sensor accuracy to deteriorate. To mount mul- tiple indicating controllers, see the external dimensions which follow. If mounting other instruments adjacent to the instrument, comply with these external dimen- sions to provide sufficient clearance between the instruments. • Locations with little mechanical vibration Install the instrument in a location subject to little mechanical vibration. • Horizontal location Mount the instrument horizontally and ensure that it is level, with no inclination to the right or left. Note If the instrument is moved from a location with low temperature and low humidity to a place with high temperature and high humidity, or if the temperature changes rapidly, condensation will result. Moreover, in the case of thermocouple inputs, measurement errors will result. To avoid such a situation, leave the instrument in the new environment under ambient conditions for more than 1 hour prior to using it. Do not mount the instrument in the following locations: • Outdoors • Locations subject to direct sunlight or close to a heater Install the instrument in a location with stable temperatures that remain close to an average temperature of 23°C. Do not mount it in locations subject to direct sunlight or close to a heater. Doing so adversely affects the instrument. • Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely affects the instrument. Do not mount the instrument in locations subject to any of these substances. • Areas near electromagnetic field generating sources Do not place magnets or tools that generate magnetism near the instrument. If the instrument is used in locations close to a strong electromagnetic field generating source, the magnetic field may cause measurement errors. • Areas close to flammable articles Absolutely do not place the instrument directly on flam- mable surfaces. If such a circumstance is unavoidable and the instrument must be placed close to a flammable item, provide a shield for it made of 1.43 mm thick plated steel or 1.6 mm thick unplated steel with a space of at least 150 mm between it and the instrument on the top, bottom, and sides. • Areas subject to being splashed with water WARNING Be sure to turn OFF the power supply to the controller before in- stalling it on the enclosure to avoid an electric shock. Mounting on a DIN Rail Insert the DIN rail into the top area of DIN rail groove (at two locations) on the rear panel, and secure in place with the bottom slide lock. DIN rail DIN rail Slide lock UT35A/MDL: 2, UT32A/MDL: 1 Fit into here Push CAUTION Make sure that foreign materials do not enter the inside of the in- strument through the case’s slit holes. 150 mm 150 mm 150 mm 150 mm Operation Guide IM 05P01D81-11EN UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) Operation Guide This operation guide describes installation, wiring, and other tasks required to make the controller ready for operation. 3rd Edition: Nov. 2017 For details of the each function, refer to the electronic manual. Manuals can be downloaded or viewed at the following URL. Functional Enhancement http://www.yokogawa.com/ns/ut/im/ «Standard Code Model» www.yokogawa.com/ns YOKOGAWA ELECTRIC CORPORATION Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN YOKOGAWA CORPORATION OF AMERICA Head office and for product sales 2 Dart Road, Newnan, Georgia 30265, USA YOKOGAWA EUROPE B.V. Headquarters Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS All Rights Reserved, Copyright © 2015 Yokogawa Electric Corporation

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN ... · Thank you for purchasing the UT35A/MDL, UT32A/MDL Controller. (The UT35A and UT32A with option /MDL have no display.)

  • Upload
    others

  • View
    41

  • Download
    3

Embed Size (px)

Citation preview

Page 1: UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN ... · Thank you for purchasing the UT35A/MDL, UT32A/MDL Controller. (The UT35A and UT32A with option /MDL have no display.)

IM 05P01D81-11EN page 1/6

Contents1. Safety Precautions2. ModelandSuffixCodes3. How to Install4. HardwareSpecifications5. HowtoConnectWires6. TerminalWiringDiagrams7. Setup Procedure8. Operations9. Troubleshooting

IntroductionThankyouforpurchasingtheUT35A/MDL,UT32A/MDLController.(TheUT35AandUT32Awithoption/MDLhavenodisplay.)Thisoperationguidedescribestheinstalling,wirings,setupflow,andtroubleshootingoftheUT35A/MDLandUT32A/MDL.Theguideshouldbeprovidedtotheenduserof this product.Besure to read thisoperationguidebeforeusing theproduct inorder toensurecorrectoperation.Fordetailsofeachfunction,refertotheelectronicmanual.Beforeusingtheproduct,refertothetableofModelandSuffixCodestomakesurethatthedeliveredproduct isconsistentwith themodelandsuffixcodesyouordered.Alsomakesurethatthefollowingitemsareincludedinthepackage.

•Controller(themodelyouordered) .........................................................x1•UnitLabel(L4502VZ) ..............................................................................x1•TagLabel(L4502VE) ..............................................................................x1(Onlywhenordered.)•OperationGuide(thisdocument) ............................................................x3(A3size)(InstallationandWiring,InitialSettings,Operations,andParameters)

lTargetReadersThisguideisintendedforthefollowingpersonnel;• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.• Personnelresponsiblefornormaldailyoperationoftheequipment.

1. Safety PrecautionsThe followingsymbol isusedon the instrument. It indicates thepossibilityof injuryto theuserordamageto the instrument,andsignifies that theusermustrefer to theoperationguideoruser’smanual forspecial instructions.Thesamesymbol isusedintheoperationguideanduser’smanualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”or“CAUTION.”

WARNING

Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences.

CAUTION

Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre-cautions that should be taken to prevent such occurrences.

AC

AC/DC

Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.

Functionalgroundingterminals (Donotusethisterminalasaprotectivegroundingterminal).

NoteIdentifiesimportantinformationrequiredtooperatetheinstrument.

Warning and Disclaimer(1)YOKOGAWAmakesnowarrantiesregardingtheproductexceptthosestatedin

theWARRANTYthatisprovidedseparately.

(2)Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilitytoanypersonorentity forany lossordamage,director indirect,arisingfromtheuse of the product or from any unpredictable defect of the product.

Safety,Protection,andModificationoftheProduct(1) Inorder toprotect thesystemcontrolledbythisproductandtheproduct itself,

andtoensuresafeoperation,observethesafetyprecautionsdescribed in theoperationguide.Useof the instrument inamannernotprescribedhereinmaycompromise the product's functions and the protection features inherent in the device.Weassumenoliabilityforsafety,orresponsibilityfortheproduct'squality,performanceorfunctionalityshouldusersfailtoobservetheseinstructionswhenoperatingtheproduct.

(2) Installationof protectionand/or safety circuitswith respect toa lightningprotector;protectiveequipmentforthesystemcontrolledbytheproductandtheproductitself;foolprooforfail-safedesignofaprocessorlineusingthesystemcontrolledbytheproductortheproductitself;and/orthedesignandinstallationofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthecustomer deems necessary.

(3)BesuretousethesparepartsapprovedbyYOKOGAWAwhenreplacingpartsor consumables.

(4)Thisproduct isnotdesignedormanufacturedtobeusedincriticalapplicationsthatdirectlyaffector threatenhuman lives.Suchapplications includenuclearpower equipment, devices using radioactivity, railway facilities, aviationequipment,airnavigation facilities,aviation facilities,andmedicalequipment.If soused, it is theuser’s responsibility to include in thesystemadditionalequipmentanddevicesthatensurepersonnelsafety.

(5)Modificationoftheproductisstrictlyprohibited.(6)Thisproductisintendedtobehandledbyskilled/trainedpersonnelforelectricdevices.(7)ThisproductisULRecognizedComponent.InordertocomplywithULstandards,

end-productsarenecessarytobedesignedbythosewhohaveknowledgeoftherequirements.

WARNING

lPower Supply Ensure that the instrument’s supply voltage matches the voltage

of the power supply before turning ON the power.l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible

or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H2S, SOX, etc.) for extended periods of time may cause a failure.

l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than

YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself.

l Damage to the Protective Construction Operation of the instrument in a manner not specified in the

operation guide may damage its protective construction.

CAUTION

This instrument is an EMC class A product. In a domestic environ-ment this product may cause radio interference in which case the user needs to take adequate measures.

2. ModelandSuffixCodes

UT35A/MDL «Standard Code Model»Model Suffixcode Option

code Description

UT35A /MDL(Required)

DigitalIndicatingController(Powersupply:100-240VAC)(providedwithretransmissionoutputor15VDClooppowersupply,2DIs,and3DOs)(*3)

Type1:Basic control

-0 Standard type

-2 Heating/coolingtype

Type2:Functions

0 None2 5additionalDIs,5additionalDOs

Type3:Opennetworks

0 None

1 RS-485communication(Max.38.4kbps,2-wire/4-wire)

2 Ethernetcommunication(withserialgatewayfunction)

3 CC-Linkcommunication(withModbusmasterfunction)

4 PROFIBUS-DPcommunication(withModbusmasterfunction)

5 DeviceNetcommunication(withModbusmasterfunction)Fixedcode -1 Temperatureunit:degC&degFCasecolor 1 Black(Lightcharcoalgray)Fixedcode -00 Always"-00"(forStandardCodeModel)

Option codes

/MDL(Required)

MountonDINrail(withoutthedisplaypartsandkeys)(*1)

/LP 24VDClooppowersupply(*1)/DC Powersupply24VAC/DC/CT Coating(*2)/CV Terminalcover

*1: When/MDLoptionand/LPoptioniscombined,only“0”canbespecifiedforType2code.*2: Whenthe/CToptionisspecified,theUT35Adoesnotconformtothesafetystandards(UL

andCSA)andCEmarking(Productswith/CToptionarenotintendedforEEA-market).*3: UT35Ahasapanelmounttype(withoutoption/MDL).PleaseseetheOperationGuide(IM

05P01D31-11EN).

UT32A/MDL «Standard Code Model»Model Suffixcode Option

code Description

UT32A /MDL(Required)

DigitalIndicatingController(Powersupply:100-240VAC)(providedwithretransmissionoutputor15VDClooppowersupply,2DIs,and3DOs)(*6)

Type1:Basic control (*7)

-0 Standard type

-2 Heating/coolingtype

Type2:Functions

0 None1 RS-485communication(Max.38.4kbps,2-wire/4-wire)(*1)

Type3:Open networks

0 None3 CC-Linkcommunication(withModbusmasterfunction)

Fixedcode -1 Temperatureunit:degC&degFCasecolor 1 Black(Lightcharcoalgray)Fixedcode -00 Always"-00"(forStandardCodeModel)

Option codes

/MDL(Required)

MountonDINrail(withoutthedisplaypartsandkeys) (*2)(*3)

/LP 24VDClooppowersupply(*3)/HA Heaterbreakalarm(*4)/DC Powersupply24VAC/DC/CT Coating(*5)/CV Terminalcover

*1: When/LPoptionisspecified,theRS-485communicationofthetype2code“1”is2-wiresystem.*2: The/MDLoptionisspecified,themodelandsuffixcodesarefollows: UT32A-010-11-00/x/MDL UT32A-003-11-00/x/MDL UT32A-210-11-00/x/MDL*3: When/MDLoptionand/LPoptioniscombined,“3”cannotbespecifiedforType3code.*4: The/HAoptioncanbespecifiedonlyinthecombinationofType2code“1”andType3code“0.”*5: Whenthe/CToptionisspecified,theUT32Adoesnotconformtothesafetystandards(UL

andCSA)andCEmarking(Productswith/CToptionarenotintendedforEEA-market).*6: UT32Ahasapanelmounttype(withoutoption/MDL).PleaseseetheOperationGuide(IM

05P01D31-11EN).*7: UT32AhasalsoaDual-looptypemodel;forinformation,seeManualsinSection-6.

Accessories (sold separately)Thefollowingisanaccessorysoldseparately.• LL50AParameterSettingSoftware

Model Suffixcode DescriptionLL50A -00 ParameterSettingSoftware

• ExternalPrecisionResistorModel Suffixcode Description

X010 SeetheGeneralSpecifications(*) ResistanceModule

*:Necessarytoinputthecurrentsignaltothevoltageinputterminal.• TerminalCover ForUT35A:ModelUTAP001;ForUT32A:ModelUTAP002• Manuals Note:Manualscanbedownloadedfromawebsite.URL:http://www.yokogawa.com/ns/ut/im/• Brackets Partnumber:L4502TP(2pcsforupperandlowersides)• Wallmountbracket ForUT32A/MDL:ModelUTAP005

3. How to Install

Installation LocationThe instrument shouldbe installed in indoor locationsmeeting the followingconditions:• Instrumented enclosure This instrument isdesignedtobemounted inan instrumentedenclosure.Mounttheinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched. Be sure to mount the instrument in an enclosure with a door.• Well ventilated locations Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-naltemperaturefromrising.

However,makesurethattheterminalportionsarenotexposedtowind.Exposureto wind may cause the temperature sensor accuracy to deteriorate. To mount mul-tiple indicatingcontrollers,seetheexternaldimensionswhichfollow. Ifmountingother instrumentsadjacent to the instrument,complywith theseexternaldimen-sionstoprovidesufficientclearancebetweentheinstruments.

• Locations with little mechanical vibration Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.• Horizontal location Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationtotherightorleft.

NoteIf the instrument ismovedfroma locationwith lowtemperatureand lowhumiditytoaplacewithhightemperatureandhighhumidity,or if thetemperaturechangesrapidly,condensationwill result.Moreover, in thecaseof thermocouple inputs,measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthenewenvironmentunderambientconditionsformorethan1hourpriortousingit.

Donotmounttheinstrumentinthefollowinglocations:• Outdoors• Locations subject to direct sunlight or close to a heater Install the instrument in a location with stable temperatures that remain close to an averagetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlightorclosetoaheater.Doingsoadverselyaffectstheinstrument.

• Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases

Thepresenceofoily fumes,steam,moisture,dust,orcorrosivegasesadverselyaffectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyofthese substances.

• Areasnearelectromagneticfieldgeneratingsources Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Iftheinstrument isusedin locationsclosetoastrongelectromagneticfieldgeneratingsource,themagneticfieldmaycausemeasurementerrors.

• Areasclosetoflammablearticles Absolutelydonotplacetheinstrumentdirectlyonflam-mablesurfaces. Ifsuchacircumstance isunavoidableandtheinstrumentmustbeplacedclosetoaflammableitem,provideashieldforitmadeof1.43mmthickplatedsteel or 1.6 mm thick unplated steel with a space of at least150mmbetweenitandtheinstrumentonthetop,bottom,andsides.

• Areas subject to being splashed with water

WARNING

Be sure to turn OFF the power supply to the controller before in-stalling it on the enclosure to avoid an electric shock.

Mounting on a DIN RailInserttheDINrailintothetopareaofDINrailgroove(attwolocations)ontherearpanel,andsecureinplacewiththebottomslidelock.

DIN rail

DIN rail

Slide lockUT35A/MDL: 2, UT32A/MDL: 1

Fit into here

Push

CAUTION

Make sure that foreign materials do not enter the inside of the in-strument through the case’s slit holes.

150 mm150 mm

150 mm

150 mm

OperationGuideIM 05P01D81-11EN

UT35A/MDL, UT32A/MDLDigital Indicating Controller (DIN Rail Mounting Type)Operation Guide

This operation guide describes installation, wiring, and other tasks required to make the controller ready for operation.

3rd Edition: Nov. 2017

For details of the each function, refer to the electronic manual. Manuals can be downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

«Standard Code Model»

www.yokogawa.com/ns

YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPANYOKOGAWA CORPORATION OF AMERICA

Head office and for product sales2 Dart Road, Newnan, Georgia 30265, USA

YOKOGAWA EUROPE B.V.Headquarters

Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

All Rights Reserved, Copyright © 2015 Yokogawa Electric Corporation

Page 2: UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN ... · Thank you for purchasing the UT35A/MDL, UT32A/MDL Controller. (The UT35A and UT32A with option /MDL have no display.)

IM 05P01D81-11EN page 2/6

Removing from the DIN RailInsertaflat-bladescrewdriver(guideline:100mmshaft length,6mmbladewidth,0.8mmbladethickness)intothebottomslidelockholeandpulldowntoreleasetheslide lock.OntheUT55A/MDL, thereare twoslide locks.Releasetheotherslidelockafteryoureleasethefirstslide lock.Whenbothslide locksareunlocked, theinstrumentcanberemovedfromtheDINrail.

DIN rail

Slide lockUT35A/MDL: 2, UT32A/MDL: 1

Pull

Push up

DIN rail

4. HardwareSpecifications

WARNING

This instrument is for Measurement Category No.1.Do not use it for measurements in locations falling under Measure-ment Categories No.2, No.3, and No.4.

Internal Wiring

Outlet

Entrance IVCable

III TO( I )

II

Category IEC/EN/CSA/UL 61010-1 EN 61010-2-030 Remarks

No.1 Measurement CategoryI O(Other) For measurements performed on circuits not direct-

lyconnectedtoMAINS.

No.2 Measurement CategoryII

Measurement CategoryII

For measurements performed on circuits directly connectedtothelow-voltageinstallation.

No.3 Measurement CategoryIII

Measurement CategoryIII

Formeasurementsperformedinthebuildinginstal-lation.

No.4 Measurement CategoryIV

Measurement CategoryIV

For measurements performed at the source of the low-voltageinstallation.

InputSpecifications

UniversalInput(Equippedasstandard)• Numberofinputs:1• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,

Input Type Instrument Range

AccuracyºC ºF

Thermo-couple

K-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor

0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±2%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleK±1%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleT

-270.0to1000.0ºC -450.0to2300.0ºF-200.0to500.0ºC -200.0to1000.0ºF

J -200.0to1200.0ºC -300.0to2300.0ºF

T-270.0to400.0ºC -450.0to750.0ºF

0.0to400.0ºC -200.0to750.0ºF

B 0.0to1800.0ºC 32to3300ºF

±0.15%ofinstrumentrange±1digitfor400°Cormore ±5%ofinstrumentrange±1digitforlessthan400°C

S 0.0to1700.0ºC 32to3100ºF±0.15%ofinstrumentrange±1digit

R 0.0to1700.0ºC 32to3100ºF

N -200.0to1300.0ºC -300.0to2400.0ºF±0.1%ofinstrumentrange±1digit±0.25%ofinstrumentrange±1digitforlessthan0°C

E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±1.5%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleE.

L -200.0to900.0ºC -300.0to1600.0ºF

U-200.0to400.0ºC -300.0to750.0ºF

0.0to400.0ºC -200.0to1000.0ºF

W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit(Note2)

Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit

PR20-40 0.0to1900.0ºC 32to3400ºF

±0.5%ofinstrumentrange±1digitfor800°Cormore Accuracyisnotguaranteedforlessthan800°C.

W97Re3-W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit

RTD

JPt100-200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit

(Note1)-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit

Pt100-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit

(Note1)-200.0to500.0ºC -300.0to1000.0ºF-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit

Standardsignal0.400to2.000V

±0.1%ofinstrumentrange±1digit

1.000to5.000V4.00to20.00mA

DCvoltage/current

0.000to2.000V0.00to10.00V0.00to20.00mA-10.00to20.00mV0.0to100.0mV

Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.

Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange between-100and200°C.

Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988

•Inputsampling(control)period:200ms•Burnoutdetection: FunctionsatTC,RTD,andstandardsignal. Upscale,downscale,andoffcanbespecified. Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4 mAorless.

•Inputbiascurrent:0.05µA(forTCorRTD)•Measuredcurrent(RTD):About0.16mA•Inputresistance: TCormVinput:1MΩormore Vinput:About1MΩ mAinput:About250Ω

•Allowablesignalsourceresistance: TCormVinput:250Ωorless Effectsofsignalsourceresistance:0.1µV/Ωorless DCvoltageinput:2kΩorless Effectsofsignalsourceresistance:About0.01%/100Ω• Allowablewiringresistance: RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires shallbeequal.)

Wiringresistanceeffect:±0.1ºC/10Ω• Allowableinputvoltage/current: TC,mV,mAandRTDinput:±10VDC Vinput:±20VDC mAinput:±40mA• Noiserejectionratio: Normalmode:40dBormore(at50/60Hz) Commonmode:120dBormore(at50/60Hz) For100-240VAC, thepower frequencycanbesetmanually.Automatic detectionisalsoavailable.

For24VAC/DC,thepowerfrequencycanbesetmanually.• Referencejunctioncompensationerror: ±1.0ºC(15to35ºC),±1.5ºC(-10to15ºCand35to50ºC)• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD

ContactInputSpecifications• Numberofinputs:SeethetableofModelandSuffixCodes.• Inputtype:No-voltagecontactinputortransistorcontactinput• Inputcontactrating:12VDC,10mAormore Useacontactwithaminimumon-currentof1mAorless.• ON/OFFdetection: No-voltagecontactinput: Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact resistanceof50kΩormoreas“OFF.” Transistorcontactinput: Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust notexceed100µAwhen“OFF.”• Minimumstatusdetectionholdtime:Controlperiod+50ms• Use:SPswitch,operationmodeswitch,andeventinput

AnalogOutputSpecifications• Numberofoutputs: Controloutput:1 Cooling-sidecontroloutputofHeating/cooling type (Retransmissionoutput terminal):1

• Outputtype:Currentoutputorvoltagepulseoutput• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless) Theaccuracy isthat inthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz.

• Voltagepulseoutput: Use:Timeproportionaloutput On-voltage:12Vormore/loadresistanceof600Ωormore Off-voltage:0.1VDCorless Timeresolution:10msor0.1%ofoutput,whicheverislarger

RetransmissionOutputSpecifications• Numberofoutputs:Retransmissionoutput;1,sharedwith15VDC looppowersupplyorCooling-sidecontroloutput.

• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy(conversionaccuracyfromPVdisplayonthesetscale):±0.1%ofspan(±5%ofspanfor1mAorless)

Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz. This isnotconversionaccuracythroughinputandoutputbut theperformanceof

transmission output itself.

15VDCLoopPowerSupplySpecifications(SharedwithretransmissionoutputorCooling-sidecontroloutput.)• Powersupply:14.5to18.0VDC• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)

StepResponseTimeSpecificationsWithin1s(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspanisapplied)

External Dimensions

UT35A/MDL

37(1.46)

96(3.78) 20(0.79) 100(3.94)

Note:TrigonometryGeneral tolerance = ±(JIS B 0401-1998 tolerance class IT18)/2

Unit: mm(inch)

60(2.36)

DIN railTH35-75A

Cable for LL50

Minimum cable curvature: R40 (1.57)

4.3(0.17)

4(0.

16)

90 (3

.54)

min

.(r

equi

red

for r

emov

ing

the

inst

rum

ent f

rom

the

DIN

rail)

120

(4.7

2) m

in.

(requ

ired

for i

nser

ting/

rem

ovin

g th

e ca

ble

for L

L50A

)

91.6

(3.6

1)

114(

4.49

)10

0(3.

94)

94.6

(3.7

2)

UT32A/MDL

15(0.59)

48.2(1.90) 20(0.79) 100(3.94)

Unit: mm(inch)

60(2.36)

DIN railTH35-75A

Cable for LL50

4.3(0.17)

4(0.

16)

91.6

(3.6

1)

114(

4.49

)10

0(3.

94)

94.6

(3.7

2)

Note:TrigonometryGeneral tolerance = ±(JIS B 0401-1998 tolerance class IT18)/2

Minimum ca

ble curva

ture: R40 (1

.57)

90 (3

.54)

min

.(r

equi

red

for r

emov

ing

the

inst

rum

ent f

rom

the

DIN

rail)

120

(4.7

2) m

in.

(requ

ired

for i

nser

ting/

rem

ovin

g th

e ca

ble

for L

L50A

)

Page 3: UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN ... · Thank you for purchasing the UT35A/MDL, UT32A/MDL Controller. (The UT35A and UT32A with option /MDL have no display.)

IM 05P01D81-11EN page 3/6

RelayContactOutputSpecifications• Contacttypeandnumberofoutputs: Controloutput:contactpoint1c;1point Heating/coolingtype:contactpoint1a;2pointsforbothheatingandcoolingsides Alarmoutput:contactpoint1a;3points(commonisindependent)• Contactrating: Contactpoint1c(controloutput):250VAC,3Aor30VDC,3A(resistanceload) Contactpoint1a(controloutput):240VAC,3Aor30VDC,3A(resistanceload) Contactpoint1a(alarmoutput):240VAC,1Aor30VDC,1A(resistanceload)• Use:Timeproportionaloutput,alarmoutput,FAILoutput,etc.• Timeresolutionofcontroloutput:10msor0.1%ofoutput,whicheverislargerNote:Thecontroloutputshouldalwaysbeusedwithaloadof10mAormore. Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.

TransistorContactOutputSpecifications• Numberofoutputs:SeethetableofModelandSuffixCodes.• Outputtype:Opencollector(SINKcurrent)• Outputcontactrating:Max.24VDC,50mA• Outputtimeresolution:Min.200ms• Use:Alarmoutput,FAILoutput,etc.

HeaterBreakAlarmSpecifications• Numberofinputs:2• Numberofoutputs:2(transistorcontactoutput)• Use:Measurestheheatercurrentusinganexternalcurrenttransformer(CT)andgeneratesaheaterbreakalarmwhenthemeasuredvalueis lessthanthebreakdetectionvalue.

• Currenttransformerinputresistance:About9.4Ω• Currenttransformerinputrange:0.0to0.1Arms(0.12Armsormorecannotbeapplied.)• Heatercurrentsettingrange:OFF,0.1to300.0Arms Heatercurrentmeasuredvaluedisplayrange:0.0to360.0Arms Note:TheCTratiocanbeset.CTratiosettingrange:1to3300• RecommendedCT:CTfromU.R.D.,Ltd. CTL-6-S-H:CTratio800,measurablecurrentrange:0.1to80.0Arms CTL-12L-30:CTratio3000,measurablecurrentrange:0.1to180.0Arms• Heatercurrentmeasurementperiod:200ms• Heatercurrentmeasurementaccuracy:±5%ofcurrent transformer input rangespan±1digit(CTerrorisnotincluded.)

• Heatercurrentdetectionresolution:Within1/250ofcurrenttransformerinputrangespan• BreakdetectionOn-time:Min.0.2second(fortimeproportionaloutput)

24VDCLoopPowerSupplySpecifications• Use:Powerissuppliedtoa2-wiretransmitter.• Powersupply:21.6to28.0VDC• Ratedcurrent:4to20mADC• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)

MaintenacePortSpecificationsThemaintenanceport isusedtoconnectadedicatedcablewhenusingtheLL50AParameterSettingSoftware (soldseparately).Through thisport, youcansetcontrollerparameters,downloadladderprograms,andsoon.Fordetails,seetheLL50AUser’sManual(IM05P05A01-02EN).

Dedicated cable

LL50A Parameter Setting Software

To USB terminal

NoteUseLL50Awiththecontrollerturnedon.(Thededicatedcablemustbeconnected.LL50ALight-loaderadaptercannotbeused.)ThemaintenanceportisnotisolatedfromthePVinputterminal.Usetheportonlyformaintenancepurposes,suchasforsettingthecontrollerparameters.

SafetyandEMCStandards• Safety: CompliantwithIEC/EN61010-1(CE),IEC/EN61010-2-201(CE),IEC/EN61010-2-030(CE),approvedbyCAN/CSAC22.2No.61010-1(CSA),approvedbyUL61010-1.

Installationcategory:II Pollutiondegree:2 Measurementcategory:I(CATI)(UL,CSA) O(Other)(CE) Ratedmeasurementinputvoltage:Max.10VDC Ratedtransientovervoltage:1500V(*) *ThisisareferencesafetystandardvalueformeasurementcategoryIofCSA/UL61010-

1,andformeasurementcategoryOofIEC/EN61010-2-030.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.

• EMCstandards: CompliantwithCEmarking EN61326-1ClassA,Table2(Foruseinindustriallocations), EN61326-2-3 *Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe

rangeduringtesting. EN55011ClassA,Group1 EN61000-3-2ClassA EN61000-3-3 EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-

ingLL50A) EN55011ClassA,Group1• KCmarking: Electromagneticwave interferencepreventionstandard,electromagneticwave

protection standard compliance

Construction,Installation,andWiring• Construction:DINrailmountingtype• Material:Polycarbonate(Flameretardancy:UL94V-0) DINrailmountingbracketmaterial:Panelsteelsheet• Casecolor:Black(Lightcharcoalgray)• Weight:1kgorless• Externaldimensions(mm): UT35A/MDL:96(width)x114(height)x100(depth) UT32A/MDL:48.2(width)x114(height)x100(depth)• CompatibleDINrails:TH35-7.5Fe,TH35-7.5Aℓ,JISC2812• Mountingposition:Horizontal.• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)

PowerSupplySpecificationsandIsolation• Powersupply: Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz 24VAC/DC(+10%/-15%)(for/DCoption)• Powerconsumption:UT35A:18VA(DC:9VA,AC:14VAif/DCoptionisspecified) UT32A:15VA(DC:7VA,AC:11VAif/DCoptionisspecified)• Databackup:Nonvolatilememory• Powerholduptime:20ms(for100VACdrive)• Withstandingvoltage Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA) Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE) Betweenprimaryterminals:1500VACfor1minute Betweensecondaryterminals:500VACfor1minute (Primaryterminals:Power*andrelayoutputterminals;Secondaryterminals: AnalogI/Osignalterminals,contactinputterminals,communicationterminals andfunctionalgroundingterminals.)

*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.• Insulationresistance:Betweenpowersupplyterminalsandagroundingterminal20MΩormoreat500VDC

• IsolationspecificationsPV (universal ) input terminals / remote input terminals

Control relay (contact point c/contact point a x 2) output terminals

Alarm-1 relay (contact point a) output terminals

Alarm-2 relay (contact point a) output terminals

Alarm-3 relay (contact point a) output terminals

Contact input terminals (all)RS-485 communication terminals

24 V DC loop power supply terminals

Contact output (transistor) terminals

Ethernet communication terminal

PROFIBUS-DP/DeviceNet/CC-Link communication terminals

Current transformer input terminals

Control, retransmission (analog) output terminals(not isolated between the analog output terminals)

Internalcircuits

Powersupply

The circuits divided by lines are insulated mutually.

EnvironmentalConditions

Normal Operating Conditions:• Ambienttemperature:-10to50°C IftheCC-Linkoptionisspecified,0to50°CforUT35A/MDL;0to40°CforUT32A/MDL.(side-by-sidemounting:0to50°CforUT55A/MDL;0to40°CforUT52A/MDL)

• Ambienthumidity:20to90%RH(nocondensationallowed)

• Magneticfield:400A/morless• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90minuteseachinthethreeaxisdirections

Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseachinthethreeaxisdirections

• Short-periodvibration:14.7m/s2,15secondsorless• Shock:98m/s2orless,11ms• Altitude:2000morlessabovesealevel• Warm-uptime:30minutesormoreafterthepoweristurnedon• Startuptime:Within10seconds *: TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.

TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelow temperature.However,thecontrolfunctionisnotaffected.

Transportation and Storage Conditions:• Temperature:-25to70ºC• Temperaturechangerate:20ºC/horless• Humidity:5to95%RH(nocondensationallowed)

Effects of Operating Conditions• Effectofambienttemperature: VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger Currentinput:±0.01%ofF.S./ºC RTDinput:±0.05ºC/ºC(ambienttemperature)orless Analogoutput:±0.02%ofF.S./ºCorless• Effectofpowersupplyvoltagefluctuation Analoginput:±0.05%ofF.S.orless Analogoutput:±0.05%ofF.S.orless (Eachwithinratedvoltagerange)

5. How to Connect Wires

WARNING

• Wiring work must be carried out by a person with basic electrical knowledge and practical experience.

• Be sure to turn OFF the power supply to the controller before wiring to avoid an electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.

• For the wiring cable, the temperature rating is 75 °C or more.• As a safety measure, always install a circuit breaker (an IEC

60947-compatible product, 5 A, 100 V or 220 V AC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.

• Install the power cable keeping a distance of more than 1 cm from other signal wires.

• The power cable is required to meet the IEC standards concerned or the requirements of the area in which the instrument is being installed.

• Wiring should be installed to conform to NEC (National Electrical Code: ANSI/NFPA-70) or the wiring construction standards in countries or regions where wiring will be installed.

• Since the insulation provided to each relay output terminal is Functional insulation, provide Reinforced insulation to the external of the device as necessary. (Refer to the drawing below.)

This product

Functional insulation

A safety voltage circuit

A safety voltage circuit

This product

Reinforced insulation

Reinforced insulation

Functional insulation

A hazardous voltage circuit

A hazardous voltage circuit

A safety voltage circuit

A safety voltage circuit

This product

Reinforced insulation

Reinforced insulation

Functional insulation

A hazardous voltage circuit

A hazardous voltage circuit

A hazardous voltage circuit

A hazardous voltage circuit

CAUTION

• When connecting two or more crimp-on terminal lugs to the single terminal block, bend the crimp-on terminal lugs before tightening the screw.

• Note that the wiring of two or more crimp-on terminal lugs to the single high-voltage terminal of the power supply and relay, etc. does not comply with the safety standard.

CAUTION

• Provide electricity from a single-phase power supply. If the power is noisy, install an isolation transformer on the primary side, and use a line filter on the secondary side. When measures against noise are taken, do not install the primary and secondary power cables close to each other.

• If there is a risk of external lightning surges, use a lightning arrester etc.

• For TC input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires.

• Since the control output relay has a life span (resistance load of 100,000 times), use the auxiliary relay to perform ON/OFF control.

• The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.

• After completing the wiring, the terminal cover is recommended to use for the instrument.

RecommendedCrimp-onTerminalLugs

(A)

(F)

(ød)

5.5 3.3

Recommendedtighteningtorque:0.6N·m Applicablewiresize:Powersupplywiring1.25mm2 or moreApplicable terminal lug Applicable wire size mm2 (AWG#) (φd) (A) (F)M3 0.25to1.65(22to16) 3.3 5.5 4.2

CableSpecificationsandRecommendedCablesPurpose Name and Manufacturer

Powersupply,relaycontactoutputs 600VGradeheat-resistantPVCinsulatedwires,JISC3317(HIV),0.9to2.0mm2

Thermocouple Shieldedcompensatingleadwires,JISC1610Forthermocoupleinput(PVinputandremoteinputwithdirectinput),shieldedcompensatingleadwireofcross-sectionalarealessthanorequalto0.75mm2isrecommended.Ifthecross-sectionalareaiswide,thereferencejunctioncompensationerrormaybelarge.

RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)Othersignals(otherthancontactinput/output) Shielded wiresOthersignals(contactinput/output) UnshieldedwiresRS-485communication Shielded wiresEthernetcommunication 100BASE-TX(CAT-5)/10BASE-TPROFIBUS-DPcommunication DedicatedcableforPROFIBUS-DP(Shieldedtwo-wires)DeviceNetcommunication DedicatedcableforDeviceNet(Shieldedfive-wires)CC-Linkcommunication DedicatedcableforCC-Link(Shieldedthree-wires)

PROFIBUS-DP/CC-LinkConnector(wiringside)(Partnumber:A1987JT)DeviceNetConnector(wiringside)(Partnumber:L4502BW)Recommendedtighteningtorque:0.5to0.6N·m

DC Relay Wiring

R

External DC power supplyRelayUT35A, UT32A

UT’s contact

Diode(Mount it directlyto the relay coilterminal (socket).)

Relay(Use one with a relay coil rating

less than the UT’s contact rating.)

AC Relay Wiring

UT35A, UT32A

R

UT’s contact CR filter(Mount it directlyto the relay coilterminal (socket).)

External AC power supply

Relay(Use one with a relay coilrating less than the UT’s

contact rating.)

Transistor Output Wiring

power+ –

UTDO

LoadCOM

Page 4: UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN ... · Thank you for purchasing the UT35A/MDL, UT32A/MDL Controller. (The UT35A and UT32A with option /MDL have no display.)

IM 05P01D81-11EN page 4/6

6. Terminal Wiring Diagrams

CAUTION

• Do not use an unassigned terminal as the relay terminal. Do not use a 100-240 V AC power supply for the 24 V AC/DC

model; otherwise, the instrument will malfunction.

UT35A/MDL

E4-terminal area

E3-terminal area

PV

E1-terminal area

PV inputTC input RTD input

Voltage (mV, V) input

A

+

-

+

-

Current (mA) input

+

-

B

b

(Suffix code: Type 1=-2)

(Suffix code: Type 1=-2)

(24 V AC/DC power supply: Option code /DC)

(Equippedas standard)

Power supply

101

102

103

104

105

106

107

108

109

110

111

501

502

503

504

505

506

507

508

509

510

511

512

407

408

409

410

411

412

301

302

303

304

305

306

201

202

203

204

205

206

207

208

210

211

212

Cooling-side control output

101-112

501-512

401-412

301-306

201-212

ALM (Equipped as standard)Contact output

External contact output (relay)

AL3

AL2

AL1

Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)

Alarm-3 output(PV high limit)

Alarm-2 output( PV low limit)

Alarm-1 output(PV high limit)

Common

Common

Common

UT104

105

106

107

108

109

100-240 V AC power supply

N

L

Allowable range: 100-240 V AC (+10%/-15%) (free voltage) 50/60 Hz shared

110

111

24 V AC/DC power supply

-

+

110

111

202

203

201

202

203

202

203

203

204

RET/OUT2Current/voltage pulse output

0-20 mA DC,4-20 mA DC,Voltage pulse (12V)

+

-

205

206

Factory default: PV input type is undefined.

OUT(Suffix code: Type1=-0)

Control output

101

102

Relay contact output

103

NC

NO

COM

Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)

Factory default: Control output is relay.

OUTCurrent/voltage pulse output

0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)

+

Retransmission output

+

-

Default: 4-20 mA DC

Default: Undefined

0-20 mA DC,4-20 mA DC

Control output (Suffix code: Type1=-0 or -2)

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

207

208

207

- 208

207

208

Can be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is not used for control output.Current output range can be changed.

RETRetransmission output

4-20 mA DC or0-20 mA DC

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

+

-

Default: 4-20 mA DC

Default: PV retransmission

Load resistance 600 Ω or less

Retransmission output (Equipped as standard)

205

206

205

206

Can be used for 15 V DC loop power supply when not used for retransmission output.

DI (Equipped as standard)Contact input

Contact rating: 12 V DC, 10 mA or more

External contact input

DI2

DI1

COM

AUTO when DI1=ONMAN when DI1=OFF

STOP when DI2=ONRUN when DI2=OFF

Common

DI2

DI1

COM

+5V

+5V

No-voltagecontact

Transistor contactUT UT

210

211

212

210

211

212

Function can be assigned to the terminals with no function.

112

112 112

N

L

Can not be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is used.Can be used for retransmission output or 15 V DC loop power supply when control output is not used.Current output range can be changed.

Heating/cooling control outputHeating/cooling relay contact output

NO

Heating-side

Cooling-side

NO

COM

Contact rating: 240 V AC, 3 A 30 V DC, 3 A (resistance load)

101

102

103

OUTOUT2

(Suffix code: Type 2=2)Contact inputExternal contact input

DI11

DI12

DI13

DI14

DI15

COMCommon

DI11

DI12

COM+5V

+5V

No-voltage contact Transistor contact

Contact rating: 12 V DC, 10 mA or more

DI13+5V

DI14+5V

DI15+5V

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

UT UT

301

302

303

304

305

306

301

302

303

304

305

306

Function can be assigned to the terminals with no function.

DI

E1-Terminal Area301-306

+

24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC)

24 V DC loop power supply

505

506

LPS24(Option code /LP)

(Suffix code: Type 2=2)Contact outputExternal contact output

DO42

DO41

DO43

DO44

DO45

COM

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

Factory default: No function

Common

UT501

502

503

504

505

506

DO

Transistor contact rating: 24 V DC, 50 mAFunction can be assigned to the terminals with no function.

E4-Terminal Area501-506E4-terminal area

E3-terminal area

E1-terminal area

101

102

103

104

105

106

107

108

109

110

111

501

502

503

504

505

506

507

508

509

510

511

512

407

408

409

410

411

412

301

302

303

304

305

306

201

202

203

204

205

206

207

208

210

211

212

101-112

501-512

401-412

301-306

201-212

112

(Suffix code: Type 3=2)

Ethernet communication (with gateway function)

10BASE-T/100BASE-TXRJ45 connector

ColorLitUnlit

Amber100M bps10M bps

Green

LinkedActiveLink failure

Color

LitBlinkUnlit

Upper side LED (baud rate)

Lower side LED (link activity)

RS-485

RSB(+)

RSA(-)

SG

407

408

409

ETHRRS-485

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

RS-485 communication(Suffix code: Type 3=1)

407

408

409

410

411

RS485

E3-Terminal Area401-412

(Suffix code: Type 3=4)

PROFIBUS-DP communication (with Modbus master)

Pin1

2

Signal name DescriptionVP

RxD/TxD-P

3 RxD/TxD-N

4 DGND5 SHIELD

+5V bus powerData signal (positive data receive/transmit)

Data signal (negative data recive/transmit)

Signal groundShield ground

RS-485

RSB(+)

RSA(-)

SG

407

408

409

PROF

If the UT is located at the end of a segment for the PROFIBUScommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (390 Ω: 2 pcs. 220 Ω: 1 pc., or an activeterminator.)

VP

RxD/TxD-PData line

Data line

390Ω

220Ω

390ΩRxD/TxD-N

DGND

CHKRDYERR

LEDCHK(red)

RDY(green)

Lit Unlit

ERR(red)

User profile error Normal

NormalNot connected, orcommunicationfailure (flashing)

NormalCommunicatingsuccessfully

No power, or Communication failure

1

2

3

4

5

(Suffix code: Type 3=3)

CC-Link communication (with Modbus master)

RS-485

RSB(+)

RSA(-)

SG

407

408

409

CC-L

If the UT is located at the end of a segment for the CC-Linkcommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (110 Ω: 1 pc.)

DA

DB

110Ω

LEDCHK(red)

L ERR(red)

L RUN(green)

Lit Unlit

CHK

L RUNL ERR

User profile error/Address error Normal

Normal

Pin12

Signal name Description

DA

DB3 DG4

SLD

5

FG

RX/TX + signal

RX/TX - signal

Flame ground

RX/TX signal ground

Shield

NormalCommunicating successfully

Communication failure (CRC error)

No carrier detected/Communication timeout

1

2

3

4

5

(Suffix code: Type 3=5)

DeviceNet communication (with Modbus master)

RS-485

RSB(+)

RSA(-)

SG

407

408

409

DNET

If the UT is located at the end of a segment for the DeviceNetcommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (121 Ω: 1 pc.)

CAN_H

CAN_L

121Ω

LEDCHK(red)

MNS(green/red)

Lit/flashing Unlit

User profile error Normal

Pin12

Signal name Description

CAN_H

CAN_L

3

V+

4

V-5

DRAINRX/TX + signal

RX/TX - signal

Shield/Drain wire

DeviceNet power supply 24V

DeviceNet power supply common

Normal, communicating successfully (green, lit).Not connected (green, flashing).

Critical link failure (red, lit).Connection timeout (red, flashing)

At power-on/Communication faulted (green/red, flashing)

No electricity

CHK

MNS

1

2

3

4

5

Page 5: UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN ... · Thank you for purchasing the UT35A/MDL, UT32A/MDL Controller. (The UT35A and UT32A with option /MDL have no display.)

IM 05P01D81-11EN page 5/6

UT32A/MDL

(Suffix code: Type 1=-2)

(Suffix code: Type1=-0) Retransmission output

4-20 mA DC or0-20 mA DC

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

+

-

Default: 4-20 mA DC

Default: PV retransmission

Load resistance 600 Ω or less

Retransmission output (Equipped as standard)PV inputTC input RTD input

Voltage (mV, V) input

A

+

-

+

-

Current (mA) input

+

-

B

b

(Equipped as standard)Control output

Relay contact output

NC

NO

COM

Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)

111

301

302

303

304

305

306

201

202

203

204

205

206

207

208

210

101

102

103

104

105

106

107

108

109

110

211

212

Current/voltage pulse output

0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)

-

Heating/cooling control output(Suffix code: Type 1=-2)

Cooling-side control output

Heating/cooling relay contact output

NO

Heating-side

Cooling-side

NO

COM

Contact rating: 240 V AC, 3 A 30 V DC, 3 A (resistance load)

E1-terminal area101-112

301-312

201-212

101

102

103

202

203

201

202

203

202

203

203

204

205

206

205

206

101

102

103

+ 205

206

Factory default: Control output is relay.Can be used for 15 V DC loop power supply when not used for retransmission output.

PV RET

(Equipped as standard)Contact input

Contact rating: 12 V DC, 10 mA or more

External contact input

DI2

DI1

COM

AUTO when DI1=ONMAN when DI1=OFF

STOP when DI2=ONRUN when DI2=OFF

Common

DI2

DI1

COM

+5V

+5V

No-voltagecontact

Transistor contactUT UT

210

211

212

210

211

212

Function can be assigned to the terminals with no function.

DI

(Equipped as standard)Contact output

External contact output (relay)

AL3

AL2

AL1

Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)

Alarm-3 output(PV high limit)

Alarm-2 output(PV low limit)

Alarm-1 output(PV high limit)

Common

Common

Common

UT104

105

106

107

108

109

ALM

OUT

OUT

RET/OUT2

Factory default: PV input type is undefined.

Current/voltage pulse output

0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)

+

-

Retransmission output

+

-

Default: 4-20 mA DC

Default: Undefined

0-20 mA DC,4-20 mA DC

Control output (Suffix code: Type1=-0 or -2)

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

207

208

207

208

207

208

Can be used for retransmission output or 15 V DC loop power suppy when current/voltage pulse output is not used for control output.Current output range can be changed.

OUT

OUT2

112

Power supply24 V AC/DC power supply

-

+

100-240 V AC power supply

Allowable range: 100-240 V AC (+10%/-15%) (free voltage) 50/60 Hz shared

N

L

(24 V AC/DC power supply: Option code /DC)

110

111

110

111

112 112

N

L

Can not be used for retransmission output or 15 V DC loop power suppy when current/voltage pulse output is used for control output.Can be used for retransmission output or 15 V DC loop power suppy when control output is not used.Current output range can be changed.

(Option code /HA)Heater break alarmHeater current detection input

CT1

CT2

COM

310

311

312

HBAExternal contact output (transistor)

Transistor contact rating: 24 V DC, 50 mA

Heater break alarm-1output

Heater break alarm-2output

Common

HAL1

HAL2

COM

UT307

308

309

307

308

309

310

311

312

+

24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC)

-

24 V DC loop power supply

(Suffix code: Type 2=0 and option code /LP)305

306

LPS24

E1-Terminal Area301-306

RS-485

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

RS-485 communication(Suffix code: Type 2=1)

301

302

303

304

305

RS485

RS-485

RSB(+)

RSA(-)

SG

RS-485 communication/24 V DC loop power supply

+

24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC)

-

301

302

303

305

306

RS485/LPS24(Suffix code: Type 2=1 and option code /LP)

CC-Link communication (with Modbus master)

(Suffix code: Type 3=3)FG: Flame ground

SLD: Shield

DG: TX/RX signal ground

DB: RX/TX signal - signal

DA: RX/TX signal + signal

CHK(red)(Lit: User profile error/Adress error, Unlit: Normal)

L ERR(red)(Lit: Communication failure(CRC error), Unlit: Normal)

L RUN(green)(Lit: Normal, Unlit: No carrier detected/Communication timeout)

Not used

301

302

303

304

305

306

307

308

309

RS-485

RSB(+)

RSA(-)

SG

310

311

312

DB

DA

110Ω

CC-LIf the UT is located at the end of a segment for the CC-Link communication wiring,terminating resistors are separately needed.These are to be prepared by users. (110 Ω: 1 pc.)

• AuthorisedRepresentativeintheEEA YokogawaEuropeBV.(Address:Euroweg2,3825HDAmersfoort,TheNether-lands) istheAuthorisedRepresentativeofYokogawaElectricCorporationforthisProductintheEEA.

• Printed ManualsModel Description

UT35A,UT32ADigitalIndicatingController(PanelMountingType)Operation Guide «StandardCodeModel»

IM05P01D31-11EN

UT35A,UT32ADigitalIndicatingController(PanelMountingType)OperationGuide«DetailedCodeModel»

IM05P01D31-15EN

UT35A/MDL,UT32A/MDLDigitalIndicatingController(DINRailMountingType)Operation Guide «StandardCodeModel»

IM05P01D81-11EN

UT32A-DDigitalIndicatingController(Dual-loop,PanelMountingType)Operation Guide «StandardCodeModel»

IM05P08D31-11EN

UT32A-D/MDLDigitalIndicatingController(Dual-loop,DINRailMountingType)Operation Guide «StandardCodeModel»

IM05P08D81-11EN

UT35A/RSP,UT32A/RSPDigitalIndicatingController(Non-isolatedRemoteInput,PanelMountingType)OperationGuide«StandardCodeModel»

IM05P01D31-81EN

UT32ADigitalIndicatingControllerOperationGuide«EntryModel» IM05P01F31-11ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11ENUTAP005WallMoountBracketUser'sManual IM05P06A31-02Z1

• ElectronicManuals Youcandownloadthelatestmanualsfromthefollowingwebsite: URL:http://www.yokogawa.com/ns/ut/im/

Model DescriptionUT35A,UT32ADigitalIndicatingController(PanelMountingType)Operation Guide «StandardCodeModel»

IM05P01D31-11EN

UT35A,UT32ADigitalIndicatingController(PanelMountingType)OperationGuide«DetailedCodeModel»

IM05P01D31-15EN

UT35A/MDL,UT32A/MDLDigitalIndicatingController(DINRailMountingType)Operation Guide «StandardCodeModel»

IM05P01D81-11EN

UT35A/UT32ADigitalIndicatingControllerUser’sManual IM05P01D31-01ENUT32A-DDigitalIndicatingController(Dual-loop,PanelMountingType)Operation Guide «StandardCodeModel»

IM05P08D31-11EN

UT32A-D/MDLDigitalIndicatingController(Dual-loop,DINRailMountingType)Operation Guide «StandardCodeModel»

IM05P08D81-11EN

UT32A-D,UT32A-D/MDLDigitalIndicatingControllerUser’sManual IM05P08D31-01ENUT35A/RSP,UT32A/RSPDigitalIndicatingController(Non-isolatedRemoteInput,PanelMountingType)OperationGuide«StandardCodeModel»

IM05P01D31-81EN

UT32ADigitalIndicatingControllerOperationGuide«EntryModel» IM05P01F31-11ENUT32ADigitalIndicatingControllerUser’sManual«EntryModel» IM05P01F31-01ENUTAdvancedSeriesCommunicationInterface(RS-485,Ethernet)User’sManual IM05P07A01-01ENUTAdvancedSeriesCommunicationInterface(OpenNetwork)User’sManual IM05P07A01-02ENLL50AParameterSettingSoftwareInstallationManual IM05P05A01-01ENLL50AParameterSettingSoftwareUser’sManual IM05P05A01-02ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11ENUTAP005WallMoountBracketUser'sManual IM05P06A31-02Z1

• GeneralSpecificationModel Description

UT35A,UT32ADigitalIndicatingController(PanelMountingType) GS05P01D31-01ENUT35A/MDL,UT32A/MDLDigitalIndicatingController(DINRailMountingType) GS05P01D81-01ENUT32A-DDigitalIndicatingController(Dual-loop,PanelMountingType) GS05P08D31-01ENUT32A-D/MDLDigitalIndicatingController(Dual-loop,DINRailMountingType) GS05P08D81-01ENLL50AParameterSettingSoftware GS05P05A01-01EN

* Thelasttwocharactersofthemanualnumberandgeneralspecificationnumberindicatethelanguageinwhichthemanualiswritten.

Page 6: UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN ... · Thank you for purchasing the UT35A/MDL, UT32A/MDL Controller. (The UT35A and UT32A with option /MDL have no display.)

IM 05P01D81-11EN page 6/6

7. Setup ProcedureThe following flowchartshows thesetupprocedure forUT35A/MDLandUT32A/MDL.PerformsetupthroughcommunicationortheLL50AParameterSettingSoftware(soldseparately).

Install and wire a controller.

Monitoring and control of regular operations

Adjust PID using auto-tuning or manually for PID control.

(Set parameters through communication.)

Operation

NO

YES

PID tuning

Installationand wiring

Power ON

ParameterSettings

ParameterSettings

Use LL50ASoftware?

LL50A: Parameter setting software (sold separately)See the LL50A Parameter Setting Software User’s Manual (IM 05P05A01-01EN).Use LL50A with the controller turned on. (The dedicated cable must be connected. LL50A Light-loader adapter cannot be used.)The maintenance port is not isolated from the PV input terminal. Use the port only for maintenance purposes, such as for setting the controller parameters.

To set parameters through communication, you need to create a program on the host device side. For controller parameter information (registers, relays), see the following manuals.• For setup through RS485 serial

communication or Ethernet communication, see the UTAdvanced Series Communi-cation Interface User’s Manual (IM 05P07A01-01EN).

• For setup through an open network, see the UTAdvanced Series Communication Interface (Open Network) User’s Manual (IM 05P07A01-02EN).

8. OperationsThecontrollerstatuscanbeverifiedwiththeLED.

Status LED Lit/Blinks DescriptionNormal Green LitCommunicationerror Green Blinks Checkthecommunicationwiringandsettings.

Instrument failure Red Lit Parametererror/Hardwarefailure/Ladderprogramcorruption.

Input error Red BlinksSensorburnout,inputover

Checktheinputwiringandsettings.

LED lamp

UT35A/MDL Front(with terminal cover)

UT32A/MDL Front(with terminal cover)

Check theoperatingstatus (run/stop,auto/manual, remote/local, etc.) of thecontroller throughcommunicationor theLL50AParameterSettingSoftware(soldseparately).Fordetails,see the(1)UT35A/UT32ADigital IndicatingControllerUser’sManual(IM05P01D31-01EN), (2)UTAdvancedSeriesCommunication Interface(RS-485,Ethernet)User’sManual(IM05P07A01-01EN),and(3)LL50AParameterSettingSoftwareUser’sManual(IM05P05A01-02EN).

9. TroubleshootingIfaproblemappearstobecomplicated,contactoursalesrepresentatives.

Is the controllerdefective?

Contact us for repair. Problem solved.

The LED lamp is unlit.

Yes

Yes

No

Yes

No

No

Yes

Check wiring of thepower terminals.

The LED lamp is flashing

in red.

(I/O signal failure?)

The LED lamp is lit in red.

Yes

No

Check the supply voltage.

Check the specifications and polarity

of connected devices .Check the communication-

related parameters.

Check the specificationsof communication

devices.

Check thecommunication wiring.

(Communication failure?)

Yes

Normal?

Check the specificationsof the controller.

Yes

NoCorrect?

Correct the error(s).

Check the I/O specificationsof the controller.

The LED lamp is flashing

in green.

Errors at Power OnTheerrorsshownbelowmayoccur in thefaultdiagnosiswhenthepower is turnedon.(FordetailsofSetpointdisplayand input/outputactionwheneacherroroccurs,seeUser’sManual(IM05P01D31-01EN).)YoucanviewthedetailsofeacherrorthroughcommunicationortheLL50AParameterSettingSoftware(soldseparately).(Viewontheregistermonitor.)Fordetailsoneachregister,seetheUTAdvancedSeriesCommunicationInterface(RS485,Ethernet)User’sManual(IM05P07A01-01EN).

LED display Register that displays error details Error description Cause and diagnosis Remedy

Unlit — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty.Contactusforrepair.

Red,lit

Setupparameter(PA.ER)(Registerno.:2068)Bit0=1 System data error System data is corrupted. Faulty.Contactusforrepair.

Setupparameter(PA.ER)(Registerno.:2068)Bit1=1 Calibrationvalueerror Initializedtocalibrateddefaultvaluebecauseofcorruptedfactorydefaultvalue. Faulty.Contactusforrepair.

Setupparameter(PA.ER)(Registerno.:2068)Bit2=1

User(parameter)defaultvalueerror

Userparameteriscorrupted.Initializedtofactorydefaultvalue. Checkandreconfiguretheinitialized

settingparameters.Errorindicationiserased when the power is turned on again.

Setupparameter(PA.ER)(Registerno.:2068)Bit4=1 Setup parameter error Setup parameter data is corrupted.

Initializedtouserdefaultvalue.Setupparameter(PA.ER)(Registerno.:2068)Bit5=1 Operation parameter error Operation parameter data is corrupted.

Initializedtouserdefaultvalue.Setupparameter(PA.ER)(Registerno.:2068)Bit8=1 FaultyFRAM Datawriting(storing)toFRAMisimpossible. Faulty.Contactusforrepair.

Setupparameter(OP.ER)(Registerno.:2070)E1-terminal:Bit0=1E2-terminal:Bit1=1E3-terminal:Bit2=1E4-terminal:Bit4=1

Nonrespondinghardwareofextendedfunction(E1toE4-terminalareas)

Inconsistenceofsystemdataandhardwareofextendedfunction.Nonrespondingcommunicationbetweenhardwareofextendedfunction(E1toE4-terminalareas).

Faulty.Contactusforrepair.

Setupparameter(LA.ER)(Registerno.:2012)Bit0=1 Corruptedladderprogram Ladderprogramiscorrupted.

Operateswithoutladderprogram. Downloadtheladderprogramagain.

Green,blinks Setupparameter(OP.ER)(Registerno.:2070)Bit10=1 Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.

Errors during OperationTheerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual(IM05P01D31-01EN).)YoucanviewthedetailsofeacherrorthroughcommunicationortheLL50AParameterSettingSoftware(soldseparately).(Viewontheregistermonitor.)Fordetailsoneachregister,seetheUTAdvancedSeriesCommunicationInterface(RS485,Ethernet)User’sManual(IM05P07A01-01EN).

LED display Register that displays error details Error description Cause and diagnosis Remedy

Red,lit

Setupparameter(AD1.E)(Registerno.:2001)Bit0=1

AnaloginputterminalADCerror•PVinput AnaloginputterminalADvalueerror Faulty.Contactusforrepair.

Setupparameter(AD1.E)(Registerno.:2001)Bit5=1

UniversalinputterminalRJCerror•PVinput UniversalinputterminalRJCerror

Faulty.Contactusforrepair.SettheparameterRJCtoOFFtoeraseerror indication.

Red,blinks

Setupparameter(AD1.E)(Registerno.:2001)Bit8=1

Analoginputterminalburnouterror•PVinput Analoginputterminalsensorburnout

Checkwiringandsensor.Errorindicationiserasedinnormaloperation.

Setupparameter(PV1.E)(Registerno.:2002)Bit0=1 PVinputburnouterror BurnoutofanaloginputconnectedtoPV

Checkwiringandsensorofconnectedanaloginputterminals.Errorindicationiserasedinnormaloperation.

Setupparameter(PV1.E)(Registerno.:2002)Over-scale:Bit4=1Under-scale:Bit5=1

PVinputover-scalePVinputunder-scale(PVvaluesoutof-5to105%)

PVinputisoutof-5to105%.Alsooccurswhenthedataoutofrangewhichistheladder calculation result is input.

Checkanaloginputvalueorladderprogram.

ChecktheerrorinLL50Asoftware.

Setupparameter(LA.ER)(Registerno.:2012)Overflow:Bit1=1Ladderprogramerror:Bit1=1Loadfactorover100%:Bit4=1Loadfactorover200%:Bit5=1

Laddercalculationoverflow Floatingpointcomputationforladdercalculationisinfinite. Checktheladderprogram.

Loadfactorover100% Computationdoesnotendwithinthecontrolperiod(loadfactoris100%ormore).Changethecontrolperiodorreducethe number of steps for the ladder program.

Loadfactorover200%(Forcedend) Computationdoesnotendwithinthecontrolperiod(loadfactoris200%ormore). Changethecontrolperiodorreducethe

numberofstepsfortheladderprogram.

Ladderprogramerror Ladderprogramiscorrupted.Downloadtheladderprogramagain.Iftheerrorindicationisstillnoterased,thereisafault.Contactusforrepair.

Green,blinks

Setupparameter(OP.ER)(Registerno.:2070)E1-terminal:Bit8=1E3-terminal:Bit10-=1E4-terminal:Bit12=1

Peer-to-peercommunicationerror Peer-to-peercommunicationerrorCheckthatthetargetdevicesareconnected correctly.Recoveryatnormalreceipt.

ChecktheerrorinLL50Asoftware.

Setupparameter(PV1.E)(Registerno.:2002)Bit14=1 Auto-tuningtime-out Auto-tuningdoesnotendevenwhen24hourshaveelapsedafterthestartof

tuning.Checktheprocess.Holddownanykeytoerase the error indication

Green,blinks

Setupparameter(OP.ER)(Registerno.:2070)E1-terminal:Bit8=1E3-terminal:Bit10-=1E4-terminal:Bit12=1

Communicationerror(RS-485communication)

FramingparityerrorBufferoverflowInter-charactertime-outChecksumerror(PClinkcommunicationwithchecksum)CRCcheckerror(Modbus/RTU)LRCcheckerror(Modbus/ASCII)

Checkthecommunicationparameters.Recoveryatnormalreceipt.Holddownanykeytostopblinking.

Communicationerror(coordinatedoperation)

InconsistenceofloopbetweencoordinatedmasterandslavesCheckthecommunicationparameters.Recoveryatnormalreceipt.Changefromremotetolocalmodetostopblinking.Whenthemodeischangedfromremotetolocal,SPtrackingdoesnotworkevenifitissettoON.

Communicationfromcoordinatedmasterisinterruptedfor2seconds.

Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.

Red,lit Setupparameter(PA.ER)(Registerno.:2068)Bit8=1 FaultyFRAM Writing(storing)datatoFRAMisimpossible. Faulty.Contactusforrepair.

Unlit — FaultyMCU/DCU(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.