Ultrasonic Testing
Weld Inspection using AWS D1.1
8/10/2019 Ut Weld Inspection Using Aws d1.1
2/65
2
Introduction
This presentation will helpstudents perform testingusing the AmericanWelding Society StructuralSteel D1.1-2000 code andprocedure.
It is important toremember that this is a
general training programand the procedure shouldbe referenced for specificinformation.
8/10/2019 Ut Weld Inspection Using Aws d1.1
3/65
3
What you will learn
Completing Form D-11
Determine the proper transducer(s) needed for
testing a weld.
Calibration using an IIW, rumpus, and DSCblock.
Scanning for discontinuities.
Calculate size and location of a discontinuity. Accept/Reject evaluation of a discontinuity.
8/10/2019 Ut Weld Inspection Using Aws d1.1
4/65
4
Form D-11
Weld Identification
Material Thickness Type of Weld Joint
Welding Process
Quality Requirements
Section Number
Year of AWS D1.1 Code used.
Testing Date
Inspected By
Some basic information should be completed on form D-11 prior
to the inspection. This information includes the following:
8/10/2019 Ut Weld Inspection Using Aws d1.1
5/65
5
Step 1Specimen Measurement
Measure the part thickness. From this thickness you will need tocalculate the skip distance. The skip distance is the area where you
will scan the part with the proper angle transducer. Mark the end of
the skip distance from the edge of the heat affected zone (HAZ).
The area in red will be used to identify the heat affected zone.
8/10/2019 Ut Weld Inspection Using Aws d1.1
6/65
6
Step 2Inspection LayoutThe skip distance will equal the surface distance of thetwo legs. You will need to know the distance of this areain order to perform a lamination scan followed by anangle beam examination
8/10/2019 Ut Weld Inspection Using Aws d1.1
7/657
Inspection Layout
Identifying the skip distance from the edge of theHAZ will ensure complete coverage of the weld
when performing an angle beam examination.
8/10/2019 Ut Weld Inspection Using Aws d1.1
8/658
Step 3Lamination Scan
A lamination scan will be performed in the areawhere the angle beam inspection will take place.This scan is performed with a straight beamtransducer.
8/10/2019 Ut Weld Inspection Using Aws d1.1
9/659
Lamination Scan
Perform a lamination scan from face A. You will needto see at least two plate thicknesses on the display. Thefirst backwall reflection shall be 50 to 75% full screenheight.
8/10/2019 Ut Weld Inspection Using Aws d1.1
10/6510
Lamination Scan
If any area of the base metal shows a total loss ofbackwall reflection, or if an indication is equal or greater
to the backwall reflection, the size and location and
depth will be reported.
8/10/2019 Ut Weld Inspection Using Aws d1.1
11/6511
Lamination Scan
Move the transducer in all directions until theamplitude of the signal is reduced by 50%. Mark the
center of the transducer.
8/10/2019 Ut Weld Inspection Using Aws d1.1
12/65
8/10/2019 Ut Weld Inspection Using Aws d1.1
13/6513
Lamination Scan
Note the location and size of the lamination on reportform D-11 or write an additional report with a drawing
showing its location.
8/10/2019 Ut Weld Inspection Using Aws d1.1
14/65
14
Step 4Transducer AngleTable 6.6 will list the transducer angles needed to test the weld.For material 0.60 the transducer angle used will be 70 degreesand will be tested from face A. On Form D-11 record thetransducer angle and face which you will be testing from. Theface is determined from Table 6.6
8/10/2019 Ut Weld Inspection Using Aws d1.1
15/65
15
Step 5Screen Range
Calculate the full V-path. This is determined by thematerial thickness and transducer angle. Choose theappropriate screen range in order to see a minimumsound path of two legs.
8/10/2019 Ut Weld Inspection Using Aws d1.1
16/65
16
Step 6Screen Range
Calculate the full V-path. This is determined by thematerial thickness and transducer angle. Choose theappropriate screen range in order to see a minimumsound path of two legs.
8/10/2019 Ut Weld Inspection Using Aws d1.1
17/65
17
Transducer
Verify the transducer is coupled to the wedgeand there are no air pockets between the two.
8/10/2019 Ut Weld Inspection Using Aws d1.1
18/65
18
Calibration - IIW Block
All measurements are taken from where the signalbreaks the baseline of the ultrasonic screen.
8/10/2019 Ut Weld Inspection Using Aws d1.1
19/65
19
Screen RangeIIW Block
Adjust the ultrasonic machine to obtain the properscreen range. With an IIW type II block shown, thebackwall reflections will be located at 2 and 4.
Position of the signals
with a 10 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
20/65
20
Screen RangeIIW Block
The position of the 2 and 4 reflections when using a5 screen range.
Position of the signals
with a 5 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
21/65
21
Screen RangeDSC BlockThe distance and sensitivity calibration block (DSC) can be
used for calibration. With the transducer placed in the position
shown, the reflections will take place at 1, 5, 9, etc.
Position of the signals
with a 10 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
22/65
22
Screen RangeDSC Block
With the transducer placed in the position shown, thereflections will take place at 1, 5, 9, etc.
Position of the signals
with a 5.0 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
23/65
23
Screen RangeDSC Block
With the transducer placed in the position shown, thereflections will take place at 3, 7, 11, etc.
Position of the signals
with a 10 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
24/65
24
Screen RangeDSC Block
With the transducer placed in the position shown, thereflections will take place at 3, 7, 11, etc.
Position of the signals
with a 15 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
25/65
25
Screen RangeRumpus Block
The miniature calibration block or rumpus block can also beused for calibration. With the transducer placed in the position
shown, the reflections will take place at 1, 4, 7, 10 etc.
Position of the signals
with a 5 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
26/65
26
Screen RangeRumpus Block
With the transducer placed in the position shown, thereflections will take place at 1, 4, 7, 10 etc.
Position of the signals
with a 10 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
27/65
27
Screen RangeRumpus Block
With the transducer placed in the position shown, thereflections will take place at 2, 5, 8, etc.
Position of the signalswith a 5 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
28/65
28
Screen RangeRumpus Block
With the transducer placed in the position shown, thereflections will take place at 2, 5, 8, etc.
Position of the signals
with a 10 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
29/65
29
Step 7Transducer Exit Point
Determine the exit point of the transducer. Peak the signal onthe ultrasonic machine and verify that the index point on theplastic wedge matches the calibration block. You may use tapeand a pen to mark the exit point. This will allow for easiermeasurements when measuring the surface distance.
8/10/2019 Ut Weld Inspection Using Aws d1.1
30/65
30
Exit PointIIW BlockThe exit point and screen range can be performed at the sametime. Slide the transducer back and forth until the signal ismaximized. The pictures below shows the location of thetransducer when verifying the exit point using an IIW type IIblock.
8/10/2019 Ut Weld Inspection Using Aws d1.1
31/65
31
Exit PointDSC BlockThe exit point and screen range can be performed at the same
time. Slide the transducer back and forth until the signal is
maximized. The pictures below shows the location of the
transducer when verifying the exit point.
8/10/2019 Ut Weld Inspection Using Aws d1.1
32/65
32
Exit PointRumpus BlockThe exit point and screen range can be performed at the same
time. Slide the transducer back and forth until the signal is
maximized. The picture below shows the location of the
transducer when verifying the exit point.
8/10/2019 Ut Weld Inspection Using Aws d1.1
33/65
33
Step 8Transducer AngleThe angle of the transducer will need to be verified. It
shall be within plus or minus 2 degrees of the required
angle.
8/10/2019 Ut Weld Inspection Using Aws d1.1
34/65
34
AngleIIW Block
Slide the transducer back and forth until the signal ismaximized. The picture below shows the location of
the transducer when verifying the transducer angle.
8/10/2019 Ut Weld Inspection Using Aws d1.1
35/65
35
AngleDSC Block
Slide the transducer back and forth until the signal ismaximized. The picture below shows the location of
the transducer when verifying the transducer angle.
8/10/2019 Ut Weld Inspection Using Aws d1.1
36/65
36
AngleRumpus Block
Slide the transducer back and forth until the signal ismaximized. The picture below shows the location of
the transducer when verifying the transducer angle.
8/10/2019 Ut Weld Inspection Using Aws d1.1
37/65
37
Step 9Transducer ResolutionThe resolution shall be checked with the instrument controls set at normal
test settings and the indications from the holes brought to midscreen height.
Resolution shall be sufficient to identify the peaks of the three holes.
Position of the signals
with a 5 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
38/65
38
Step 10Reference Level
The amplitude of a known size reflector will beadjusted from 50-75% full screen height. The dB will
be recorded as the reference level on form D-11.
IIW block
DSC block
Rumpus block
8/10/2019 Ut Weld Inspection Using Aws d1.1
39/65
39
Reference LevelIIW BlockThe transducer shall be placed in the position shown and the signal
amplitude from the hole will be maximized. Adjust the dB in order to obtain a
signal from 50 to 75% full screen height. This will be used as the reference
level b on form D-11.
Position of the signals
with a 10 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
40/65
40
Reference LevelDSC BlockThe transducer shall be placed in the position shown and the
signal amplitude from the notch will be maximized. Adjust the
dB in order to obtain a signal from 50 to 75% full screen height.
This will be used as the reference level b on form D-11.
Position of the signals
with a 10 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
41/65
41
Reference LevelRumpus BlockThe transducer shall be placed in the position shown and thesignal amplitude from the hole will be maximized. Adjust the dBin order to obtain a signal from 50 to 75% full screen height.This will be used as the reference level b on form D-11.
Position of the signals
with a 5 screen range.
8/10/2019 Ut Weld Inspection Using Aws d1.1
42/65
42
Step 11Reference Level
In this example the reference level b would berecorded as 42 dB. The reference screen height used
is 60% FSH.
8/10/2019 Ut Weld Inspection Using Aws d1.1
43/65
43
Step 12Scanning Level
Scanning level is based on sound path distance and notmaterial thickness. If table 6.2 (Statically loaded nontubular
connections) are tested, the following scanning levels will be
used.
Above ZeroSound Path (in) Reference, dB
0.0 to 2.5 14
>2.5 to 5 19
>5 to 10 29
>10 to 15 39
8/10/2019 Ut Weld Inspection Using Aws d1.1
44/65
44
Scanning Level
If table 6.3 (Cyclically loaded nontubular connections) aretested, the following scanning levels will be used.
Above ZeroSound Path (in) Reference, dB
0.0 to 2.5 20
>2.5 to 5 25
>5 to 10 35
>10 to 15 45
8/10/2019 Ut Weld Inspection Using Aws d1.1
45/65
45
Scanning Level
This shows the screen presentation when using ascanning level 14 dB above the reference level.
8/10/2019 Ut Weld Inspection Using Aws d1.1
46/65
46
Step 13Initial Information Scan
Perform an initial information scan marking thelocation of any suspected discontinuities.
8/10/2019 Ut Weld Inspection Using Aws d1.1
47/65
47
Weld Configuration
You can draw a diagram of the weld on the ultrasonic screenwith a water based marker or grease pencil. The line is drawn
at the end of the 1st, 2nd, and 3rdleg. This may help you
visualize the location of the discontinuity in the weld.
8/10/2019 Ut Weld Inspection Using Aws d1.1
48/65
48
Step 14Surface Distance
Calculate the surface distance in order to determine ifthe signal is located in the weld.
8/10/2019 Ut Weld Inspection Using Aws d1.1
49/65
49
Step 15Discontinuity Depth
Calculate the depth in order to determine if the signalis located in the weld.
8/10/2019 Ut Weld Inspection Using Aws d1.1
50/65
50
Step 16Sound Path
Move the transducer in all directions in order to peakthe signal from the discontinuity. Record the Sound
Path on Form D-11.
8/10/2019 Ut Weld Inspection Using Aws d1.1
51/65
51
Step 17Sound Path
Record the Leg on Form D-11.
8/10/2019 Ut Weld Inspection Using Aws d1.1
52/65
52
Step 18Indication LevelIncrease or decrease the dB until the screen height from the
discontinuity is equal to the reference level. Record the dBunder indication level (column b).
dB reference level - 60% FSH.
8/10/2019 Ut Weld Inspection Using Aws d1.1
53/65
53
Step 19Attenuation FactorSubtract one inch from the sound path distance and multiply theremainder by two. This number will be rounded to the nearestwhole number. If the number is less than 0.5 dB it will belowered to the nearest whole number. If the number is 0.5 orgreater, it will be increased to the nearest whole number.
In this example, the sound
path is 1.9
1.9 1 = 0.9
0.9 x 2 = 1.8
Rounded to the nearest
whole number - 2
8/10/2019 Ut Weld Inspection Using Aws d1.1
54/65
54
Attenuation Factor
On Form D-11, fill out the attenuation factor. This islocated under Decibels- Attenuation Factor.
In this example, the sound
path is 1.0
1.01 = 0.0
0.0 x 2 = 0.0
If the attenuation factor is
less than 0.5, the
attenuation factor will be
zero.
8/10/2019 Ut Weld Inspection Using Aws d1.1
55/65
55
Step 20Indication Rating
The indication rating is calculated by taking theIndication level minus Reference level minus
Attenuation factor. A-B-C=D
The answer D is
your indication rating
and can be positive or
negative. Write this
number in column D
under Decibels,
Indication Rating
8/10/2019 Ut Weld Inspection Using Aws d1.1
56/65
56
Step 21Discontinuity Length
Maximize the signal amplitude from the discontinuity.
8/10/2019 Ut Weld Inspection Using Aws d1.1
57/65
57
Step 22Discontinuity Length
Slide the transducer parallel with the weld until thesignal amplitude has reduced by 50%. Mark thelocation next to the weld aligned with the center of thetransducer. Perform this procedure in both directions.
8/10/2019 Ut Weld Inspection Using Aws d1.1
58/65
58
Discontinuity Length
Record the length on Form D-11.
8/10/2019 Ut Weld Inspection Using Aws d1.1
59/65
59
Step 23Discontinuity Class
From Table 6.2 or 6.3, determine the DiscontinuitySeverity Class. This is based on the Indication Rating
and Length.
Class A (large discontinuity)
Any indication in this category shall be rejected regardless of length
Class B (medium discontinuity)
Any indication in this category having a length greater than shall be rejected.
Class C (small discontinuity)
Any indication in this category having a length greater than 2 shall be rejected.
Class D (minor discontinuity)
Any indication in this category shall be accepted regardless of length or location in
the weld.
S 24 Di i i E l i
8/10/2019 Ut Weld Inspection Using Aws d1.1
60/65
60
Step 24Discontinuity Evaluation
On Form D-11 under Discontinuity Evaluation list theclass of the discontinuity.
St 25 A t/R j t
8/10/2019 Ut Weld Inspection Using Aws d1.1
61/65
61
Step 25Accept/RejectOn Form D-11 under Remarks accept or reject the
discontinuity.
8/10/2019 Ut Weld Inspection Using Aws d1.1
62/65
62
Step 26Distance from YOne side of the plate or weld can be identified with a Y
location point. From the edge of the weld measure to thebeginning of the discontinuity. Record Distance from Y on
Form D-11.
Distance from Y = 1.0 Distance from Y = 0.3
8/10/2019 Ut Weld Inspection Using Aws d1.1
63/65
63
Step 27Distance from XFrom the center of the weld (marked in black), if the
discontinuity is located opposite the Y location mark, it will bemeasured as a positive number. This will be recorded under
Distance from X on Form D-11.
Distance from X = 0.2
8/10/2019 Ut Weld Inspection Using Aws d1.1
64/65
64
Step 28Distance from X
From the center of the weld (marked in black), if the
discontinuity is located on the same side as the Y location
mark, it will be measured as a negative number. This will be
recorded under Distance from X on Form D-11.
Distance from X = -0.2
8/10/2019 Ut Weld Inspection Using Aws d1.1
65/65
Step 29Scanning Level
Return to the scanning level and locate the nextdiscontinuity for evaluation.