4
Current Issue Archive Subscribe Search: Using Dissolved Gas Analysis to Detect Active Faults in Oil-Insulated Electrical Equipment Lance R. Lewand, Doble Engineering Company Tags: oil analysis The analysis of gases from petroleum products has been performed for decades using gas chromatography. However, this technique was not applied specifically to transformer mineral oil until the late 1960s/early 1970s and is now commonly called dissolved gas-in-oil analysis (DGA). Some of the early developers of the technique were Dr. James Morgan of Morgan Schaffer Systems, Canada, and researchers J.E. Dind, R. Daust and J. Regis from the Canadian utility Hydro-Quebec. 1 Because the technique was so successful and provided a wealth of diagnostic information to detect incipient faults, other laboratories such as Doble Engineering in Massachusetts began utilizing the technique shortly thereafter. DGA has now become a standard in the utility industry throughout the world and is considered to be the most important oil test for insulating liquids in electrical apparatus. More importantly, an oil sample can be taken at anytime from most equipment without having to take it out of service, allowing a “window” inside the electrical apparatus that helps with diagnosing and trouble-shooting potential problems. Insulating fluid analysis is performed using an array of physical, chemical and electrical tests. Physical tests include analysis for interfacial tension, pour point, relative density, viscosity, color and others. Tests such as water content, neutralization number, oxidation inhibitor and polychlorinated biphenyls (PCBs) are considered chemical tests. Electrical tests consist of analyses for dielectric breakdown voltage and power factor. There are many other tests that can be performed but these are the main ones executed on a routine basis. Most tests performed in North America are based on ASTM test methods. In Europe and other parts of the world, similar test methods come under the auspices of the International Electrotechnical Committee TC10. Because oil and solid insulation degrade with service in electric apparatus, periodic sampling and testing are necessary to ensure that deterioration is detected before it becomes excessive. The rate at which the insulating materials degrade depends on several factors, such as the type of oil preservation system (amount of oxygen present), operating temperature, water content of the insulation, and the amounts and types of contaminants. The frequency at which testing is conducted varies with the test, importance of the equipment, whether an incipient-fault condition is known to be present or a problem exists, and when a family of transformers has been identified as having a history of problems. The tests mentioned above provide information on the oil quality itself but fail to provide in-depth diagnostic information on the operating condition or health of the electric apparatus. In addition, because most transformers in the United States are considered to be sealed systems (equipped with preservation systems that retard the ingress of moisture and oxygen), oil degradation can occur quite slowly over many years. Many of the transformers in the United States that have been in-service for more than 30 years still contain oil that is in good condition. There is one test however, also performed on the insulating oil of the transformer, which provides a means for diagnosing the operating condition of the electrical apparatus, namely DGA. Dissolved Gas-in-Oil Analysis Dissolved gas-in-oil analysis, performed in accordance with ASTM D3612 or IEC 60567, is by far the most frequently requested diagnostic test and the single most important test performed on transformer oil. As the insulating materials of an electrical apparatus, such as a transformer, break down from excessive thermal or electrical stress, gaseous byproducts form. The byproducts are characteristic of the type of incipient-fault condition, the materials involved and the severity of the condition. Indeed, it is the ability to detect such a variety of problems that makes this test such a powerful tool for detecting incipient-fault conditions and for root-cause investigations after failures have occurred. Dissolved gases are detectable in low concentrations (ppm level), which usually permit early intervention before failure of the electrical apparatus occurs, and allow for planned maintenance. The DGA technique involves extracting or stripping the gases from the oil and injecting them into a gas chromatograph (GC). Detection of gas concentrations usually involves the use of a flame ionization detector (FID) Related Articles Justifying an Oil Analysis Program Laboratory-based Technician Skills to be Standardized Know the Proper Base Number of Your Oil Measuring Relative Density of Lubricants White Papers The Importance of Lubricant and Fluid Analysis in Predictive Maintenance Home | Buyers Guide | Glossary | Events | Bookstore | Newsletters | Browse Topics GREASES HYDRAULICS INDUSTRIAL LUBRICANTS SYNTHETICS FILTRATION STORAGE/HANDLING OIL ANALYSIS Tweet 0 1 Like Like Share Share Using Dissolved Gas Analysis to Detect Active Faults in Oil-Insulated... http://www.machinerylubrication.com/Read/457/dissolved-gas-analysis 1 of 4 7/7/2014 4:14 PM

Using Dissolved Gas Analysis to Detect Active Faults in Oil-Insulated Electrical Equipment

Embed Size (px)

DESCRIPTION

Transformer oil analysis

Citation preview

  • Current Issue

    ArchiveSubscribe

    Search:

    Using Dissolved Gas Analysis to DetectActive Faults in Oil-Insulated ElectricalEquipmentLance R. Lewand, Doble Engineering Company Tags: oil analysis

    The analysis of gases from petroleum products has been performed for decades using gas chromatography.However, this technique was not applied specifically to transformer mineral oil until the late 1960s/early 1970sand is now commonly called dissolved gas-in-oil analysis (DGA). Some of the early developers of thetechnique were Dr. James Morgan of Morgan Schaffer Systems, Canada, and researchers J.E. Dind, R.Daust and J. Regis from the Canadian utility Hydro-Quebec.1

    Because the technique was so successful and provided a wealth of diagnostic information to detect incipientfaults, other laboratories such as Doble Engineering in Massachusetts began utilizing the technique shortlythereafter. DGA has now become a standard in the utility industry throughout the world and is considered tobe the most important oil test for insulating liquids in electrical apparatus. More importantly, an oil sample canbe taken at anytime from most equipment without having to take it out of service, allowing a window insidethe electrical apparatus that helps with diagnosing and trouble-shooting potential problems.

    Insulating fluid analysis is performed using an array of physical, chemical and electrical tests. Physical testsinclude analysis for interfacial tension, pour point, relative density, viscosity, color and others. Tests such aswater content, neutralization number, oxidation inhibitor and polychlorinated biphenyls (PCBs) are consideredchemical tests. Electrical tests consist of analyses for dielectric breakdown voltage and power factor. Thereare many other tests that can be performed but these are the main ones executed on a routine basis. Mosttests performed in North America are based on ASTM test methods. In Europe and other parts of the world,similar test methods come under the auspices of the International Electrotechnical Committee TC10.

    Because oil and solid insulation degrade with service in electric apparatus, periodic sampling and testing arenecessary to ensure that deterioration is detected before it becomes excessive. The rate at which theinsulating materials degrade depends on several factors, such as the type of oil preservation system (amountof oxygen present), operating temperature, water content of the insulation, and the amounts and types ofcontaminants. The frequency at which testing is conducted varies with the test, importance of the equipment,whether an incipient-fault condition is known to be present or a problem exists, and when a family oftransformers has been identified as having a history of problems.

    The tests mentioned above provide information on the oil quality itself but fail to provide in-depth diagnosticinformation on the operating condition or health of the electric apparatus. In addition, because mosttransformers in the United States are considered to be sealed systems (equipped with preservation systemsthat retard the ingress of moisture and oxygen), oil degradation can occur quite slowly over many years.Many of the transformers in the United States that have been in-service for more than 30 years still contain oilthat is in good condition. There is one test however, also performed on the insulating oil of the transformer,which provides a means for diagnosing the operating condition of the electrical apparatus, namely DGA.

    Dissolved Gas-in-Oil AnalysisDissolved gas-in-oil analysis, performed in accordance with ASTM D3612 or IEC 60567, is by far the mostfrequently requested diagnostic test and the single most important test performed on transformer oil. As theinsulating materials of an electrical apparatus, such as a transformer, break down from excessive thermal orelectrical stress, gaseous byproducts form. The byproducts are characteristic of the type of incipient-faultcondition, the materials involved and the severity of the condition. Indeed, it is the ability to detect such avariety of problems that makes this test such a powerful tool for detecting incipient-fault conditions and forroot-cause investigations after failures have occurred. Dissolved gases are detectable in low concentrations(ppm level), which usually permit early intervention before failure of the electrical apparatus occurs, and allowfor planned maintenance.

    The DGA technique involves extracting or stripping the gases from the oiland injecting them into a gas chromatograph (GC). Detection of gasconcentrations usually involves the use of a flame ionization detector (FID)

    Related ArticlesJustifying an Oil Analysis Program

    Laboratory-based Technician Skills to beStandardized

    Know the Proper Base Number of Your Oil

    Measuring Relative Density of Lubricants

    White PapersThe Importance of Lubricant and FluidAnalysis in Predictive Maintenance

    Home | Buyers Guide | Glossary | Events | Bookstore | Newsletters | Browse Topics

    GREASES HYDRAULICS INDUSTRIAL LUBRICANTS SYNTHETICS FILTRATION STORAGE/HANDLING OIL ANALYSIS

    Tweet 0 1LikeLike ShareShare

    Using Dissolved Gas Analysis to Detect Active Faults in Oil-Insulated... http://www.machinerylubrication.com/Read/457/dissolved-gas-analysis

    1 of 4 7/7/2014 4:14 PM

  • and a thermal conductivity detector (TCD). Most systems also employ amethanizer, which converts any carbon monoxide and carbon dioxidepresent into methane so that it can be burned and detected on the FID, avery sensitive sensor.

    Removing the gas from the oil is one of the more difficult and criticalportions of the procedure. The original method, now ASTM D3612A,required that the oil be subjected to a high vacuum in an elaborate glass-sealed system to remove most of the gas from the oil. The gas was then

    collected and measured in a graduated tube by breaking the vacuum with a mercury piston. The gas wasremoved from the graduated column through a septum with a gas-tight syringe and immediately injected intoa GC. In the present modern day laboratory, however, mercury is not a favorite material of chemists. For thisreason, two additional extraction techniques have been developed to eliminate mercury.

    ASTM D3612B is called the direct injection technique. In this method, the stripping of gases from the oil andthe gas analysis takes place inside the GC. Originally developed in the mid-1980s for this application, theprocess involves injecting the oil into a sample loop in the GC. When the GC run is initiated, the sample looptransfers the oil through a series of valves into a stripper column. The stripper column is composed of metalspheres in one end in which the oil overlays the surface of the spheres to increase the surface area. Carriergas is passed over the spheres and extracts dissolved gases from the oil, which then pass through a seriesof columns and on through the detectors. The oil is back-flushed and purged from the system before the nextsample is introduced.

    The newest method, ASTM D3612C, was approved about a year ago and is called the headspace method.Headspace technology was used for DGA analysis for almost a decade. However, it was never developedinto a robust, reliable standard method until several years ago when Jocelyn Jalbert of Hydro-Quebecdeveloped a headspace method using a Hewlett Packard (now Agilent Technologies) instrument.2 Thetechnique involves injecting an exact volume of oil into a purged and pressurized headspace vial. The gas inthe oil is then allowed to develop an equilibrium with the vial headspace under shaking and heatingconditions. After a predetermined sample extraction time, the autosampler removes a portion of the gas fromthe vial headspace and injects it into the GC. The advantage of this method is that it can be automated andreduces the risk of operator error from excessive handling of the sample during preparation and injection.

    Of course, each method has its advantages and disadvantages. Method A (ASTM D3612A) is by far thelongest-standing technique and is still widely used today and offers accurate, reliable sample preparation iffollowed rigorously. However, the alternative methods, which are more easily automated, are gainingacceptance as they are shown to be reliable. None of the extraction techniques completely removes all thegases from the oil. This is due to the solubility coefficient of each gas, which must be accounted for in thefinal concentration determination. Laboratories must also work with commercial suppliers to develop gas andgas-in-oil standards or they must prepare standards themselves, because these are not currently availablefrom national standardization bodies such as the NIST. Repeatability and accuracy are also of the utmostimportance as small changes, even several ppm in some cases, can mean the difference between an activeincipient fault condition that requires immediate attention or one that is stable and requires no attention.

    Just like with industrial oil analysis, good sampling practice is important for obtaining accurate DGA data. Keygases such as hydrogen and carbon monoxide could easily be lost from a sample because of their lowsolubilities in oil. In order to minimize the loss of gases, ASTM D3613 requires samples to be taken usinggas-tight glass syringes or metal bulbs; these are available from several suppliers or from commercialtransformer oil analysis labs.

    Gases Detected and Their RelevanceTypical gases generated from mineral oil/ cellulose (paper and pressboard) insulated transformers include:

    Hydrogen, H2Methane, CH4Ethane, C2H6Ethylene, C2H4Acetylene, C2H2Carbon Monoxide, COCarbon Dioxide, CO2

    Additionally, oxygen and nitrogen are always present, their concentrations vary with the type of preservationsystem used on the transformer. Also, gases such as propane, butane, butene and others can be formed aswell, but their use for diagnostic purposes is not widespread. The concentration of the different gasesprovides information about the type of incipient-fault condition present as well as the severity. For example,four broad categories of fault conditions have been described and characterized in Table 13.

    Electrical discharges or inadequate cooling of the paper insulation cause it to overheat, generating carbonoxide gases. Examination of the relative composition or ratios of gases present can provide furtherrefinement of the diagnosis. This typically involves using either Rogers ratio or Dornenberg ratios.

    Reliability Centered Maintenance ProjectManager's Guide

    Buyers GuideOil Analysis Laboratories

    Oil Analysis Instruments

    Oil Sampling Hardware

    PollHow often is oil analysisperformed on equipment atyour plant?

    Daily

    Weekly

    Monthly

    Annually

    Never

    Using Dissolved Gas Analysis to Detect Active Faults in Oil-Insulated... http://www.machinerylubrication.com/Read/457/dissolved-gas-analysis

    2 of 4 7/7/2014 4:14 PM

  • The severity of an incipient-fault condition is ascertained by the total amount of combustible gases present(CO, H2, C2H2, C2H4, C2H6, CH4) and their rate of generation. Generally, transformers will retain a large

    portion of the gases generated and therefore produce a cumulative history of the insulating materialsdegradation. This is an important tool for detecting and trending incipient problems. However, it also meansthat care is needed in interpreting values for a first-time analysis on service-aged transformers (more thanseveral years old), which could contain residual gases from previous events.

    Some gas generation is expected from normal aging of the transformer insulation. Therefore it is important todifferentiate between normal and excessive gassing rates. Normal aging or gas generation varies withtransformer design, loading and type of insulating materials. Routinely, general gassing rates for alltransformers are used to define abnormal behavior. Specific information for a family of transformers can beused when sufficient dissolved gas-in-oil data are available.

    Acetylene is considered to be the most significant gas generated. An enormous amount of energy is requiredto produce acetylene, which is formed from the breakdown of oil at temperatures in excess of 700C.Excessively high overheating of the oil will produce the gas in low concentrations; however, higherconcentrations are typically symptomatic of sustained arcing, a more serious operational issue that can causea transformer failure if left unchecked.

    DGA is used not only as a diagnostic tool but also to stem apparatus failure. Failure of a large powertransformer not only results in the loss of very expensive equipment (costs can exceed one million U.S.dollars) but it can cause significant collateral damage as well. Revenue losses due to customers outagesmay be the least worrisome consequence of a failure. Replacement of that transformer can take up to a yearif the failure is not catastrophic and can result in tremendous revenue losses and fines. If the failure iscatastrophic, then additional loses could be realized, such as adjacent transformers, environmental problemsfrom the release of oil, which could be as much as 20,000 gallons, and the resulting fire that must becontained and smothered, all of which are a utilitys worst nightmare. In order to avoid such a failure, thesample frequency of most large power transformers is between one and three years. However, samplingfrequencies will increase as an incipient fault is detected and monitored. Often times sampling frequenciesare dictated by insurance requirements, which often stipulate that annual transformer oil analysis must beconducted to ensure continued coverage.

    The following examples are extreme but serve to illustrate how the dissolved gas-in-oil test can be used tohighlight active problems.

    EXAMPLE 14The utility suspected that the magnetic shunt pads attached to the inside of this transformer tank had comeloose and were either touching the core (layered steel structure around which the copper winding is installed)or were coming very close. The result was intermittent unintentional core grounding and stray flux causinglocalized overheating of the oil.

    EXAMPLE 25 It was suspected that a single line to ground through-fault caused the failure of thistransformer. The fault was of enough energy to destroy one of the windings. Acetylene was a predominant

    Using Dissolved Gas Analysis to Detect Active Faults in Oil-Insulated... http://www.machinerylubrication.com/Read/457/dissolved-gas-analysis

    3 of 4 7/7/2014 4:14 PM

  • gas possibly indicating that arcing may have occurred. The acetyleneto-ethylene ratio indicated the problemcould be either high temperature overheating of the oil, arcing or both. The problem was likely in the windingbecause it involved cellulosic materials, as witnessed by the comparatively high carbon monoxide and carbondioxide concentrations.

    EXAMPLE 35 A technician noticed that this transformer was enveloped in a cloud of steam during arainstorm. This prompted an investigation where it was found that the temperature indicator pegged. It wasestimated that the temperature in the unit had been greater than 200C. It was discovered also that the unitbecame highly overloaded during some switching functions due to current imbalances in the three phases.The condition probably existed on and off for two years. An internal investigation found the cellulosic paperused as an insulant was brittle and crumbly. Again, the key gas indicators for this condition were carbonmonoxide and carbon dioxide.

    Oil testing is an important part of a utilitys electric apparatus condition assessment. As these cases illustrate,dissolved gas-in-oil analysis is the most important diagnostic test for detecting a wide range of problems.

    References

    Dind, J.E., Daoust, R., Regis, J. and Morgan, J., (1971). Analysis of Gases Dissolved in TransformerOils, Progress Report. Minutes of the Thirty-Eighth Annual International Conference of Doble Clients.Sec. 6-1101.

    1.

    Jalbert, J., Gilbert, R. and Brillante, S., (1995). Dissolved Gas Analysis of Transformer Insulating Oilsby Headspace/Capillary Gas Chromatography. Hewlett Packard Application Note. pp. 228-310.

    2.

    Griffin, P.J., (1998). Criteria for the Interpretation of Data for Dissolved Gases in Oil from Transformers(A Review). ASTM Special Technical Publication 998.

    3.

    Lewand, L.R. and Griffin, P.J., (2000). The Effective Use of Laboratory Analysis of Insulating Oil as aMaintenance Tool. Proceedings of the Sixty-Seventh Annual International Conference of DobleClients. Sec. 5-8.

    4.

    Griffin, P. J. and Lewand, L.R., (1995). A Practical Guide for Evaluating the Condition of CellulosicInsulation in Transformers. Proceedings of the Sixty-Second Annual International Conference of DobleClients. Sec. 5-6.

    5.

    Practicing Oil Analysis (3/2003)

    Related Articles

    Particles: Friend or Foe? Understanding the Value of Particles in Oil Analysis

    Using Unscheduled Oil Analysis for Early Predictive Maintenance

    6 Ways to Maximize Your Oil Analysis Software Value

    Anatomy of an Oil Analysis Report

    Get 60 Questions to Ask Your LubricantSupplier absolutely FREE when you sign upfor our free Lube-Tips newsletter. Email:

    Machinery Oil AnalysisPresents the practice of oil analysis as a conditionmonitoring tool for machines. Covers each step inthe sampling, testing and diagnostic process.Includes latest advances in technology andinstrumentation.Table of Contents | Read Excerpts

    Oil Analysis BasicsPresents the fundamentals of oil analysis formachinery condition monitoring in an easy tounderstand format. Learn everything from how totake a proper oil sample to how to select a test slatefor your applications.Table of Contents | Read Excerpts

    Services Subscribe | Contact Us | Privacy Policy | RSS | AdvertiseQuick Links Home | Buyers Guide | Glossary | Events | Bookstore | Newsletters | Browse Topics

    NORIA CORPORATION MACHINERY LUBRICATION | RELIABLE PLANT

    Using Dissolved Gas Analysis to Detect Active Faults in Oil-Insulated... http://www.machinerylubrication.com/Read/457/dissolved-gas-analysis

    4 of 4 7/7/2014 4:14 PM