    show the entry listUsing an INSYS Pocket 56k modem

    QUESTION:Which entries are required STEP 7-Micro/WIN V3.1 to be able to use an INSYS Pocket 56k modem?

    ANSWER:

    The INSYS Pocket 56k modem is a standard modem that also supports 11-bit protocols. Thefollowing communication settings are required for an 11-bit connection:

    Important:When using the PC/PPI cable (MLFB 6ES7 901-3BF00-0XA0), the "DTE" setting cannot be enabled.This is why it is necessary to have an additional zero modem adapter between the remote modemand the PC/PPI cable.

    Open the communications window in STEP 7-Micro/WIN V3.1 and select the Properties of the PC/PPIcable. The further procedure is described in the manual "S7-200 Automation System, CPU22x" in thesection 7.4 "Communicating with Modem" (see Entry ID: 1109582).

    If you want to set up a connection between your PC and an S7-200 controller, then please proceed as

    follows:

    1. Connect the local modem to the PC.2. Connect the remote modem to the SIMATIC S7-200 controller via the PC/PPI cable.

    PC/PPI cable:(6ES7 901-3BF20-0XA0)

    Baud rate 19200

    Switch 4 OFF (11 bits)

    Switch 5 ON (DTE)

    STEP 7-Micro/WIN V3.1 Modem connection(local connection)

    Baud rate 19200(PPI)

    S7-200 CPU: CPU212, 214, 215 (Port0), 216, 221, 222, 224,226

    19200 Kbaud

    Page 1 of 5Siemens - Industry Automation and Drive Technologies - Service& Support - Automation...

    10.09.2010http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286 ...

    http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286
  • 8/2/2019 Using an INSYS Pocket 56k Modem Www.otomasyonegitimi.com

    2/5

    3. Take the following entry in STEP 7-Micro/WIN V3.1 as the local (upper) modem:Initialization string: AT&F&D0E0\G0&K0\N0X3Communications string: S23=12

    Page 2 of 5Siemens - Industry Automation and Drive Technologies - Service& Support - Automation...

    10.09.2010http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286 ...

    http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286
  • 8/2/2019 Using an INSYS Pocket 56k Modem Www.otomasyonegitimi.com

    3/5

    4. Click "Program/Test" to transfer the initialization string to the modem. After a few seconds themessage "Successful" is displayed in the "Status" area.

    5. Take the following entry in STEP 7-Micro/WIN V3.1 as the remote (lower) modem:Initialization string: AT&F&D0E0\G0&K0\N0X3S0=1Communications string: S23=12Suffix: &W0^M

    Page 3 of 5Siemens - Industry Automation and Drive Technologies - Service& Support - Automation...

    10.09.2010http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286 ...

    http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286
  • 8/2/2019 Using an INSYS Pocket 56k Modem Www.otomasyonegitimi.com

    4/5

    6. Click "Program/Test" to transfer the initialization string to the modem. After a few seconds themessage "Successful" is displayed in the "Status" area.

    Description of the AT command:

    Note:The settings are retained on the modem even after a power failure. The firmware of the tested INSYSPocket 56k modem had the following version: V2.100-V90_2M_DLS. If a different firmware is loadedin the modem and a connection is not set up, then please get in touch with the manufacturer of themodem:

    INSYS GmbHContact: Ms Anna WelsWaffnergasse 8

    AT &F Reset to works settings

    &D0 Ignore DTR

    E0 Switch off echo from modem

    \G0 Switch off the modem-modem data flow control

    &K0 No data flow control

    \N0 Switch off error correction

    X3 No call-connected recognition

    S0=1 Pick-up after first ringing

    S23=12 Setting of the protocol 19200, 8, E, 1

    &W0 Saving the initialization in the Profile 0

    Page 4 of 5Siemens - Industry Automation and Drive Technologies - Service& Support - Automation...

    10.09.2010http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286 ...

    http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286
  • 8/2/2019 Using an INSYS Pocket 56k Modem Www.otomasyonegitimi.com

    5/5

    D-93047 RegensburgPostfach 10 03 42D-93016 Regensburg

    With the command "ATI3" you can check whether the firmware version of your modem matches thatof the tested modem.

    Search terms:Teleservice

    Tel. +49 (0)941 - 56 00 61

    Fax. +49(0)941 - 56 34 71

    E-mail: mailto:[email protected]

    Internet: http://www.insys-tec.de

    Entry ID:6242286 Date:2001-10-01

    I regard this article.... as helpful as not helpful

    Copy link Suggestion for the entry Send to a friend

    Print

    Siemens AG 2010 - Corporate Information - Privacy Policy - Terms of Use