USI O&M HVAC Controls Optimization WorkshopNorth Carolina State-Owned Facilities Utilities Cost Profile
FY-02 Utilities Use by All State-owned Facilities(total $214M)
Electrical59%
Nat Gas & LP12%
UNC Coal11%
Fuel Oil6%
Water & Sewer12%
USI O&M HVAC Controls Optimization WorkshopUtilities Costs by Department
FY02 Utilities Costs by Department
Transportation
UNC
AdministrationJuvenile
Environment
Other
Agriculture
HealthCorrections
CommercePublic Safety
USI O&M HVAC Controls Optimization WorkshopUtilities Costs by Campus
FY-02 Utilities Costs by Campus
UNC-CH
NCSU
NCSSMNCSA
GA
ECSUWSSU
FSU
UNCC
UNCW
NCA&T
ASU
NCCU
UNCP
ECU
UNC-G
UNCA
WCU
USI O&M HVAC Controls Optimization WorkshopUtilities Costs by Campus
Educational Buildings Energy End Uses(EIA and NREL 2000)
Lighting20%
DHW22%
Misc Eq8%
HVAC50%
USI O&M HVAC Controls Optimization WorkshopUtilities Costs by Agency
FY02 Utilities Costs by Agency
Transportation
Public Safety
Commerce
Corrections
Health
AgricultureOther
Environment
Juvenile
Administration
USI O&M HVAC Controls Optimization WorkshopUtilities Costs by Agency
South Atlantic Commercial Building Site-Energy End Use Intensities [KBTU/SF]
(EIA 1995 data)
Lighting, 22.2, 27%
HVAC, 29.4, 37%
DHW, 9.3, 11%
Misc Eq't, 20.6, 25%
USI O&M HVAC Controls Optimization WorkshopState Buildings Usage Profile
Asset Use Total % of # % all(GSF) Total GSF Bldgs Bldgs
Educational 18,299,844 19.4% 611 5.0%Housing 13,800,138 14.6% 1,068 8.7%Office 11,543,629 12.2% 1,153 9.4%Storage 7,235,953 7.7% 3,128 25.5%Health Services 6,880,523 7.3% 301 2.5%Corrections 6,719,393 7.1% 665 5.4%Assembly 5,507,974 5.8% 187 1.5%Research/Laboratory 3,307,210 3.5% 233 1.9%Library 3,016,577 3.2% 33 0.3%Shop 2,990,317 3.2% 722 5.9%Agricultural 1,997,161 2.1% 450 3.7%Armory 1,847,076 2.0% 102 0.8%Food Service 1,548,260 1.6% 143 1.2%Other 1,377,157 1.5% 285 2.3%Student Union 925,353 1.0% 19 0.2%Retail Sales 923,258 1.0% 179 1.5%Museum 880,357 0.9% 41 0.3%Office/Storage Mixed 807,304 0.9% 76 0.6%Utilities 762,745 0.8% 770 6.3%Historical 699,080 0.7% 148 1.2%Vehicle Storage 543,628 0.6% 190 1.5%Recreational 532,975 0.6% 730 6.0%Animal Housing 499,110 0.5% 143 1.2%Greenhouse 449,271 0.5% 133 1.1%TV Studio/Commun. 297,179 0.3% 132 1.1%Laundry 284,039 0.3% 19 0.2%Wash House/Toilet 226,701 0.2% 400 3.3%Welcome Ctr./Visitor 180,307 0.2% 76 0.6%Religious 159,387 0.2% 50 0.4%Marine Research 102,397 0.1% 6 0.0%Unidentified 80,157 0.1% 19 0.2%Kitchen/Cannery 77,053 0.1% 11 0.1%Weigh Station 14,768 0.0% 38 0.3%Office/Housing Mixed 113 0.0% 1 0.0%All Facilities = 94,516,394 GSF 12,262 FacilitiesFY 02 Utilities cost = $214,000,000 = 2.26$ per GSF
• Initial 25% survey sample included 600 buildings, totaling 24Million GSF
• Estimated potential annual ECO savings of $7Million
• Extrapolates to $26Million potential annual savings if all ECOs are addressed in all State-owned buildings.
• Additional surveys available upon request.• Follow-up verification visits.
USI O&M HVAC Controls Optimization WorkshopO&M Program – ECO Surveys
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Is weather stripping on windows and doors well maintained to minimize infiltration?
12%
29%59%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Do blinds and shades appear to be adjusted to allow daylight and regect direct solar heat gain?
8%
60%
32%No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are fluorescent task lamps present to enable background lighting levels to be reduced?
64%19%
17%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are occupancy sensor controls present to automatically switch-off lights?
94%
3%
3%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Have incandescent lamps been replaced with self-ballasted fluorescents?
41%
19%
40% No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Have old 34W fluorescent lamps and old ballasts been replaced with T-8 lamps and electronic ballasts?
67%
14%
19%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are building exhaust fans switched-off w ith the HVAC systems for unoccupied periods?
52%
2%
46%No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are reasonable heating and cooling setpoints maintained?
23%
26%
51%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are the thermostats routinely calibrated?
12%
0%
88%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Is the supply air discharge temperature automatically raised from 55F to minimize reheat energy consumption (Reheat HVAC systems only)?
35%
4%61%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Has the supply air flow from the air handling unit(s) been reduced to match the load?
44%
5%
51%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Has direct conditioning of unoccupied areas been minimized?
33%
28%
39%NoSomeYes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Has the introduction of outdoor air been minimized to recommended ASHRAE ventilation rates?
37%
5%
58%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are OA dampers controlled to close during unoccupied periods?
64%0%
36% No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are OA dampers controlled to modulate during when the ambient temperature is below 65F?
37%
6%
57%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are air filters replaced on a regular basis to ensure good airflow?
2%
1%
97%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are steam or hot water pipes well insulated?
3%
4%
93%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are steam traps and valving regularly inspected?
6%
4%
90%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are heat exchanger surfaces regularly cleaned?
3%
0%
97%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
If a boiler is present, is the burner tuned on an annual basis?
6%
0%
94%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
For cooling towers, has the concentration ratio been increased to "6" to conserve water?
38%
0%
62%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Has a water meter been installed on the cooling tower for a sewer charge credit?
63%0%
37% No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are hot water storage tanks, heat exchangers and piping well insulated?
3%
3%
94%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Is a timer used to switch-off the hot water circulating pump for unoccupied periods?
79%
1%
20%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are low-flow lavatory faucet and showerhead aerators present?
34%
15%
51%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Have flush valves on urinals and water closets been adjusted for the lowest/shortest practical flow?
34%
10%
56%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Is the compressed air system regularly inspected for leaks?
7%
0%
93%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Is cooled air provided to the compressor?
76%
2%
22%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Has the compressor discharge pressure been minimized?
21%
0%
79%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are PREMIUM efficiency motors regularly purchased?
12%
15%
73%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are variable frequency drives controlling fans and pumps to enable flow control?
53%
16%
31%No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are cogged V-belts utilized?
25%
22%
53%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Has computer software been installed to automatically switch-off monitors?
44%
36%
20%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Have electric-heated defrost cycles been minimized and scheduled for off-peak periods (night)?
58%
0%
42% No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Has lighting been removed from all vending machines?
69%
10%
21%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Have refrigerated drinking fountains been switched-off?
93%
1%
6%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopSurvey Checklist Data from 300 State-owned Buildings
Are demand-limiting controls present on equipment that may be switched off during peak demand
periods?
80%
0%
20%
No
Some
Yes
USI O&M HVAC Controls Optimization WorkshopEstimated ECO Annual Savings (600 State-owned Buildings)
EstimatedAnnualSavings& Costs:
Envelope & Lighting
ECOs Savings
Envelope & Lighting
ECOs Costs
3 Low-cost HVAC ECOs
Savings
3 Low-cost HVAC ECOsCosts
4 No-costECOs
Savings
In onlythe 600
surveyedbuildings
$3.6M $14.3M $3.4M $1.7M $200K
In all12,300
buildings $13M $53M $12M $6M $700K
USI O&M HVAC Controls Optimization WorkshopEnvironmental Benefits of Energy Conservation
Pounds of Pollutants per Energy Unit
Energy Type& Unit
# CO2per unit
# NOxper unit
# SOxper unit
Electricity(60/40 coal/nuc)
(per 1,000 KWHs)1,240 4 9
Natural Gas(per DecaTherm) 117 0.002 0.0006
Distillate F.O.(per gallon) 22 0.02 0.15
Coal(per ton)
+/- 5,000 15 35