87
http://www.powersys.kr

User Manual Document Version 1.5 Feb 28, 2019

  • Upload
    others

  • View
    10

  • Download
    4

Embed Size (px)

Citation preview

Page 1: User Manual Document Version 1.5 Feb 28, 2019

User Manual Document Version 1.5 Feb 28, 2019

http://powersys.kr/http://www.powersys.kr

Page 2: User Manual Document Version 1.5 Feb 28, 2019

Revision History

Revision Date Remark1.0 2013-10-08 the first edition1.1 2015-08-03 the first update1.2 2017-01-01 the second update1.3 2017-10-01 the third update1.4 2018-02-07 the fourth update1.5 2019-02-28 the fifth update

Page 3: User Manual Document Version 1.5 Feb 28, 2019

1. Safety Information

Please make sure if the product is broken before installing.

Please check if all the control power, current, voltage are off before

connecting or taking apart.

The terminal has a high current and high voltage so it can be

life-threatening when you touch it directly.

The setting should be done along the distribution line configuration.

The machine shows wrong information or malfunction caused by a

different setting from the distribution line configuration.

Connect the side connector along correct connector number with

current/voltage/DO/DI.

The appliance’s earthing terminal should be earthed to ground.

Caution !

Before installing the product, please read the instructions.

Page 4: User Manual Document Version 1.5 Feb 28, 2019

CONTENTS

1. Safety Information

2. Introduction ························································································ 1 2.1. Summary ··········································································································· 1

2.2. Main functions and features ······································································· 1

3. Technical Data ··················································································· 3 3.1. Power and Input/Output ·············································································· 3

3.2. Environmental ·································································································· 5

3.3. Communication ······························································································· 6

3.4. Measurements ································································································· 7

3.5. Mechanical Performance and Size ····························································· 8

4. Installation Instructions ···································································· 18 4.1. Front Panel and names of each part ······················································· 18

4.2. LCD Control and Setting ············································································· 21 4.2.1 Button Function ····················································································································· 21

4.2.2 LCD Display during Power Up ·························································································· 22

4.2.3 LCD Menu Operation ·········································································································· 23

4.2.4. LCD Menu Items ·················································································································· 23

4.3. Order of Installation Test Operation ························································ 33

5. LCD Menu ··························································································· 34 5.1. Display ··············································································································· 34 5.1.1. Display operation ················································································································· 34

5.1.2. Display Menu ························································································································ 34

5.2. Protection Setting Menu ·············································································· 35 5.2.1. Operation Principle of Recloser ······················································································· 35

5.2.2. Operation Principle of FI ··································································································· 36

5.2.3. Phase Fault ···························································································································· 38

5.2.4. Ground Fault ························································································································· 41

5.2.5. SEF Fault ································································································································· 42

5.2.6. Trip & Reclose ······················································································································ 43

5.2.7. Auxiliary Func ························································································································ 45

Page 5: User Manual Document Version 1.5 Feb 28, 2019

5.2.8. Select Group ·························································································································· 49

5.3. Configuration Menu ······················································································· 50 5.3.1. Analog ····································································································································· 50

5.3.2. DI Debounce Time ·············································································································· 52

5.3.3. DO Pulse Width ··················································································································· 52

5.3.4. Backup Set / Clear ·············································································································· 52

5.3.5. Analog Gain Adjust ············································································································· 52

5.3.6. Waveform ······························································································································· 53

5.3.7. Check Auto Battery ············································································································· 53

5.3.8. V/I Unbalance ······················································································································· 53

5.3.9. Sag/Swell ································································································································ 54

5.3.10. THD Alarm ··························································································································· 54

5.3.11. VI Wear ································································································································ 54

5.3.12. Analog High Alm ··············································································································· 54

5.3.13. Analog Low Alm ················································································································ 55

5.3.14. Misc. Config ························································································································ 55

5.4. Communication Menu ··················································································· 56

5.4.1. SCADA Port ··························································································································· 56

5.4.2. Modem Control ···················································································································· 56

5.4.3. DNP Config ····························································································································· 56

5.4.4. IEC101 Config ························································································································· 57

5.4.5. IEC104 Config ························································································································· 58

5.4.6. TCP/IP Config ·························································································································· 58

5.4.7. PSTN Modem ·························································································································· 58

5.4.8. PPP Config ······························································································································· 58

5.4.9. SMS Config ······························································································································ 59

5.4.10. Time Sync Option ·············································································································· 59

5.5. Time Set Menu ······························································································· 59

5.6. Event View Menu ··························································································· 61

APPENDIX A. COMTRADE File’s Formats ··········································· 62

APPENDIX B. RECLOSER Characteristic Curve ·································· 661. TC Curve ·················································································································· 66

2. TC Curve 1~4 ······································································································· 67

3. TC Curve 5~8 ······································································································· 68

4. TC Curve 8*~13 ··································································································· 69

5. TC Curve 14~18 ·································································································· 70

6. TC Curve A~D ······································································································ 71

7. TC Curve E~M ····································································································· 72

Page 6: User Manual Document Version 1.5 Feb 28, 2019

8. TC Curve N~T ······································································································ 73

9. TC Curve V~Z ······································································································ 74

10. TC Curve IEC NI~SI ···························································································· 75

11. TC Curve IEEE MI~NI ························································································· 76

12. TC Curve ANSI U8, U2 ······················································································ 77

13. TC Curve ES NI, VI ····························································································· 78

14. TC Curve KEPCO N1~N4 ·················································································· 79

15. TC Curve DEF 1S, 10S ······················································································· 80

APPENDIX C. Remote Control(option) ················································ 81

Page 7: User Manual Document Version 1.5 Feb 28, 2019

- 1 -

2. Introduction

2.1. SummaryReclosers are used in distribution system. In case of line fault, due to temporarily

overcurrent, Reclosers can break and make currents several times, thus avoiding longer

network interruptions due to temporary faults. But, in case of permanent fault, because

fault current is still detected after trip and reclosing actions of pre-set sequences, Recloser

is locked out finally as opened.

The pre-set sequences are available to set five times, and for both phase and ground, the

combined operations are possible within the range of 5 instantaneous or 5 times delayed

operating. The first interruption of a fault regarding instantaneous operation, is done

quickly and instantaneously, so that even the fuses in the system do not operate. After

setting time, it recloses back on. And the next interruption has a definite or inverse time

delay. Thus downstream fuses or other protection devices in the network have the chance

to operate and isolate the affected network section, restoring normal operation in the

remaining work. Therefore reclosers make the range of fault section to be limited.

Mainly Reclosers which are installed in overhead distribution line, provide the measurement

of electric current flowing in the distribution line. In case of load current occurrence and

fault detection, it opens and recloses repeatedly according to setting sequence, and at the

sametime, it transmits the status/receives the command to/from HOST and remote controls

of opening/reclosing to minimize the accident. Besides, it stores the whole events in

distribution line, provides the fault causes, and it performs remote monitoring and controls

by transmitting data through DNP3.0, IEC60870-5-101, IEC60870-5-104 protocols.

2.2. Main functions and features◆ Protection Function - Fault Detection about phase and ground fault

- SEF(Sensitive Earth Fault) used on non-grounded network

- Inrush current control function during fault detection

- In case of Cold Load, Fault Pickup Level adjustment

- Phase Loss Detection

- Phase Sync Fail Detection about source and load voltage

- Automatic breaking and reclosing by detecting phase and ground fault

- Detecting fault and monitoring the status in distribution line

- Built-in 50 types of recloser curves including IEC, ANSI/IEEE, McGraw Edison Recloser

curve

- Equiped with 4 types of curves(N1, N2, N3, N4) developed by Korea Electric Power

Research Institute(KEPRI, under KEPCO)

Page 8: User Manual Document Version 1.5 Feb 28, 2019

- 2 -

- Additionally user defined 4 types of curves available

- 3 steps protection characteristics implementable, established with definite time elements

and high-current elements

◆ Measuring Function- Current, voltage magnitude and phase angle

- Symmetrical component about 3-phase voltage and current

- Active, reactive, apparent power, and power factor

- Active and reactive energy

- Frequency

- Power quality information : THD, sag/swell, harmonic 2~32th

◆ Control Function- Recloser switch Open / Close control

- Battery Test control

- Preparatory control

◆ State Monitoring Function- Recloser Open / Close status

- Handle locked status

- Gas pressure low status(option)

- External AC low status

- Battery overcharge status

- Door Open

- Spare status 1,2

- Over dischager

- Chager fail

◆ Various Communication Interface- System Interface Port : RS232C

DNP3.0

IEC60870-5-101

- System Interface Port(option) : Ethernet

DNP3.0 over TCP/IP

IEC60870-5-104

- Maintenance Port : USB-A, Wi-Fi(option)

MODBUS RTU

◆ Various Event Information ◎ Operation Event

It stores and manages events occurred during operation such as control(On, Off, Trip)event

and diagnosis event up to 30,000 cases in time sequence.

Page 9: User Manual Document Version 1.5 Feb 28, 2019

- 3 -

◎ Fault Event

It stores and manages various fault information(occurred time, type of fault, operation

relaying element) during distribution line accidents up to 1024 cases in time sequence.

◆ Fault Wave Storage Function It saves and manages the latest fault 160Cycle(16Sample standard) sample data up to 6

cases. The user can use save fault wave to analyze the cause of faults.

◆ Convenient interface for users Through RS232 communication port, it is convenient to manage various set values and

stored measuring information search on PC.(using company supplied S/W)

◆ Self-diagnosis and Backup functions during power-offEPIC-R300 operates self-diagnosis such as CPU check, memory error diagnosis, I/O

diagnosis, and control power diagnosis. It saves warning output and diagnosis event on

occasion of failure. Therefore the user can have a speedy response.

3. Technical Data

3.1. Power and Input/Output◆ Power Supply

◆ Current Input(Ground System)

◆ Current Input(Non-Ground System)

Voltage input Power consumption

DC 24V within 10W

Channel Rating input Input burden

4 channels

(Ia,Ib,Ic,I0)

Rated current(Ia,Ib,Ic) : 1A (Max:12A)

Rated current(I0) : 1A (Max:12A)Under 1VA

Channel Rating input Input burden

4 channels

(Ia,Ib,Ic,In)

Rated current(Ia,Ib,Ic) : 1A (Max:12A)

Rated current(In) : 1A (Max:12A)Under 1VA

Page 10: User Manual Document Version 1.5 Feb 28, 2019

- 4 -

◆ Voltage Input

◆ Digital Input

◆ Digital Output

◆ Logic Functions (option)EPIC-R300 provides logic function. It can output the information about inside device with

DO, DI, etc, which are processed by using the functions of AND, OR, NOT, Timer, SR

Latch, etc, with DO, DI. And it can also be passed to the upper system through

communication.

Basic logic function is as shown below table.

Input Type Point Number Input Circuit Others

Opto-Isolation 10 Port DC 24V Input Biased Debounce Delay

(1~500ms)

Control contact (Photomos) Normal contact

100mA/250VAC 5A/250VAC

2EA 4EA, 8EA(option)

Purpose : Recloser Open / Close Purpose : Battery Test / Spare

Channel Rating input Input burden

6 channels

(Va,Vb,Vc,

Vr,Vs,Vt)

Rated voltage : 4V (Max : ~8V) Under 0.1VA

Function Description

Input Physical input, virtual input,

Output Physical output, virtual output

AND For two inputs, AND gate

OR For two inputs, OR gate

NOT For one inputs, NOT gate

NAND For two inputs, NAND gate

XOR For two inputs, XOR gate

SR Latch of Set / Reset

Timer Timer with settings of Set, Reset, On/Off Delay Timer

D Flip-Flop To maintain froze the input signal for one PLC cycle

Page 11: User Manual Document Version 1.5 Feb 28, 2019

- 5 -

3.2. Environmental

Items Spec

TemperatureOperating -25 ~ 85℃

Storage -40 ~ 95℃

Humidity < 95% RH

Altitude < 4000m

Insulation Resistance DC500V, > 100MΩ

Dielectric Withstand AC 60Hz 2000V/1Min

ImpulseIEC60255-5 6kV : Current

IEC60255-5 4kV : Voltage, Power, DIO

High Frequency

DisturbanceIEC60255-22-1 2.5kV

EFT/Burst IEC60255-22-4 Class A : 4kV

Radiated -

electromagnetic fieldIEC60255-22-4 10V/m

ESD 60255-22-2: Contact(6kV), Air(8kV)

EMI IEC 60255-25

Vibration IEC 60255-21-1 class 2

Page 12: User Manual Document Version 1.5 Feb 28, 2019

- 6 -

3.3. Communication

◆ System Interface Port1

◆ System Interface Port2(can select RS232c or RS485)

Items Spec

RS232C

9 Pin SignalDCD(1), RX(2), TX(3), DTR(4), GND(5)

DSR(6), RTS(7), CTS(8), NC(9)

Speed 1200, 2400, 4800, 9600, 19200, 38400

Opto-Isolation Circuit (Dielectric level : 1kV)

DNP3.0

Protocol

support DNP3.0 Subset Level3

multi-frame transmission

Enable / Disable Unsolicited Response for each class

Save Event which is not transmitted

IEC60870

-5-101

Protocol

support single character NACK

Regular update about measurement data

capable to set address size

Items Spec

RS232C

9 Pin SignalRX(2), TX(3), GND(5)

RTS(7), CTS(8),

Speed 1200, 2400, 4800, 9600, 19200, 38400

Opto-Isolation Circuit (Dielectric level : 1kV)

RS485

9 Pin Signal 485+(6), 485-(9)

Speed 1200, 2400, 4800, 9600, 19200, 38400

Opto-Isolation Circuit (Dielectric level : 1kV)

MODBUS-RTU Slave Mode : To communicate with SCADA

Page 13: User Manual Document Version 1.5 Feb 28, 2019

- 7 -

◆ System Interface Port3(option)

◆ Maintenance Port(USB-A, Wi-Fi)

Items Spec

USB-A4 Pin Signal VCC(1), D-(2), D+(3), GND(4)

Speed 38400bps

MODBUS

-RTU

Protocol

setting, measuring, confirmation function of stored information

(failure information, driving information, Wave)

Maximum 120 point Read at once

Supply special SW for Maintenance

Option Connection via Wi-Fi

3.4. Measurements

Items Accuracy Range

Voltage 1% 40kV (Including PT ratio)

Current 1% 12,000A (Including CT ratio)

kW,kVar,kVA 2% 0~99MW

Power Factor 2% 0~±1

Frequency ±0.01Hz 45~65Hz

kWh, kVarh 2% 0~999999999kW

THD 2% 0~200%

Items Spec

Ethernet10/100 Base-T

Tr Isolation Circuit

DNP3.0 over

TCP/IP

Protocol

Network Access Protocol for DNP3.0

Using standard TCP/IP network

(connection-oriented secure data transmission)

IEC60870

-5-104

Protocol

Network Access Protocol for IEC60870-5-101

Application layer is based on IEC60870-5-101

Using standard TCP/IP network

(connection-oriented secure data transmission)

Page 14: User Manual Document Version 1.5 Feb 28, 2019

- 8 -

3.5. Mechanical Performance and Size

◆ Weight : 3.5 kg

◆ FRONT VIEW

<Figure 3-1> Front View

Page 15: User Manual Document Version 1.5 Feb 28, 2019

- 9 -

◆ SIDE VIEW

343.0

0

310.0

0

91.00

<Figure 3-2> Side View

Page 16: User Manual Document Version 1.5 Feb 28, 2019

- 10 -

◆ TOP VIEW 84.0

260.0

225.0

1.0

.0t

<Figure 3-3> Top View

Page 17: User Manual Document Version 1.5 Feb 28, 2019

- 11 -

◆ REAR VIEW

180.0

120.0

<Figure 3-4> Rear View

Page 18: User Manual Document Version 1.5 Feb 28, 2019

- 12 -

◆ Terminal Arrangement

RS232C(SCADA PORT)

RS232C(SCADA PORT)

Control Source Connector

DI (Status) Connector

DO(Control) Connector

ETHERNETConnector

AI(Voltage) Connector

AI(Current) Connector

<Figure 3-5> Terminal Arrangement

Page 19: User Manual Document Version 1.5 Feb 28, 2019

- 13 -

◆ Pin Assignment(Up Side View)

1) Control Power Connector4 3

24G 24VIN

2 1

FG FG

2) DI (Status) Connector14 13 12 11 10 9 8

DI_COM3 DI10(Spare2) DI_COM2 DI9

(Spare1) DI_COM1 DI8(Gas Low)

DI7(Handle Lock)

7 6 5 4 3 2 1DI6

(Door Open)

DI5(Charger

Fail)DI_COM1 DI4

(Batt Low)DI3

(AC Loss)DI2

(Close)DI1

(Open)

3) DO (Control) Connector12 11 10 9 8 7

DO6-(Rec

Close)

DO6+(Rec

Close)DO4- DO4+ DO3-

(Bat Test-)DO3+

(Bat Test+)

6 5 4 3 2 1DO5-(Rec

Open)

DO5+(Rec

Open)

DO2-(Close-)

DO2+(Close+)

DO1-(Open-)

DO1+(Open+)

4) AI(Voltage) Connector 10 9 8 7 6

V6 V4 V_COM V_COM V2

5 4 3 2 1

V5 V_COM V_COM V3 V1

5) AI(Current) Connector6 5 4 3 2 1

IN(0)- IN(0)+ Icom IC IB IA

Page 20: User Manual Document Version 1.5 Feb 28, 2019

- 14 -

◆ Pin Assignment

FGFG

24VI

N24

GDI

1(O

pen)

DI2

(Clo

se)

DI3

(AC

Loss

)DI

4(B

attL

ow)

DI_C

OM

1DI

5(C

harg

erFa

il)DI

6(D

oorO

pen)

DO1+

(Ope

n+)

IAIB

ICIco

mIN

(0)+

IN(0

)-

DO1-

(Ope

n-)

DO3+

(Bat

Test

+)DO

3-(B

atTe

st-)

DO2+

(Clo

se+)

DO4+

DO2-

(Clo

se-)

DO4-

DO5+

DO6+

DO5-

DO6-

DI7

(Han

dleL

ock)

DI8

(Gas

Low

)DI

_COM

1DI

9(S

pare

1)DI

_CO

M2

DI10

(Spa

re2)

DI_C

OM

3

V1V3

V_CO

MV_

COM

V5V6V2

V_CO

MV_

COM

V4

RS23

2C(S

CADA

Port

)RS

232C

RS48

5Po

rt

<Figure 3-6> Pin Assignment

Page 21: User Manual Document Version 1.5 Feb 28, 2019

- 15 -

◆ Assembly Drawing

INTERNAL PANEL

DOOR

VENTILATOR

MODEM

CABLE HOLE

MS CONNECTOR

130

<Figure 3-7> Assembly Drawing

Page 22: User Manual Document Version 1.5 Feb 28, 2019

- 16 -

◆ Controller PCB

215.00

103.90

121.10

112.50

112.50

235.00

205.00

<Figure 3-8> Controller PCB

Page 23: User Manual Document Version 1.5 Feb 28, 2019

- 17 -

◆ Battery Check PCB

<Figure 3-9> Battery Check PCB

5.090.0

50.0

20.025.025.020.05.0 5.0

50.0

10.0

27.0

R5.5

R7.0

87.0

100.0

Page 24: User Manual Document Version 1.5 Feb 28, 2019

- 18 -

4. Installation Instructions

4.1. Front Panel and names of each part

<Figure 4-1> Front Panel Configuration

1) Operation Status LED

- Run LED : LED which shows CPU’s operation state

- Error LED : LED which shows device’s diagnosis fail

- AC Power LED : LED which shows external power

- Battery Low : LED which shows low battery voltage

- Handle Lock : LED which show Recloser’s handle lock status

- Gas Low : LED which show Recloser’s gas low status only SF6 gas insulation type(option)

3

2

5

6

8

12

7

15

10

9

13

16

1

11 14

4

Page 25: User Manual Document Version 1.5 Feb 28, 2019

- 19 -

2) LCD

It shows EPIC-R300’s measuring, setting, stored information, and search information.

It is convenient 20*4 character module LCD to move the screen through controling

manipulation button.

3) System Communication LED

LED which shows communication state when EPIC-R300 communicates with host system.

- RX LED : Receiving

- TX LED : Transmitting

- RTS LED : Request transmission to Modem

4) ALT SET Button

Button which select function group. LED on, EPIC-R300’s operate by primary group. LED

off, by reverse group.

5) Manipulation Button

Button which controls LCD screen.

- Menu(M) Button : Button which moves to upper menu

- Up(▲) Button : Button which increases set value or moves the menu upwards

- Down(▼) Button : Button which decreases set value or moves the menu downwards

- Enter(⤶) Button : Button which enters the menu or saves set value

6) Distribution Fault Status LED

LED which shows fault on Distribution Line. It shows distribution line’s source and whether

it is load’s voltage, and whether it is synchronous.

- Live Source LED : LED which shows whether it supplies voltage on source side

- Live Load LED : LED which shows whether it supplied voltage on load side

- Phase Sync. Fail LED : LED which shows synchronous fail of phase A/R or B/S or C/T voltage

- Phase A/B/C Loss LED : LED which show phase loss of phase A/B/C on source side

- Phase R/S/T Loss LED : LED which show phase loss of phase R/S/T on load side

- Phase A LED : A Phase Fault LED

- Phase B LED : B Phase Fault LED

- Phase C LED : C Phase Fault LED

- Phase N LED : N Phase Fault LED

- Phase SEF LED : Zero Phase Fault LED on Non-Ground System

- Recloser Ready LED : LED which shows recloser and a control are ready to start a new

auto-reclosing sequence

- Recloser Cycle LED : LED which shows reclosing sequence is in progress

- Recloser Lockout LED : LED which shows recloser goes to lockout with open

- Trip Info Min LED : LED which shows the measured phase current is over the set

minimum operating current

- Trip Info Volt LED : LED which shows the recloser operates by voltage protection

elements

Page 26: User Manual Document Version 1.5 Feb 28, 2019

- 20 -

- Trip Info Freq LED : LED which shows the recloser operates by frequency protection

elements

- Power flow LED(Reverse) : LED which shows whether forward or reverse power

flow

7) Non Reclosing Button

It is used to set whether to allow auto-reclosing sequence after the trip due to

overcurrent and protection elements. Push the button to toggle current functionality. When

the indicator turns on, reclosing operation is restricted.

8) Protection Blocked Button

It is used to restrict operation of all protection elements. It can be temporarily used to

restrict operation of all protection elements. Push the button to toggle current

functionality.

9) Ground Trip Blocked Button

It is used to set whether operation of protection elements for ground overcurrent and SEF.

Push the button to toggle current functionality. When the indicator turns on, operation of

protection elements for ground overcurrent and SEF is restricted.

10) Fault Reset Button

It is a button to reset fault and diagnosis signal LED. It reset actual fault

information with LED.

11) Battery Test Button and LED

It is a button to test battery and battery charger circuit. It shows the test result on Battery

Low LED. If battery low LED is on, which means test fail.

12) Lamp Test Button

It is a button to test LEDs. When push lamp test button, all of the LEDs are turn on.

13) Control Lock Button

It is a button to prevent control operation when doing open / close REC switch on local

or remote when turn on control lock LED. If the control lock LED is on, the protection

function of Recloser also becomes locked. Push control lock button to turn off control lock

LED and then use open / close button to operate.

14) Hot Line Tag

When Activating hot line tag function

- Operation of all protection elements is set to be single shot mode.

- It operates by fast curve.

- It restricts closed operation for the recloser from all sources.

- Tag can be only removed by the tagging source.

Page 27: User Manual Document Version 1.5 Feb 28, 2019

- 21 -

15) Maintenance Port (USB-A)

It is USB-A port for maintenance. It uses MODBUS-RTU protocol as well as a special S/W

provided by NEOPIS.

16) Switch Control Button and LED

It is a button to control Recloser and LED to show the state.

o REMOTE CONTROL (R/C) Button : It is a button which selects remote and local control

mode. If you push the button, remote and local mode select are toggled. If REMOTE LED

is on, which means remote control mode is on so it is not possible to operate on local.

In order for local control, push the button to turn off REMOTE LED. Then operate at the

local as using OPEN/ CLOSE button on the side.

o OPEN Button : It is a button to open Recloser on local. If OPEN LED is turned on,

which means Recloser’s status is changed.

o CLOSE Button : It is a button to close Recloser on Local. CLOSE LED is turned off when

Recloser’s status is changed.

4.2. LCD Control and Setting

4.2.1 Button Function

Buttons Function

Menu(M)Return to upper menu

Cancel setting

Up(▲) Increase set value

Move to upwards of menu

Down(▼) Decrease set value

Move to downwards of menu

Enter(⤶)

Move to lower menu

Save set value

Choose set value

Page 28: User Manual Document Version 1.5 Feb 28, 2019

- 22 -

4.2.2 LCD Display during Power UpWhen EPIC-R300’s power is connected, the product name, EPIC-R300, and company name

is on LCD for a second. Then measuring screen shows voltage and current.

◆ Power Up for 1 second on LCD DisplayIt is the screen of EPIC-R300. A second later, LCD top display shows.

E P I C R 3 0 0

N E O P I S

<Figure 4-2> LCD Display

◆ LCD Top DisplayThis Top Menu is that displays Recloser’s operation state. Using up/down button, you can

move to the main measurement menu which shows the measured value of current and

voltage. The menu items for Recloser’s operation state are as follows.

- SeqN : Current reclosing counts

- R/C Status : Open/Close/Unknown

- Rcl T : Reclosing time remained

- Reset T : Return time remained

- R/C Ready, Progress, Lockout state

Without controling key, the main measurement menu always returns to top screen 10

minutes later.

[ R / C C o n t r o l l e r ]S e q N : 0 R /C : U n k n o w nR c l T : 0 R e s e t T : 0

< N o t R e a d y >

I a : 0 . 0 0 0 . 0 0 / 0 . 0 0 Ib : 0 . 0 0 0 . 0 0 / 0 . 0 0 I c : 0 . 0 0 0 . 0 0 / 0 . 0 0 In : 0 . 0 0 < A B C / R S T >

<Figure 4-3> Recloser’s Operation State Menu

Page 29: User Manual Document Version 1.5 Feb 28, 2019

- 23 -

4.2.3 LCD Menu Operation

<Figure 4-4> LCD Menu in Top Menu

4.2.4. LCD Menu ItemsNext, it is a list of overall menu items. Menu is divided into main menu and lower menu.

<Table 4-1. LCD Menu>

Main menu Lower menu Contents

Top menu Display operation state of Recloser

Main Measurement Menu Display voltage and current measured

Display

PowerActive/reactive/apparent power,

power factor, frequency

Energy Active, reactive energy

Voltage / CurrentVoltage and current’s symmetrical

component

THDVoltage and current’s total harmonic

distortion

Phase DiffVoltage and current’s phase

difference

Reset / SW CountPower On/Off count, watchdog reset

count, switch Open/Close count

Fault Counttotal and individual phase’s fault

count

VI Wear Count It displays residual contact wear

DI Status DI status

Self-Diagnosis self-diagnosis state

Comm Monitoring It displays communication packets

Device Info device information

Protection

Set

Func

Group

Phase

Fault

Op Level &

TimePickup Level Setting operating level for phase fault

Page 30: User Manual Document Version 1.5 Feb 28, 2019

- 24 -

1~4

Fast Curve Setting fast operating value curve

Fast MultiplierSetting fast operating value control

multiplier

Fast Time Add Set fast operating value time delayed

Fast Min ResponseSet fast operating value min. response

time

Fast Reset Time Set fast reset time of definite time

Delay Curve Set delay curve-operating value

Delay Multiplier Set delay control multiplier

Delay Time Add Set delay time added

Delay Min Resp Set delay min. response time

Delay Reset Time Set delay reset time of definite time

Delay DT Level Set operating value at definite time

Delay DT TimeSet operating time for operating value at

definite time

HCT LevelSet operating value at high current trip

level

HCT TimeSet operating time at high current trip

time

Func In Use Set phase fault operation functions

Save Set Save the operation setting

Block Flt

Pickup

Cold Load Multi

A multiplier to prevent the

mis-recognizing as a fault by increasing

a multiply of pick-up level under cold

load condition.

Return Normal I Set cold load return current

Cold Load Time Set restraining time of cold load

Use Cold Load Set cold load Use/Not use

Inrush Multiply Set inrush control multiplier

Inrush Time Set inrush operating time

Use Inrush Set phase fault inrush Use/Not use

2nd Harmonic Set 2nd harmonic inrush control level

2nd_H Detect Time Set 2nd harmonic time level

Use 2nd Harmonic Set 2nd harmonic inrush Use/Not use

Save Set Save the operation setting

Fault

Direction

Trip Direction Set trip direction in fault section

3V1 ThresholdSet positive sequence voltage pickup

level

3I1 ThresholdSet positive sequence current pickup

level

3I1 AngleSet operating angle directional

current

Dir Block OC Set fault direction block

Page 31: User Manual Document Version 1.5 Feb 28, 2019

- 25 -

Save Set Save the operation setting

Ground

Fault

Op Level &

Time

Pickup Level Set operating level for ground fault

Fast Curve Set fast operating value curve

Fast MultiplierSet fast operating value control

multiplier

Fast Time Add Set fast operating time delay added

Fast Min ResponseSet fast operating value min.

response time

Fast Reset Time Set fast reset time of definite time

Delay Curve Set delay operating value curve

Delay MultiplierSet delay operating value control

multiplier

Delay Time Add Set delay operating value delay time added

Delay Min RespSet delay operating min. response

time

Delay Reset Time Set delay reset time of definite time

Delay DT Level Set operating value at definite time

Delay DT TimeSet operating time for operating

value at definite time

HCT LevelSet operating value at high current trip

level

HCT TimeSet operating time at high current trip

time

Func In Use Set phase fault operation functions

Save Set Save the operation setting

Block Flt

Pickup

Cold Load Multi

A multiplier to prevent the

mis-recognizing as a fault by

increasing a multiply of pick-up level

under cold load condition.

Return Normal I Set cold load return current

Cold Load Time Set restraining time of cold load

Use Cold Load Set cold load Use/Not use

Inrush Multiply Set inrush control multiplier

Inrush Time Set inrush operating time

Use Inrush Set phase fault inrush Use/Not use

2nd Harmonic Set 2nd harmonic inrush control level

2nd_H Detect Time Set 2nd harmonic time level

Use 2nd Harmonic Set 2nd harmonic inrush Use/Not use

Save Set Save the operation setting

Fault

Direction

Trip Direction Set trip direction in fault section

3V0 Threshold Set zero phase voltage pickup level

3I0 Threshold Set zero phase current pickup level

Page 32: User Manual Document Version 1.5 Feb 28, 2019

- 26 -

3I0 AngleSet operating angle directional

current

Dir Block OC Set fault direction block

Save Set Save the operation setting

SEF

Fault

Op Level &

Time

3I0 PickupSet zero phase current operating

value

-3V0 PickupSet zero phase voltage operating

value

SEF Reset Time Set SEF reset time of definite time

Func In Use Set SEF operating functions

Save Set Save the operation setting

Block Flt

Pickup

Inrush Multiply Set inrush control multiplier

Inrush Time Set inrush operating time

Use Inrush Set phase fault inrush Use/Not use

2nd Harmonic Set 2nd harmonic inrush control level

2nd_H Detect Time Set 2nd harmonic time level

Use 2nd Harmonic Set 2nd harmonic inrush Use/Not use

Save Set Save the operation setting

Fault

Direction

Op Angle Set SEF operating angle

Op Time Set SEF operating time

Save Set Save the operation setting

Trip &

Reclose

Phase Rec

Count

Phase Oper CntSet phase fault sequence operating

counts

Phase Fast CntSet fast operating counts for phase

fault

Phase HCT CntSet HCT operating section for phase

fault

Save Set Save phase fault operation setting

GND Rec

Count

GND Oper CntSet ground fault sequence operating

counts

GND Fast CntSet fast operating counts for ground

fault

GND HCT CntSet HCT operating section for ground

fault

Save Set Save ground fault operation setting

SEF Rec

Count

SEF Oper CntSet SEF fault sequence operating

counts

SEF Fast Cnt Set fast operating counts for SEF fault

Save Set Save SEF fault operation setting

Reclose

Time

Rec Time 1st Set 1st reclosing operating time

Rec Time 2nd Set 2nd reclosing operating time

Rec Time 3rd Set 3rd reclosing operating time

Rec Time 4th Set 4th reclosing operating time

Page 33: User Manual Document Version 1.5 Feb 28, 2019

- 27 -

Reset Time Set reset time of reclosing counter

Save Set Set reclose time setting

SEF

Reclose

Time

SEF Rec Time 1st Set 1st reclosing operating time(SEF)

SEF Rec Time 2nd Set 2nd reclosing operating time(SEF)

SEF Rec Time 3rd Set 3rd reclosing operating time(SEF)

SEF Rec Time 4th Set 4th reclosing operating time(SEF)

SEF Reset TimeSet reset time of reclosing

counter(SEF)

Save Set Set SEF reclose setting

Reclosing

Option

Single Shot Time Set single shot time

Seq CoordinationSet sequence coordination Use/Not

use

Save Set Save operating setting

Auxiliary

Func

Open Line

Detect

Volt On Set open line voltage on level

Volt Off Set open line voltage off level

Delay Off Set open line delay time setting

Use FuncSet whether open line function is

available

Save Set save open line set value

Sync Check

Phase OffSet sync check phase difference

permission setting

Delay TimeSet sync check phase difference delay

time setting

Use FuncSet whether sync check function is

available

Save Set save sync check set value

Live Line

Detect

Volt Level Set live line voltage on level

Detect Time Set live line detecting delay time

Save Set save live line set value

Negative

OC

I2/I1 PickupSet reverse phase current operation

value

Delay TimeSet reverse phase current operation

time

I1 Threshold Set Positive current threshold value

2nd Harmonic Blk Select 2nd Harmonic block/ non-block

Func In Use Set negative OC operating functions

Save Set Save the operation setting

Under

Voltage

U-V Pickup Set pickup level for under voltage

U-V Op Time Set operation time for under voltage

Use FuncSet whether under voltage function is

available

Save Set Save under voltage set value

Page 34: User Manual Document Version 1.5 Feb 28, 2019

- 28 -

Over

Voltage

O-V Pickup Set pickup level for over voltage

O-V Op Time Set operation time for over voltage

Use FuncSet whether over voltage function is

available

Save Set Save over voltage set value

Under

Frequency

U-F Pickup Set pickup level for under frequency

U-F Op TimeSet operation time for under

frequency

Use FuncSet whether under frequency function

is available

Save Set Save under frequency set value

Over

Frequency

O-F Pickup Set pickup level for over frequency

O-F Op Time Set operation time for over frequency

Use FuncSet whether over frequency function

is available

Save Set Save over frequency set value

Close

Interlock

Live Load Select whether live load is available

Sync Fail Select whether sync fail is available

Save Set Save close interlock set value

Loop

Automation

Loop SelectionSelect operating mode for the

recloser

Deadbus Open TimeSet open time for determining

distribution line’s dead line state

Tie Sw Open Time Set Open time for tie sw

Tie Sw SourceSelect whether Tie sw source is ABC or

RST

Tie Sw Close Time Set close time for tie sw

Rec Block Time Set Reclosing Blocking Time

Enable RestoreSet whether restoration after clearing

fault

Rec Close Time Set recloser closing time after open

Tie On delta ISet delta I level to restore for Tie

recloser after fault

Save Set Save loop automation set value

Select

Group

Primary Group Select a group which will be actvated

Sel Auto GroupSelect whether auto group function is

available

Reverse Group Select a alternative group

Save Sel Group Save select group set value

Default Fact Set Set all settings to factory settings

Configurat-

ionAnalog

Line Config Set 3P4W / 3P3W

Frequency Set frequency(50/60Hz)

Rated Volt Set rated voltage

Page 35: User Manual Document Version 1.5 Feb 28, 2019

- 29 -

CT Ratio Set CT ratio

NCT Ratio Set NCT ratio

Avg Interval Set average value process interval

Select FI Reset Set FI reset way(Auto / Manual)

Display VoltageSelection of line to phase voltage and

line to line voltage

Phase Position Select phase position

Phase RotationSelect whether phase rotation is ABC

or ACB

Source Side

Select which side will be power

source between ABC side and RST

side

Energy log duty Set duty time for energy logging

Closing delay Set delay time to close CB

Check V for FISelect whether to consider voltage

when FI set

Reclaim T for FI Set reclaim time for FI clear

Important Key DelaySet Delay about Important Key(ALT

SET, CLOSE, OPEN)

V Sensor Fail Delay Set delay time for Voltage Sensor Fail

I Cut Level Set level for current cutting

V Cut Level Set level for voltage cutting

Save Config Save analog configuration setting

DI

Debou

nce

Time

DI1~ DI10 Set DI1~10 debounce time

Save Config Set save DI debounce Configuration

DO

Pulse

Width

DO1~DO6 Set DO1~DO6 pulse width

Save Config Save DO pulse width setting

Backup

Set/Cle

ar

Set Switch Cnt Set number of switch operation

Clear Event Clear event information

Clear Fault Clear fault information

Clear Oper Count Clear operation information

Analog

Gain

Adj

Ia~In, Va~Vt Adjust analog gain

Save Config Save analog gain config setting

Clear Gain Data Clear analog gain config setting

Wavefo

rm

Sample RateSet sample rate when capturing

waveform

Record Size Set record size of waveform

Pre Cycle Set pre cycle number of waveform

Post Cycle Set post cycle number of waveform

Save Config Save waveform config setting

Page 36: User Manual Document Version 1.5 Feb 28, 2019

- 30 -

Check

Auto

batt

Check Day Set auto checking day for battery

Check Hour Set auto checking hour for battery

Check Min Set auto checking minute for battery

Save ConfigSave config set value for battery auto

checking

Check

Auto

batt(op

tion)

Auto-Check Day Set auto checking day for battery

Detect Batt-Low Set voltage level for battery low

Cut-Off Voltage Set voltage level for battery cutoff

Cut-Off Delay Set delay time for battery cutoff

Save ConfigSave config set value for battery auto

checking

V/I

Unbala

nce

V Unbalance Set unbalance level for voltage

V Unbalance Time Set unbalance time for voltage

I Unbalance Set unbalance level for current

I Unbalance Time Set unbalance time for current

Save Config Save V/I unbalance set value

Sag/Sw

ell

Sag Level Set pickup level for sag

Sag Time Set operation time for sag

Swell Level Set pickup level for swell

Swell Time Set operation time for swell

Interrupt Level Set pickup level for interruption

Interrupt Time Set operation time for interruption

Save Config Save config set value for Sag/Swell

THD

Alarm

V THD Alarm Level Set alarm level for voltage THD

V THD Alarm Time Set alarm time for voltage THD

I THD Alarm Level Set alarm level for current THD

I THD Alarm Time Set alarm time for current THD

Save Config Save config set value for THD alarm

VI

Wear

Max Op CountSet the type of the VI used in the

recloser

Alarm LevelSet alarm level for residual contact

wear

Duty Factor A Set duty factor for A phase’s VI

Duty Factor B Set duty factor for B phase’s VI

Duty Factor C Set duty factor for C phase’s VI

Save Config Save config set value for VI Wear

Clear Wear Info Clear wear information

Analog

High Phase Current

Set phase current level for Analog

High Alarm function

Page 37: User Manual Document Version 1.5 Feb 28, 2019

- 31 -

Alm

Ground CurrentSet ground current level for Analog

High Alarm function

Phase VoltageSet phase voltage level for Analog

High Alarm function

System PowerSet system power level for Analog

High Alarm function

Enable High AlarmSelect whether Analog High Alm

function is available

Save ConfigSave config set value for Analog High

Alarm

Analog

Low

Alm

Phase CurrentSet phase current level for Analog

Low Alarm function

Ground CurrentSet ground current level for Analog

Low Alarm function

Phase VoltageSet phase voltage level for Analog

Low Alarm function

System PowerSet system power level for Analog

Low Alarm function

Enable Low AlarmSelect whether analog low alm

function is available

Save ConfigSave config set value for Analog Low

Alarm

Miscell

aneous

Config

Door Open Contact Set contact type for door open(DI6)

AC POWER LEDSet condition of AC POWER LED

On(DI3)

Insulator Type Set type of insulator

Save Confg Save config set value for Misc. config

Communica

tion

SCADA

Port

Baud Rate Set Baud rate

Parity Set serial communication Parity

Slave D/L Addr Set DNP slave or IEC-101 D/L address

ASDU Common Addr Set IEC870 ASDU Common address

Select Protocol Set communication protocol

Select MapSelect Protocol map, full map or user

map

Clear User Map Clear downloaded user map

Save SCADA Port Save SCADA port related setting

Mode

m

Control

Comm Line Set modem communication line

RTS Off Delay Set RTS off delay time

CTS Timeout Set CTS set timeout time

DCD Timeout Set DCD Set timeout time

Save Modem Ctrl Save modem control related setting

DNP

Config

D/L Retry Set data link layer retry

D/L Timeout Set data link layer timeout

D/L Confirm Set data link layer confirm

A/L Retry Set application layer retry

A/L Timeout Set application layer timeout

Unsol Response Class Set unsolicited response transmission class

Page 38: User Manual Document Version 1.5 Feb 28, 2019

- 32 -

Unsol Response Delay Set unsolicited response transmission delay

Unsol Resend Delay Set unsolicited resend transmission delay when no ACK

SBO Timeout Set select before operation timeout

Master Address Set master address for unsolicited response

Frame Interval Set link layer frame interval

DNP Port Num Set DNP-TCP Port Number

Cls Evt when RSTSelect whether clear event or not

after device restart

Event Time SyncSelect whether save event only after

time sync or save event always

BI Change Default VariationSelect whether with time or without

time when sending BI event data

AI Change Default VariationSelect whether with time or without

time when sending AI event data

Save DNP Set Save DNP related setting

IEC101

Config

Link Addr Size Set link address size

Common Addr Size Set common address size

IOA Size Set Information Object address size

COT Size Set COT address size

Time Format Select Time Format, CP24, CP56 or NO

Single Character N/ACK Set 1-character ACK, NACK function

Arm Timeout Set arm timeout

Analog Data Type Set analog data type

Scan Analog Change Set scan analog change information

Scan Binary Change Set scan binary change information

Save IEC Set Save IEC101 related setting

IEC104

Config

Conn Timeout(t0) Set connection timeout

APDU Timeout(t1) Set APDU timeout

Ack Timeout(t2) Set ack timeout

Test Period(t3) Set time period

Xmt SpontaneousSelect whether spontaneous response

function is available

Max Xmt I-APDU(k) Set max transmitting I-APDU

Max Rcv I-APDU(w) Set max receiving I-APDU

Save IEC104 Set Save IEC104 related setting

TCP/IP

Config

IP Address Set IP address

Subnet Mask Set subnet mask bit set

Gateway Set gateway address

NTP Server Set NTP server address

Save TCPIP Set Save TCP/IP related setting

Page 39: User Manual Document Version 1.5 Feb 28, 2019

- 33 -

4.3. Order of Installation Test Operation① Check if the connection is right. Turn On the control power.

② Check CT/PT rate on System Config. Menu. If necessary, adjust it following CT/PT rate control.

③ Check connection system on System Config. Menu. If necessary, adjust it.

④ Check & Control Alarm contact’s setting state on DO Config. Menu. If necessary, adjust it.

⑤ On Relay setting menu, check if Relays are correctly setting. If necessary, adjust it.

⑥ After all adjustments, EPIC-R300 works properly.

⑦ If RUN LED on front panel blinks regularly and SYS-FAIL LED is turned off, which

means it works properly.

PSTN

Config

PSTN Modem Select PSTN mode type, PPP, dialup or SMS

Auto Hangup Time Set Auto hangup time

Dial Timeout Set dial timeout

Attempt Delay Set dial attempt delay time

Max Attempts Set dial max attempt

Save PSTN Set Save PSTN related setting

PPP

Config

Our IP Addr Set our IP address

Their IP Addr Set their IP address

DNS1 IP Addr Set DNS1 IP address

DNS2 IP Addr Set DNS2 IP address

Save PPP Set Save PPP related setting

SMS

Config

Trip Enable Set sending trip information

FI Enable Set sending FI information

Open Enable Set sending open information

Door Open Enable Set sending door information

AC fail Enable Set sending AC fail information

Save SMS Set Save SMS related setting

Time

sync

option

SNTP sync Enable Select whether to enable SNTP

SNTP sync Period Set SNTP cycle duty

Select Time Zone Select time zone

Save TimeSync Set Save TimeSync related setting

Time Set Time setting

Event View

Fault Event Fault event

Op Event Display Operation event

Demand I Display Demand current

Demand P Display Demand power

Max Demand I Display Max demand current

Max Demand P Display Max demand Power

Page 40: User Manual Document Version 1.5 Feb 28, 2019

- 34 -

5. LCD Menu

5.1. Display 5.1.1. Display operationMoving on display items is like below.

<Figure 5-1> Display Operation

5.1.2. Display MenuDisplay menu shows measuring value(voltage, current, phase, symmetrical component),

operation count, fail count, DI status, self-diagnosis, and status information.

<Figure 5-2> Display Menu

1) Power : Active / Reactive / Apparent Power, Power Factor, Frequency display

2) Energy : Active / Reactive Energy display (kWh). If it is over 999999999kWh, then it

[ D I S P L A Y M E N U ]

-> 1 . P o w e r

2 . E n e r g y

3 . V o l t a g e / C u r r e n t

4 . T H D

5 . P h a s e D i f f

6 . R e s e t / S W C o u n t

7 . F a u l t C o u n t

8 . V I W e a r C o u n t

9 . D I S t a t u s

1 0 . S e l f - D i a g n o s i s

1 1 . D e v i c e I n f o

Page 41: User Manual Document Version 1.5 Feb 28, 2019

- 35 -

becomes clear to 0.

3) Voltage/Current : display items like Voltage (Va, Vb, Vc) and Current (Ia, Ib, Ic)’s

Positive Sequence, Negative Sequence, Zero Sequence

4) THD : display Voltage(Va, Vb, Vc) and Current(Ia, Ib, Ic)’s Total Harmonic Distortion value

(measure up to h=2~32th)

5) Phase Diff : display Voltage(Va, Vb, Vc) and Current(Ia, Ib, Ic)’s phase difference

6) Reset / SW Count : display Power On Reset Count and Watchdog Reset Count. display

the number of Switch’s On/Off

7) Fault Count : display each phase’s fault count and total fault count

8) VI Wear Count : display residual contact wear for each phase’VI

9) DI Status : DI Status display. it shows 4 items at once. In order to see the next item,

use Up/Down Key to move. Display items are below,

- Open, Close, Handle Lock, External AC Fail, Over Discharge, Door, Charger fail

- Spare1,2, DI status. If DI status is Enable it shows 1.

10) Self-Diagnosis : device’s self-diagnosis information display

11) Comm Monitoring

It displays communication packets

12) Device Info : device’s information(name of the device, manufacturer, program version,

Web site display

5.2. Protection Setting Menu

5.2.1 Operation Principle of RecloserThe figure below shows the case of lockout state that, when set with 2F3D of reclosing

sequence, Recloser operates twice of fast operation and 3 times of delay operation against

fault, and then locked out as opened.

Page 42: User Manual Document Version 1.5 Feb 28, 2019

- 36 -

<Figure 5-3> Permanent fault for Recloser Sequence

The following figure shows the successful reclosing case that Recloser operates twice of

fast action and inputted. After the lapse of set-Reset Time, Recloser returns, and then

display of LED and LCD are changed from Progress into Ready status. If a fault occurs

again during Reset Time, when the counts of reclosing action reaches to total counts

which shall be calculated from remaining fault counts, the Recloser becomes locked out.

<Figure 5-4> Temporary fault for Recloser Sequence

5.2.2 Operation Principle of FIIf there is a fault on distribution line, protection device(CB, Recloser) does tripping to

protect the system. Then EPIC-R300, Feeder RTU, operates Protection function to detect the

fault, through which it is possible to explore fault section. It is a menu to set and manage

related set value. The basic principle of operation is like a picture below. If there is

permanent or temporary Fault, it detects zero voltage with protective device(CB or

⓵ 1st TRIP - 1st FAST TCC ⓶ 1ST RECLOSE INTERVAL

⓷ 2ND TRIP - 2ND FAST TCC ⓸ 2ND RECLOSE INTERVAL

⓹ 3rd TRIP - 1ST SLOW TCC ⓺ 3rd RECLOSE INTERVAL

⓻ 4th TRIP - 2nd SLOW TCC ⓼ 4th RECLOSE INTERVAL

⓽ 5th TRIP - 3rd SLOW TCC ⓾ LOCKOUT

⓵ 1st TRIP - 1st FAST TCC ⓶ 1ST RECLOSE INTERVAL

⓷ 2ND TRIP - 2ND FAST TCC ⓸ 2ND RECLOSE INTERVAL

⓹ 3rd TRIP - 1ST SLOW TCC

Page 43: User Manual Document Version 1.5 Feb 28, 2019

- 37 -

Recloser) after fault current. After detecting zero voltage, EPIC-R300 generates FI. With

protective device’s reclosing success, normal current and voltage are returned. If FI Auto

Reset was set, FI is reset automatically.

If not, push FI reset button on the front or it is reset with transmitted FI reset order in

remote. R300 is designed to generate FI not only for the case that R300 becomes tripped

itself against a fault, but also that other protection devices are tripped.

- Temporary Fault

<Figure 5-5> Temporary Fault

- Permanent

Fault

<Figure 5-6> Permanent Fault

Protection set value divides into 4 Groups to manage. Choose applied group through

Active Group setting.

Page 44: User Manual Document Version 1.5 Feb 28, 2019

[ S e t t i n g M E N U ]

→ 1 . F u n c G r o u p 1

2 . F u n c G r o u p 2

3 . F u n c G r o u p 3

4 . F u n c G r o u p 4

5 . S e l e c t G r o u p

[ F u n c S e t t i n g ]

→ 1 . P h a s e F a u l t

2 . G r o u n dd F a u l t

3 . S E F F a u l t

4 . T r i p & R e c l o s e

5 . A u x i l i a r y F u n c

- 38 -

<Figure 5-7> Setting Menu- Func Group

5.2.3. Phase FaultIn order to detect phase fault, setting items and ranges are like below.

<Table 5-1> Detecting phase fault

Category Item Range Default Step Unit Explanation

Op Level

& Time

Pickup Level 10~2000 400 1 A Set operation level

Fast Curve 1~50 A Curve Set fast curve

Fast Multiplier 0.05~2 1.00 0.01Set a multiplier of fast operating curve.

Fast Time Add 0.00~1.00 0.00 0.01 secSet operating delayed time under fast curve condition

Fast Min

Response0.00~1.00 0.00 0.01 sec

Set min. operating response time

under fast curve conditionFast Reset Time 0.00~1.00 0.00 0.01 sec Set fast reset time of definite time

Delay Curve 1~50 B Curve Set delay curve

Delay Multiplier 0.05~2 1.00 0.01Set a multiplier of delay operating curve.

Delay Time Add 0.00~1.00 0.00 0.01 secSet operating delayed time under delay curve condition

Delay Min Resp 0.00~1.00 0.00 0.01 secSet minimum operating response time under delay curve condition

Delay Reset Time 0.00~1.00 0.00 0.01 sec Set delay reset time of definite timeDelay DT Level 25~10000 OFF 1 A Set operating value at delay DT levelDelay DT Time 0.01~2 2.00 0.01 sec Set operating time at delay DT time

HCT Level 25~10000 OFF 1 ASet operating value at high current trip level

HCT Time 0.01~1 0.04 0.01 secSet operating time at high current trip time

Func In Use NO/YES YES Set phase fault operation functions

Block flt

Pickup

Cold Load Multi 1~10 2 1

A multiplier to prevent the mis-recognizing as a fault by increasing a multiply of pick-up level under cold load condition.

Return Normal I 0~30 0.3 0.01 secSet the return current of restraining operation against cold load

Cold Load Time 0~180 3 1 min Set restraining time of cold loadUse Cold Load NO/YES NO Set cold load Use/Not use

Inrush Multiply 1~10 2 1

A multiplier to prevent the mis-recognizing as a fault by increasing a multiple of pick-up level under inrush condition

Inrush Time 0~30S 0.02 0.01 sec Set restraining time of InrushUse Inrush NO/YES NO Set inrush Use/Not use

2nd Harmonic 1-50 20 1 %A level of regarding 2nd harmonic as inrush

Use 2nd Harmonic 0.02~1 0.02 0.01 sec Set 2nd harmonics Use/Not use

Page 45: User Manual Document Version 1.5 Feb 28, 2019

- 39 -

1) Fast Operation

This menu is for setting “FAST” among Recloser’s operation sequence

2) Delay Operation

This menu is for setting “Delay” among Recloser’s operation sequence

3) Delay DT Protection

This menu is for setting Delay Definite Time regardless of targeted section among

Recloser’s operation sequence

4) HCT Protection

This menu is for setting the protection against the high current trip of Recloser

5) Cold load Operation

If a load has not been powered for a prolonged period, and when the power has again

resumed i.e. by input of circuit breaker, this can impose a higher current than the pickup

value of time-delay overcurrent protection, which could exceed normal settings. These

conditions can exists for an extended period and must not be interpreted as a fault. In

other words, this function is recognized as Cold load circumstance, when no current

measured in the Recloser is maintained for 5 minutes(300sec). If the measured current is

less than the multiples of pick-up, Recloser does not recognize it as a failure. If it is larger

than the multiples of pick-up, Recloser regards the situation as an actual fault, and

performs the same reclosing sequence same as normal operation.

<Figure 5-8> ColdLoad

Fault

Direction

Trip Direction OFF/FWD/REV OFF Selection of phase fault direction

3V1 Threshold 0~100 20 1 %Set positive sequence voltage operating value

3I1 Threshold 0~100 20 1 %Set positive sequence current operating value

3I1 Angle 0~359 300 1 °Set positive sequence current operating angle

Dir Block OC NO/YES NO Set direction function block

Page 46: User Manual Document Version 1.5 Feb 28, 2019

[ F u n c S e t t i n g ]

->1 . P h a s e F a u l t

2 . G r o u n dd F a u l t

3 . S E F F a u l t

4 . T r i p & R e c l o s e

5 . A u x i l i a r y F u n c

[ F u n c S e t t i n g ]

→ 1 . P h a s e F a u l t

2 . G r o u n dd F a u l t

3 . S E F F a u l t

4 . T r i p & R e c l o s e

5 . A u x i l i a r y F u n c

[ P h a s e F a u l t ]

→ 1 . O p L e vv e l & T i m e

2 . B l o c k F l t P i c k u p

3 . F a u l t D i r e c t i o n

[ O P L e v e l & T i m e ]

→ 1 . P i c k u p L e v e l

2 . F a s t C u r v e

3 . F a s t M u l t i p l i e r

4 . F a s t T i m e A d d

5 . F a s t M i n R e s p o n s e

6 . F a s t R e s e t T i m e

7 . D e l a y C u r v e

8 . D e l a y M u l t i P l i e r

9 . D e l a y T i m e A d d

1 0 . D e l a y M i n R e s p

1 1 . D e l a y R e s e t T i m e

1 2 . D e l a y D T L e v e l

1 3 . D e l a y D T T i m e

1 4 . H C T L e v e l

1 5 . H C T T i m e

1 6 . F u n c I n U s e

1 7 . S a v e S e t

[ P i c k u p L e v e l ]

S E T : 4 0 0 A

( 1 0 - 2 0 0 0 A : 1 A )

- 40 -

6) Inrush Restraint

When the circuit breaker is putted in order to supply the electricity to a load, Inrush

current is generated in a short time. Inrush restraint is a function to prevent Recloser’s

mis-operation of fault detection elements due to that kind of inrush current at the time of

energization in the line. Inrush restraint can be achieved by two methods ; multiplier can

be applied to pick-up current, and another way is, in case that 1st and 2nd harmonics

contents of generated current is over the constant current, to restrain current for the

setting time.

In order to detect Phase Fault, setting items and ranges are like below. The order to set is

like below.

1) Choose the menu with Up/Down Key. Press Enter Key to enter the menu.

<Figure 5-9> Setting menu

2) On Phase Fault menu, choose the setting item you want with Up/Down Key. Press Enter

Key to enter the setting item.

<Figure 5-10> Phase Fault-Pickup Level

Page 47: User Manual Document Version 1.5 Feb 28, 2019

[ U p d a t e S e t t i n g ]

→ P r e s s E n t e r

[ O P L e v e l & T i m e ]

→ 1 . P i c k u p L e v e l

2 . F a s t C u r v e

3 . F a s t M u l t i p l i e r

4 . F a s t T i m e A d d

5 . F a s t M i n R e s p o n s e

6 . F a s t R e s e t T i m e

7 . D e l a y C u r v e

8 . D e l a y M u l t i P l i e r

9 . D e l a y T i m e A d d

1 0 . D e l a y M i n R e s p

1 1 . D e l a y R e s e t T i m e

1 2 . D e l a y D T L e v e l

1 3 . D e l a y D T T i m e

1 4 . H C T L e v e l

1 5 . H C T T i m e

1 6 . F u n c I n U s e

1 7 . S a v e S e t

- 41 -

3) Change set value with Up/Down Key. Press Enter Key to confirm. If you want to cancel

the changed set value, press M Key.

4) When the setting is completed, choose 17. Save Set to save the set value in backup

memory and come out from the item. Then the set value is applied to the device.

<Figure 5-11> Phase Fault-Save Set

5.2.4. Ground FaultIn order to detect ground fault, setting items and ranges are like below.

<Table 5-2> Detecting ground fault

Category Item Range Default Step Unit Explanation

Op Level &

Time

Pickup Level 5~2000 400 1 A Set operation level

Fast Curve 1~50 1 Curve Set fast curve

Fast Multiplier 0.05~2 1.00 0.01 Set a multiplier of fast operating curve.

Fast Time Add 0.00~1.00 0.00 0.01 secSet operating delayed time under fast curve condition

Fast Min

Response0.00~1.00 0.00 0.01 sec

Set min. operating response time under fast curve condition

Fast Reset Time 0.00~1.00 0.00 0.01 sec Set fast reset time of definite time

Delay Curve 1~50 8 Curve Set delay curve

Delay Multiplier 0.05~2 1.00 0.01 Set a multiplier of delay operating curve.

Delay Time Add 0.00~1.00 0.00 0.01 secSet operating delayed time under delay curve condition

Delay Min Resp 0.00~1.00 0.00 0.01 secSet minimum operating response timeunder delay curve condition

Delay Reset

Time0.00~1.00 0.00 0.01 sec Set delay reset time of definite time

Page 48: User Manual Document Version 1.5 Feb 28, 2019

- 42 -

The way to set is identical with 5.2.3

5.2.5. SEF FaultSEF(Sensitive Earth Fault) fault is used when ground fault current is small in ungrounded

system. Next it is operation diagram about operation area. Like the picture, +-90° becomes

operation area by setting’s op-Angle. When earth current and voltage volume is over the

set value with a fault and earth current’s phase is in operation area based on earth

voltage, then it is picked up as fault. If this condition is kept during operation time, SEF

Fault is set.

To detect SEF Fault, setting items and ranges are like below.

<Table 5-3> Detecting Set Fault

Category Item Range Default Step Unit Explanation

Op Level

& Time

3I0 Pickup 0.1~20 5.0 0.1 A Set 3I0 current operation value

-3V0 Pickup 0~80 30 1 % Set 3V0 voltage operation value

SEF Reset Time 0.00~1.00 0.00 0.01 sec Set SEF reset time of definite time

Func In UseOFF/ALARM/

TRIPOFF Set SEF fault operation functions

Delay DT Level 25~10000 OFF 1 A Set operating value at delay DT level

Delay DT Time 0.01~2 2.00 0.01 sec Set operating time at delay DT time

HCT Level 25~10000 OFF 1 ASet operating value at high current trip level

HCT Time 0.01~1 0.04 0.01 secSet operating time at high current trip time

Func In Use NO/YES YES Set phase fault operation functions

Block flt

Pickup

Cold Load Multi 1~10 2 1

A multiplier to prevent the mis-recognizing as a fault by increasing a multiply of pick-up level under cold load condition.

Return Normal I 0~30 0.3 0.01 secSet the return current of restraining operation against cold load

Cold Load Time 0~180 3 1 min Set restraining time of cold load

Use Cold Load NO/YES NO Set cold load Use/Not use

Inrush Multiply 1~10 2 1

A multiplier to prevent the mis-recognizing as a fault by increasing a multiple of pick-up level under inrush condition

Inrush Time 0~30S 0.02 0.01 sec Set restraining time of Inrush

Use Inrush NO/YES NO Set inrush Use/Not use

2nd Harmonic 1-50 20 1 % A level of regarding 2nd harmonic as inrush

Use 2nd

Harmonic0.02~1 0.02 0.01 sec Set 2nd harmonics Use/Not use

Fault

Direction

Trip Direction OFF/FWD/REV OFF Selection of ground fault direction

3V0 Threshold 0~100 20 1 % Set zero sequence voltage operating value

3I0 Threshold 0~100 20 1 % Set zero sequence current operating value

3I0 Angle 0~359 300 1 ° Set zero sequence current operating angle

Dir Block OC NO/YES NO Set direction function block

Page 49: User Manual Document Version 1.5 Feb 28, 2019

- 43 -

<Figure 5-12> Operation Diagram of SEF

The way to set is identical with 5.2.3

5.2.6. Trip & Reclose1) Phase Rec Count

This is the menu for setting the counts of reclosing operation against phase fault.

2) GND Rec Count

This is the menu for setting the counts of reclosing operation against GND fault.

3) SEF Rec Count

This is the menu for setting the counts of reclosing operation against SEF fault.

4) Single Shot Operation

In single shot operation, Recloser goes directly to lockout after a trip, and will not reclose.

This operation occurs in two cases ; one is the case when Recloser disable in the front,

the controller goes to lockout without reclosing. and another case is that, after Recloser is

put, the fault occurs during the Single Shot setting time, then it goes to trip and

locked-out.

5) Sequence Coordination

When operating with 2 or more Recloser connected in series in distribution line, in order

to prevent the operation of all Reclosers’ being opened at the same time which are

installed both in power supply side and in load side, the Sequence Coordination function

is used to. This function is that, when multiple Reclosers in load side are connected to

Block Flt

Pickup

Inrush Multiply 1~10 2 1 Set inrush control multiplierInrush Time 0~30 0.02 0.01 sec Set inrush operating timeUse Inrush NO/YES NO Set phase fault inrush Use/Not use

2nd Harmonic 1~50% 20 1 % Set 2nd harmonic inrush control level

2nd_H Detect Time 0.02~1 0.02 0.01 sec Set 2nd harmonic time level

Use 2nd Harmonic NO/YES NO Set 2nd harmonic inrush Use/Not useFault

Direction

Op Angle 0~345 90 1 ° Set operating angle

Op Time 0.1~30 1.0 0.1 sec Set operating time

Page 50: User Manual Document Version 1.5 Feb 28, 2019

- 44 -

one Recloser on the power supply side, only the Recloser experienced a fault is set to

perform the opening operation.

As shown below, if the Recloser in power supply is Active state in Sequence Coordination

mode, in case of line fault, while Recloser in power supply detects the fault current and

operates the opening delayed action, it returns to normal situation by the operation of

Recloser in load side, and then Recloser in power supply will increase the operation

sequence only by one time. Therefore, only sequence of Recloser(power supply side) is in

progress without opening operation, so that even when load Recloser operates to delay

action, Recloser from supply side does not progress the other instantaneous actions in

sequence, but operates to delay action in the same way with load Recloser. If the

reclosing function is restrained, the Sequence Coordination function does not work.

The following rules apply to the Sequence coordination

1) All Reclosers both in supply side and the load must be set at same instantaneous time,

delay characteristics and the same minimum operating Pickup current value. (If the

minimum operating pickup current is wrongly set, the pickup value of power supply must

be larger than the load)

2) All Reclosers must have the same reclosing Time.

3) Recloser in supply should resume 100ms or more of delay time than load Recloser, or

the value of the minimum operating pickup current must be larger than that of load

Recloser.

4) The reset time of power supply Recloser must be set longer than the longest reclosing

time of the load Recloser. This is to prevent Recloser in supply side to be reset mode

during reclosing of load Recloser.

<Figure 5-13> Sequence Coordination

Page 51: User Manual Document Version 1.5 Feb 28, 2019

- 45 -

The setting items and ranges of Trip & Recloser are as follows.

<Table 5-4> Setting for Trip&RecloserCategory Item Range Default Step Unit Explanation

Phase

Rec

Count

Phase Oper Cnt 1~5 4 1Counts of reclosing operation against

phase fault

Phase Fast Cnt 0~5 2 1

Set fast operation section among

counts of reclosing operation against

phase fault

Phase HCT Cnt 0~5 0 1Counts of HCT operation against

phase fault

GND Rec

Count

GND Oper Cnt 1~5 4 1Counts of reclosing operation against

ground fault

GND Fast Cnt 0~5 2 1

Set fast operation section among

counts of reclosing operation against

ground fault

GND HCT Cnt 0~5 0 1Counts of HCT operation against

ground fault

SEF Rec

Count

SEF Oper Cnt 1~5 4 1Counts of reclosing operation against

SEF fault

SEF Fast Cnt 0~5 2 1

Set fast operation section among

counts of reclosing operation against

SEF fault

Reclose

Time

Rec Time 1st 0.3~180 2.0 0.1 sec Set 1st reclosing operation timeRec Time 2nd 1~180 10 1 sec Set 2nd reclosing operation timeRec Time 3rd 1~180 15 1 sec Set 3rd reclosing operation timeRec Time 4th 1~180 30 1 sec Set 4th reclosing operation timeReset Time 2~300 30 1 sec Set reclosing return time

SEF

Reclose

Time

SEF Rec Time 1st 0.3~180 2.0 0.1 sec Set 1st SEF reclosing operation timeSEF Rec Time 2nd 1~180 10 1 sec Set 2nd SEF reclosing operation timeSEF Rec Time 3rd 1~180 15 1 sec Set 3rd SEF reclosing operation timeSEF Rec Time 4th 1~180 30 1 sec Set 4th SEF reclosing operation timeSEF Reset Time 2~300 30 1 sec Set SEF reclosing return time

Reclosing

Option

Single Shot Time 0~180 10 1 sec Set single shot time

Seq Coordination NO/YES NOSet sequence coordination Use/Not

use

5.2.7 Auxiliary FuncThis function is for monitoring and additional functions of distribution line, key functions

are as follows.

1) Open Line Detect : To set the Phase Loss in distribution line

When phase voltage is maintained below a set value of voltage off for over delay time, it

is determined as Phase Loss. As the phase voltage grows more than setting value, the

Phase Loss is turned off. The percentage of voltage off in Open Line Detect shall be set

equal to or lower than the Live Line Detect voltage level. This is to avoid monitoring the

Open Line when 3 phase voltages are less than Live Line.

2) Sync Check : To check the voltage synchronization of the Source and Load side.

Once the voltages of the Source side and Load side are maintained for the set time,

within the setting range, the Sync Check is “OK”.

Page 52: User Manual Document Version 1.5 Feb 28, 2019

- 46 -

If the voltages of Source and Load sides are out of phase setting range, Sync Fail occurs

and then sync LED operates.

3) Live Line Detect : Setting for monitoring live line

Any of the phase from 3 phase voltage from source side is over Voltage On, Hot Line

Source LED light will be on and determines the Source side as Hot Line.

Load side also operates in the same principle.

4) Negative OC : Protection function for reverse phase current.

The setting items and ranges of Auxiliary Function are as follows.

5) Under Voltage : Settings associated with under voltage protection

If you select “3. Use Func” as TRIP, when low-voltage occurs, it trips circuit breaker, and

does not perform any reclosing operation. If you select it as Alarm, it does not trip the

circuit breaker, and record the alarm status in operating information, and it transmits to

the host system over the communication.

6) Over Voltage : Setting associated with over voltage protection

If you select “3. Use Func” as TRIP, when over-voltage occurs, it trips circuit breaker, and

does not perform any reclosing operation. If you select it as Alarm, it does not trip the

circuit breaker, and record the alarm status in operating information, and it transmits to

the host system over the communication.

7) Under Frequency : Settings associated with low-frequency protection

If you select “3. Use Func” as TRIP, when low-frequency occurs, it trips circuit breaker, and

does not perform any reclosing operation. If you select it as Alarm, it does not trip the

circuit breaker, and record the alarm status in operating information, and it transmits to

the host system over the communication.

8) Over Frequency : Settings associated with over-frequency protection

If you select “3. Use Func” as TRIP, when over-frequency occurs, it trips circuit breaker, and

does not perform any reclosing operation.

If you select it as Alarm, it does not trip the circuit breaker, and record the alarm status

in operating information, and it transmits to the host system over the communication.

9) Close Interlock : Settings associated with the function of inhibiting the input depending

on the situation of power system, when Recloser is applied.

For the case of Live Load function with “Enable”, it inhibits the input only when the

voltage is applied to both Source side and Load side. And, in case of Sync Fail function

with “Enable”, it inhibits the input when the synchronization of voltage on the Source side

and Load side is not suitable.

10) Loop Automation : When a fault occurs in a distribution line, protection device

Page 53: User Manual Document Version 1.5 Feb 28, 2019

- 47 -

perfoms protecton operation and the load in the lower side of protection devise will

experience a power outage. Thus, the blackout range of the distribution line are spread

to normal condition section as well as fault occurrence section.

For coping with those case, loop control function will operate in the way of separating the

fault section, and supplying power to normal section, then it helps to minimize the outage

time.

EPIC-R300 provides those loop control function which is operable in service only by using

the information about voltage, current, and operating state.

Depending on the configuration of recloser being installed, 3 modes of loop control can

be selected.

- Feeder recloser : the recloser is installed near the substation or inside.

- Midpoint recloser : installation point is between feeder recloser and tie recloser.

- Tie-point recloser : the recloser are usually installed at tie point where two distribution

lines are interconnected.

1) feeder recloser

Protection elements are generally operate when downstream fault occurs in the distribution

line. If it detects voltage loss at power supply, recloser will trip after set time.

In both cases that trip by protection elements and remote operation, loop control function

is automatically stopped.

2) Mid point recloser

Protection elements are generally operate when downstream fault occurs in the distribution

line. If, due to the action at power source side, it detects voltage loss at both sides, it

shall be automatically changed into another setting group after set time.

After downstream recloser or tie point recloser’s operation, the power supply starts to

provide from reverse side. For this moment, the reclosing action shall be hold for a certain

period of time.

3) Tie-point recloser

When voltage loss is detected in the set side, it close after the set time.

After closing, when the fault is detected, it stops and holds reclosing for a sertain period

of time.

The operation by protection elements is possible after normalization of reclosing element.

The activated operation group shall be changed according to feeding direction or setting

- “Dead bus open time”

The loop automation operates when the distribution line is in dead state.

It can be determined by using setting value based on voltage whether distribution line is

dead or not.

The state of loop automation shall be determined as “dead” only when the dead bus state

is maintained for a set time.

The voltage values of all sources and load side shall not exceed the set values.

Page 54: User Manual Document Version 1.5 Feb 28, 2019

- 48 -

- “Tie SW open time”

This is the time required to open a “Tie Sw open” in order to repair the distribution lines

to the normal state, if power is supplied from both Tie Sw after the fault is recovered.

- “Tie Sw Source”

It is used to determine the conditions of Tie Sw closing.

BOTH : If any loss for both side, it operates after Tie Sw closing time.

ABC : ABS side is power side, and when RST side is de-energized, then it closes after the

close time.

RST : RST side is power side, when RST side is de-energized, then it closes after the close

time.

Loop Operation procedure

Tie

REC

MID

REC

Feeder

RECCB CB

1) Feeder recloser trips when the voltage at power supply side is lost.

2) Mid recloser changes to Alt group setting when the voltage of power supply and load

side is dead due to the trip of protection device at power supply, and also changes to

the single shot mode which does not operate reclosing.

3) Tie recloser closes if one side voltage is lost.

4) Feeder recloser closed when the voltage at power supply become live after it is

repaired.

5) Mid recloser closes when the voltage is supplied to both side.

6) Tie recloser opens when the voltage is supplied to both ends.

<Table 5-5> Auxiliary FunctionCategory Item Range Default Step Unit Explanation

Open Line

Detect

Volt On 50~90 90 1 %Voltage setting to reset phase

loss(standard on rating voltage)

Volt Off 35~75 75 1 %Voltage setting to set phase

loss(standard on rating voltage)

Delay Off 0.1~30 30 0.1 secIf voltage is kept under volt off

during delay time

Use Func NO/YES YESShow whether open line detect

function is available

Sync Check

Phase Off 5~60 5 1 ° degree setting to check phase syncDelay Time 0.1~30 30 0.1 sec delay time setting to check phase sync

Use Func NO/YES YESShow whether sync check function is

availableLive Line

Detect

Volt Level 10~90 30 1 % Set voltage level monitoring operationDetect Time 0.05~1 0.10 0.01 sec Set voltage level operating time

Negative

OC

I2/I1 Pickup 30~100% 50 1 % Set negative current operating levelDelay Time 0.1~10 10.0 0.1 sec Set negative OC operation timeI1 Threshold 5~200 10 1 A Set Positive current threshold value

2nd Harmonic Blk OFF/ALM/TRIP OFF Select 2nd Harmonic block/ non-block

Func In Use OFF/ALM/TRIP OFFSet negative OC fault operation

functions, No Use/Alarm/Trip

Page 55: User Manual Document Version 1.5 Feb 28, 2019

- 49 -

5.2.8. Select GroupIt is a menu to set currently applied Primary Group among 4 setting groups.

Default value is set 1. If Sel Auto Group is selected as “YES”, it selects automatically the

primary group and reverse group, depending on the power flow. If the current flows from

load side to source side, side flows from Load side to power side, the reverse group is

applied.

[ S e t t i n g M E N U ]

1 . F u n c G r o u p 1

2 . F u n c G r o u p 2

3 . F u n c G r o u p 3

4 . F u n c G r o u p 4

> 5 . S e l e c t G r o u p

[ S e l G r o u p M e n u ]

> 1 . P r i m a r y G r o u p

2 . S e l A u t o G r o u p

3 . R e v e r s e G r o u p

[ P r i m a r y G r o u p ]

S E T : 1

( 1 - 4 : 1 )

<Figure 5-14> Setting Menu

Under

Voltage

U-V Pickup 30~98 75 1 % Set pickup level for under voltage U-V Op Time 0.1~100 3 0.1 sec Set operation time for under voltage

Use Func OFF/ALM/TRIP OFFSet whether under voltage function is

available

Over

Voltage

O-V Pickup 102~150 120 1 % Set pickup level for over voltage O-V Op Time 0.1~100 3 0.1 sec Set operation time for over voltage

Use Func OFF/ALM/TRIP OFFSet whether over voltage function is

available

Under

Frequency

U-F Pickup 47~59.98 49.8 0.01 Hz Set pickup level for under frequency

U-F Op Time 0.1~60 1 0.1 secSet operation time for under

frequency

Use Func OFF/ALM/TRIP OFFSet whether under frequency function

is available

Over

Frequency

O-F Pickup 50.02~63.00 60.02 0.01 Hz Set pickup level for over frequency O-F Op Time 0.1~60 1 0.1 sec Set operation time for over frequency

Use Func OFF/ALM/TRIP OFFSet whether over frequency function is

availableClose

Interlock

Live Load NO/YES NO Select whether live load is availableSync Fail NO/YES NO Select whether sync fail is available

Loop

Automation

Loop SelectionOFF/FEEDER/MI

D/TIEOFF Select operating mode for the recloser

Deadbus Open

Time0~600 0 1 sec

Set open time for determining

distribution line’s dead line stateTie Sw Open

Time0~600 0 1 sec Set open time for tie sw

Tie Sw Source BOTH/ABC/RST BOTH Select whether Tie sw source is ABC or RSTTie Sw Close

Time0~600 0 1 sec Set close time for tie sw

Rec Block Time 0~600 60 1 sec Set Reclosing Blocking Time

Enable Restore Disable/Enable DisableSet whether restoration after clearing

faultRec Close Time 0~600 30 1 sec Set recloser closing time after open

Tie On Delta I 5~95 5 1 %Set delta I level to restore for Tie

recloser after fault

Page 56: User Manual Document Version 1.5 Feb 28, 2019

- 50 -

5.3. Configuration MenuIt provides menus for analog current and voltage input related setting, Debounce Time

setting to prevent DI chattering, DO output pulse adjustment related setting, Event Log

information setting and clear related setting.

5.3.1. Analog Analog voltage / current input related setting items and ranges are like below.

<Table 5-6> Setting for Analog voltage / current

The order to set is like below.

1) Choose the menu with Up/Down Key. Press Enter Key to enter the menu.

[ C o n f i g M e n u ]

-> 1 . A n a l o g

2 . D I D e b o u n c e T i m e

3 . D O P u l s e T i m e

4 . B a c k u p S e t / C l e a r

5 . A n a l o g G a i n A d j

6 . W a v e f o r m

7 . C h e c k A u t o B a t t

8 . V / I U n b a l a n c e

9 . S a g / S w e l l

1 0 . T H D A l a r m

<Figure 5-15> Config Menu

2) On Analog menu, choose the item you want with Up/Down Key. Press Enter Key to

enter the item.

Item Range Default Step Unit Explanation

Line Config 3P4W/3P3W 3P4W Distribution line’s connection

Frequency 50/60 60Hz Distribution line’s frequency

Rated Voltage 3.8~21 13.2 0.01 kV Distribution line’s rated voltageCT ratio 100~2000 1000 1 CT ratio

NCT ratio 100~2000 1000 1 NCT ratio

Avg Interval 5-15 15 5 min Average process time about demand value

Select FI Reset Auto/Man ManWay to FI reset

Refer 5.2.2

Display voltage L-N/L-L L-N Selection of line to phase voltage and line to line voltage

Phase PositionABC/ACB/BCA/

BAC/CAB/CBAABC Select phase position

Phase Rotation ABC/ACB ABC Select whether phase rotation is ABC or ACB

Source Side ABC/RST ABCSelect which side will be power source between

ABC side and RST sideEnergy Log Duty Week/Month Week Set duty time for energy logging

Closing Delay 0~300 0 1 sec Set delay time to close CBCheck V for FI NO/YES YES Select whether to consider voltage when FI setReclaim T for FI 0~120 2 1 sec Set reclaim time for FIImport Key Delay 1~5 1 1 sec Set import key delay

Fail V Sensor 0~120 10 1 sec Set delay time for voltage sensor failI Cut Level 0~10 0.1 0.1 % Set level for current cuttingV Cut Level 0~50 10 1 % Set level for current cutting

Page 57: User Manual Document Version 1.5 Feb 28, 2019

- 51 -

[ A n a l o g M e n u ]

->1 . L i n e C o n f i g

2 . F r e q u e n c y

3 . R a t e d V o l t

4 . C T r a t i o

5 . N CTT r a t i o

6 . A v g I n t e r v a l

7 . S e l e c t F I R e s e t

8 . D i s p l a y V o l t a g e

9 . P h a s e P o s i t i o n

1 0 . P h a s e R o t a t i o n

1 1 . S o u r c e S i d e

1 2 . E n e r g y L o g D u t y

1 3 . C l o s i n g D e l a y

1 4 . C h e c k V f o r F I

1 5 . R e c l a i m T f o r F I

1 6 . I m p o r t K e y D e l a y

1 7 . F a i l V S e n s o r

1 8 . S a v e C o n f i g

[ L I N E C O N F I G ]

S E T : 3 P 4 W

( 3 P 4 W / 3 P 3 W )

<Figure 5-16> Analog Menu-Line Config

3) Change set value with Up/Down Key. Press Enter Key to check. If you want to cancel

the changed set value, press M Key.

4) After change, choose 18. Save Config to save the set value in backup memory and

come out from the item. Then the set value is applied to the device.

[ A n a l o g M e n u ]

->1 . L i n e C o n f i g

2 . F r e q u e n c y

3 . R a t e d V o l t

4 . C T r a t i o

5 . N CTT r a t i o

6 . A v g I n t e r v a l

7 . S e l e c t F I R e s e t

8 . D i s p l a y V o l t a g e

9 . P h a s e P o s i t i o n

1 0 . P h a s e R o t a t i o n

1 1 . S o u r c e S i d e

1 2 . E n e r g y L o g D u t y

1 3 . C l o s i n g D e l a y

1 4 . C h e c k V f o r F I

1 5 . R e c l a i m T f o r F I

1 6 . I m p o r t K e y D e l a y

1 7 . F a i l V S e n s o r

1 8 . S a v e C o n f i g

[ U p d a t e S e t t i n g ]

- > P r e s s E n t e r

<Figure 5-17> Analog Menu-Save Config

Page 58: User Manual Document Version 1.5 Feb 28, 2019

- 52 -

5.3.2. DI Debounce Time It is a menu to set debounce time to prevent DI Chattering. It is available to set on each channel.

During set time, DI status value should be kept to be considered with the changed value.

<Table 5-7> DI Debounce Setting Item Range Default Step Unit ExplanationDI_1 1~500 10 1 ms DI 1’s debounce time settingDI_2 1~500 10 1 ms DI 2’s debounce time settingDI_3 1~500 10 1 ms DI 3’s debounce time setting... ... ... ... ... ...

DI_10 1~500 10 1 ms DI 10’s debounce time setting

The way to set is identical with 5.3.1

5.3.3. DO Pulse Width It sets DO1~6’s on pulse output time.

<Tabel 5-8> DI Pulse Setting

The way to set is identical with 5.3.1

5.3.4. Backup Set / ClearIt is a menu operating switch operation count, Event data clear, Fault data and clear.

<Table 5-9> Backup Set / Clear

The way to set is identical with 5.3.1

5.3.5. Analog Gain AdjustIt is a menu to adjust analog voltage / current volume gain. EPIC-R300 is set in calibration

about voltage / current signal input from factory. However if measuring value is different

because of external sensor’s error, use the menu to adjust.

<Table 5-10> Analog Gain Adjust

Item Range Default Step Unit Explanation

DO_1 10~2000 500 10 ms DO 1’s pulse width time settingDO_2 10~2000 500 10 ms DO 2’s pulse width time settingDO_3 10~2000 500 10 ms DO 3’s pulse width time settingDO_4 10~2000 500 10 ms DO 4’s pulse width time settingDO_5 10~2000 500 10 ms DO 5’s pulse width time settingDO_6 10~2000 500 10 ms DO 6’s pulse width time setting

Item Range Default Step Unit Explanation

Set Switch Cnt 0~65535 0 1 Set the number of switch operation

Clear Event NO/YES NODelete saved event information in backup

memoryClear Fault NO/YES NO Delete save fault information in backup memory

Clear Oper Count NO/YES NoDelete save operation information in backup

memory

Item Range Default Step Unit Explanation

Ia Gain Adjust 10~2000 0 1 A Adjust current Ia’s gain

Page 59: User Manual Document Version 1.5 Feb 28, 2019

- 53 -

The way to set is identical with 5.3.1

5.3.6. WaveformSettings associated with the condition of capturing the waveform and storing it.

“1. sample rate” : to select the sample rate which saves a waveform per one cycle.

“2. Record size” : to select the length of the waveform.

“3. Pre-cycle” : to set the stotage size before a failure occurance as a ratio of the total

size.

“4. Post-cycle” : to set the stotage size after a failure occurance as a ratio of the total

size.

<Table 5-11> WaveformItem Range Default Step Unit Explanation

Sample rate 16/32/64/128 32 sampleSet sample rate when capturing

waveform

Record size 20~600 20 1 cycle Set record size of waveform

Pre-cycle 10~50 10 1 % Set pre-cycle number of waveform

Post-cycle 10~50 10 1 % Set post cycle number of waveform

5.3.7. Check Auto BatteryTo automatically set the cycle of testing battery.

<Table 5-12> Check Auto Item Range Default Step Unit Explanation

Check Day 1~31 1 1 day Set auto checking day for battery

Check Hour 0~23 0 1 hour Set auto checking hour for battery

Check Minute 0~59 0 1 minute Set auto checking minute for battery

*optionItem Range Default Step Unit Explanation

Auto-Check Day 1~31 1 1 day Set auto checking day for battery

Detect Batt-Low 18.7~24.0 21.6 0.1 V Set voltage level for battery low

Cut-Off Voltage 18.7~23.0 20.8 0.1 V Set voltage level for battery cutoff

Cut-Off Delay 1~600 60 1 s Set delay time for battery cutoff

Ib Gain Adjust 10~2000 0 1 A Adjust current Ib’s gain

Ic Gain Adjust 10~2000 0 1 A Adjust current Ic’s gain

In Gain Adjust 10~2000 0 1 A Adjust current In’s gain

Va Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Va’s gain

Vb Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vb’s gain

Vc Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vc’s gain

Vr Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vr’s gain

Vs Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vs’s gain

Vt Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vt’s gain

Clear Gain DataDelete save gain data in backup

memory

Page 60: User Manual Document Version 1.5 Feb 28, 2019

- 54 -

5.3.8. V/I UnbalanceSettings relating to the level and operating time for detecting the unbalance of Voltage

and Current.

<Table 5-13> V/I UnbalanceItem Range Default Step Unit Explanation

V unbalance 0~100 0 1 % Set unbalance level for voltage

V unbalance time 0.1~60 0.1 0.1 sec Set unbalance time for voltage

I unbalance 0~100 0 1 % Set unbalance level for current

I unbalance time 0.1~60 0.1 0.1 sec Set unbalance time for current

5.3.9. Sag/SwellSettings related to the level and operating time to detect Sag, Swell, and Interruption.

<Table 5-14> Sag/SwellItem Range Default Step Unit Explanation

Sag Level 50~99 90 1 % Set pickup level for sag

Sag Time 0.02~10 1.0 0.01 sec Set operation time for sag

Swell Level 101~150 120 1 % Set pickup level for swell

Swell Time 0.02~10 1.0 0.01 sec Set operation time for swell

Interrupt Level 10~50 10 1 % Set pickup level for interruption

Interrupt Time 0.02~10 1.0 0.01 sec Set operation time for interruption

5.3.10. THD AlarmSettings relating to the alarm level and operating time of the Voltage/Current’s THD(Total

Harmonic Distortion).

<Table 5-15> THD AlarmItem Range Default Step Unit Explanation

V THD Alarm Level 1~100 3 1 % Set alarm level for voltage THD

V THD Alarm Time 0.02~60.00 0.02 0.01 sec Set alarm time for voltage THD

I THD Alarm Level 1~100 3 1 % Set alarm level for current THD

I THD Alarm Time 0.02~60.00 0.02 0.01 sec Set alarm time for current THD

5.3.11. VI WearSelect VI type which is used in the recloser, and it displays residual contact wear for each

phase’ VI and total operation times.

<Table 5-16> VI Wear

Page 61: User Manual Document Version 1.5 Feb 28, 2019

- 55 -

Item Range Default Step Unit Explanation

Max Op Count 1000~10000 2000 1Set the type of the VI used in the

recloser

Alarm Level 0~100 45 1 %Set alarm level for residual contact

wear

Duty Factor A 0~100 100 1 % Set duty factor for A phase’s VI

Duty Factor B 0~100 100 1 % Set duty factor for B phase’s VI

Duty Factor C 0~100 100 1 % Set duty factor for C phase’s VI

Clear Wear InfoDelete save wear information in

backup memory

5.3.12. Analog High AlmSettings relating to the alarm level and operating time of the Voltage/Current’s THD(Total

Harmonic Distortion).

<Table 5-17> Analog High AlmItem Range Default Step Unit Explanation

Phase Current 1~16000 400 1 ASet phase current level for Analog

High Alarm function

Ground Current 1~16000 400 1 ASet ground current level for Analog

High Alarm function

Phase Voltage 1~38000 13200 1 VSet phase voltage level for Analog

High Alarm function

System Power 1~54000 5280 1 kVSet system power level for Analog

High Alarm function

Enable High Alarm Disable/Enable DisableSelect whether Analog High Alm

function is available

5.3.13. Analog Low AlmSettings relating to the alarm level and operating time of the Voltage/Current’s THD(Total

Harmonic Distortion).

<Table 5-18> Analog Low AlmItem Range Default Step Unit Explanation

Phase Current 1~15999 110 1 ASet phase current level for Analog

Low Alarm function

Ground Current 1~15999 110 1 ASet ground current level for Analog

Low Alarm function

Phase Voltage 1~37999 510 1 VSet phase voltage level for Analog

Low Alarm function

System Power 1~53999 0 1 kVSet system power level for Analog

Low Alarm function

Enable Low Alarm Disable/Enable DisableSelect whether analog low alm

function is available

5.3.14. Misc. ConfigSettings relating to the miscellaneous config(Door contact, AC POWER LED, Insulator

Type...).

Page 62: User Manual Document Version 1.5 Feb 28, 2019

- 56 -

<Table 5-19> Misc. ConfigItem Range Default Step Unit Explanation

Door Open Contact N.O(A)/N.C(B) N.O(A) Set contact type for door open(DI6)

AC POWER LEDAC Fail/AC

NormalAC Fail Set contact type for AC POWER(DI3)

Insulator Type Mold/SF6-GAS Mold Set contact type for Gaslow(DI7)

5.4. Communication MenuIt is a menu to set communication port to connect with upper system.

On this menu there are communication port setting in connection with SCADA system,

modem control signal setting in connection with modem, DNP3.0, IEC60870-5-101,

IEC60870-5-104, TCP/IP protocol related setting.

5.4.1. SCADA PortIt is a menu to set communication port in connection with SCADA system.

<Table 5-19> SCADA Port

The way to set is identical with 5.3.1

5.4.2. Modem ControlIt is a menu to set modem control signal to connect SCADA system and modem.

<Table 5-20> Modem Control

The way to set is identical with 5.3.1

5.4.3. DNP ConfigIt is a menu to set DNP3.0 communication related items.

Item Range Default Step Unit Explanation

Baud Rate 1200~38400 9600 bpsPort connected with SCADA’s

communication speed setting

Parity NO/EVEN/ODD NO Serial communication parity setting

Slave/DL Address 0~65534 2 1 DNP slave or IEC-101 D/L address setting

ASDU Comm

Addr0~65534 2 1 ASDU common address setting

Select ProtocolDNP/DNP-TCP/IEC-

101/IEC-104/DNP

DNP3.0 and DNP-TCP and IEC870-5-101

protocol and IEC870-5-104 protocol setting

Select Map Full Map/User Map Full Map Protocol map type setting

Clear User Map Delete saved user map in backup memory

Item Range Default Step Unit Explanation

Comm Line 2 / 4 4 Modem communication line setting

RTS Off Delay 10~500 100 10 ms After TX completion, delay setting for RTS Off

CTS Time out 0~255 3 1 s After RTS enable, CTS waiting time setting

DCD Time out 0.1~30 10 0.1 s TX waiting time when DCD is enable on 2 Line

Page 63: User Manual Document Version 1.5 Feb 28, 2019

- 57 -

<Table 5-21> DNP Config

The way to set is identical with 5.3.1

5.4.4. IEC101 ConfigIt is a menu to set IEC870-5-101 communication related item.

<Table 5-22> IEC101 Config

The way to set is identical with 5.3.1

Item Range Default Step Unit Explanation

D/L Retry 0~2 0 1 Set the number of data link layer retry

D/L Timeout 1~255 3 1 s Set data link layer timeout

D/L ConfirmNO/YES/

SOMETIME

SOMETI

MEChoose if data link layer ask confirm is used

A/L Retry 0~2 0 1 Set the number of application link layer retry

A/L Timeout 1~255 10 1 s Set application layer timeout

Unsol Resp Class NO/YES NOAfter power on, choose if unsolicited response

is set

Unsol Resp Delay 0~60 1 1 s Unsolicited response delay time setting

Unsol Resend Dly 0~60 1 1 s Unsolicited response delay time setting

SBO Timeout 1~255 5 1 sAfter selection, if set timeout is over for

operation order, select is lifted

Master Addr 0~65534 65534 1 Upper master’s address setting

Frame Interval 10~500 20 10 msIf D/L timeout confirm is NO, choose link

frame’s interval

DNP Port Num 0~65534 20000 1 Set DNP-TCP Port Num

Cls Evt when RSTDisable/Enabl

eDisable

Select whether Clear Event when Reset

function is available

Event Time SyncDisable/Enabl

eDisable

Select whether Event Time Sync function is

available

BI Chg Dflt Var

With

time/Without

time

Without

timeSelect whether with time or without time

AI Chg Dflt Var

With

time/Without

time

Without

timeSelect whether with time or without time

Item Range Default Step Unit Explanation

Link Addr Size 0~2 2 1 Data link address sizeCommon Addr Size 1~2 2 1 Common address size

IOA Size 1~3 2 1 Information object address sizeCOT Size 1~2 1 1 COT address size

Time Format CP24/CP56/NO CP56 Select Time Fomat, CP24, CP56 or NO

Single Char N/ACK Disable/Enable Disable Set character ACK, NACK information

Arm Timeout 1~255 5 1 s Set arm timeout

Analog Data TypeNORMAL/SCALE

/FLOATNORMAL Set analog data type

Scan Analog Chg Disable/Enable Disable Set scan analog change information

Scan Binary Chg Disable/Enable Disable Set scan binary change information

Page 64: User Manual Document Version 1.5 Feb 28, 2019

- 58 -

5.4.5. IEC104 ConfigIt is a menu to set IEC870-5-104 communication related item.

<Table 5-23> IEC104 Config

The way to set is identical with 5.3.1

5.4.6. TCP/IP ConfigIt is a menu to set TCP/IP address to connect SCADA system by Ethernet.

<Table 5-24> TCP/IP Config

The way to set is identical with 5.3.1

5.4.7. PSTN ModemSettings required to connect to the PSTN network.

<Table 5-25> PSTN Modem

The way to set is identical with 5.3.1

5.4.8. PPP ConfigSettings for using the PPP(Point to Point Protocol).

<Table 5-26> PPP Config

The way to set is identical with 5.3.1

Item Range Default Step Explanation

IP Address 0~255 0.0.0.0 1 Set IP address of FTU

Subnet Mask 0~255 255.255.255.0 1 Set subnet mask bits

Gateway 0~255 192.168.0.0 1 Set gateway addressNTP Server 0~255 192.168.0.0 1 Set NTP Server address

Item Range Default Step Unit Explanation

Conn Timeout(t0) 1~255 30 1 sec Set connection timeout

APDU Timeout(t1) 1~255 15 1 sec Set APDU timeout

Ack Timeout(t2) 1~255 10 1 sec Set ack timeout

Test Period(t3) 1~255 20 1 sec Set time period

Xmt Spontaneous Disable/Enable DisableSelect whether spontaneous

response function is available

Max Xmt I-APDU(k) 1~32767 15 1 Set max transmitting I-APDU

Max Rcv I-APDU(w) 1~32767 10 1 Set max receiving I-APDU

Item Range Default Step Unit Explanation

PSTN Modem NO/PPP/Dialup/SMS NO Select PSTN mode type,PPP, dialup or SMS

Auto Hangup Time 0~255 30 1 sec Set Auto hangup time

Dial Timeout 10~255 90 1 sec Set dial timeout

Attempt Delay 10~3600 60 1 sec Set dial attempt delay time

Max Attempts 1~5 3 1 sec Set dial max attempt

Item Range Default Step Explanation

Our IP address 0~255 192.168.0.0 1 Set our IP address

Their IP address 0~255 192.168.0.0 1 Set their IP address

DNS1 IP address 0~255 192.168.0.0 1 Set DNS1 IP address

DNS2 IP address 0~255 192.168.0.0 1 Set DNS2 IP address

Page 65: User Manual Document Version 1.5 Feb 28, 2019

- 59 -

5.4.9. SMS ConfigSettings for using the SMS(short message service).

<Table 5-27> SMS Config

The way to set is identical with 5.3.1

5.4.10. Time Sync OptionSettings for using the Time Sync Option.

<Table 5-28> Time Sync Option

The way to set is identical with 5.3.1

5.5. Time Set MenuIt is a menu to set time on the device. Like a picture below, RTC present time is on 2

upper lines and time for editing is on 2 down lines. The order to change the time you

want is like below.

1) Press Enter Key to change the time. Then the cursor blinks on the year you want to change.

Press Up/Down Key to change.

N o w : 2 0 1 2 / 0 9 / 2 7

T i m e : 1 4 : 3 0 : 2 6

E d i t : 2 0 1 3 / 0 9 / 2 7

T i m e : 1 4 : 3 0 : 2 6

<Figure 5-18> Time Set-year

2) To change the month, press Enter Key. Then the cursor blinks.

Press Up/Down Key to change.

N o w : 2 0 1 2 / 0 9 / 2 7

T i m e : 1 4 : 3 0 : 2 6

E d i t : 2 0 1 3 / 1 0 / 2 7

T i m e : 1 4 : 3 0 : 2 6

<Figure 5-19> Time Set-month

Item Range Default Step Explanation

Trip Enable NO/YES NO Set sending trip information

FI Enable NO/YES NO Set sending FI information

Open Enable NO/YES NO Set sending open information

Door Open Enable NO/YES NO Set sending door information

AC fail Enable NO/YES NO Set sending AC fail information

Item Range Default Step Unit Explanation

SNTP Enable NO/YES NO Select whether to enable SNTP

SNTP Period 1~24 1 1 hour Set SNTP cycle duty

Select Time ZoneUTC-12:00 ~

UTC+14:00

UTC+09:0

0 SEOULSelect time zone

Page 66: User Manual Document Version 1.5 Feb 28, 2019

- 60 -

3) To change the date, press Enter Key then the cursor blinks.

Press Up/Down Key to change.

N o w : 2 0 1 2 / 0 9 / 2 7

T i m e : 1 4 : 3 0 : 2 6

E d i t : 2 0 1 3 / 1 0 / 2 9

T i m e : 1 5 : 2 2 : 1 1

<Figure 5-20> Time Set-day

4) To change the time, press Enter Key. Then the cursor blinks.

Press Up/Down Key to change.

N o w : 2 0 1 2 / 0 9 / 2 7

T i m e : 1 4 : 3 0 : 2 6

E d i t : 2 0 1 3 / 1 0 / 2 9

T i m e : 1 5 : 3 0 : 2 6

<Figure 5-21> Time Set-hour

5) To change the minute, press Enter Key. Then the cursor blinks.

Press Up/Down Key to change.

N o w : 2 0 1 2 / 0 9 / 2 7

T i m e : 1 4 : 3 0 : 2 6

E d i t : 2 0 1 3 / 1 0 / 2 9

T i m e : 1 5 : 2 2 : 2 6

<Figure 5-22> Time Set-minute

6) To change the second, press Enter Key. Then the cursor blinks.

Press Up/Down Key to change.

N o w : 2 0 1 2 / 0 9 / 2 7

T i m e : 1 4 : 3 0 : 2 6

E d i t : 2 0 1 3 / 1 0 / 2 9

T i m e : 1 5 : 2 2 : 1 1

<Figure 5-23> Time Set-second

7) After changing, press Enter Key then the menu below shows. Press Enter Key again

then the edited time is saved.

[ U p d a t e S e t t i n g ]

- > P r e s s E n t e r

<Figure 5-24> Update Setting

Page 67: User Manual Document Version 1.5 Feb 28, 2019

- 61 -

5.6. Event View MenuIt is a menu to check various recorded information in EPIC-R300. Event List shows in a

chronological order from the latest one. You can check information with Up/Down Key.

There is information of Event List and maximum number of storage below.

<Table 5-30> Event View Menu

Event Items Description Max Event Num

Fault Event Save Fault Event history 512

Op Event

Save Operation Event history

(save operation history about Power On, DO/DI

operation, setting, Fault/Pickup operation)

20,480

Demand I Average current during Demand time 255

Demand P Average electricity during Demand time 255

Max Demand I Record maximum Demand I value for a day 63

Max Demand P Record maximum Demand P value for a day 63

Page 68: User Manual Document Version 1.5 Feb 28, 2019

- 62 -

APPENDIX A. - COMTRADE File’s FormatsThe COMTRADE record generated by your device consist of two files: the configuration

file (*.cfg) and the data file (*.dat). These files are structured as described in IEEE Power

Engineering Society C37.111 COMTRADE data format. Please refer to the IEC website for

the most up-to-date COMTRADE data format information.

Configuration File FormatThe configuration file is an ASCII text file that contains the information necessary to

interpret the data (*.dat) file. The configuration file will have the same filename as the

data file but with the .cfg file extension, and will be included in every COMTRADE record.

For more details refer to the IEEE COMTRADE data format documentation.

Configuration file layoutThe configuration (*.cfg) file is laid out as follows:

Configuration file fieldsThe configuration (*.cfg) file fields are described in following table:

Page 69: User Manual Document Version 1.5 Feb 28, 2019

- 63 -

Page 70: User Manual Document Version 1.5 Feb 28, 2019

- 64 -

Configuration field detailsThe following table describes the channel identifier(ch_id) and channel phase identification

(ph) values:

Data file formatThe data (*.dat) file contains the sample number, time stamp and data values of each

channel, for each sample in the file. The data file has the same name as the configuration

file but with a .dat file extension, and contains binary formatted data.

Data file layoutThe data (*.dat) file layout is as follows:

Data file fieldsThe data (*.dat) fields are described in the following table:

Page 71: User Manual Document Version 1.5 Feb 28, 2019

- 65 -

Example - configuration file

Page 72: User Manual Document Version 1.5 Feb 28, 2019

- 66 -

APPENDIX B. TC Curve

1. TC CurveThe EPIC-R300 supports analog recloser curves, IEC curves, ANSI/IEEE curves, and KEPCO

curves, The list is as follows.

◆ TC curve equationThe equation of TC curve supported by EPIC-R300 is as follows.

×

- I = Fault current

- I> = Pick up current setting value

- k = Multiplier setting value

No. 1 2 3 4 5 6 7 8 9 10

TC Curve A B C D E K L M N P

No. 11 12 13 14 15 16 17 18 19 20

TC Curve R T V W Y Z 1 2 3 4

No. 21 22 23 24 25 26 27 28 29 30

TC Curve 5 6 7 8 8* 9 11 13 14 15

No. 31 32 33 34 35 36 37 38 39 40

TC Curve 16 18 IEC NI IEC VI IEC EI IEC LI IEC SI IEEE MI IEEE VI IEEE EI

No. 41 42 43 44 45 46 47 48 49 50

TC Curve IEEE NI ANSI U2 ANSI U8 ES NI ES VI KEPCO N1 KEPCO N2 KEPCO N3 KEPCO N4

Standard Curve A B C

IEC

Normal Inverse(NI) 0.14 0.02Very Inverse(VI) 13.5 1Extremely Inverse(EI) 80 2Long-time Inverse(LI) 120 1Short-time Inverse(SI) 0.05 0.04

IEEE/ANSI

Moderately Inverse(MI) 0.0515 0.114 0.02Very Inverse(VI) 19.61 0.491 2Extremely Inverse(EI) 28.2 0.1217 2Normal Inverse(NI) 0.0086 0.0185 0.02

ANSILong-time Inverse(U8) 5.95 0.18 2Short-time Inverse(U2) 0.2394 0.0169 0.02

ESNormal Inverse(NI) 0.011 0.042 0.02Very Inverse(VI) 3.985 0.1084 1.95

Page 73: User Manual Document Version 1.5 Feb 28, 2019

- 67 -

2. TC Curve 1~4

100 101

10-1

100

101

102

Tim

e[se

c]

Current In Multiplies of Setting

1 2 3 4

Page 74: User Manual Document Version 1.5 Feb 28, 2019

- 68 -

3. TC Curve 5~8

100 101

10-1

100

101

102

Tim

e[se

c]

Current In Multiplies of Setting

5 6 7 8

Page 75: User Manual Document Version 1.5 Feb 28, 2019

- 69 -

4. TC Curve 8*~13

100 101

10-1

100

101

102

Tim

e[se

c]

Current In Multiplies of Setting

8* 9 11 13

Page 76: User Manual Document Version 1.5 Feb 28, 2019

- 70 -

5. TC Curve 14~18

100 101

10-1

100

101

102

Tim

e[se

c]

Current In Multiplies of Setting

14 15 16 18

Page 77: User Manual Document Version 1.5 Feb 28, 2019

- 71 -

6. TC Curve A~D

100 101

10-1

100

101

102

Tim

e[se

c]

Current In Multiplies of Setting

A B C D

Page 78: User Manual Document Version 1.5 Feb 28, 2019

- 72 -

7. TC Curve E~M

100 101

10-1

100

101

102

Tim

e[se

c]

Current In Multiplies of Setting

E K L M

Page 79: User Manual Document Version 1.5 Feb 28, 2019

- 73 -

8. TC Curve N~T

100 101

10-1

100

101

102

Tim

e[se

c]

Current In Multiplies of Setting

N P R T

Page 80: User Manual Document Version 1.5 Feb 28, 2019

- 74 -

9. TC Curve V~Z

100 101

10-1

100

101

102

Tim

e[se

c]

Current In Multiplies of Setting

V W Y Z

Page 81: User Manual Document Version 1.5 Feb 28, 2019

- 75 -

10. TC Curve IEC NI~SI

100 101

10-1

100

101

102

103

104

IEC NI IEC VI IEC EI IEC LI IEC SI

Current In Multiplies of Setting

Tim

e[se

c]

Page 82: User Manual Document Version 1.5 Feb 28, 2019

- 76 -

11. TC Curve IEEE MI~NI

100 101

10-1

100

101

102

103

IEEE MI IEEE VI IEEE EI IEEE NI

Current In Multiplies of Setting

Tim

e[se

c]

Page 83: User Manual Document Version 1.5 Feb 28, 2019

- 77 -

12. TC Curve ANSI U8, U2

100 101

10-1

100

101

102

103

ANSI U8 ANSI U2

Current In Multiplies of Setting

Tim

e[se

c]

Page 84: User Manual Document Version 1.5 Feb 28, 2019

- 78 -

13. TC Curve ES NI, VI

100 101

10-1

100

101

102

ES NI ES VI

Current In Multiplies of Setting

Tim

e[se

c]

Page 85: User Manual Document Version 1.5 Feb 28, 2019

- 79 -

14. TC Curve KEPCO N1~N4

100 101

10-1

100

101

102

Tim

e[se

c]

Current In Multiplies of Setting

N1 N2 N3 N4

Page 86: User Manual Document Version 1.5 Feb 28, 2019

- 80 -

15. TC Curve DEF 1S, 10S

100 10110-1

100

101

DEF 1S DEF 10S

Current In Multiplies of Setting

Tim

e[se

c]

Page 87: User Manual Document Version 1.5 Feb 28, 2019

- 81 -

APPENDIX C. Remote Control(option)The EPIC-R300 can be closed/opened to the recloser with the supplied remote control. IR

receiver is located on the bottom of the recloser control box. You can point the supplied

remote control to the IR receiver and then enter the button. The remote control uses only

two buttons 'OFF' and 'ON'.

1) OFF

Recloser is opened.

2) ON

Recloser is closed.

1

2