Installation Instructions
USB-to-Data Highway Plus CableCatalog Number 1784-U2DHP
About the CableThe 1784-U2DHP USB-to-Data Highway Plus Cable lets you connect a computer to a Data Highway Plus (DH+) network via an unused USB port on the computer. You can also use the cable to connect the computer to PLC-5 processors (except for Classic PLC-5 processors, such as PLC-5/10, PLC-5/12, PLC-5/15, and PLC-5/25) or SLC 5/04 processors. Communication on the DH+ link requires the RSLinx Classic software DF1 serial 1770-KF2/1785-KE drive.
Topic Page
Important User Information 2
Environment and Enclosure 3
Install the Cable 5
Configure the DH+ Node Address 11
Consider the Traffic Analyzer Software 11
About Using Multiple Cables 12
Status Indicators 13
Specifications 15
Additional Resources 18
2 USB-to-Data Highway Plus Cable
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
http://literature.rockwellautomation.com/idc/groups/literature/documents/in/sgi-in001_-en-p.pdfhttp://www.rockwellautomation.com/literature/
USB-to-Data Highway Plus Cable 3
Environment and Enclosure
Preventing Electrostatic Discharge
ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as enclosed equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional installation requirements. NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static. Do not touch connectors or pins on component boards. Store the equipment in appropriate static-safe packaging when not
in use.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf
4 USB-to-Data Highway Plus Cable
At the end of its life, this equipment should be collected separately from any unsorted municipal waste.
The 1784-U2DHP cable replaces both the 1784-PCMK communication card and 1784-PCM6 cable (for computers without PCMCIA slots).
IMPORTANT The cable will not connect to Classic PLC-5 processors, such as PLC-5/10, PLC-5/12, PLC-5/15, and PLC-5/25, without an adapter. An adapter can be purchased separately from third-party companies.
To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a source compliant with safety extra low voltage (SELV) or protected extra low voltage (PELV).
USB Cable0.61 m (2 ft)
8-pin DIN Cable2.44 m (8 ft)
Communication Rate Switch
Status Indicators
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
USB-to-Data Highway Plus Cable 5
The cable operates at DH+ communication rates of 57.6 Kbps, 115.2 Kbps, and 230.4 Kbps.
The 1784-U2DHP cable supports these DH+ network cable lengths.
Install the CableFollow the procedures on the following pages to install the cable.
Obtain the Device Driver for the CableFollow these steps to download the device driver for the cable.
1. Visit http://www.rockwellautomation.com/support/pccards.
2. Click the 1784_u2dhp.inf file.
3. Save the file to a directory on the computer on which you want to install the cable.
IMPORTANT The DH+ communication rate is read only when power is applied. To change the communication rate, you must disconnect the cable from the USB port, use the Communication Rate switch to change the communication rate setting, then reconnect the cable to the USB port.
DH+ Communication Rate Max. DH+ Network Cable Length
57.6 Kbps 3048 m (10,000 ft)
115.2 Kbps 1524 m (5000 ft)
230.4 Kbps 762 m (2500 ft)
IMPORTANT If RSLinx Classic software, version 2.53 or later, is installed on the computer, the device driver is already installed on the computer. Skip this section.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
http://www.rockwellautomation.com/support/pccards
6 USB-to-Data Highway Plus Cable
Connect and Configure the Cable
1. Insert the end of the cable having the USB connector into an unused USB port on a computer.
The Found New Hardware wizard appears.
If you do not see the Found New Hardware wizard, proceed tostep 9. Otherwise, continue with the next step.
2. Select No, not this time and click Next.
3. Select Install from a list or specific location and click Next.
4. Select Search for the best driver.
5. Check only the Include this location checkbox.
6. Browse to the location where you saved the 1784_u2dhp.inf file and click OK.
7. Click Next.
8. Click Finish.
TIP If you do not see the Found New Hardware wizard, the drivers have already been installed. If RSLinx Classic software, version 2.53 or later, is installed on the computer, the device driver was installed at C:\Program Files\Rockwell Software\RSLINX\PnP_Drivers\1784-U2DHP.
TIP If you see a Microsoft Windows error message that displayscode 10, disconnect the cable from the USB port, then reconnect the cable to the USB port, so that the Windows operating system recognizes the device.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
USB-to-Data Highway Plus Cable 7
9. Insert the other end of the cable having the 8-pin mini DIN connector to a device on your Data Highway Plus network.
10. Verify which computer COM port the cable is using.
a. Right-click My Computer and choose Manage.b. Select Device Manager.c. Click the + to the left of Ports.d. Make note of the port (for example, COM3) for the 1784-U2DHP
cable.
Configure the RSLinx Classic Software Driver for the CableConfigure the cable driver for use with your DH+ networked device.
ATTENTION: The USB cable is not to exceed 3.0 m (9.84 ft).
TIP The operating system of the computer you are using assigns a COM port to the cable.
USB Connector
8-pin DIN Connector
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
8 USB-to-Data Highway Plus Cable
RSLinx Classic Software, Version 2.52 and Earlier
Do these steps to configure the cable device driver by using RSLinx Classic software, version 2.52 and earlier.
1. Open RSLinx Classic software and then, from the Communication menu, choose Configure Drivers.
2. From the Available Driver Types pull-down menu, choose RS-232 DF1 Devices.
3. Click Add New.
4. Enter a name for the driver you just added and click OK.
The Configure RS-232 DF1 Devices dialog box appears.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
USB-to-Data Highway Plus Cable 9
5. Enter configuration information in each field.
6. Click OK.
RSLinx Classic Software, Version 2.53 and Later
Do these steps to configure the cable device driver by using RSLinx Classic software, version 2.53 and later.
1. Open RSLinx Classic software and then ,from the Communication menu, choose Configure Drivers.
2. From the Available Driver Types pull-down menu, choose 1784-U2DHP for DH+ devices.
3. Click Add New.
4. Enter a name for the driver you just added and then click OK.
In this field Do this
Comm Port Select the COM port you verified in step 10 on page 7.
Device Select 1770-KF2/1785-KE/SCANport.
Station Number (node address)
Enter the DH+ Station Number for this cable. The defaultis 0.The 1784-U2DHP cable can use any DH+ network address from 0...77 octal. The first packet sent from RSLinx Classic software to the 1784-U2DHP cable sets the DH+ network address the first time that RSLinx Classic software communicates through the 1784-U2DHP cable after power is applied. See Configure the DH+ Node Address on page 11.
Error Checking Select CRC.
Protocol Select Full Duplex.
Baud Rate Not used.
Parity Not used.
Stop Bits Not used.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
10 USB-to-Data Highway Plus Cable
The Configure 1784-U2DHP dialog box appears.
5. Enter configuration information in each field.
6. Click OK.
In this field Do this
Comm Port Select the COM port you verified in step 10 on page 7.
Station Number (node address)
Enter the DH+ Station Number for this cable. The default is 0.The 1784-U2DHP cable can use any DH+ network address from 077 octal. The first packet sent from RSLinx Classic software to the 1784-U2DHP cable sets the DH+ network address the first time that RSLinx Classic software communicates through the 1784-U2DHP cable after power is applied. See Configure the DH+ Node Address on page 11.
IMPORTANT Do not disconnect the cable without first using RSLinx Classic software to stop the driver. Disconnecting the cable without stopping the driver can shut down or cause RSLinx Classic software to become unresponsive.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
USB-to-Data Highway Plus Cable 11
Configure the DH+ Node AddressThe cable DH+ node address (station number) is automatically set the first time the cable sees traffic from RSLinx software to the DH+ network.
To change the node address of the cable, you must do these steps.
1. In RSLinx Classic software, from the Communication menu, choose Configure Drivers.
2. Choose the driver and click Stop.
3. Click Configure.
4. Enter the new node address and click OK.
5. Cycle power to the cable by disconnecting the 1784-U2DHP cable USB connector from the USB port, then reconnecting it.
6. Verify the driver is still selected and click Start.
7. Initiate traffic from RSLinx Classic software to the DH+ network.a. From the Communication menu, choose RSWho.b. Choose the driver from the list.
Consider the Traffic Analyzer SoftwareThe 1784-U2DHP cable is designed to work with Frontlines NetDecoder traffic analyzer software. For more information on Frontlines product, go to http://www.rockwellautomation.com/encompass or http://www.fte.com.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
http://www.rockwellautomation.com/encompass/http://www.fte.com/
12 USB-to-Data Highway Plus Cable
About Using Multiple Cables
Once you have installed the device driver for a 1784-U2DHP cable, a unique COM port will be created and associated with that module (for example, COM9). If you connect a different 1784-U2DHP cable to the same computer, a new COM port will be created and associated with the new cable(for example, COM10).
Each time you connect a new 1784-U2DHP cable to the computer, refer tostep 10 on page 7 to determine the correct COM port for the additional cables.
When you are using multiple 1784-U2DHP cables on the same computer, you must do one of these procedures.
Change the RSLinx Classic software driver settings to specify the appropriate COM port for the connected cable.
Configure multiple RSLinx Classic software drivers.
Product DimensionsThe following illustration shows the product dimensions.
USB Cable Length 0.61 m (2 ft)
8-pin DIN Cable Length 2.44 m (8 ft)
EnclosureLength: 7.62 cm (3 in.)Width: 5.08 cm (2 in.)Thickness: 2.54 cm (1 in.)
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
USB-to-Data Highway Plus Cable 13
Status IndicatorsThe following table describes the cable status indicators.
Cable Status Indicators
Indicator State Description
USB Solid green The cable is configured, but no network traffic is present.
Blinking green Network traffic is present.
Off Unable to transfer data. Disconnected from host. In one of the following states:
Default Powered Address Suspend
Power Solid green The cable is powered.
Off No power to the cable.
DH+ NetworkPower
USB
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
14 USB-to-Data Highway Plus Cable
DH+ Network Off Node address not present.
Blinking green Not connected to the DH+ network.Incorrect DH+ communication rate selected.Break or short in wiring.
Solid green Communicating with the DH+ network.
Blinking red Duplicate node detected.
Solid red Internal diagnostic test failed.
Cable Status Indicators
Indicator State Description
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
USB-to-Data Highway Plus Cable 15
Specifications
Technical Specifications - 1784-U2DHP
Attribute Value
Enclosure type rating Meets IP30
Power dissipation, max 1.575 W max
Supply voltage 5.00V DC5.25V DC, max
Supply current 125 mA
Power consumption, max 1.575 W
Isolation voltage 30V (continuous), Basic Insulation TypeDH+ to USB, Type tested at 500V AC for 60 s
Wiring category 2 - on communication ports(1)
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf
16 USB-to-Data Highway Plus Cable
Environmental Specifications - 1784-U2DHP
Attribute Value
Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
055 C (32131 F)
Temperature, nonoperatingIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-1085 C (14185 F)
Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
595% noncondensing
Shock, nonoperatingIEC 60068-2-27 (Test Ed, Unpackaged Shock)
1000 mm (3.28 ft)
EmissionsCISPR 11
Group 1, Class A
ESD immunityIEC 61000-4-2
8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 802000 MHz10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz10V/m with 1 kHz sine-wave 80% AM from 20002700 MHz
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
USB-to-Data Highway Plus Cable 17
EFT/B immunityIEC 61000-4-4
2 kV at 5 kHz on DH+ port
Surge transient immunityIEC 61000-4-5
2 kV line-earth (CM) on DH+ port
Conducted RF immunityIEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on DH+ port
Certifications - 1784-U2DHP
Certification(1) Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
CE European Union 2004/108/EC EMC Directive, compliant with:EN 61326; Meas./Control/Lab., Industrial RequirementsEN 61000-6-2; Industrial ImmunityEN 61000-6-4; Industrial EmissionsEN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Environmental Specifications - 1784-U2DHP
Attribute Value
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
http://www.ab.com/
18 USB-to-Data Highway Plus Cable
Additional ResourcesThese documents contain additional information concerning related Rockwell Automation products.
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://www.ab.com
USB-to-Data Highway Plus Cable 19
Notes:
Rockwell Automation Publication 1784-IN045C-EN-P - May 2010
Rockwell Automation Support
Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.
Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
New Product Satisfaction ReturnRockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature,
United States or Canada 1.440.646.3434
Outside United States or Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.
United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Publication 1784-IN045C-EN-P - May 2010 PN-76634
Allen-Bradley, Rockwell Software, Rockwell Automation, Data Highway Plus, RSLinx Classic, PLC-5, SLC, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Supersedes Publication 1784-IN045B-EN-P - March 2009 Copyright 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/locations/http://www.rockwellautomation.com/support/americas/phone_en.htmlhttp://www.rockwellautomation.com/literature/
1784-IN045C-EN-P, USB-to-Data Highway Plus Cable Installation InstructionsAbout the Cable
Important User InformationEnvironment and EnclosurePreventing Electrostatic Discharge
Install the CableObtain the Device Driver for the CableConnect and Configure the CableConfigure the RSLinx Classic Software Driver for the Cable
Configure the DH+ Node AddressConsider the Traffic Analyzer SoftwareAbout Using Multiple CablesProduct Dimensions
Status IndicatorsSpecificationsAdditional ResourcesBack Cover
/ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False
/CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice
Introduction_Catagory Types
This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.
Publication Type and Print Category
Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder MinOrder MaxLife Cycle Usage / Release Option
ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal
APA3D2Application Solution or Customer Success Story5100Presale / External
ARNANAArticle/Editorial/BylineNANAPresale / Internal
/News Release (press releases should not be checked into DocMan or printed)
ATB3, B4D5Application Techniques5100Presale / External
BRA2 Primary, A1NABrochures5100Presale / External
CAC2 Primary, C1NACatalogue150Presale / External
CGNANACatalogue Guide150Presale / External
CLNANACollection550Presale / External
COA5, A6, A9D5Company Confidential InformationNANANA / Confidential
CPE-onlyE-only, D5Competitive Information550NA / Confidential
DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal
DIA1, A3NADirect Mail5100Presale / Internal
DMNANAProduct Demo550Presale / Internal
DSB3D5Dimensions Sheet15Post / External
DUB3D5Document Update15Post / External
GRB2D6Getting Results15Post / External
INB3D5Installation instructions15Post / External
LMNANALaunch KitMaterials550Presale / Internal
PCB3D5Packaging Contents
PLE-only Primary, B3E-onlyPrice List550Presale / Internal
PMB2D6Programming Manual15Post / External
PPA3D1Product Profile NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External
QRB2 Primary, B3, B5D5, D6Quick Reference15Post / External
QSB2 Primary, B3, B5D5, D6Quick Start15Post / External
RMB2D5, D6Reference Manual15Post / External
RNB3D5Release Notes15Post / External
SGB1 Primary, B4D5, D6Selection Guide Colour5100Presale / External
SGB2D5, D6Selection Guide B/W5100Presale / External
SPA1, A2, A3, A4NAService ProfileSales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal
SRB2, B3D5, D6Specification Rating Sheet5100Presale / External
TDB2 Primary B3, B4, B5D5, D6Technical Data5100Presale / External
TGB2, B3D6Troubleshooting Guide15Post / External
UMB2 Primary, B4D6User Manual B/W15Post / External
WDB3D5Wiring Diagrams / Dwgs15Post / Internal
WPB3 Primary, B5D5White Paper5100Presale / External
Pre-sale / MarketingAll paper in this category is White Brightness, 85% or better. Opacity 87% or better
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements
A14 color170gsm 2pp100# gloss cover, 100# gloss text
A24 color170gsm, folded, 4pp100# gloss cover, 80# gloss text
A34 colorCover 170gsm with Body 120gsm, > 4pp80# gloss cover, 80# gloss text
A42 color80# gloss cover, 80# gloss text
170gsm Silk 120gsm Silk
A52 color80# gloss cover, 80# matt sheet text
170gsm Silk 120gsm Silk
A61 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet text
A74 color cover10 Point Cover C2S
2 color textCategory being deleted50# matte sheet text
Selection Guide
A84 color coverCategory being deleted50# matte sheet text, self cover
2 color text
Selection Guide
A92 color100gsm bond50# matte sheet text, self cover
Selection Guide
Post Sale / Technical Communication
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements
B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S
2 color text50# matte sheet text
B21 color60# Cover
160gsm Colortech & 100gsm Bond50# matte sheet text
B31 color50# matte sheet text, self cover
100gsm bond
B42 color60# Cover
160gsm Colortech & 100gsm Bond50# matte sheet text
B52 color50# matte sheet text, self cover
100gsm bond
Catalogs
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements
C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S
4 color text45# Coated Sheet
C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S
2 color text32#-33# Coated Sheet
JIT / POD
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements
D14 color170gsm white silk80# gloss cover, coated 2 sides
D24 color120gsm white silk80# gloss text, coated 2 sides, self cover
D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides
D41 color160gsm tab90# index
D51 color80gsm bond20# bond, self cover
D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond
D72 color160gsm tab90# index
D82 color80gsm bond20# bond, self cover
D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond
D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond
Print Spec Sheet
JIT Printing SpecificationsRA-QR005D-EN-P - 4/03/2009
Printing SpecificationYOUR DATA HEREInstructionsNO
(required) Category:D5Select Print Category A,B,C or D from category list, on "Introduction_Catagory Types" tab11 x 17LOOSE -Loose LeafYESPre-sale / MarketingTOP
(required) Finished Trim Size Width:4.75 x 7 (slightly smaller half-size)8.5 x 11PERFECT - Perfect BoundA1LEFT
(required) Publication Number :1784-IN045C-EN-PSample: 2030-SP001B-EN-P3 x 5SADDLE - Saddle StitchA2RIGHTCORNER
Use Legacy NumberYES or NO18 x 24 PosterPLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE
Legacy Number if applicable:Sample Legacy Number: 0160-5.3324 x 36 PosterSTAPLED1 -1 positionA3
Publication Title:USB-to-Data Highway Plus Cable Installation InstructionsSample: ElectroGuard Selling Brief36 x 24 PosterSTAPLED1B - bottom 1 positionA5
(required) Business Group:Marketing CommercialAs entered in DocMan4 x 6STAPLED2 - 2 positionsA6
(required) Cost Center:19021As entered in DocMan - enter number only, no description. Example - 19021CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 191054.75 x 7 (slightly smaller half-size)THERMAL - Thermal bound (Tape bound)A7
Binding/Stitching:SADDLE - Saddle StitchReview key on right...Saddle-Stitch Items All page quantities must be divisible by 4.20 sheets max. on 20# (text and cover); 20 sheets = 80-page pub16 sheets max. on 20# (text) and 90# (cover); 16 sheets = 64-page pub
Perfect Bound Items475 sheets max. on 20# no cover; 475 sheets = 950-page pub470 sheets max. w/cover / 90# index unless indicated otherwise); 470 sheets = 940-page pub
Coil Bound Items400 sheets max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 400 sheets = 800-page pub
Tape Bound Items125 sheets max. on 20# no cover; 125 sheets = 250-page pub120 sheets max. w/cover (90# index unless indicated otherwise); 120 sheets = 240-page pub
Double Wire Bound Items250 sheets max. on 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 250 sheets = 500-page pub4.75 x 7.75THERMALO - Thermal Bound (Tape bound - offline)A8
(required) Page Count of Publication:20Total page count including cover5.5 x 8.5 (half-size)Wire O - Double Wire Bound (offline)A9
Paper Stock Color:White is assumed. For color options contact your vendor.6 x 4Post Sale / Technical Communication
Number of Tabs Needed:5 tab in stock at RR Donnelley7.385 x 9 (RSI Std)B1
Stitching Location:SIDEBlank, Corner or Side8.25 x 10.875B2
Drill Hole YES/NONOAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of inch from the inner page border.8.25 x 11 (RA product profile std)B3
Glue Location on Pad:Glue location on pads8.375 x 10.875B4
Number of Pages per Pad:Average sheets of paper.. 25, 50 75,100 Max9 x 12 (Folder)B5
Ink ColorOne color assumes BLACK / 4 color assume CMYK / Indicate PMS number hereA4 (8 x 11 ) (210 x 297 mm)Catalogs
Used in Manufacturing:YESA5 (5.83 x 8.26) (148 x 210 mm)C1
Comments:C2
Part Number:PN-76634JIT / POD
D1
D2
D3
D4
D5
D6
D7
D8
D9