177
Puerto Rico Transporta0on Technology Transfer Center Department of Civil Engineering and Surveying University of Puerto Rico at Mayagüez Call Box 9000 * Mayagüez, PR 00681 Tel. 7878346385 * Fax: 7872655695 * www.prltap.org February 12 & 13, 2015 St. Thomas, US Virgin Islands Instructor Dr. Walter F. SilvaAraya Professor Department of Civil Engineering and Surveying University of Puerto Rico – Mayagüez Campus URBAN DRAINAGE DESIGN Part 2 29 th Anniversary of Excellence in the Training of Transportation Officials at Municipal, State and Federal Level in Puerto Rico and Virgin Islands

URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Puerto  Rico  Transporta0on  Technology  Transfer  Center  Department  of  Civil  Engineering  and  Surveying  

University  of  Puerto  Rico  at  Mayagüez  Call  Box  9000  *  Mayagüez,  PR  00681  

Tel.  787-­‐834-­‐6385  *  Fax:  787-­‐265-­‐5695  *  www.prltap.org      

February  12  &  13,  2015  St.  Thomas,  US  Virgin  Islands  

Instructor    

Dr.  Walter  F.  Silva-­‐Araya  Professor    

Department  of  Civil  Engineering  and  Surveying  University  of  Puerto  Rico  –  Mayagüez  Campus  

URBAN  DRAINAGE  DESIGN  Part  2  

29th Anniversary of Excellence in the Training of Transportation Officials at Municipal, State and Federal Level in Puerto Rico and Virgin Islands

Page 2: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Module  5    

Hydraulics:  Pavement  Drainage  

Page 3: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

PAVEMENT DRAINAGE

1Dr. Walter F. SilvaUPR Mayaguez

Page 4: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Design Frequency and Spread

Variables to consider:

Frequency of the design runoff event

Allowable spread of water on the pavement.

*Spread and Design frequency are not independent.*

[2] 2

Page 5: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Selection of Design Frequency and Design Spread

Safety of travelling public is the primary consideration.

Major considerations:

1. Classification of the highway.

2. Design speed (hydroplaning).

3. Projected traffic volumes.

4. Intensity of rainfall events.

5. Capital costs.

3

Page 6: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Selection of Design Frequency and Design Spread cont.

Relative elevation of the highway and surrounding terrain is considered

where water can be drained only through a storm drainage system.

Spread on traffic lanes can be tolerated to greater widths where traffic

volumes and speeds are low.

Spread of one-half are usually considered for low-volume local roads.

4

Page 7: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Selection of Design Frequency and Design Spread cont.

Minimum design frequencies and spread based on the type of highway and traffic speed.

ADT = Average daily trafifc[1]

5

Page 8: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Selection of Design Frequency and Design Spread cont.

Design frequency for depressed sections and underpasses where ponded

water can be removed only through the storm drainage system is a 50-year

frequency event.

The use of lesser frequency event such as 100-year storm, to asses hazards

at critical locations is commonly referred to as a check storm or check event.

Check storm should be used any time runoff could cause unacceptable flooding

during less frequent events.

6

Page 9: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Surface Drainage When the rain falls on a sloped pavement surface, the depth of water on the

pavement increases and so does the potential for vehicular hydroplaning.

Design guidance of the following drainage elements is important for

minimizing the effects of hydroplaning:

1. Longitudinal pavement slope

2. Cross or transverse pavement slope3. Curb and gutter design4. Roadside and median ditches5. Bridge decks6. Median Barriers7. Impact attenuators

7

Page 10: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Hydroplaning

Water begins to build in front of the tire to a point where it can produce a hydrodynamic force which can lift the tire off the pavement.

Hydroplaning is a function of :

water depth

roadway geometrics

vehicle speed

tread depth

tire inflation pressure

conditions of the pavement surface[3]

8

Page 11: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Hydroplaning cont. Hydroplaning may be reduced by:

1. Design the highway to reduce the drainage path lengths of the water flowing over the pavement.

2. Increase the pavement surface texture depth.

3. Use of open graded asphaltic pavements.

4. Use of drainage structures along roadway to capture the flow of water over the pavement.

Open graded Asphalt

9

Page 12: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

LOGITUDINAL SLOPE

Minimum longitudinal gradient is more important for

a curbed pavement than for an uncurbed pavement.

Gutter grades should not be less than 0.5%

(absolute minimum is 0.3%)

In sag vertical curves, a minimum slope of 0.3%

should be maintained within 15 meters (50 ft.) of the

low point of the curve.

10

Page 13: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Cross (Transverse) Slope Acceptable range of cross slopes as specified in AASHTO’s policy

on geometric design of highway and streets.

[1]

11

Page 14: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Curb and Gutter

Typical Gutter Sections

[1]

Gutter and Curb Designs

[5]

[4]

12

Page 15: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Curb and Gutter

Typical Gutter Sections

[1]

Gutter and Curb Designs

[5]

[4]

13

Page 16: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Flow in Gutters Gutter sections can be categorized as:

Conventional – Usually have a triangular shape.

Shallow swale type – Typically have a V-shape or circular sections.

[10]

[9]

Spread on pavement and flow depth at curb are often used as criteria for spacing pavement drainage inlets 14

Page 17: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Flow in Gutters Capacity Relationship:

Gutter flow calculations are necessary to establish the spread of water.

Use a modification of Manning’s equation:

where:Ku = 0.376 (0.56 in English units)n = Manning’s coefficientQ = Flow rate m3/s (ft3/s)T = Width of flow (spread)Sx = Cross slope, m/m (ft./ft.)SL = Longitudinal slope, m/m (ft/ft.)

Q = (Ku/n) Sx1.67 SL

0.5 T2.67 T = [ ( Qn )/ ( Ku Sx1.67 SL

0.5 ) ] 0.375

15

Page 18: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Flow in Gutters

16

Page 19: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example: Uniform Gutter Sec. Given: Gutter section illustrated in Figure 4-1 a.1.

SL = 0.010 m/m (ft/ft) Sx = 0.020 m/m (ft/ft) n = 0.016

Find: (1) Spread at a flow of 0.05 m3/s (1.8 ft3/s)

(2) Gutter flow at a spread of 2.5 m (8.2 ft)

17

Page 20: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example: Uniform Gutter Sec. Solution (1):

Step 1. Compute spread, T, using Equation:

𝑇 =𝑄 𝑛

𝐾𝑢𝑆𝑥1.67𝑆𝐿

0.5

0.375

𝑇 =(0.5)(0.016)

(0.376)(0.02)1.67(0.01)0.5

0.375

𝑇 = 2.7𝑚

18

Page 21: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example: Uniform Gutter Sec. Solution (2):

Step 1. Using Equation:

with T = 2.5 m and the information given above, determine Qn.

19

Q = (Ku/n) Sx1.67 SL

0.5 T2.67

𝑄𝑛 = 𝐾𝑢𝑆𝑥1.67𝑆𝐿

0.5𝑇2.67

𝑄𝑛 = (0.376)(0.021.67)(0.01)0.5(2.5)2.67

𝑄𝑛 = 0.00063 𝑚3 𝑠

𝑄 = 0.039 𝑚3 𝑠

𝑄 =0.00063

0.016

Page 22: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Composite Gutter Section Section divided into discharge within the depressed

(gutter) section and the discharge in the roadway above depressed section

Q = Qw + Qs

The spread: 𝑇 = 𝑊 + 𝑇𝑠

Depth of flow at curb at fase

𝑦 = 𝑑 + 𝑎 = 𝑇 𝑆𝑥 + 𝑎

Gutter depression cross slope

𝑆𝑤 = 𝑆𝑥 + 𝑎/𝑊

20

Page 23: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Composite Gutter Section Use Manning’s equation to get

discharge within the roadway above depressed section

Express discharge in the depressed section as a fraction of the total discharge

Substituting total Q and solving

21

𝑄𝑠 =𝐾𝑢𝑛𝑆𝑥5/3

𝑇𝑠8/3

𝑆𝑜1/2

𝐸0 =𝑄𝑤𝑄

𝑄 =𝑄𝑠

1 − 𝐸0

Page 24: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Composite Gutter Section The fraction of the total discharge

flowing in the depressed gutter section is:

22

𝐸0 = 1 +

𝑆𝑤𝑆𝑥

1 +

𝑆𝑤𝑆𝑥

𝑇𝑊 − 1

8 3

− 1

−1

Page 25: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example: Composite Gutter Secn. Given: Gutter section illustrated in Figure with:

W = 0.6 m (2 ft)

SL = 0.01

Sx = 0.020

n = 0.016

Gutter depression, a = 50 mm (2 in)

Find:

1. (1) Gutter flow at a spread, T, of 2.5 m (8.2 ft)

2. (2) Spread at a flow of 0.12 m3/s (4.2 ft3/s) 23

Page 26: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example: Composite Gutter Secn.Solution (1):

Step 1. Compute the cross slope of the depressed gutter, Sw, and the width of spread from the junction of the gutter and the road to the limit of the spread, Ts.

𝑆𝑤 =𝑎

𝑊+ 𝑆𝑥

𝑆𝑤 =50/1000

0.6+ 0.02 = 0.103 𝑚/𝑚

𝑇𝑠 = 𝑇 −𝑊 = 2.5𝑚 − 0.6𝑚 = 1.9𝑚

Step 2. From Manning’s Equation (using Ts) compute Qs:

𝑄𝑠𝑛 = 𝐾𝑢𝑆𝑥1.67𝑆𝐿

0.5𝑇𝑠2.67

𝑄𝑠𝑛 = (0.56)(0.021.67)(0.01)0.5(6.2)2.67

𝑄𝑠𝑛 = 0.011 𝑓𝑡3/𝑠

𝑄𝑠 =𝑄𝑠𝑛

𝑛=

0.011

0.016= 0.69 𝑓𝑡3/𝑠𝑒𝑐24

Page 27: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example: Composite Gutter Secn.Step 3. Determine the fraction of total flow to depressed gutter flow by using Equation

𝐸0 = 1 +

𝑆𝑤𝑆𝑥

1+

𝑆𝑤𝑆𝑥𝑇𝑊−1

8/3

−1

−1

𝑇

𝑊=8.2

2= 4.10

𝑆𝑤𝑆𝑥

=0.103

0.020= 5.15

𝐸0 = 1/ 1 +5.15

1 +5.15

4.10 − 1

2.67

− 1

𝐸0 = 0.70

25

Step 4. Determine the composite gutter flow, Q, using equation

𝑄 =𝑄𝑠

1−𝐸0

𝑄 =0.69

1 − 0.7

𝑄 = 2.3 𝑓𝑡3/𝑠𝑒𝑐

Page 28: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example: Composite Gutter Secn.Solution (2):

Since the spread cannot be determined by a direct solution, an iterative approach must be used.

Step 1. Try Qs = 1.4 ft3/s

Step 2. Compute Qw

Qw = Q - Qs = 4.2 -1.4

Qw = 2.8 ft3/s

Step 3. Using Equation or Chart determine W/T ratio

Eo = Qw / Q = 2.8 / 4.2 = 0.67

Sw/Sx = 0.103 / 0.020 = 5.15

W/T = 0.23 26

Page 29: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example: Composite Gutter Secn.Solution (2):

Step 4. Compute spread based on the assumed Qs

T = W / (W/T) = 2.0 / 0.23

T = 8.7 ft

Step 5. Compute Ts based on assumed Qs

Ts = T - W = 8.7-2.0 = 6.7 ft

Step 6. Use Manning’s Eq. to determine Qs for computed Ts

𝑄𝑠𝑛 = 𝐾𝑢𝑆𝑥1.67𝑆𝐿

0.5𝑇𝑠2.67

𝑄𝑠𝑛 = (0.56)(0.021.67)(0.01)0.5(6.7)2.67

𝑄𝑠𝑛 = 0.0131 𝑓𝑡3/𝑠

𝑄𝑠 =𝑄𝑠𝑛

𝑛=0.0131

0.016= 0.82 𝑓𝑡3/𝑠𝑒𝑐

Step 7. Compare computed Qs with assumed Qs.

Qs assumed = 1.4 > 0.82 = Qs computed

Not close - try again 27

Page 30: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Step 8. Try a new assumed Qs and repeat

Steps 2 through 7.

Assume Qs = 1.9 ft3/s

Qw = 4.2 -1.9 = 2.3 ft3/s

Eo = Qw / Q = 2.3/4.2 = 0.55

Sw / Sx = 5.15

W / T = 0.18

T = 2.0/0.18 = 11.1 ft

Ts = 11.1 - 2.0 = 9.1 ft

Qsn = 0.30 ft3/s

Qs =0.30 / 0.016 = 1.85 ft3/s

Qs assumed = 1.9 ft3/s close to

1.85 ft3/s = Qs computed28

Example: Composite Gutter Secn.

Page 31: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

END

29

Page 32: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

REFERENCES1. Federal Highway Administration, 2009. Urban Drainage Design Manual, Hydraulic

Engineering Circular No. 22, 3rd edition, FHWA-NHI-10-009, Washington, D.C.

2. http://farm5.static.flickr.com/4032/4384544575_78f8f44907.jpg

3. http://www.pakwheels.com/forums/attachments/news-articles-driver-education-safety/1316432d1386546108-hydroplaning-aquaplaning-driving-rain-hidden-danger-have-you-ever-experienced-v236753_ane_hydroplane.00001.jpg

4. http://www.coloradocoringandcutting.com/wp-content/uploads/2012/06/curb-and-gutter.jpg

5. http://www.ellsworthinc.com/images/curbgutter.jpg

6. http://upload.wikimedia.org/wikipedia/commons/5/59/Taconic_State_Parkway_from_NY_217_in_Ghent,_NY.jpg

7. http://www.thomasengineeringpa.com/images/Swale%202.JPG

8. http://graphics8.nytimes.com/images/blogs/themoment/posts/111708highway.jpg

9. http://www.fhwa.dot.gov/engineering/hydraulics/pubs/08090/06.cfm

10. Akan, A. O., & Houghtalen, R. J. (2003). Urban hydrology, hydraulics, and stormwater quality: Engineering applications and computer modeling. Hoboken, N.J: J. Wiley & Sons.

30

Page 33: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Module  6    

GuKer  Inlets  Design  

Page 34: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

PAVEMENT DRAINAGE

Dr. Walter F. Silva, UPRM

Page 35: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Drainage Inlet Design

Storm drain inlets are used to collect runoff and

discharge it to an underground storm drainage

system.

Inlets are typically located in gutter sections, paved

medians, and roadside and median ditches.

Inlets used for the drainage of highway surfaces can

be divided into the following four classes:

1. Grate inlets: opening in the gutter or ditch covered by

a grate

2. Curb-opening inlets: are vertical openings in the curb

covered by a top slab

3. Slotted inlets: a pipe cut along the longitudinal axis

with bars perpendicular to the opening to maintain the

slotted opening

4. Combination inlets: both a curb-opening inlet and a

grate inlet placed in a side-by-side

Page 36: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Drainage Inlet Design

Grate inlets, as a class, perform satisfactorily over

a wide range of gutter grades.

Are installed along the roadway where the water is

flowing.

May be clogged by floating trash or debris

Curb-opening inlets are most effective on flatter

slopes, in sags, and with flows which typically carry

significant amounts of floating debris

The interception capacity of curb-opening inlets

decreases as the gutter grade steepens.

Consequently, the use of curb-opening inlets is

recommended in sags and on grades less than 3%.

They are bicycle safe

Page 37: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Drainage Inlet Design Combination inlets provide the advantages of both curb

opening and grate inlets.

This combination results in a high capacity inlet which

offers the advantages of both grate and curb-opening

inlets.

Slotted drain inlets can be used in areas where it is

desirable to intercept sheet flow before it crosses onto a

section of roadway.

Their principal advantage is their ability to intercept flow

over a wide section.

Are very susceptible to clogging from sediments and

debris,

Not recommended for use in environments where

significant sediment or debris loads may be present.

Slotted inlets on a longitudinal grade do have the same

hydraulic capacity as curb openings when debris is not a

factor.

Page 38: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Drainage Inlet Design1. P-50 Parallel bar grate with bar spacing 48 mm (1-7/8 in) on center (Figure 4-5).

2. P-50 x 100 Parallel bar grate with bar spacing 48 mm (1-7/8 in) on center and 10 mm (3/8 in) diameter lateral rods spaced at 102 mm (4 in) on center (Figure 4-5).

3. P-30 Parallel bar grate with 29 mm (1-1/8 in) on center bar spacing (Figure 4-6).

4. Curved Vane Curved vane grate with 83 mm (3-1/4 in) longitudinal bar and 108 mm (4-1/4 in) transverse bar spacing on center (Figure 4-7).

5. 45°- 60 Tilt Bar 45° tilt-bar grate with 57 mm (2-1/4 in) longitudinal bar and 102 mm (4 in)

6. transverse bar spacing on center (Figure 4-8).

7. 45°- 85 Tilt Bar 45° tilt-bar grate with 83 mm (3-1/4 in) longitudinal bar and 102 mm (4 in)

8. transverse bar spacing on center (Figure 4-8).

9. 30°- 85 Tilt Bar 30° tilt-bar grate with 83 mm (3-1/4 in) longitudinal bar and 102 mm (4 in)

10. transverse bar spacing on center

11. Reticuline "Honeycomb" pattern of lateral bars and longitudinal bearing bars

Page 39: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Drainage Inlet

Page 40: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Factors Affecting

Inlet interception capacity, Qi, is the flow intercepted by an inlet under a

given set of conditions.

The efficiency of an inlet, E, is the percent of total flow that the inlet will

intercept for those conditions.

The efficiency of an inlet changes with changes in cross slope, longitudinal

slope, total gutter flow, and, to a lesser extent, pavement roughness.

In mathematical form, efficiency, E, is defined by the following equation:

E = Q1 / Q

where: E = Inlet efficiency

Q = Total gutter flow, m3/s (ft3/s)

Qi = Intercepted flow, m3/s (ft3/s)

Page 41: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Factors Affecting

Charts for grate inlet interception have been made and are applicable

to all grate inlets tested for the Federal Highway Administration.

The chart for frontal flow interception is based on test results which

show that grates intercept all of the frontal flow until a velocity is

reached at which water begins to splash over the grate.

At velocities greater than "Splash-over" velocity, grate efficiency in

intercepting frontal flow is diminished.

Grates also intercept a portion of the flow along the length of the

grate, or the side flow. A chart is provided to determine side-flow

interception.

[1]

Page 42: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Factors Affecting

Grates are effective highway pavement drainage inlets where clogging

with debris is not a problem.

Where clogging may be a problem, see Table where grates are ranked for

susceptibility to clogging based on laboratory tests using simulated

"leaves." This table should be used for relative comparisons only.

Page 43: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Factors Affecting

When the velocity approaching the grate is less than the "splash-over"

velocity, the grate will intercept essentially all of the frontal flow.

When the gutter flow velocity exceeds the "splash-over" velocity for the

grate, only part of the flow will be intercepted.

A part of the flow along the side of the grate will be intercepted, dependent

on the cross slope of the pavement, the length of the grate, and flow

velocity.

Page 44: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Interception Capacity The ratio of frontal flow to total gutter flow, Eo, for a

uniform cross slope is expressed by :

where: Q = Total gutter flow, m3/s (ft3/s)

Qw = Flow in width W, m3/s (ft3/s)

W = Width of depressed gutter or grate, m (ft)

T = Total spread of water, m (ft)

Page 45: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Interception Capacity The ratio of side flow, Qs, to total gutter flow is:

The ratio of frontal flow intercepted to total frontal flow, Rf, is expressed by

where: Ku = 0.295 (0.09 in English units)

V = Velocity of flow in the gutter, m/s

Vo = Gutter velocity where splash-over first occurs, m/s

(Note: Rf cannot exceed 1.0)

This ratio is equivalent to frontal flow interception efficiency.

Page 46: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Interception Capacity

The ratio of side flow intercepted to total side flow, Rs,

or side flow interception efficiency, is expressed by

The efficiency, E, of a grate is expressed as provided

Ku = 0.0828 (0.15 in English units)

Page 47: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Interception Capacity

The first term on the right side of this Equation is the

ratio of intercepted frontal flow to total gutter flow, and

the second term is the ratio of intercepted side flow to

total side flow.

The second term is insignificant with high velocities and

short grates.

Page 48: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example Interception Capacity Given: Gutter section illustrated in Figure with:

W = 0.6 m (2 ft)

SL = 0.01

Sx = 0.020

n = 0.016

Gutter depression, a = 50 mm (2 in)

T = 2.5 m (8.2 ft) SL = 0.010

W = 0.6 m (2.0 ft) Sx = 0.02

n = 0.016

Continuous Gutter depression, a = 50 mm (2 in or 0.167 ft)

Find: The interception capacity of a curved vane grate 0.6 m by 0.6 m (2 ft by 2 ft)

Page 49: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Example Interception Capacity

Solution Sw = 0.103 m/m (ft/ft)

Eo = 0.70

Q = 0.06 m3/sec (2.3 ft3/sec)

Step 1. Compute the average gutter velocity

V = Q / A = 2.3 / A

A = 0.5 T2 Sx + 0.5 a W

A = 0.5 (8.2)2 (0.02) + 0.5(0.167)(2.0)

A = 0.84 ft2

V = 2.3 / 0.84= 2.74 ft/s

Step 2. Determine the frontal flow efficiency

using Chart 5.

Rf = 1.0

Step 3. Determine the side flow efficiency using

Equation 4-19 or Chart 6.

Rs = 1/[1+ (Ku V1.8) / (Sx L2.3)]

Rs = 1/[1+ (0.15) (2.74)1.8 / [(0.02) (2.0)2.3]

Rs = 0.10

Step 4. Compute the interception

capacity using Equation :

Qi = Q[Rf Eo + Rs (1 - Eo)]

= (2.3)[(1.0)(0.70)+(0.10)(1- 0.70)]

Qi = 1.68 ft3/s

Page 50: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

CHARTS

Page 51: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

CHARTS

Page 52: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed
Page 53: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed
Page 54: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

END

Page 55: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Module  7    

DetenAon  and  RetenAon  Ponds  

Page 56: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Detention and Retention Ponds

Movement of flood waves

1

Page 57: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Detention and Retention Ponds

• Land development activities, including the construction of roads, convert natural pervious areas to impervious and otherwise altered surfaces.

• These activities cause an increased volume of runoff because infiltration is reduced, the surface is usually smoother thereby allowing more rapid drainage, and depression storage is usually reduced.

• In addition, natural drainage systems are often replaced by lined channels, storm drains, and curb-and-gutter systems.

• These man-made systems produce an increase in runoff volume and peak discharge, as well as a reduction in the time to peak of the runoff hydrograph.

2

Page 58: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Detention and Retention Ponds

• A retention pond is designed to hold a specific amount of water indefinitely. Usually the pond is designed to have drainage leading to another location when the water level gets above the pond capacity, but still maintains a certain capacity.

• A detention pond is a low lying area that is designed to temporarily hold a set amount of water while slowly draining to another location.

• Detention/retention of excess storm water runoff as a means of controlling the quantity and quality of storm water releases is a fundamental principle in storm water management and a necessary element of a growing number of highway storm drainage systems.

3

Page 59: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Detention and Retention Ponds • The storage of storm water can

reduce the frequency and extent of downstream flooding, soil erosion, sedimentation, and water pollution.

• Detention /retention facilities also have been used to reduce the costs of large storm drainage systems by reducing the required size for downstream storm drain conveyance systems.

• The use of detention/retention facilities can reduce the peak discharge from a given watershed.

• The reduced post-development runoff hydrograph is typically designed so that the peak flow is equal to or less than the pre-developed runoff peak

4

Page 60: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Flood Routing

• Temporal and spatial variations of a flood wave through a river reach, pond or reservoir

• Used to predict the outflow hydrograph from a watershed

• Flood Routing Methods: • Hydrologic Routing

– Involves the balancing of inflow, outflow, and volume of storage through the use of the continuity equation.

• Hydraulic Routing – It is more complex and accurate than hydrologic routing and is

based on the solution of the continuity and the momentum equation for unsteady flow in open channel. These differential equations are known as Saint Venant equations.

5

Page 61: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Routing

• Routing – is a process whereby an outflow hydrograph is determined at a point in a stream, reservoir, pond or lake resulting from a known inflow hydrograph at an upstream point.

6

Page 62: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Storage and River Routing

• These are the two most common hydrologic routing methods

• In storage routing the outflow is only a function of the storage level (example: lake, reservoir of pond)

• In river routing the storage in a river reach of length L depends on more than just the outflow

7

Page 63: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Storage and River Routing

Storage routing

• The outflow is only a function of the storage level (example: lake, reservoir of pond)

• The peak outflow must intersect the inflow hydrograph

River routing

• The storage in a river reach of length L depends on more than just the outflow. It depends on inflow and outflow

• The peak outflow do not necessarily intersect the inflow hydrograph

8

These are the two most common hydrologic routing methods

Page 64: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Storage and River Routing

• RESERVOIR ROUTING

• The peak of the outflow from a reservoir should intersect the inflow hydrograph.

• RIVER ROUTING

• The peak of the outflow occurs after the interception of the inflow and outflow hydrographs.

9

Page 65: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Continuity Equation

I = Inflow Q = Outflow

ΔS = change in storage Δt = change in time

• Storage is the area between the inflow and outflow curves

10

tOISS

OOO

III

tOIS

dtOIS

01

2121

and

2 and

2

where

or

Page 66: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Storage Routing

• In addition to the mass balance equation, a storage-discharge relationship is required for the hydrologic routing.

• The required relation could be

• Weir equation

• Orifice Equation

• Spillway Equation

• Discharge curve

11

Page 67: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Storage and River Routing

12

Page 68: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

INCI 5008 13

Hydrologic Reservoir Routing

5.1

023

2

'2

hhLgCQ

ghACQ

eweir

odorifice

Page 69: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pond Storage Computations

• Inflow and outflow hydrographs for a pond are given.

• A) Determine the average storage for each one-day period (Dt = 1 day)

• Graph storage vs time for the pond. Assume that the reservoir is empty at the beginning of the event.

• What is the approximate maximum storage reached by the pond during this event.

14

0

2000

4000

6000

8000

10000

12000

0 5 10 15

Dis

ch

arg

e,

cfs

Time, days

Adapted from Mc Cuen

Page 70: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pond Storage Computations

• Basic continuity equation

1 2 3 Time (days)

I (cfs)

O (cfs)

0.5 500 250 1.5 3500 1000 2.5 9000 3000 3.5 9750 4500 4.5 8000 5750 5.5 4500 6000 6.5 2250 5250 7.5 1250 4250 8.5 250 3250 9.5 0 2500 10.5 0 1500 11.5 0 1000 12.5 0 750 13.5 0 0 15

tOIS

0

2000

4000

6000

8000

10000

12000

0 5 10 15

Dis

ch

arg

e,

cfs

Time, days

Data given

I

Page 71: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pond Storage Computations

1 2 3 4 5 6 Time (days)

I (cfs)

O (cfs)

ΔS/Δt (cfs)

Time (days)

Storage (ac-ft)

0.5 500 250 250 1 496 1.5 3500 1000 2500 2 5455 2.5 9000 3000 6000 3 17355 3.5 9750 4500 5250 4 27769 4.5 8000 5750 2250 5 32231 5.5 4500 6000 -1500 6 29256 6.5 2250 5250 -3000 7 23306 7.5 1250 4250 -3000 8 17355 8.5 250 3250 -3000 9 11405 9.5 0 2500 -2500 10 6446

10.5 0 1500 -1500 11 3471 11.5 0 1000 -1000 12 1488 12.5 0 750 -750 13 0 13.5 0 0 0 14 0 16

t

SQI

4Column

tt

SSS

1

01 6Column

Compute storage as a function of time

Page 72: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Module  8    

Hydraulics:  Pump  Systems  

Page 73: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

PUMP SYSTEMS

Page 74: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Used to remove storm water from highway sections that can not be drained by gravity.

High operational costs.

Recommended only where other systems are not feasible.

Introduction

Page 75: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Design Considerations

Wet-pit vs. dry-pit

Type of pumps

Number and capacity of pumps

Motor

Peak flow vs. storage

Force main vs. gravity

Above grade vs. below grade

Monitoring Systems

Backup systems

Maintenance requirements

Pump station design presents the designer with a challenge to provide a cost-effective drainage system that meets the need of the project.

To assure cost-effectiveness, the designer should assess eachchoice and develop economic comparisons of alternatives based onengineering judgment and experience.

Page 76: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Location

Pump stations should be located near the low point in the highway drainage system they are intended to serve.

The stations should be located on high ground to obtain access if the highway becomes flooded.

Soil borings should be made during the selection of the site to determine the allowable bearing capacity and identify any potential problems.

Architectural and landscaping decisions should be made in the location for above-round stations so the station will blend into the surrounding community.

Page 77: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Hydrology Pump stations serving major expressways and arterials are usually

designed to accommodate 50-year storm.

It is desirable to check the drainage system for the 100-year storm to determine the extent of flooding and the associated risk.

Drainage area tributary to the station should be keep as small as possible.

By-pass or pass-through all possible drainage to reduce pumping requirements.

Avoid future increases in pumping by isolating the drainage area.

Hydrologic design should be based on the ultimate development of the area which must drain to the station.

Page 78: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Hydrology cont. Storage must be considered in addition to that which exists in the wet well

at all pump station sites.

Additional storage, skillfully designed, may greatly reduce the peak pumping rate required.

Storage well is usually located below normal ground level because of the nature of the sites where highway pump stations are located.

If storage is used to reduce peak flow rates, a routing procedure must be used to design the system. This procedure integrates the following elements to determine the required pump rate:

Inflow hydrograph Stage-storage relationship Stage-discharge relationship

Page 79: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Collection Systems

To avoid siltation problems in the collection system, a minimum grade that produces a velocity of 1 m/s (3 ft./s) in the pipe while flowing full is suggested.

The inlet pipe should enter the station perpendicular to the line of pumps.

The inflow should distribute itself equally to all pumps.

Collector lines should preferably terminate at a forebay or storage box. However they may discharge directly into the station.

Page 80: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Collection Systems cont.

The capacity of the collectors and storage are critical to provide cycling time for the pump and must be carefully calculated.

To minimize siltation problems in storage units, a minimum grade of 2% should be used.

It is recommended that screens be used to prevent large objects from entering the system and possible damaging the pumps.

Larger debris may also be screened at the surface or inside the wet well/storage system.

Page 81: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Station Types

Wet-Pit Station In this type of station, the pumps are submerged in a wet well or sump

with the motors and the controls located overhead.

The motor is commonly connected to the pump by a long drive shaft located in the center of the riser pipe.

Another type of wet-pit design involves the use of submersible pumps. This pumps requires less maintenance and less horsepower because

a long drive shaft is not required. Submersible pumps allow for convenient maintenance in wet-pit

stations because of easy pump removal.

Page 82: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Typical Axial Pump Wet-Pit Station

[1]

Page 83: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Typical Centrifugal Pump Wet-Pit Station

[4] [5]

Page 84: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Station Types cont. Dry-Pit Station

This type of station consist of two separate elements: The storage box

or wet well and the dry well.

Storm water is stored in the wet well which is connected to the dry well

by horizontal suction piping.

Centrifugal pumps are usually used and located on the floor of the dry

well.

The main advantage of this type of station is the availability of a dry

area for personnel to perform routine and emergency pump and pipe

maintenance.

Page 85: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Typical Centrifugal

Pump Dry-Pit

Station

[1]

Page 86: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pump Types

The most common types of storm water pumps are:

Axial flow (propeller) Radial flow (impeller) Mixed flow (combination of axial and radial flow).

[6][7]

Page 87: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Submergence

The submergence depth is very important if a submersible pump is used.

Is the depth of water above the pump inlet necessary to prevent cavitation or vortexing.

Varies with pump type and speed and atmospheric pressure.

The dimension is usually provided by manufacturer.

The available net positive suction head (NPSH) should be calculated and compared to the manufacturer’s requirement.

Page 88: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Centrifugal Pumps Terminology:

Head: Energy per unit weight. Have units of length.

Pressure Head: Amount of energy in water due to water pressure.

P = static pressure.

γ = specific weight

16

Phpress

Page 89: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Friction head: (hf): Head required to overcome resistance to flow in the pipes.

Velocity head: (hv): Specific kinetic energy of fluid. Also called dynamic head.

Static suction head (hz(s)): Vertical distance above the centerline of the pump inlet to the

free level of the fluid source. If the free level of the fluid is below the pump inlet hz will be negative and is known as static suction lift.

17

gVhv 2

2

Terminology

Page 90: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Terminology Static discharge head (hz(d)):

The vertical distance above the centerline of the pump inlet to the point of free discharge.

Total Dynamic Head: (TDM): Difference in height between the hydraulic grade line

(HGL) on the discharge side of the pump and the (HGL) on the suction side of the pump.

18

Page 91: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pump System

19

Page 92: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pump Characteristic CurvePump Curves

Manufactures test each centrifugal pump, type and publish a pump curve for each pump type and size.

Every centrifugal pump operates at less than 100% efficiency, generally between 50% and 85%

The pump’s efficiency can decrease dramatically if the pump is operated at other than its optimum discharge. 20

Page 93: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pump Characteristic Curve

21

Page 94: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

PumpsOperation

22

Page 95: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Discharge Head and System Curve cont.

Because pumps operate over a range of water levels, the designer is required to specify at least three (3) points on the performance curve.

This points are the conditions for the highest TDH, the design head and the lowest head expected over the full operating range of the pump.

The designers must study the curves of TDH vs. pump capacity provided by manufacturers in order to understand the pump conditions throughout the full range of head that the pump will operate under.

Page 96: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Typical Performance Curve

[1]

Page 97: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Typical Performance Curve

[10]

Page 98: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Discharge Head and System Curve

Pumps are sensitive to changes in head, therefore, all valve and bend losses should be considered in computations.

Total dynamic head (TDH) is the combination of static head, velocity head and various head losses in the discharge system due to friction.

TDH is computed as:

TDH = Hs + Hf + Hv + Kl

Hs = Static Head, m (ft)

Hf = Friction head, m (ft) Hv = Velocity head, m(ft) [ V2/ 2g] Hl = Losses through fittings, valves, etc., m (ft)

Page 99: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Discharge Head and System Curve cont.

[8]

Page 100: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Discharge Head and System Curve cont.

[9]

Page 101: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pumps Operation

System curves

Is a plot the energy required to operate the hydraulic system for different flow rates.

Depends on the configuration of the section and discharge lines.

29

Page 102: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pumps OperationOperating Point

The intersection of the pump curve (supplied by the manufacturer) and system curve locates the OPERATING POINT This point defines the pumping head and the system discharge.

The design operating point should be close to the highest pump efficiency.

30

Page 103: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Discharge Head and System Curve cont.

It is usual to minimize the head losses by selection of correctly sized discharge lines and other components.

Once the head losses are computed, the system curve (Q vs. TDH) can be plotted to define the energy required to pump any flow through the system.

System curve Flow vs TDH

[1]

Page 104: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pumps Operation

32

Page 105: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pumps Operation

33

Page 106: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pumping Power

Pump output power (hydraulic power or waterpower) is the net power actually transferred to the fluid.

Pump input power is the net power at the motor-pump. This is known as the BRAKE POWER.

The difference between input and output power are the friction or mechanical losses, volumetric losses and electrical losses.

34

Page 107: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pumping Power The Pump Efficiency:

Is the ratio of the hydraulic power and the break-power:

Pump efficiency is a function of the specific speed and the flow rate. The overall efficiency of the pump installation is the product of the pump and motor efficiencies

35

BPPhQ

powerpumpbrakepowerhydraulicy p

P

mpnnn

Page 108: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pumps in Parallel Useful for systems with variable demand.

Add the capacity timer the number of pumps (assuming all pumps are equal), keeping the same head.

With pump X operating alone the capacity is given by Q1. When pump Y is added, the capacity increases to Q3 (with an increase in total head!).

36

Page 109: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pumps in Parallel

37

Page 110: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pumps in Series Useful to increase discharge head

38

YX

Page 111: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

CavitationCauses:

High suction lift or low suction head

Excessive pump speed

High liquid temperature (high vapor pressure)

NPSH (Net positive suction head)

Cavitation occurs when the available head is less than the required head for satisfactory operation.

The minimum fluid energy required at the pump inlet for satisfactory operation is the NPSH required.

39

Page 112: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Cavitation and NPSH The NPSHR is a function of the pump and is given by the

manufacturer

The net positive suction head available (NPSHA) is the actual fluid energy at the inlet.

NPSHA= Hs –Hloss=

hres = reservoir head

hatm = atmospheric head

hz(s) = potential head at the suction side

hf(s) = friction plus minor losses in the suction side

hvp = vapor pressure head (function of temperature) 40

vpsfatmres hhhhhsz

)()(

Page 113: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Affinity or similarity laws Assumptions for both pumps

1. Operate in turbulent region2. Have the same efficiency

In reality, larger pumps will be more efficient than smaller pumps.Simplified versions are obtained if pumps have the same impeller diameter or the same speed.

41

Page 114: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Main and Spare Pumps

The designer should determine the number of pumps needed.

Is recommended to use two to three pumps as minimum.

Use equal-size pumps so they can be freely alternated into service.

Considering short duration of high flows, the low frequency of the design storm, spare or standby pumps are typically not warranted in storm water applications.

Page 115: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Storage Is important to evaluate how much storage capacity should be provided in

a pump station.

The total storage can be determine comparing inflow hydrograph to the controlling pump discharge rate.

The volume of water in the

shaded area is beyond the

capacity of the pumps

and must be stored.

[1]

Page 116: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Storage cont.

For cases of highway with either short underpasses or long depressions sections, is not reasonable to consider above ground storage.

Water that originates outside the depressed areas should not be allowed to enter the depressed areas because of the need to pump all this water.

In this situations the simplest form of storage is either the enlargement of the collection system or the construction of an underground storage facility.

Page 117: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pump Station Storage Requirement

Storage capacity is required as part of pump station design to permit the use of smaller, more economical pumps.

Increasing the storage will minimize the required pump size.

The approach to evaluate the relationship between pump station storage and pumping rate requires development of an inflow mass curve and execution of a mass curve routing procedure.

Page 118: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Inflow Mass Curve The inflow mass curve is develop by:

Dividing the inflow hydrograph into uniform time increments. Computing the inflow volume over each time step. Summing the inflow volumes to obtain cumulative inflow volume and

plotted against time to produce the curve.

[1]

Page 119: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Mass Curve Routing

Is important to the designer to understand how a typical pump station operates prior to start the mass curve routing.

As storm water flow to the pump station, the water will be stored and the water level will rise to an elevation which activates the first pump.

If the inflow is greater than the pump rate, the water level will continue to rise and activates the second pump.

This process continues until the inflow rate subsides.

To develop the mass curve routing, is necessary to have an inflow hydrograph, a stage-storage curve and a stage-discharge curve.

Page 120: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Mass Curve Routing cont.

Stage-storage curve Stage-discharge curve[1]

Page 121: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Mass Curve Routing cont.

Mass curve routing diagram

At point A, the first pump will start.

At point B, storage has been emptied and pump turns off.

At point C, volume started accumulated and first pump starts again.

At point D, storage has filled to the elevation where second pump starts.

At point E, second pump turns off.

At point F, first pump turns off. [1]

Page 122: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

References1. Federal Highway Administration, 2009. Urban Drainage Design Manual, Hydraulic Engineering Circular No.

22, 3rd edition, FHWA-NHI-10-009, Washington, D.C.

2. http://www.awmawatercontrol.com.au/products/flap-gate/

3. http://www.quora.com/Why-are-manholes-called-manholes

4. http://sewagetreatment.us/wp-content/uploads/2010/11/Pumping_Station.jpg

5. http://www.jensenengineeredsystems.com/wp-content/uploads/2011/05/wet-well.jpg

6. http://www.weirminerals.com/images/lewis-pump-axial-flow-600.jpg

7. http://www.arqhys.com/construcciones/fotos/construcciones/Tipos-de-Bombas.jpg

8. http://water.me.vccs.edu/image15U.jpg

9. http://www.mathalino.com/reviewer/fluid-mechanics-and-hydraulics/energy-and-head

10. https://www.isa.org/uploadedImages/Content/Standards_and_Publications/ISA_Publications/InTech_Magazine/2013/August/int_2013-08---Special-Section--Fig-1.jpg

Page 123: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

END

Page 124: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Module  9    

Hydraulics:  Erosion  Control  PracAces  and  Measures  

Page 125: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Erosion Control Practices and MeasuresPart IClassification and Construction Sequence

Page 126: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Erosion and sediment impacts

• Pollution

• Ecological impacts

• Hydraulic modifications

• Property damage

• Construction costs and schedule

• Lawsuits

July 22, 2012 Footer text here2

Page 127: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Pollution

July 22, 2012 Footer text here3

Page 128: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Ecological impacts

July 22, 2012 Footer text here4

Page 129: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Hydraulic modifications

July 22, 2012 Footer text here5

Page 130: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Property damage

July 22, 2012 Footer text here6

Page 131: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Construction costs and schedule

• Stop work ordered for noncompliance

• Fines/ penalties for noncompliance

• Repair damage to adjacent properties

• Missed deadlines, litigation, other additional work.

July 22, 2012 Footer text here7

Page 132: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Lawsuits

July 22, 2012 Footer text here8

Page 133: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Classifications of E & SC Practices

• Primary vs Secondary• Primary: Keep soil in place and protect from erosive forces

• Secondary or backup: Attempt to control the sediment

• Structural vs Non-Structural• Structural measures: Engineering practices adequate to prevent erosion or controlling runoff requiring

design and installation

• Non-Structural: Management alternatives to prevent soil erosion and sediment generation mostly through vegetative measures

• Type of Problem Area• Slopes

• Receiving waters

• Open drainage ways

• Culverts and outfalls

• Adjacent properties

Page 134: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Erosion on Slopes

• slope length is long, the slope is steep, the soil is highly erodible, or that the soil cover (vegetation) has been removed and will take some time to be reestablished.

• Slope erosion can occur on cuts, fills, stockpiles, or cleared but ungraded surfaces.

• Measures include some combination of:• vegetative and structural protective covers (temporary seeding, permanent. seeding, groundcover,

mulch, sodding, erosion control matting, and topsoiling)

• water conveyance (temporary or permanent diversions and slope drains)

• temporary construction road stabilization.

Page 135: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Erosion on Slopes

Page 136: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Receiving Waters

• Include streams, lakes and waterways

• protect from increased runoff quantities, and sediment loads from the construction site.

• Increase in runoff could lead to stream bank erosion and downstream flooding.

• Measures include combination of:• sediment barriers (straw or hay bale barriers, silt/geotextile fence, brush barrier)

• water conveyance (outlet protection)

• sediment detention ponds and basins

• stream and stream bank protection

Page 137: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Sediment Barriers water conveyance (outlet protection)

Page 138: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Sediment detention ponds and basins

Page 139: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Stream and stream bank protection

Page 140: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Open Drainage ways

• Open drainage ways can become significant sources of sediment

• Drainage ways need to be designed, constructed, and maintained.

• They should not be overtopped and do not transport the runoff at

• Velocities that will erode the bottom or sides of the drainage way.

• Measures include some combination of:

• vegetative and structural protective cover (mulch, sodding, and erosion control matting)

• water (conveyance check dams, inlet protection, and outlet protection)

• stream and stream bank protection (riprap).

Page 141: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Open Drainage waysvegetative and structural protective cover

Erosion control matting

Sodding

Mulch

Page 142: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Open Drainage wayswater (conveyance check dams, inlet protection, and outlet protection)

Conveyance check dams Inlet protection Outlet protection

Page 143: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Open Drainage ways

stream and stream bank protection (riprap).

Page 144: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Culverts and outfalls

• Culverts and outfalls need specific measures to ensure that their entrances are not blocked, that they do not become filled with sediment, and that their outlets do not erode down slope or downstream areas.

• Erosion control measures with application to culverts and outfalls include:• water conveyance (temporary slope drains, inlet protection, and outlet protection).

Page 145: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Adjacent properties

• Adjacent properties need to be protected from increased runoff and sediment load.

• Slopes within the construction site need to be protected from runoff from adjacent properties.

• Erosion control measures include:• sediment barriers

• water conveyance (temporary and permanent diversions)

• Sediment detention ponds and basins (temporary sediment traps and sediment basins).

Page 146: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Minimum recommendations for BMP’s in construction sites

• Minimize the amount of existing vegetation that you must disturb for construction. Keep out of sensitive areas and their buffers.

• Before construction activities begin adjacent to sensitive areas

• Perimeter protection to filter sediment for sheet erosion shall be located downslope of all disturbed areas and properly installed prior to upslope grading.

• One hundred linear feet of silt fence per 0.25 acre and the necessary stakes to hold the fence in place shall be stockpiled onsite.

• Stabilized construction entrances will be installed as the first step of clearing and grading.

Page 147: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Minimum recommendations for BMP’s in construction sites

• Stabilized construction entrances will be installed as the first step of clearing and grading.

Page 148: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Minimum recommendations for BMP’s in construction sites

• Roads and parking areas will be stabilized immediately after the initial grading.

• Unsurfaced driveway entrances, access roads and parking areas used by construction traffic will be stabilized to minimize erosion and prevent tracking mud.

• The paved areas shall not be cleaned by washing/flushing streets.

• Dirty equipment, especially concrete trucks, should not be cleaned in or near waterways.

• Sediment retention facilities will be installed before grading.

• If sediment retention facilities need to be removed for grading, additional ponds/traps/systems to accommodate storage capacity need to be installed onsite. This will be prior to removal of existing facility.

Page 149: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Minimum recommendations for BMP’s in construction sites

• Dust is to be controlled on construction sites.

• Water truck is used to control dust on dirty/grades areas only.

• Water truck will only drop enough water to control the dust. No runoff is to be generated.

• Erosion and sediment measures will be inspected a minimum of once a week and within 24 hours of significant storms (0.5 inches/24-hour, or where runoff is generated).

• A 24-hour phone number for the Erosion Sediment and Control Designated Inspector will be posted in clearly visible location on the project site.

Page 150: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Minimum recommendations for BMP’s in construction sites

• Water truck is used to control dust on dirty/grades areas only

Page 151: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

SUMMARY

SUMMARY

Page 152: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Module  10    

Channel  Data  Tables  and  Graphs  

Page 153: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Channel DataTables and graphs

Page 154: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Open Channel FlowDesign Tables

Page 155: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed
Page 156: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed
Page 157: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed
Page 158: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Normal depth solution procedure: (a) trapezoidal channels (m side slope)

kM = 1.0 for SI kM = 1.49 for BS

Page 159: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Normal depth solution procedure: (b) circular channels (d0 diameter)kM = 1.0 for SIkM = 1.49 for BS

Page 160: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed
Page 161: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Critical depth solution procedure: trapezoidal channels

Page 162: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Critical depth solution procedure: circular channels

Page 163: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Module  11    

Hydraulic  Machines  Problems  

Page 164: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINES

Problems

Dr. Walter F. Silva, UPRM

Page 165: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINES1) A centrifugal pump has a power of 20 hp and pumpst at the rate of 400 gpm producing a total dynamic head of 75 psi. What is the overall efficiency of the pump?

Answer:

• bhp = Pump horsepower

• = specific weight

• Q = pump discharge

• H = total dynamic head

• e = pump efficiency

Solving for e:

e = 0.88

From PE Principles and practice of engineering

𝑏ℎ𝑝 =𝛾𝑄𝐻

550 𝑒

𝑄 = 4001

448.8= 0.8913 𝑓𝑡3 𝑠

𝐻 = 75 𝑝𝑠𝑖 2.31 𝑓 𝑡 𝑝 𝑠𝑖 = 173.25 𝑓𝑡

20 ℎ𝑝 =62.4 𝑥 0.8913 𝑥 173.25

550 𝑒

Page 166: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINES

SOLUTION

Draw a Sketch:

Definition of power:

Apply Energy Equation between point 1 and 2:

Conversion of units:

Obtain velocities:

2) A discharge of 2000 gal/min of thickened sludge with a specific gravity of 1.2 and a temperature

of 600 F is pumped through a pump with an inlet diameter of 12 in and an outlet diameter of 8 in.

The centerlines of the inlet and the outlet are at the same elevation. The inlet pressure is 8 in of

mercury (vacuum). A discharge pressure gauge located 4 ft above the pump discharge centerline

reads 20 psig. The pump efficiency is 85%. All the pipes are schedule 40. How much is the pump

input power ?

Page 167: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINESSOLUTION

Convert manometer readings to pressure:

Convert vacuum pressure to absolute pressure:

Convert absolute pressure to pressure head:

Repeat the same for the outlet pressure:

Substitute pressures and velocities in the energy equation and solve for hp:

Convert to power:

(a) 26hp(b) 31 hp(c) 37 hp(d) 53 hp

Page 168: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

Solution

• Draw a sketch:

• Estimate minor losses:

• Write energy equation between inlet and outlet:

HYDRAULIC MACHINES3) A discharge of 1.25 ft3/s (35 l/s) of water at 700 F are pumped from the bottom of a tank

through 700 ft (230 m) of steel pipe schedule 40 with a nominal diameter of 4 in (10.2 cm). The

pipeline includes 50ft (15m) of rise elevation, two right angle elbows and one wide-open gate

valve. The working pressure at the end of the line must be close to 20 psig (140 kPa). How much

is the hydraulic power required for this system?

Page 169: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINES• Compute Reynolds number and relative roughness:

• Compute flow velocity:

• Go to Moody diagram to get friction factor:

• Compute total losses:

Page 170: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINES• Get elevation, pressure head and velocity head differences:

• Substitute in the energy equation and solve for pump head:

• Convert pump head in pump power:

Page 171: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINES6)

Page 172: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINES

The operating point is at Q = 190 gal/min, hA = 97 ft.

Page 173: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

• The friction factors must be checked. The velocities and Reynolds numbers are:

HYDRAULIC MACHINES

Page 174: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

• SOLUTION

b) Write the energy equation between upper tank and point B

• Solve for velocity iteratively assuming a value of fAB = 0.02 for the first iteration

HYDRAULIC MACHINES

1

Page 175: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

• SOLUTION

• Since assumed fAB = 0.02 and computed fAB = 0.0183 another

iteration is required:

• Therefore the answer is

• QB = 0.703 ft3/s = 315 gpm

HYDRAULIC MACHINES

Page 176: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINESComputation of NPSHA

7) A pump located 6 m above the sea level, has a NPSHr of 6.5 m at 1,600 lpmand is fed by a tank with water at 15oC pressurized at 20 kPa and with a liquid level of 4 m below the suction of the pump. The head losses in the suction pipeline is 1.5m and the losses in the other components (local losses) is 1.0 m. The discharge is 1,600 liters per minute. The schematic of Figure shows the pump suction. How much it the NPSH available?

Note: The NPSHA shouldBe calculated to ensure thatit EXCEEDS the NPSHR providedby the manufacturer to preventcavitation in the pump.

Page 177: URBANDRAINAGEDESIGNprltap.org/eng/wp-content/uploads/2015/02/Handout-2... · 2020. 8. 16. · Selection of Design Frequency and Design Spread cont. Design frequency for depressed

HYDRAULIC MACHINEShres + hatm = (20 + 101.3) x 1000/ (999x9.81) = 12.38 m

hz(s) = Zt – Zs = 2 – 6 = -4 m

Vapor pressure (15oC) = 1.7057 kPa hvp = 1705.7/(999x9.81) = 0.174 m

Head losses (given) = hf(s) = 1.5 + 1.0 = 2.5 m

NPSHA = 12.38 -4 – 0.174 –2.5 = 5.706 m

Pump is under risk of cavitation!