2

Click here to load reader

Updates to NSF/ANSI 58 Reverse Osmosis Drinking …archive.wcponline.com/pdf/V55N11 Water Matters.pdf · Frequent updates Although the NSF/ANSI DWTU Standards have been around for

Embed Size (px)

Citation preview

Page 1: Updates to NSF/ANSI 58 Reverse Osmosis Drinking …archive.wcponline.com/pdf/V55N11 Water Matters.pdf · Frequent updates Although the NSF/ANSI DWTU Standards have been around for

N o v e m b e r 2 0 1 3Water Conditioning & Purification

Water Matters

By Rick AndrewNSF/ANSI 58 Reverse Osmosis Drinking Water Treatment Systems is the American National Standard for POU RO systems. This

standard includes requirements addressing various aspects of these systems, including safety of materials in contact with drinking water, structural integrity, TDS reduction performance, efficiency rating, recovery rating, contaminant reduction performance and information for the end user. Like other NSF/ANSI Drinking Water Treatment Unit (DWTU) standards, it is subject to continuous improvement through a consensus process administered by NSF and guided by the NSF Joint Committee on Drinking Water Treatment Units. This committee uses a variety of tools, such as an online workspace, physical meetings and conference calls to conduct its mission to move forward with

development and adoption of new standards and updates to current standards to reflect

new regulatory requirements, technological advances and other changes. As a result of this continuous improvement process, NSF/ANSI-2012a was recently published and includes two revised requirements:

• Single-capacity claim• Sampling regime for days two through 4 of TDS reduction

and contaminant reduction testing

Single capacity claimThis change established that for any filter conforming to NSF/

ANSI 42, NSF/ANSI 53 and/or NSF/ANSI 58, the capacity cannot exceed the lowest capacity for any contaminant, regardless of the

Updates to NSF/ANSI 58 Reverse Osmosis

Drinking Water Treatment Systems

Test operation

Allow system to operate for four hours and empty product-water storage tank completely.

Allow system to fill completely, starting with empty product-water storage tank and ending with automatic shut-off valve turning off.

For TDS reduction testing, next is a partial fill of product-water storage tank, starting with tank partially full at the point where automatic shut-off valve turns on and ending with automatic shut-off valve turning off. The product water storage tank is then emptied again.

After 12 total hours of testing, empty product-water storage tank completely.

For TDS reduction testing, after 16 total hours of testing, empty product-water storage tank completely.

Operate normally

Stagnation

At the beginning of the day, empty product-water storage tank completely.

Allow system to operate for four hours and empty product-water storage tank completely.

For TDS reduction testing, next is a partial fill of product-water storage tank, starting with tank partially full at the point where automatic shut-off valve turns on and ending with automatic shut-off valve turning off. The product-water storage tank is then emptied again.

Sampling

Sample for TDS or contaminant concentration after four hours.

For TDS reduction testing, after the four-hour sample point, measure recovery based on empty tank, open faucet and amount of reject water compared to total volume of water entering system.

For TDS reduction testing, after the recovery measurement, measure daily production rate based on total amount of product water and total amount of time for both operation modes (complete fill of product-water storage tank and partial fill of product-water storage tank).

For TDS reduction testing, while measuring daily production rate, measure efficiency based on total amount of product water and total amount of reject water for both operation modes.

Sample for TDS or contaminant concentration after 12 hours.

For TDS reduction testing, sample for TDS concentration after 16 hours.

Collect five percent of daily production rate at beginning of the day, after six hours and after 12 hours and analyze for TDS or contaminant concentration.

None

Sample for TDS or contaminant reduction at the beginning of the day.

Sample for TDS or contaminant concentration after four hours.

For TDS reduction testing, after the four-hour sample point, measure recovery based on empty tank, open faucet and amount of reject water compared to total volume of water entering system.

For TDS reduction testing, after the recovery measurement, measure daily production rate based on total amount of product water and total amount of time for both operation modes (complete fill of product water storage tank, and partial fill of product-water storage tank).

For TDS reduction testing, while measuring daily production rate, measure efficiency based on total amount of product water and total amount of reject water for both operation modes.

Day of test

1 2 – 4

5 and 6

7

Figure 1. Test operation and sampling regime: TDS and contaminant reduction tests—POU RO systems with storage tank and automatic shut-off valves

Page 2: Updates to NSF/ANSI 58 Reverse Osmosis Drinking …archive.wcponline.com/pdf/V55N11 Water Matters.pdf · Frequent updates Although the NSF/ANSI DWTU Standards have been around for

N o v e m b e r 2 0 1 3Water Conditioning & Purification

standard. For example, a filter certified for 500-gallon capacity for lead reduction under NSF/ANSI 53 could not have a claimed 2,000-gallon capacity for chlorine reduction under NSF/ANSI 42, even though the filter might be capable of reducing chlorine for 2,000 gallons. This change was a clarification to what had been a long-standing interpretation that was not clearly documented in the standards. It is relevant to NSF/ANSI 58 because activated carbon post-filters can have claims for VOC reduction under this standard. For a more in-depth discussion regarding the single-capacity claim issue, please see October 2013 Water Matters.

Sampling regime: days two through fourThe following discussion relates specifically to POU RO

systems with storage tanks and automatic shut-off valves, which is by far the most prevalent product configuration. There are some variations in the test protocol for systems without storage tanks and/or without automatic shut-off valves, the most significant being systems that cannot claim an efficiency rating.

TDS reduction and membrane-based contaminant reduction tests in NSF/ANSI 58 feature testing conducted according to a seven-day protocol. Days one and seven involve sampling under two conditions: first, complete product-water storage tank fills and second, minimal partial tank fills, to assess performance under these varying conditions. For TDS reduction testing, days one and seven also involve measurement of the daily production rate, efficiency rating and recovery rating of the system. Days five and six of the test involve a stagnation period, in which no samples are taken and no product water is withdrawn from the storage tank. This leaves days two through four.

Previously, the standard had indicated that samples were to be collected every six hours on days two through four. Every other test under the NSF/ANSI DWTU Standards, however, involves a 16-hour daily test operation. This means that a laboratory would need to operate an additional two hours per day to perform all of the required sampling on days two through four when testing POU RO systems. This additional laboratory operation requirement for POU RO samples only would lead to increased costs for testing these systems.

In practice, several laboratories performing this type of testing were already interpreting that samples on days two

through four are collected at the beginning the day, after six hours of operation and after 12 hours of operation. This interpretation helped keep testing costs in check and also resulted in an operational regime that was nearly identical to the literal interpretation of the standard language.

So, the NSF Joint Committee on Drinking Water Treatments reviewed the situation and ultimately decided to revise the standard language describing the test method to be officially in line with how these several laboratories were already interpreting the standard. NSF/ANSI 58-2012a requires that on days two through four, samples are collected at the beginning of the day, after six hours of operation and after 12 hours of operation. A summary of the operations and sample collection regime for these tests is included in Figure 1.

Frequent updatesAlthough the NSF/ANSI DWTU Standards have been around

for many years, they are continually being updated. Keeping up to date is important for manufacturers who claim conformance to these standards, especially if they hold certifications. Although many changes to the standards are relatively minor and don’t require retesting to establish continued conformance (such as the changes described here), occasionally there are significant changes that can require retesting and even product modifications. One important tool to help keep track of these changes is the Foreword of each standard. This section, included after the Table of Contents, includes a summary of all changes included in the current edition of the standard. It is recommended to check the Foreword each time there is a new edition of the standard to quickly assess the changes in that edition.

About the author S Rick Andrew is NSF’s Director of Global Busi-ness Development–Water Systems. Previously, he served as General Manager of NSF’s Drinking Water Treatment Units (POU/POE), ERS (Protocols) and Biosafety Cabinetry Programs. Andrew has a Bachelor’s Degree in chemistry and an MBA from the University of Michigan. He can be reached at (800) NSF-MARK or email: [email protected]