UCL ESTATES Fire Safety ___________________________________________________________________________________________________________________________ Date Last Amended: Jul 18 EP: 1 of 7. Issued by: Fire Safety Manager, Safety Services, UCL Estates, Gower Street, London WC1E 6BT / [email protected] UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 1 - 19 TORRINGTON PLACE University College London 1-19 Torrington Place, London, WC1E 7HB Contents 1. Introduction ........................................................................................................................................................................... 1 2. General Building Description .............................................................................................................................................. 2 3. Means of Escape (MoE) ...................................................................................................................................................... 2 4. Instruction to Building Occupants ..................................................................................................................................... 4 5. Emergency Disabled Evacuation Provisions .................................................................................................................... 5 6. Centrally Timetabled Space - Disabled Access Provisions ........................................................................................... 6 7. Specific Evacuation Instructions ........................................................................................................................................ 7 8. Fire Alarm (specific Information) ........................................................................................................................................ 8 9. Fire Extinguishers .................................................................................................................................................................... 8 10. Other Information ................................................................................................................................................................. 8 INTRODUCTION NOTES This document provides information that you need to know in order to use your building safely whilst complying with UCL policy and fire safety legislation. Each UCL building has been given a risk rating, and this dictates how often fire safety reviews take place, as well as how often departmental staff and fire evacuation marshals should receive full fire safety training. UCL Departments must ensure that: all new staff are provided with adequate induction training; this training is refreshed periodically (depending on the fire risk rating below); fire evacuation marshals (FEM) are appointed for each floor of the building; fire evacuation marshals are suitably trained, including refresher trained periodically (depending on the fire risk rating); departmental areas and the risks contained therein are managed safely; appropriate arrangements are in place to ensure the safe evacuation of disabled people; Fire Safety Reviews - UCL Fire Safety Team will periodically carry out fire risk assessments and fire safety reviews. The period in which these reviews will take place will be dictated by the determined risk category of the building. Fire Drill - UCL will deliver drills on a risk-based programme. Fire drills are incorporated into the fire risk assessment programme to create a fire safety package at each building on a risk-based frequency. A full fire evacuation rehearsal will be carried out at a frequency determined by the Building Category 1. Introduction This short guide provides basic fire safety information for occupants and visitors at the 1-19 Torrington Place.

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

UCL ESTATES Fire Safety

___________________________________________________________________________________________________________________________ Date Last Amended: Jul 18 EP: 1 of 7.

Issued by: Fire Safety Manager, Safety Services, UCL Estates, Gower Street, London WC1E 6BT / [email protected]

UNIVERSITY COLLEGE LONDON

PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005

1 - 19 TORRINGTON PLACE University College London

1-19 Torrington Place, London, WC1E 7HB Contents 1. Introduction ........................................................................................................................................................................... 1 2. General Building Description .............................................................................................................................................. 2 3. Means of Escape (MoE) ...................................................................................................................................................... 2 4. Instruction to Building Occupants ..................................................................................................................................... 4 5. Emergency Disabled Evacuation Provisions .................................................................................................................... 5 6. Centrally Timetabled Space - Disabled Access Provisions ........................................................................................... 6 7. Specific Evacuation Instructions ........................................................................................................................................ 7 8. Fire Alarm (specific Information) ........................................................................................................................................ 8 9. Fire Extinguishers .................................................................................................................................................................... 8 10. Other Information ................................................................................................................................................................. 8

INTRODUCTION NOTES

This document provides information that you need to know in order to use your building safely whilst complying with UCL policy and fire safety legislation. Each UCL building has been given a risk rating, and this dictates how often fire safety reviews take place, as well as how often departmental staff and fire evacuation marshals should receive full fire safety training.

UCL Departments must ensure that:

all new staff are provided with adequate induction training;

this training is refreshed periodically (depending on the fire risk rating below);

fire evacuation marshals (FEM) are appointed for each floor of the building;

fire evacuation marshals are suitably trained, including refresher trained periodically (depending on the fire risk rating);

departmental areas and the risks contained therein are managed safely;

appropriate arrangements are in place to ensure the safe evacuation of disabled people;

Fire Safety Reviews - UCL Fire Safety Team will periodically carry out fire risk assessments and fire safety reviews. The period in which these reviews will take place will be dictated by the determined risk category of the building.

Fire Drill - UCL will deliver drills on a risk-based programme. Fire drills are incorporated into the fire risk assessment programme to create a fire safety package at each building on a risk-based frequency. A full fire evacuation rehearsal will be carried out at a frequency determined by the Building Category

1. Introduction This short guide provides basic fire safety information for occupants and visitors at the 1-19 Torrington Place.

Page 2: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) ___________________________________________________________________________________________________________________________

___________________________________________________________________________________________________________________________ Date Last Amended: Jul 18 EP: 2 of 8.

Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / [email protected]

2. General Building Description Completed in 1960 by Mullard Ltd which used 1-19 Torrington as their company headquarters before being bought out by the Dutch Philips Electronics company and becoming Philips UK headquarters. The name was then changed to Philips House; UCL purchased the building in the late 1990s.

The premises comprises of an ‘L’ shaped building with a eleven story tower running west / east along Torrington Place and ground to sixth floor west wing running north / south along Tottenham Court Road. The building is approximately 35m high, has a 2-storey podium to the front with a 10-storey block to the rear. It has a subbasement, basement, ground, levels 1 – 10, 11th floor plant room and roof. New teaching space has been created at the basement and ground levels and associated refurbished reception, entrance and facilities in 2018.

For fire safety purposes 1 - 19 Torrington Place (Bldg: 086) and 188 Tottenham Court Road (Bldg: 363) except for retail shops at ground & lower ground levels are a single building, with interconnecting fire alarm systems. A separate fire premises handbook is provided for 188 TCR. The shops have separate emergency evacuation arrangements to the UCL demise, but have a right of escape from lower ground level through the rear car park of 1-19 TP and out to the street.

1 - 19 Torrington Place (1-19TP) - is formed of the Main Tower (East Wing) comprising of ground & 11 storeys with lower ground floor and sub-basement area. The West Wing is formed over the shops on Tottenham Court Road between first floor & fifth floors attached at upper levels to the main east tower. There is escape to ground level but no separate building access to the west wing except through the main tower (east wing).

188 Tottenham Court Road (TCR) - forms the basement of the west wing with the ground level/lower ground floors occupied by shops & businesses except for the small UCL entrance to sub-basement located at 188 TCR, which has its own separate Fire Strategy (Bldg: 363).

General arrangement plans are attached including the Fire Assembly Point location

3. Means of Escape (MoE) Teaching Space Ground Floor:

o teaching space occupants can escape through main entrance and reception and out to street level;

o additionally, teaching space users can escape into the west lift lobby merging with occupants escaping from upper floors through Stair A and out through triple escape doors to street level;

o Note - the east stair (Stair B) occupants do not escape through the Reception and main entrance but continue to lower ground level and leave via doors to the rear of the building and travel further up the east vehicle ramp to street level;

Page 3: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) ___________________________________________________________________________________________________________________________

___________________________________________________________________________________________________________________________ Date Last Amended: Jul 18 EP: 3 of 8.

Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / [email protected]

Teaching Space Basement / Lower Ground Level: o teaching space users escape through the east stair lift lobby (Stair B)

and leave via doors to the rear of the building and travel further up the east vehicle ramp to street level;

o additionally, teaching space users can escape through central escape doors and cross bridge to the rear of the building and continue traveling up the east vehicle ramp to street level;

East (Main) Tower - the means of escape from each floor is served by two x stair enclosures at each end of building, with access to either stair. These stairs are not discounted for escape purposes, as they are provide 2 x fire doors forming a fire and smoke lobby of 60 minutes protection;

o Stair A (West Stair) - discharges into west lift lobby and out to street level via;

o Stair B (East Stair) - fire escape exit is at lower ground floor into rear courtyard and travel further out via the east vehicle ramp to street level;

o Note - these fire & smoke lobbies are to remain sterile with no storage permitted.

West Wing - the means of escape from each floor is served by two x stair enclosures at each end of the wing and the central exit leading into East Tower and Stair A;

o Stair N (West Wing North Stair) - fire escape discharges at lower ground level into rear courtyard with travel further out via the east (or West) vehicle ramp to street level;

o Stair R (West Wing South Stair) - discharges at street level onto Torrington Place, adjacent to the west vehicle ramp;

o Stair S (No Escape) - central accommodation stair only;

3.1. Other Information: You should receive local fire safety familiarisation from your department,

walking you through the fire escape routes from the building;

Fire Risk Assessment and staff training schedules for 1-19 Torrington Place;

BASE FRACategory 2 Initial FRA

Training (Dept.)

Staff (eLearning)FEMs (eLearning)

Toolbox TalkFEMs

TYPE 3 FRACategory 2

Every 3rd Year

Training (Dept.)

Staff (eLearning)FEMs (eLearning)

Toolbox TalkFEMs

Fire DrillType 1 Review

FEM Toolbox Talk

Fire DrillType 1 Review

FEM Toolbox Talk

Fire Risk Assessment (FRA) Category 2 Risk Building - Action Time Line

Fire DrillType 1 Review

FEM Toolbox Talk

Base FRA = initial FRA &Building Inspection / Type 1 = fire safety walk round likely to be completed in conjunction with Fire Drill / Type 2 = Intermediate Inspection & Review completed midway through review period / Type 3 = a full FRA Inspection & Review of the premises;

Category 1 = reviewed every 4 years / Category 2 = reviewed every 3 years / Category 3 = reviewed every 2 years (see TN075 for details)

TYPE 2 FRA( Midway Year 2)

~~~~~~Head of

Department to Undertake TN077

Review

Year 1.

Year 2.

Year 3.

Page 4: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) ___________________________________________________________________________________________________________________________

___________________________________________________________________________________________________________________________ Date Last Amended: Jul 18 EP: 4 of 8.

Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / [email protected]

4. Instruction to Building Occupants

Relevant Information

Building Fire Risk Rating: Category 2 Risk.

Fire Risk Assessment (risk rating timeline):

Fire Risk Assessment in this building will be undertaken every 3 years

(subject to building changes or alterations)

Fire Risk Assessment (FRA) Reviews:

The UCL Fire Safety Team will conduct a building review prior to the annual fire drills. A comprehensive fire risk assessment audit inspection will be carried out in the interim between the defined risk assessment periods as follows: for Cat 3 risk buildings – 1 year following main FRA; for Cat 2 risk buildings – every 1/½ years following main FRA; for Cat 1 risk buildings – every 2 years following main FRA;

Department Fire Risk Review (iaw TN077 & TN077A):

Departments - review periodically (but at least annually or more frequently if higher risk) and keep completed copies locally for fire brigade inspection; FEMs or other designated persons conduct building inspections iaw TN77a and Department Managers should update records iaw TN077.

Staff Training (TN086):

New Staff Induction – within 3 days upon arrival carry out full walk of building, escape routes. The new arrival must then complete ‘Basic Fire Safety’ eLearning on Moodle. Refresher - full training as per induction to be completed by all staff / contractors within periods determined by the risk rating time line indicated above for this building (every 3 Years).

FEM Training (TN099):

Minimum number of trained FEMs per floor & wing in this building is: Four (4)

New / Initial FEM training - completed through eLearning on Moodle.

Refresher - the FEM refresher period is determined by the risk rating timeline, indicated above, for this building. (Additional refresher training will be delivered by means of Toolbox Talks to

FEMs annually, following the fire evacuation drill)

Fire Drill: Fire drills are incorporated into the fire risk assessment programme to create a fire safety package at each building on a risk-based frequency.

Persons with Disabilities:

Department to provide PEEPs and specific arrangements (see details below)

Other Information: None

Page 5: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) ___________________________________________________________________________________________________________________________

___________________________________________________________________________________________________________________________ Date Last Amended: Jul 18 EP: 5 of 8.

Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / [email protected]

5. Emergency Disabled Evacuation Provisions

Relevant

Information

Mobility Impaired Persons (MIP) or Persons with Disabilities:

Department’s local management arrangements and fire evacuation strategy for MIP and disabled persons should not rely solely on the Fire & Rescue Service, rescuing people waiting in refuges, but for the Department to have satisfactory arrangements in place to assist persons from the building to a place of permanent safety.

Personal Emergency Evacuation Plan (PEEP)

Managers should develop Personal Emergency Evacuation Plans (PEEPs) for all MIP or staff and students with disabilities under their responsibility. PEEPs should be conducted for all areas that persons with disabilities are likely to visit and should be completed iaw the instructions provided on RiskNET under the section ‘Risk Assessments’ > Personal Emergency Evacuation Plans. Further information is also available from www.ucl.ac.uk/fire/documents under ‘Disabled Staff and Student Guidance’

Disabled Refuge Facilities: (Generally, only provided on individual Risk Assessment or as part of a PEEP initiated by the Department):

Some UCL buildings have refuge areas, which are surrounded by fire-resisting construction. These are to be considered as temporary waiting areas only. Disabled people should never be left in the building, as departments must always have sufficient procedures in place to evacuate disabled persons. The refuge may be used as a safe place for a less ambulant person to wait for everyone else to leave, before making their way down the stairs (with assistance if necessary) at their own pace.

Disabled Refuge Communications Facilities: (Communication for disabled refuges have BT big button phone or system complying BS5839-9):

(1). Local communications by phone or talk box with specific building instructions and numbers to call; (2). Mobile Users should call the UCL Security Control Room (available 24/7) who can arrange help and assistance on:

020 7679 2222 (Ext: 222) Alternative Number (24/7) - 020 7387 5256; UCL Security Ops (24/7) - 020 7679 2108 (Ext: 32108);

Disabled Evacuation Lift: None – progressive horizontal evacuation available

Deaf Persons Fire Alarm Alerting Facilities (Change to alerting facilities for hearing impaired people):

Deaf Messaging System (DMS) (see UCL Fire Safety Tech Note TN 007) - a DMS is provided and connected to the fire alarm system to send out a text message upon fire alarm activation to those who have opted into the service. Blue information stickers at the entrance to the building provide the text information and instructions;

DMS Ref text 1-19TPDMS30

General Emergency Evacuation Plan (GEEP):

The building is provided with fire safe lobbies to each stair - which will provide time for arrangements to be made for others to assist. The person you are visiting will take you to the refuge, which is within the evacuation stairway at each level of the building and ensure that FEM s or others are informed that a refuges is being used. If you are able, make you own way down the stairs in your own time, once all other occupants have passed you.

Other Information:

Refuges - safe refuges are provided on the landings or within the stair enclosure of first to tenth floors, west stair (Stair A);

Page 6: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) ___________________________________________________________________________________________________________________________

___________________________________________________________________________________________________________________________ Date Last Amended: Jul 18 EP: 6 of 8.

Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / [email protected]

6. Centrally Timetabled Space - Disabled Access Provisions

Centrally Timetabled Lecture Theatres & Seminar Rooms - Mobility Impaired Persons (Wheelchair) Emergency Egress Facilities /

Arrangements

Lecture Theatre / Seminar Room

Locations

Accessible / Egress

Evacuation Arrangements (None1 / Limited2 / Accessible3)

Seminar Rm 433 (West Wing 4th

Floor) Limited

Access via staff entrance (west) ramp to entrance lobby and up to 4th floor via staff lifts along west wing corridor to seminar room, some assistance may be required.

Emergency Egress - progress to west end lobby or move into main stair landing once occupants have all passed, which provided up to two hours of fire protection from floors.

Galton L/T Room 115 (1st Floor) None Lecture Theatre is not wheelchair accessible

Computer Cluster Room 113 (1st Floor)

Limited

Access via staff entrance (west ramp) and ground floor corridor (Note a number of doors in corridor some need to be kept shut and assistance may be required).

Emergency Egress - progress to west end lobby or move into main stair landing once occupants have all passed, which provided up to two hours of fire protection from floors.

Ground Floor Lecture Theatres & Seminar Rooms - G08, G09, G10, G12, G13 & G20

Accessible

Access via main entrance lift or staff entrance (west ramp) via link corridor (Note a number of doors in corridor some need to be kept shut and assistance may be required).

Emergency Egress - move to main entrance staff entrance or at the west end - and self-evacuate through disabled doors to lift or ramp to Torrington Place.

Basement (Lower Ground Floor)

Lecture Theatres & Seminar Rooms - B07, B08, B09, B17

& B20

Accessible

Access via main entrance lift or staff entrance (west ramp) via link corridor (Note a number of doors in corridor some need to be kept shut and assistance may be required) and use lift to descend to lower ground level.

Emergency Egress - progress to central exit from corridor or base east stairs (Stair B) or to side fire exit from B17 lecture theatre and move into the rear car park / service yard.

From rear carpark / service yard, egress to street level is via principally the east vehicle ramp (west may be used if available) - assistance will be required reach street level due to the steep incline of the ramps. However, the carpark and service yard may present a temporary safe (refuge area) location initially as out of the building.

1 None - No MIP (specifically wheelchair) Access or Egress available due to location, steps or lifts; 2 Limited - Emergency egress requires management & other assistance, should be planned & written up on PEEP; 3 Accessible - MIP Access and Egress available without general assistance as generally facility where practical to self-escape;

Page 7: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) ___________________________________________________________________________________________________________________________

___________________________________________________________________________________________________________________________ Date Last Amended: Jul 18 EP: 7 of 8.

Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / [email protected]

7. Specific Evacuation Instructions

Local fire information:

Fire Action Notices (and in some premises, additional supplementary instructions) located throughout the premises at fire points and within residential sleeping accommodation rooms provide the local fire Emergency Plan and you should be aware of their contents.

Action on discovering a

fire:

On discovery or being made aware of a fire, immediately raise the alarm to give warning throughout the building by operating the nearest fire alarm manual call point (red).

On hearing the fire alarm:

On hearing the fire alarm, leave the building immediately by the nearest available fire exit (this may not necessarily be the way you entered the building).

The fire alarm system:

(1). This building is equipped with a single stage addressable fire alarm system. Which when activated, emits a continuous warning throughout the building. (2). Automatic Fire Detection (AFD) – smoke & heat detecting devices are provided for early warning of fire to aid faster escape. (3). Manual Call Points (MCPs) - means for raising the fire alarm in addition to fire detection is by operating MCPs that may be found on routes leading from the building (including corridors, landings, staircases & final exits).

Calling the fire brigade:

Dial Ext: 222 (020-7679-2222) on a UCL Internal Extension and report the fire (use the Building Reference number to assist in identifying the premises or the address shown on the UCL Fire Action Notices). This building’s fire alarm system is monitored on a 24-hour basis who will summon the Fire Brigade. However, you should always make an Emergency Telephone call (Ext: ‘222’) to raise the alarm.

Evacuation procedure

and using lifts during fire:

On hearing the alarm or being directed by a Fire Evacuation Marshal (FEM), occupants are to evacuate the building by the nearest available escape stair, corridor or exit route to the Final Exit from the building. If your escape route is blocked / obstructed by fire or smoke, you should turn your back on the fire and follow the alternative route from the building by following the green fire escape directional signage provided.

Lifts should not be used in the event of the fire alarm sounding.

Fire Assembly Point:

On leaving the building you should proceed to the Fire Assembly Point; the location of the Fire Assembly Point(s) is indicated on the local Fire Action Notices provided, which may also be supplemented with additional information such as local escape route plans etc. Do not obstruct the building entrances as this may hinder access to the fire brigade crews & appliances.

Beware of the road traffic and your and others safety during the evacuation!

Electronic security door

release mechanisms

see TN002 and TN004:

Where fitted doors forming part of the Means of Escape (MoE) may be provided with Electromagnetic Security Locks (Gallagher): (1). Generally, locks release on activation of the fire alarm system (but there are some specialist exceptions to this requirement); (2). Each door in direction of escape is provided with an independent ‘break glass’ emergency release device (green box) that may be activated to release the door in an emergency.

Page 8: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) ___________________________________________________________________________________________________________________________

___________________________________________________________________________________________________________________________ Date Last Amended: Jul 18 EP: 8 of 8.

Issued by: Fire Safety Manager, UCL Estates, Gower Street, London WC1E 6BT / [email protected]

8. Fire Alarm (Specific Information) Call points - fire alarm ‘manual call points’ are found in routes leading from

the building (including corridors, landings, staircases & final exits), to raise the alarm manually;

Sounders - fire alarm sounders are formed a two tone electronic sounders;

Weekly testing of the fire alarm – see www.ucl.ac.uk/fire/documents TN062; Lifts, ground on activation of the fire alarm;

9. Fire Extinguishers Extinguishers;

o 6 x Litre multi-purpose Water Mist extinguishers (lower ground floors) ;

o 2 x fire hose reels provided on upper floors in cupboards;

o 1 x 2 Kg carbon dioxide (CO2) extinguishers adjacent to hose reels;

o Additionally, extinguishers provided at other high risk activities;

Fire Blankets - are provided in kitchens and tea points;

See www.ucl.ac.uk/fire/documents TN027A, TN028, TN031 & TN035;

10. Other Information (a). Location and Provision of Lockers (Circulation Areas) - stairs and some

corridors are to remain free of any storage including lockers.

See www.ucl.ac.uk/fire/documents TN070;

(b). Kitchens and Tea Points: Management of unwanted alarms and fire risks - please see TN105A

on the definition of kitchens, tea points, what equipment and activities is permitted within them.

See www.ucl.ac.uk/fire/documents TN105a;

Take every opportunity to familiarises yourself with the building and the fire arrangements

Page 9: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Issued by: the Fire Safety Manager, Safety Service, UCL Estates, Gower Street, London, WC1E 6BT / [email protected]

Fire Action 1 - 19 Torrington Place &

188 Tottenham Court Road

On discovering a fire - operate the nearest fire alarm call point.

Dial extension '222' on a UCL internal telephone giving the building name and this FIRE ZONE Number – 086 & 363

Only attempt to fight the fire, if it is safe and practical to do so – always read the multi-purpose fire extinguisher instructions prior to tackling the fire incident.

Water Mist Extinguishers are safe to use on Electrical and Flammable Liquid fires

On hearing the fire alarm - leave the building by the nearest AVAILABLE FIRE EXIT.

CLOSE - all doors and windows as you leave.

Do NOT - stop to collect belongings.

Do NOT - use the lift.

Do NOT - re enter the building until instructed to do so by the Senior Fire Officer present.

When clear of the building - proceed to your designated FIRE ASSEMBLY POINT at:

Huntley Street

or

Tottenham Court Road

Page 10: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

__________________________________________________________________________________________________________ Issued by: Fire Safety Manager, Safety Services, UCL Estates, Gower Street, London, WC1E 6BT / [email protected]

Fire Action 1 - 19 Torrington Place &

188 Tottenham Court RoadTorrington Place

Additional Fire Action Instructions: The fire alarm warning in this building is an electronic alarm with a distinctive:

'TWO TONE' Signal This warning denotes that you are to evacuate the premises immediately by the nearest available exit, on leaving the building proceed directly to a Fire Assembly Point.

Do not use the lifts, Do not congregate by the main building entrances, Do not obstruct the road or pavements,

TO

TT

EN

HA

M C

OU

RT

RO

AD

HU

NT

LE

Y S

TR

EE

T UCL: 1-19 Torrington

Place

TORRINGTON PLACE

QUEENS YARD

CAPPER STREET Fire Assembly

Points:

Huntley Street Tottenham Court

Road UCL 188

TCR

Page 11: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

FIRE ALARM INFORMATION

_____________________________________________________________________________________________________________ Issued by the: Dec 17

Fire Safety Manager, Safety Services, UCL Estates, Gower Street, London, WC1E 6BT / Email: [email protected]

Deaf MessagingService

(Fire Alert)

at 1-19 Torrington Place &

188 Tottenham Court Road

DEAF TEXT MESSAGING SERVICE INSTALLED

in this building

To connect to the Fire Alarm Activation Deaf Messaging Service for

1-19 Torrington Pl & 188 TCR

TEXT this Location: 1-19TPDMS30

To: 07797 - 870999

Page 12: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:
Page 13: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:
Page 14: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:
Page 15: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

StairQ

Q

TORRINGTON PLACE

FIREEXIT

StairF

StairH

H

StairD

D

StairO

O

StairP

P

B1

StairB1

Openings with roller shutters(60 minutes fire resistance

operated by fusible link)

Main access to this area isfrom 188 Tottenham Court

Road

MAIN RISERDRAIN VALVE

Computer Suite &Plant Room coveredby Gas Suppression

System

StairE

E

CompressedGas Cylinders

FIRE ALARMPANELS - GASSUPPRESSION

SYSTEM

MainElectricIntake

FIRE ALARMPANELS - GASSUPPRESSION

SYSTEM

SB8

SB84AREA

SB84A

SB7WC

SB6STORE A

SB3PLANTROOM

SB4PLANTROOM

SB83STAIR 3

SB15PLANTROOM

SB1SWITCHGEAR

ROOM

SB16DATA CENTRE

SB14LIFTPIT

SB77

SB89

SB95

SB1MEETING ROOM 1

SB2MEETING ROOM 2

SB3MEETING ROOM 3

SB4MEETING ROOM 4

SB5MEETING ROOM 5

SB1ABEVERAGE

ROOM

SB4ASTORE 3

SB89

CIRCULATION

AREA

SB

82

CO

RR

IDO

R

SB90STAIRLOBBY

SB8MALEWC

SB9FEMALE

WC

SB90ALIFT

SB7PUMPROOM

SB6DIS. WC

SB88

SB

88B

SB88A

SB89A

SB1BSB1C SB81

ST

AIR

1

SB

9A

STAIR 6

BU

LK

HE

AD

OV

ER

UP

STAIR 2

PR

ES

SU

RE

VA

LV

E

SB3A

SB13MMR

SB5CONTROL

ROOM

SB94LOBBY

SB93SOUTH CORRIDOR/

STORAGE AREA

SB80HYPOXIC

PLANTROOM

SB2FREEZER

STORE

SB99LOADING BAY

SB81NORTH

PLANT ROOM

SB20UPS A

SB10TP 1 DATA HALL

SB12BUILDROOM

SB11TP3 DATA HALL

SB18POD 3.1

SB78NE LOBBY

SB85NE SERVICE

CORRIDOR

SB87SE SERVICECORRIDOR

SB90CENTRAL

DC

CORRIDOR

SB97SB96

SB88SB92

SB82NON-

ESSENTIALPLANTROOM

SB19UPS B

SB91CENTRAL

DC

CORRIDOR

SB86SERVICE

CORRIDORS

SB79

Ju

nct

ion

Box

SB17POD 4.1

UP

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

SUB BASEMENT

Fire Safety & Fire Brigade Contingency Plans

086-04-1

Drawn: S.H. Rev: S.H. May 2018Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Rev. Date Description

Page 16: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Bldg. No. 363,188 Tottenham

Court Road

TO

TT

EN

HA

MC

OU

RT

RO

AD

StairK

StairL

StairM

L

M

K

StairN

N

StairI

StairJ

J

I

StairF

F

StairH

H

H

StairO

FIREEXIT

WATERISOLATION

W

Water inletmain forsprinklersystem &

valve

PLENUMCHAMBER

Main sprinklerstop valve forBasement &

Garage

FIREEXIT

FIREEXIT

FIREEXIT

FIREEXIT

FIREEXIT

StairP

P

FIREEXIT

T

StairT

TORRINGTON PLACE

FIREEXIT

StairQ

Q

FIREEXITFIRE

EXIT

FIREEXIT

StairB

StairB1

B

StairD

D

Mobile phone mast cabineton roof control - High

Voltage

GASISOLATION

Openings with roller shutters(60 minutes fire resistance

operated by fusible link)

StairC

StairE

E

C

WATERISOLATION

GASISOLATION

B02MALE WC

B03MJN

MAINTENANCEROOM

B03A

B68

B01FEMALE

WC

B22CSTORE

B19STRONG ROOM B22D

STORE

B22BSTORE

B22

B22ASTORE

B67B89

PLANT ROOM

B94LIFT

LOBBYB93

LIFTS

B92

B95CORRIDOR

B09CLASSROOM(62 persons)

B69

B97GOODS

LIFT

RAMP

B04OFFICE

B20SERVER ROOM

B11ANCILLARY ROOM

B08CLASSROOM(56 persons)

B85CORRIDOR

B17LECTURE THEATRE

B87

B05D

B91

B17B B17C

B98LIFTS

B15UKPN

B14UKPN

B18STORE ROOM CB76

B12

DISABLEDWC

B13FEMALE

WC

B90CORRIDOR

B07TEAL CLASSROOM

(34 persons)

B55PUBLIC HOUSE

B54SHOP

B53SHOP

B52SHOP

B51CAFE

AREA

Vehicle barrier protection

Vehicle barrier protection

Steel

access

stair

B66TP3 CHILLERCOMPOUND

B75

B70PLANTROOM

B71

B63POWER CENTRE

Substation Level (Lower)Generator Level (Upper)

B65SWITCH ROOM

B9

6C

lnr

Cpd

B05PLANT ROOM

B21CLASSROOM(16 persons)

B16LECTURE

THEATRE STORE

B91B

B22E

O

B1SEMINAR ROOM

B90LIFT

B1APlantRoom

ExistingVoid

BUILDING363

Disabled ExitDisabled Exit

VehicleAccessRamp(1)

VehicleAccessRamp(2)

W

StairW

FIREEXIT

FIREEXIT

FIREEXIT

FIREEXIT

FIREEXIT

CVVOID

I O

IO

IO

IO

CVVOID

I O

CVVOID

FireFighting

Lift

DRYRISER

B72STAND BY

GENERATORROOM

B74HV

TRANSFORMER

B73LV

SWITCHROOM

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

BASEMENT

Fire Safety & Fire Brigade Contingency Plans

086-04-2

Drawn: S.H. Rev: S.H. June 2018Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Rev. Date Description

I O

Page 17: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

G69PUBLIC HOUSE

TORRINGTON PLACE

StairR

StairF

F

R

StairS

StairI

StairJ

J

I

StairK

StairL

StairM

L

M

K

NO ESCAPE TOGROUND FLOOR

VIA STAIR 'S' -(Accommodation

Stair Only)

NOESCAPE

S

StairN

N

StairH

H

ENTRANCEBldg. No. 363,188 Tottenham

Court Road

FIREEXIT

FIREEXIT

FIREEXIT

AHU ExtractionPanel

Slave FireAlarm Panel

Roller Shutter

Fireman'sover-rideswitch for

Lifts

DRY RISER INLET

StairE

FIREEXIT

StairA

StairC

StairB

C

Gate & turnstilesrelease on activation

of fire alarm

MASTER FIREALARM PANEL

FIREEXIT

B

StairT

Zone 99 - NetworkFire Alarm Panel

No: 1

Pavement Smoke Vents Pavement Smoke Vents Pavement Smoke Vents Pavement Smoke Vents Pavement Smoke VentsPavement Smoke Vents

Pavement Smoke VentsPavement Smoke Vents

FIRE ALARMREPEATER

PANEL

G65CAFE

G66CAFE

G67SHOP

G68SHOP

G69PUBLIC HOUSE

RAMP

G78

G77

BUILDING363

188 TOTTENHAM CRT RD

TO

TT

EN

HA

MC

OU

RT

RO

AD

G63POWER CENTRE

G64STAIRS

G04

G02A

G01

G93A

G93STAFF

ENTRANCE

G05

G85A

G88

G45

G110C

G89LIFTS

G21ASTORE

G21B

Lifts Lifts

Lift

FIRECONTROL

LIFT

RAMP

SHUTTER

BARRIER

G06MALE WC

G07FEMALE WC

G85

G02Multifunctional

Room

G84

G08CLASSROOM(18 persons)

G09CLASSROOM(18 persons)

G10CLASSROOM(20 persons) G10A

G91

G80

G10BRISER

ACC. WC

G97UNISEX

WCLOBBY

G82MAIN HALLWAY

G13LECTURE THEATRE

(120 persons)

G81MAIN

ENTRANCE

G11RECEPTION

G20FLEXIBLE

CLASSROOM(18 persons)

A

T

FIRECONTROL

LIFT

G12LECTURE THEATRE

(120 persons)

MASTEREMERGENCY

LIGHTING PANEL

VehicleAccessRamp(1)

VehicleAccessRamp

(2)

NOTE!Stair B Fire EscapeRoute is down to

basement and out &not through Main

Entrance

B

FIREEXIT

FIREEXIT

StairW

W

Exit Sign todirect occupants

to final exit

IO

IO

IO

IO

IO

IO

IO

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

GROUND FLOOR

Fire Safety & Fire Brigade Contingency Plans

086-04-3

Drawn: S.H. Rev: S.H. Jan. 2018Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Rev. Date Description

I O

Page 18: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

140OFFICE

141OFFICE

164

139OFFICE 142

OFFICE

138OFFICE 143

OFFICE

137OFFICE 144

OFFICE

165 145OFFICE

136OFFICE

135OFFICE

146COMMON

ROOM

134OFFICE

133OFFICE

132OFFICE

129OFFICE

128OFFICE

127OFFICE

126OFFICE

125OFFICE

124OFFICE

168

16

7

169

123OFFICE

122COMPUTER ROOM

166

147

ST

OR

E

146B 146A

KITCHEN

172LIFT

171 170

163

121OFFICE

175

176

120OFFICE

179Cleaner's

119SERVERROOM

177LIFTS

181

183GOODS

LIFT

180FEMALETOILETS

182MALE

TOILETS

184

101

PH

OT

OC

OP

Y

161

118STORE

161

117COMMON

ROOM

115GALTON LECTURE

THEATRE

102SEMINAR

ROOM

103OPEN PLAN

OFFICE

103D

103C

103EOFFICE

103AMEETING

ROOM

115ASTORE

160

114OPEN PLAN

OFFICE

114AMEETING

ROOM

190

113CLUSTER ROOM

112OPEN PLAN

OFFICE

188

RAMP

187

185LIFTS

186

159PUBLICHOUSE

Stair blockedoff - NoEscape

N

StairN

StairS

S

A

StairA

StairR

R

B

StairB

Y

StairT

DryRiser

VentWindows

Opening with roller shutter(60 minutes fire resistance

operated by fusible link)

116SEMINAR

ROOM

TORRINGTON PLACE

TO

TT

EN

HA

MC

OU

RT

RO

AD

TO

TT

EN

HA

MC

OU

RT

RO

AD

RAMP

112OPEN PLAN OFFICE

108OFFICE

109OFFICE

110OFFICE

107KITCHEN

105MEETING

ROOM

106OFFICE

112A

StairY

T

ACCESS TO SECONDFLOOR FRONT ROOF

AREA VIA STAIR 'Y'Duct

104OFFICE

131AOFFICE

130OFFICE

131OFFICE

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

FIRST FLOOR

Fire Safety & Fire Brigade Contingency Plans

086-04-4

Drawn: S.H. Rev: S.H. July 2016Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Page 19: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

247CLASSROOM

248AOFFICE

245OFFICE

244OFFICE

243OFFICE

242OFFICE

241OFFICE

240OFFICE

239OFFICE

238OFFICE

237OFFICE

236OFFICE

235OFFICE

234OFFICE

233OFFICE

297

299

296

232OFFICE

249OFFICE

250OFFICE

251OFFICE

251AOFFICE

252AOFFICE

295

252BSTORE

294

293

292LIFT

252C

290

291

253TEA POINT

231OFFICE

289

288

285

254COMPUTER

HUB

211OFFICE

212OFFICE

213OFFICE

214OFFICE

215OFFICE

216OFFICE

217OFFICE

218OFFICE

219OFFICE

210OFFICE

209OFFICE

208OFFICE

201KITCHEN

203OFFICE

204OFFICE

205OFFICE

206OFFICE

207OFFICE

284STORE

283

279

28

2A

278

276 275

280GOODS

LIFT

286LIFT

287LIFT

RAMP RAMP

282MALE

TOILETS

281FEMALETOILETS

RAMP

RAMP

273 272

270

20

7A

271LIFTS

269TENANTS

ROOF

A

StairA

DryRiser

VentWindows

Opening with roller shutter(60 minutes fire resistance

operated by fusible link)

B

StairB

StairR

StairS

S

R

N

StairN

Fire

Exit

Y

StairY

Zone 98 - NetworkFire Alarm Panel

No: 2

TORRINGTON PLACE

TO

TT

EN

HA

MC

OU

RT

RO

AD

TO

TT

EN

HA

MC

OU

RT

RO

AD

ACCESS FROM STAIR 'T' OFFVEHICLE RAMP OR FIRST

FLOOR RM 112

246CLASSROOM

Duct

243AOFFICE

248BOFFICE

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

SECOND FLOOR

Fire Safety & Fire Brigade Contingency Plans

086-04-5

Drawn: S.H. Rev: S.H. October 2017Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Page 20: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

BIOHAZARDCATEGORY

B

StairB

A

StairA

DryRiser

VentWindows

Opening with roller shutter(60 minutes fire resistance

operated by fusible link)

TORRINGTON PLACE

COMPRESSEDGAS CYLINDER

StairR

StairS

S

R

StairN

N

N

StairN

392

302AOFFICE

302OFFICE

303OFFICE

304OFFICE

305LAB

306LAB

318OFFICE

317OFFICE

316OFFICE

315OFFICE

314OFFICE

313OFFICE

312OFFICE

311OFFICE

310OFFICE

309STUDENT

STUDY AREA

301TEA

POINT

360SERVER

376

379

RAMP

377LIFT

378LIFT

374Duct

373FEMALE

WC

372MALEWC

373A

370

371GOODS

LIFT

DUCT

367366

364

361

RAMP RAMP

306A

DU

CT

362LIFTS

331OPEN PLAN

OFFICE

387LIFT

357STORE

381

357A

375A

DUCT 369DUCT

375STORE

358OFFICE

359DIS.WC

307OFFICE

308AOFFICE

308OFFICE

363

351STORE

WA

LK

WA

Y

392ASERVER

390

386

385

380

382

388

352OFFICE349

OFFICE

348OFFICE

353OFFICE

347OFFICE

354OFFICE

355AOFFICE

346OFFICE

345OFFICE 355B

OFFICE

356AOFFICE

344OFFICE

356BOFFICE

343OFFICE

342OFFICE

341OFFICE

340OFFICE

338OFFICE

337OFFICE 352

OFFICE

336OFFICE 383

333OFFICE

334OFFICE

335OFFICE

350STORE

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

THIRD FLOOR

Fire Safety & Fire Brigade Contingency Plans

086-04-6

Drawn: S.H. Rev: S.H. Dec. 2018Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Page 21: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

456SERVER

47

3S

TO

RE

474

478

477

RAMP

475LIFT

476LIFT

472

471MALE

WC

470FEMALE

WC

47

1A

46

8

469GOODS

LIFT 466

401PHOTO

-COPIERROOM

465

401AOFFICE

402OFFICE

403OFFICE

404OFFICE

405OFFICE

406OFFICE

464 462

460

RAMP RAMP

40

6A

Ele

c.

461LIFTS

417OFFICE

416OFFICE

415OFFICE

414OFFICE

413OFFICE

412OFFICE

411OFFICE

410OFFICE

409OFFICE

408OFFICE

407OFFICE

B

StairB

A

StairA

DryRiser

VentWindows

Opening with roller shutter(60 minutes fire resistance

operated by fusible link)

446SEMINAR

445OFFICE

444SEMINAR

489

488

448OFFICE

449OFFICE

450OFFICE

443OFFICE

442OFFICE

441AOFFICE

441OFFICE

440OFFICE

439OFFICE

438OFFICE

436OFFICE

435OFFICE

434OFFICE

434AOFFICE

433SEMINAR

481

482 432OFFICE

431COMMON

ROOM

483

484LIFT

452STORE

487

453WC

480453A

479

454

KITCHEN

455

WC

StairR

StairS

S

R

StairN

N

Zone 97 - NetworkFire Alarm Panel

No: 3

TORRINGTON PLACE

TO

TT

EN

HA

MC

OU

RT

RO

AD

TO

TT

EN

HA

MC

OU

RT

RO

AD

451AOFFICE

451OFFICE

451BOFFICE

Duct

Duct

486

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

FOURTH FLOOR

Fire Safety & Fire Brigade Contingency Plans

086-04-7

Drawn: S.H. Rev: S.H. October 2014Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Page 22: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

B

StairB

A

StairA

DryRiser

VentWindows

Opening with roller shutter(60 minutes fire resistance

operated by fusible link)

StairR

StairS

S

R

StairN

N

BioHazard

FlammableCabinet

CompressedGas Cylinder

TORRINGTON PLACE

TO

TT

EN

HA

MC

OU

RT

RO

AD

TO

TT

EN

HA

MC

OU

RT

RO

AD

ACCESS TO WEST WING ROOFPLANT AT SIXTH FLOOR LEVEL

501TEA POINT

512MEETING ROOM

503OPEN PLAN OFFICE

506MEETING

ROOM

506A

507POST ROOM

563

RAMP RAMP

560

561LIFTS

562

568

576LIFT

577LIFT

569

573

570GOODS

LIFT

574STORE

550SERVER

572A

572FEMALE

WC

571MALEWC

575RAMP

578579

549MALEWC

547FEMALE

WC

548KITCHEN

580

581

585LIFT

586

531LAB

532ALAB

532BLAB

533AOFFICE

582

583

533BOFFICE

533COFFICE

534LAB

535LAB

536OFFICE

584

537OFFICE

537ALAB

537BSEMINAR

537CLAB

538OFFICE

587

546DSTORE

546C

546E

546F

546BEXAMROOM

546AEXAMROOM

545OFFICE

588STORE

539OFFICE

544SEMINAR544A

540AOFFICE

589

541OFFICE

590

543AOFFICE

543BOFFICE

592

542OFFICE

593Half heightpartitioning

Duct

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

FIFTH FLOOR

Fire Safety & Fire Brigade Contingency Plans

086-04-8

Drawn: S.H. Rev: S.H. October 2014Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Page 23: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

B

StairB

A

StairA

DryRiser

VentWindows

Opening with roller shutter(60 minutes fire resistance

operated by fusible link)

EQ

UI P

ME

NT

SC

RE

EN

Vertical ladderto plant roof

StairR

StairS

S

R

Zone 96 - NetworkFire Alarm Panel

No: 4

TORRINGTON PLACE

TO

TT

EN

HA

MC

OU

RT

RO

AD

TO

TT

EN

HA

MC

OU

RT

RO

AD

ACCESS TO ROOF PLANTFROM FIFTH FLOOR (STAIR R)

ONLY

608MEETING

ROOM

612OPEN PLAN

OFFICE

607OFFICE

607A

601MEETING

ROOM

670

672

671LIFTS

RAMPRAMP

679FEMALETOILET

680MALE

TOILET

RAMPRAMP

676

677

678GOODS

LIFT681

682STORE

683SERVER

680A

615STAFF / INFORMAL

MEETING ROOM

TEAPOINT

614STORE

686

687

684LIFT

685LIFT

650

651PLANT ROOM

652LIFT MOTOR

ROOM

654PLANTROOM

ROOF

653PLANT SPACE

ROOF

WA

LK

WA

Y

674

EQ

UIP

ME

NT

SC

RE

EN

Duct

613MEETING

ROOM

BREAKOUT SPACE

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

SIXTH FLOOR

Fire Safety & Fire Brigade Contingency Plans

086-04-9

Drawn: S.H. Rev: S.H. November 2016Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Page 24: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

715OFFICE

715ASERVER

773

ST

OR

E

772

765

776777

RAMP RAMP

771FEMALE

WC

770MALEWC

770Duct

77

1A

774LIFT

775LIFT

768

769GOODS

LIFT

703OPEN PLAN

OFFICE

70

3A

Ele

c.

763

760

761LIFTS

RAMPRAMP

B

StairB

A

StairA

DryRiser

VentWindows

Opening with roller shutter(60 minutes fire resistance

operated by fusible link)

DUCT

DUCT

DUCT

TORRINGTON PLACE

701KITCHEN

Duct

Duct

706MEETING

ROOM707

MEETINGROOM

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

SEVENTH FLOOR

Fire Safety & Fire Brigade Contingency Plans

086-04-10

Drawn: S.H. Rev: S.H. October 2014Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Page 25: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

870A

812PRINTING /SCANNING

813MEETING ROOM

815SERVER

872STORE

876

875

864

RAMPRAMP

871

86

9A

873LIFT

874LIFT

870MALE

WC

869FEMALE

WC

866

867

868GOODS

LIFT

801KITCHEN

809ASTORE

802OPEN PLAN OFFICE

806MEETING

ROOM

805MEETING

ROOM

804MEETING

ROOM

877BREAK OUT

803BMEETING

ROOM

803AMEETING

ROOM

862

802A

Ele

c.

860

861LIFTS

RAMPRAMP

DUCT

DUCT B

StairB

A

StairA

DryRiser

VentWindows

Opening with roller shutter(60 minutes fire resistance

operated by fusible link)

Zone 95 - NetworkFire Alarm Panel

No: 5

TORRINGTON PLACE

Duct

807MEETING

ROOM808

MEETINGROOM

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

EIGHTH FLOOR

Fire Safety & Fire Brigade Contingency Plans

086-04-11

Drawn: S.H. Rev: S.H. October 2014Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

Page 26: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

B

StairB

A

StairA

DryRiser

VentWindows

Opening with roller shutter(60 minutes fire resistance

operated by fusible link)

912STORE

911POST &

PRINT ROOM

908OPEN PLAN

OFFICE

906PHOTOCOPY

906A

901MEETING

ROOM

902MEETING

ROOM

900RECEPTION /BREAKOUT

914TEA POINT

915MEETING

ROOM

913BREAK OUT

973MALE

WC

972STORE975

974

979 978

976LIFT

977LIFT

965

RAMP RAMP

971

970FEMALE

WC

969MALE

WC

967

968GOODS

LIFT

970A

RAMP

RAMP

960

962

961LIFTS

900A

TORRINGTON PLACE

DUCT

903OFFICE

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

NINTH FLOOR

Fire Safety & Fire Brigade Contingency Plans

Drawn: S.H. Rev: S.H. October 2014Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

086-04-12

Page 27: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:
Page 28: UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK · Premises Fire Safety Handbook Bldg Name: 1 - 19 Torrington Place (086) Date Last Amended: Jul 18 EP: 3 of 8. Issued by:

Vertical ladder to10th Floor balcony

Vertical ladder to10th Floor balcony

Rooftop Plan &mobile phonemasts/cabins

DryRiser

StairA

WATER TANK

SERVICEDUCT

DUCT

DUCT

WCBLOCK

AIR HANDLINGUNIT

ROOF

A

StairA

1101B

ST

OR

E

1163No. 1 LIFT

MOTOR ROOM

1162No. 2 (GOODS)

LIFTMOTOR ROOM

1101A

Cup

b'd

1105PLANT ROOM

1106FILE STORE

1107STORE

1161

1160No. 3 LIFT

MOTOR ROOM1101

TANK ROOM

LOWER LEVEL BALCONY

LOWER LEVEL BALCONY

1102STORE

1103B.T. SATELLITE

ROOM

1104STORE

1164

RADIOFREQUENCY

HAZARDS

RADIOFREQUENCY

HAZARDS

1165

DO NOT SCALE OFF THIS DRAWING.ALL DIMENSIONS MUST BE CHECKED ON SITEPRIOR TO ANY WORK BEING PUT IN HAND.ANY DISCREPANCIES ARE TO BE BROUGHT TOTHE ATTENTION OF THE PROJECT MANAGERIMMEDIATELY UPON DISCOVERY.

NOTES

UCL ESTATESGOWER STREET, LONDON WC1E 6BT

DWG. NO.rev

University College London1-19 Torrington PlaceLondonWC1E 7HB

ELEVENTH FLOOR & ROOF

Fire Safety & Fire Brigade Contingency Plans

Drawn: S.H. Rev: S.H. October 2017Date: October 2014Scale: N.T.S.File: UCL Estates/086/Fire

086-04-14