Unitate de Protectie Transformator TPU TD410

Embed Size (px)

Citation preview

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    1/14

    4DV002007 1 / 14

    TRANSFORMER PROTECTION UNIT TPU TD410

    OVERVIEW  

     The Transformer Protection Unit TPU TD410 is a protective

    device with a full-integrated design. It is based on modern

    digital technology and it complies with International Quality 

    Standards. With four central processing units, the TPU TD410

    is certified as complying with the latest IEC Standards con-

    cerning electromagnetic compatibility.

     The TPU TD410 performs a wide range of protective functions.

    Provided with many user-programmable options, it features

    good accuracy in the setting of the current and voltage

    thresholds, timings, and time-current functions. All protective

    settings are independent. Two sets of parameters for each

    protective function are available. All protective functions have

    demanding security and speed constrains. As an example, the

    differential function makes the amplitude matching of the

    currents (according to the CT ratios of both sides), the proper

    phase adjustments and eliminates the zero-sequence

    component of the currents.

     The graphic display in the frontal panel represents a synopticwith the panel complete state. In the frontal panel there are

    also several functional keys that allow an easy command or

    change of the panel working mode.

    As a terminal unity, the TPU TD410 features accurate

    measures of the differential and through-current for each

    phase and for both sides of the transformer, as well as a set of 

    monitoring functions, including oscillography and data-

    logging. These functions support the integration of the TPU

     TD410 as a remote unity of the Supervisory Control and Data

    Acquisition Systems of EFACEC-SE for Substations, while still

    providing a link to PC.

     APLICATION 

     The Transformer Protection Unit TD410

    was designed for fast and selectiveprotection of two-winding transformers in

    Distribution Substations.

    FEATURES 

     PROTECTION

    •  Unrestrained differential protection(87T)

    •  Differential protection (87T), withharmonic restraint

    •  High Set Overcurrent with High-Speedtripping (50, 50N)

    •  Low Set Overcurrent with Definite orInverse Time (51, 51N)

    •  Overcurrent with Extensive SettingRange for both Time and Current (2nd

    51 and 2nd 51N)

    •  Restricted earth fault protection (87N) –option 

    •   Tank Overcurrent protection (50G) -option 

    •  2 Setting sets

    MONITORING

     •  Circuit breaker close lock (86T)

     •  Measurement of the RMS values of thetwo winding-currents, differential-

    current and its second and fifth

    harmonics.

     •  Data-logging with 1 ms time-tagging

     •  10 seconds of currents oscillography 

     •  Self-Tests and “watch dog”

     •  9 independent Contact Inputs

     •  5 independent Contact Outputs •  It can be expanded up to 41 binary 

    Inputs and 17 binary Outputs

    INTERFACES

     •  Passwords for Security Access

     •  Serial link RS232 for PC connection

     •  Linkable to a Local Area Network usingLON TALK or ETHERNET 

    Sistemas de Electrónica, S.A.Power Systems Automation and Control

    APCERCERTIFICADO

    . .SISTEMA PORTUGUÊSDA QUALIDADE

    NP EN ISO 9002

    87T

    50/51, 51

    50/51N, 51N

    86T

    (87N)

    (50G)

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    2/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 2 / 14

    TPU TD410TPU TD410

     PROTECTIVE RELAYING

    Two-windings transformerdifferential protection (87T)

     The transformers differential pro-

    tection is a fast and selective re-

    laying function aimed at protect-

    ing transformers and at isolating

    them from the Power System

    when internal faults arise.

    Adapting the sensed currents

    A transformer differential protec-

    tion start-up is constrained by the

    value of the sensed differential

    current (input current minus out-put current). It can also be con-

    strained by the restraining cur-

    rent (image of the current flowing

    through the transformer). There-

    fore, it is very important to use

    the real values of those currents

    which, as a rule, do not equal the

    sensed currents.

     The TPU TD410 assures a perfect

    compensation for the sensed cur-

    rents, in such a way that the dif-

    ferential current image is zero forall the load and external fault

    situations.

     Therefore, the computation of the

    differential and the restraining

    currents includes a few compen-

    sations, to avoid false differential

    as well as false restraining cur-

    rents resulting from unbalances

    between HV and MV. Those com-

    pensations depend on the trans-

    former type and on the connected

    CTs, and aim at:

    • Eliminating any zero current cir-culating in the transformer

    windings, to avoid the tripping of 

    the associated overcurrent vir-

    tual relay against external

    faults.

    • Compensating the phase differ-ence resulting from the trans-

    former type.

    • Balancing the RMS values of thecurrents of different windings, to

    compensate for different CT ra-

    tios in the HV and MV sides of 

    the transformer.

    Non restrained differentialrelaying

     The non restrained differential

    protection function for 2-windings

    transformers operates with no

    delay for differential currents

    greater than a set threshold, usu-

    ally a threshold high enough

    (larger that the maximum inrush

    current).

    Restrained differential relaying

     The operation of the differential

    protection function for 2-windings

    transformers is conditioned by 

    comparing the value of the differ-

    ential current with that of the re-straining current, and also by the

    2nd and the 5 th harmonics.

     The operating characteristic ap-

    plied to compare the differential

    and the restraining currents is

    made up by three continuous

    segments, and it shows up as fol-

    lows:

    Idif 

    Irest

    TRIP

    LOCK α1

    Imin

    α2

    Itth (to 2nd Slope)

     The differential and the restrain-

    ing currents are computed ac-

    cording to the following expres-

    sions:

    IDIF = I HV – I MV

    IREST  = ½| I HV + I MV |

     These currents have already been

    compensated for any mismatch

    depending on the particular

    transformer and CTs. The follow-

    ing directions are assumed:

    IHV   IMV

     The first segment of the operating

    characteristic is a minimum oper-

    ating threshold (maximum sensi-

    tivity).

     The second segment accounts

    mainly for the transformer tap

    changing, as well as for any inac-

    curacy in the CTs and the relay it-

    self.

     The last segment accounts for CT 

    saturation with high value cur-

    rents arising with external faults.

    2nd and 5th harmonic restraining

     The harmonic restrain is applied

    to avoid spurious tripping of the

    differential protection, for high

    magnetising currents. It is a tra-

    ditional and well proved way to

    recognise those currents.

     The harmonic restrain works as

    usually: it locks the protection op-

    eration with the 2nd  harmonic in

    the differential current for inrush

    currents, and it locks it with the

    5th  harmonic for overfluxing re-

    sulting from either overvoltage or

    underfrequency situations

     The constrain is done by com-

    paring the harmonic RMS values

    to the RMS value of the funda-mental frequency component in

    the differential currents. This

    comparison is done for every 

    phase but is locking is performed

    also for different phases.

    Restricted Earth FaultProtection for the LV side(87N) - option

     The TPU TD410 provides for the

    LV side of the transformer an

    instantaneous earth currentdifferential protection for solidly or

    low impedance earthed systems.

     The trip decision of this function

    depends on the difference

    between the sum of the three

    phase currents and the neutral

    point current.

     The protection is unaffected by CT 

    saturation, inrush currents or

    external faults.

    Due to stabilise this function

    against CT saturation, its

    differential current sensitivity 

    depends on the through-current

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    3/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 3 / 14

    TPU TD410TPU TD410

    of the CT s (Irest), as shown on the

    picture bellow:

    Idif 

    Irest

    TRIP

    LOCK α1

    Imin

    Up to a certain limit, stability is

    guaranteed with a linear

    characteristic, with configurable

    slope.

    Tank OvercurrentProtection, for the HV side(50G) option

     The TPU TD410 provides, as an

    option for the HV side of the

    transformer, the tank overcurrent

    protection, which monitors the

    current between earth and

    transformer tank. This function

    trips when this current is up to

    the threshold value, which one is

    normally set to a very sensitivevalue.

    High Set Overcurrent with high-speed tripping (50, 50N)

     The High Set Overcurrent function

    is recommended as backup for

    transformer faults and is provided

    for the HV side of the transformer.

    As a rule, the High Set

    Overcurrent protection is targeted

    for a selective coordination based

    on the RMS current (cut off ). In

    the TPU TD410, High Sets are

    independent for protection from

    phase faults and from phase to

    ground faults. A selective timing

    can also be set.

    Low Set Overcurrent with timesets (51, 51N)

     The Low Set Overcurrent function

    is recommended as backup for

    network faults. This protection

    function is provided for the HVside of the transformer.

     The Low Set Overcurrent

    protection offers sensitivity and

    step timings for selective

    coordination (time-lag  over-

    current). The TPU TD410 provides

    both the independent and the

    inverse time options. Theseoptions comply with International

    Standards, which is a guaranty 

    for compatibility with other

    devices. The Standards are IEC

    255-3 and IEEE 37.112 .

    Setting the Low Set Overcurrent

    relays is also independent for

    phase-to-phase and for ground

    faults.

    For the IEC complying option, the

    time-current functions follow the

    general expression:

    [ ]1)/(   −>

    =b I  Icc

    aT  st op

    NI a=0,14=A b=0,02VI a=13,5=A b=1EI a=80=A b=2

    For the IEEE-complying option,

    the time-current functions follow

    the general expression:

    [ ]   IEEE op   T ed  I  Icc

    c st   

     

     

     

     +

    −>=

    1)/(

    NI c=0,0103 d=0,02 e=0,0228 A=100cVI c=3,922 d=2 e=0,0982 A=cEI c=5,64 d=2 e=0,02434 A=c

     The TD410 Unity supports the

    timed resetting option in the time-

    inverse operation of Low Set

    Overcurrent.

    Option for Timed Reset

    Even for IEC time-inverse

    functions, the TD410 supports the

    option of timed resetting, thus

    approximating the replication of 

    the conductors cooling down.

     The resetting time follows the

    expression:

    trearme [s]= 1)/(   2−> I  I  A

    Normal Inverse time-current curves, accordingto the IEC-255-3 standard

    Very Inverse time-current curves, according tothe IEC-255-3 standard

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    4/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 4 / 14

    TPU TD410TPU TD410

    Extreme Inverse time-current curves, accordingto the IEC-255-3 standard

    Normal Inverse time-current curves, accordingto the IEEE C37.112 standard

     The TPU TD410 is original in

    extending the timed resetting as

    defined by the IEEE C37.112

    Very inverse curves for IEEE C37.112 standard

    Extreme inverse curves for IEEE C37.112standard

    standard to the IEC 255-3 time-

    current curves. Thus, the user

    can choose to account for the

    Normal inverse curves for timed resetting ac-cording to IEC 255-3 standard

    Very inverse curves for timed resetting ac-

    cording to IEC 255-3 standard

    usually slow cooling down of the

    protected conductors after fault

    elimination.

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    5/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 5 / 14

    TPU TD410TPU TD410

    Extreme inverse curves for timed resetting ac-cording to IEC 255-3 standard

    Normal inverse curves for timed resettingaccording to IEEE C37.112 standard

    Timed resetting time-current curves accordingto IEEE C37.112, for very inverse protection

    Timed resetting time-current curves accordingto IEEE C37.112, for extreme inverse protection

    It is worthy mentioning that the

    accuracy of both the IEEE and the

    IEC time-inverse curves is

    guaranteed for the full range of 

    settings.

    Also, the implementation of both

    standards follows the dynamic

    definition of IEEE 37.112,

    providing a definite behaviour for

    time-evolving faults.

     This behaviour also supports a

    dynamic co-ordination between

    the relay and fuses as well as

    traditional Reclosers downstream

    in the feeder

    Definite Time Overcurrent relaywith large setting ranges(Universal Overcurrent Relay)

     The Low Set Overcurrent function

    is recommended as backup for

    network faults. This protection

    function is provided for the HV

    side of the transformer.

     The TPU TD410 performs a

    second Definite Time overcurrent

    protection function, running inparallel and independence re-

    garding the previous protective

    functions.

     The large setting ranges of this

    protective function (Universal

    Definite Time overcurrent relay)

    supports a set of applications:

    •  For feeders with occasionallittle short-circuit capacity, in

    which the operating times of 

    time-inverse overcurrentfunctions can feature big

    delays, the Universal overcur-

    rent protection provides a

    limit for the operating time of 

    those low-set overcurrent

    protective functions;

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    6/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 6 / 14

    TPU TD410TPU TD410

    Universal Overcurrent protection applied tolimit overall operating times

     Application of the Universal overcurrent relayas a second High Set step element

    •  As a second step of High Setovercurrent relaying,coordinated in time and in

    current with other High Set

    overcurrent relays down-

    stream in the network;

    •  As the main Low Setovercurrent protection

    element, with Definite Time,

    the inverse time protective

    element becoming available to

    replicate the thermal behavior

    of the feeder conductors,particularly in the extreme

    inverse option with timed

    resetting.

    Option between a virtual imageof the zero sequence current

    and the observation of the 4thcurrent input

     The TPU TD410 is prepared to

    observe the neutral current of the

    HV winding of the transformer in

    its 4th current input. However, the

     TPU TD410 also performs by 

    software the computation of the

    zero sequence current in that

    winding, directly from the virtual

    addition of the three phase cur-

    rents observed at their inputs.

    As a matter of fact, the neutral

    current transformer available fre-

    quently has a primary rated

    current which is smaller than the

    rated currents of the phase CT.

     This fact may lead to saturation

    whenever large fault currents

    arise.

     The virtual addition of the three

    phase currents by the TPU TD410

    supports the exploitation of the

    extensive range of the phasecurrent transformers, while still

    be-meting from the better accu-

    racy reached by the 4th current

    input for small currents.

     The TPU TD410 makes it possible

    to choose the residual current

    source for each one of the three

    ground fault relays, thus

    supporting the combination of a

    high sensitivity to high impedance

    faults with the right observation of 

    strong ground fault currents.

    Setting Sets

     The TPU TD410 supports two

    complete sets of settings, which

    can be fully programmed by the

    user.

    Switching from a set to another

    can be defined by a daily schedule

    or by decisions from software

    logic. This feature supports the

    adaptation to different loadprofiles or network short-circuit

    capacities, as time goes.

     CONTROLING FUNCTIONS

    Circuit breaker commands

     The TPU TD410 supports thecommand of both HV and MV

    circuit breakers, both for opening

    and for closing, through func-

    tional keys. These commands are

    allowed either local or remotely,

    and logic conditions can be

    implemented, to provide full

    automation.

    Working modes

    In the front-end 2 working modes

    are established which may bechanged by pushing functional

    keys. The actual working mode is

    signaled by leds.

    Manual/Automatic Mode

     The manual mode inhibits all the

    automatisms.

    Local/Remote Mode

     The local mode inhibits the com-

    mands that may come from LAN.

    Trip circuit monitoring

     The TPU TD410 uses a contact

    input aiming to constantly 

    supervise the trip circuit of the

    circuit breaker when this is open.

    In case there is any discontinuity 

    in the trip circuit when the circuit

    breaker is closed (it needs to

    monitor the state of the circuit

    CIRCUIT BREAKEROPENING CONTACT

    TRIPPINGCOIL

    CONTACT INPUT  TO MONITOR THE

     TRIP CIRCUIT TPU TD410OPENING

    ORDER

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    7/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 7 / 14

    TPU TD410TPU TD410

    breaker), the input ceases to be

    energized and an alarm is

    generated.

    Circuit breaker failure protec-tion

    Following an order to trip the

    circuit breaker, the circuit

    breaker failure is verified.

    If the protection does not reset

    after a user-programmable time

    (for example by circuit breaker

    failure) a control is generated over

    another equipment (for example

    over the upstream circuit

    breaker).

    Circuit breaker close lock(86T)

     The TPU TD410 blocks the HV

    and MV circuit breakers close

    command after a differential

    protection trip or another

    condition indicating a transformer

    internal fault, such as the

    Bucholz trip monitored by the

    protection. This blocking condition

    remains activated until the usersets the permission to put the

    transformer in service again.

    Interlocking and logical condi-tioning

     The TPU TD410 contact inputs, as

    well as a inner set of free logical

    variables, which can be

    associated to signals to be re-

    ceived from the LAN and also to

    the many protective functions,

    can be logically combined andassociated to programmable

    timers.

     This flexibility in logical

    conditioning can be applied to

    define, for example, additional

    interlocks to circuit breaker close

    lock and trip commands.

     MONITORING FUNCTIONS

    Measurements

     The TPU TD410 provides the

    following metering values from its

    steady-state condition:

    •  RMS values for the threephase and the ground

    currents (4th  input), for both

    transformer windings.

    •  RMS values for the 1st, 2ndand 5th  harmonics of the

    differential currents.

     These values are available either

    on the TPU TD410 itself, or

    remotely through a link to a local

    area network and to the Supervi-

    sory Control and Data Acquisition

    systems of EFACEC.

     The good accuracy achieved by 

    the performed measurements

    usually make it possible to avoid

    additional measurement

    converters.

    Other measurement informa-tion

     The TD410 also computes and

    records, with time-tags:

    •  The peak RMS values for thecurrents (1 second average)

    •  The addition of the I2 interruptedby each pole of the circuit

    breaker, as well as the number

    of its trips.

    Oscillography

     The TPU TD410 records and

    stores the oscillography of the

    phase and zero sequence

    currents. The total length of each

    oscillography is variable although

    limited to 1 second, of which 0,1

    seconds are for pre-fault values. A

    variable number of oscillographies

    up to 10 recorded seconds are

    stored with a frequency of 1000

    Hz.

     The oscillographies can be

    displayed on a PC, applying a

    suitable software and retrieving

    the information stored in the TPU

     TD410 either through a front-end

    connector, or remotely through

    the Supervisory Control and Data

    Acquisition System of EFACEC.

     The good accuracy reached by the

    performed measures usually 

    make it possible to avoid

    additional measurement convert-

    ers.

    Sequence of Events Records

     The TPU TD410 monitors all the

    existing contact inputs andoutputs, as well as a set of inner

    logic variables and any change on

    the settings, performing an

    accurate time-tagging of the

    changes of state with a 1 millisec-

    ond resolution and a programma-

    ble debounce filtering time.

     The record of the events stored by 

    the TPU TD410 can also be dis-

    played on a PC, applying a

    suitable software package and

    retrieving the information either

    local or remotely.

     INTERFACES

    Contact inputs

     The base version of TPU TD410

    has nine programmable contact

    inputs that are isolated from one

    another.

    With an expansion board, nine

    (expansion board type 1) or

    sixteen (expansion board type 2)

    extra programmable contactinputs can be added.

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    8/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 8 / 14

    TPU TD410TPU TD410

     This allows a maximum of 41

    programmable contact inputs

    with two extra expansion boards.

    In the complementary inputs (forexample switches state, circuit

    breaker open and close), if both

    states are being monitored, the

    invalidity state is reported if both

    inputs have the same logical

    value. However, only one input to

    report the switches state can be

    used, but, in this case, it is not

    possible to report the invalidity 

    state.

    Contact outputs

     The base version of the TPU

     TD410 has six independent

    isolated contact outputs, of which

    five are programmable.

     The sixth output is double

    (“change ove r”) and it is operated

    by the inner “Watch-dog ” if the

    relay fails.

    With an expansion board type 1

    six extra programmable contact

    outputs are added.

     This allows a maximum of 17

    programmable contact inputs

    with two extra expansion boards.

    WinProt

     To make the handling of the TPU

     TD410 easier and to enhance its

    features, the WinProt software on

    a friendly and self-exploring

    Windows environment is

    available.

    WinProt  not only allows the exe-

    cution of any operation on the

    front-end, either locally or

    remotely, but it also supports

    more advanced functions, whose

    highlights are:

    à   To retrieve, to change and to

    save all the settings of the

     TPU TD410. It is also possible

    to print a brief report with

    those settings.

    à   To retrieve the oscillographies

    saved by the TPU TD410, and

    to display them with

    advanced zoom and format-

    ting functions.

    à   To collect and to display the

    sequence of events records.

    Communication

     The TPU TD410 provides a fibber

    optic adapter on its back, for links

    to a Local Are Network, using the

    communication protocol LON

     TALK or ETHERNET.

    With the Supervisory Control and

    Data Acquisition systems of 

    EFACEC, all WinProt  features are

    available remotely.

    Man Machine Interface

    In the frontal panel is supported a

    graphic display where it is

    presented a synoptic with the

    state of the panel that is being

    protected. By functional keys it ispossible to select and commandthe switches represented in the

    synoptic (if they are

    commandable, if not TD410 only 

    monitories its state).

     The possible synoptics are chosen

    from a set, by selecting the one

    that better fits to the panel where

    is associated the TD410.

    By functional keys it is possible to

    change the panel working mode

    as well.

    In an alarm window, in which the

    alarms are there until they are

    recognised it is possible to

    recognise any incident in thatpanel.

     The TD410 still supports a menu

    mode where it is possible to

    parameterise the protection

    functions, to programme the

    inputs and outputs, to command

    the circuit breaker, to configure

    the transformer measures relation

    and to visualise informations.

     The pursued philosophy regarding

    the setting and command security is that everyone can access all the

    information. However, no one can

    change values without a

    password.

     The TPU TD410 has two security 

    levels. The first one only allows

    the change of the setting of the

    monitoring functions. The second

    level allows the change of the

    settings of the protection

    functions.

    After leaving an option level of themenu, the changes have to be

    confirmed; otherwise, they will not

    become effective. Not confirming

    those changes in 5 minutes after

    leaving the menu level will reset

    all the parameters to the original

    values.

    Set ProtectionsSet AutomationConfigure I / OOther ConfigurationData-Logger 

    MeasurementsOther InformationSet Data and TimeInsert Password

    Cancel ↑ Up   ↓ Down

    CB Information

    Cancel ↑ U    ↓ Down

    Sum I ^2 A = 0.00 KA2Sum I ^2 B = 0.00 KA2Sum I ^2 C = 0.00 KA2Trip Count : 236Clear Total I ^2Clear Trip Count

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    9/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 9 / 14

    TPU TD410TPU TD410

     AVAILABLE VERSIONS

    Version Transformer

    differential (87T)

    Phase over-

    current (50/51)

    Earth-fault

    overcurrent

    (50/51N)

    Restricted earth-

    fault (87N)

     Tank overcurrent

    (50G)

     TD410 - B   •  •  • 

     TD410 - R   •  •  •  • 

     TD410 - C   •  •  •  • 

     TD410 - RC

      • 

    • 

    • 

    • 

    • 

    Sistemas de Electrónica, S.A.

    TPU - TD410TPU - TD410

    ONON

    LANLAN

    CC

    00

    IILocalLocalRemoteRemoteNormalNormal

    EmergEmerg

    L/RL/R

    M/AM/A

    EE

    60 Hz In=5A60 Hz In=5A38-138 V=38-138 V=

    CLRCLR SELSEL

    IR = 103.2 AIR = 103.2 A

    Corrente IRCorrente IR

    Corrente ISCorrente ISCorrente ITCorrente IT

    I0 TerraI0 TerraTensão URTensão URTensão USTensão US

    Tensão UTTensão UTTensão U0Tensão U0

    Tensão URSTensão URSTensão USTTensão UST

    Tensão UTRTensão UTRFrequênciaFrequênciaP.P. ActivaActiva

    Corrente IRCorrente IR

    LeituraLeitura dasdas medidasmedidas

    L/R – Local/Remote working mode selection

    M/A - Manual/Automatic working mode selection

    CLR – Recognise alarm signalling (supervision and command

    mode)

    SEL – Selection of the switches to be operated (supervision and

    command mode)

    I – Switches close order (supervision and command mode)

    O – Switches open order (supervision and command mode)

    ↑/↓ - Navigation keys (menu mode)

    E – Accept option or entry in a submenu (menu mode)

    C Cancel an option or exit of a submenu (menu mode)

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    10/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 10 / 14

    TPU TD410TPU TD410

     ORDERING FORM

     TPU TD410 - I A/Io A, Hz - _  VERSION TPU TD410 – B B

     TPU TD410 – R R

     TPU TD410 – C C

     TPU TD410 – RC RC

    RATED CURRENT ON PHASECURRENT TRANSFORMERS5 A 5

    1 A 1

    RATED CURRENT ON NEUTRAL CURRENT TRANSFORMERS

    1 A 1

    0,2 A 0,2

    POWER FREQUENCY

    50 Hz 50

    60 Hz 60

    L ANGUAGE

    Portuguese PT  

    English UKFrench FR

    SUPPLY VOLTAGE

    19 .. 53 V cc A

    38 .. 138 V cc B

    90 .. 280 V cc C

    1ST E XPANSION BOARD

     Type 1 (9I + 6O) 1

     Type 2 (16I) 2

    Absent 0

    2ND E XPANSION BOARD

     Type 1 (9I + 6O) 1

     Type 2 (16I) 2

    Absent 0

    COMMUNICATION BOARD

    Present X

    Absent 0

    Example:

     TPU TD410 - B I 1 A / Io 0,2 A, 50 Hz PT _ B12X

     TPU TD410 with basic configuration (differential and phase overcurrent protection) 5A rated current in phasesand 1 A in the neutral current input, 50 Hz. The man machine interface is in English. The unity is feed in a 38

    to 138 V range and has an expansion board type 1, another expansion board type 2 (a total of 34 inputs and

    11 outputs) and a communications board.

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    11/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 11 / 14

    TPU TD410TPU TD410

    CONNECTION DIAGRAM

    1 2IPA 

    WA WB

    WATCHDOG

    WC1 2IPB

    1 2IPC

    1 2IPN

    1 2ISN

    1 2ISA 

    1 2ISB

    1 2ISC

     A 

    OUT 2

    B A 

    OUT 3

    B A 

    OUT 4

    B A 

    OUT 5

    B

    +IN 1

    - +IN 2

    - +IN 3

    - +IN 4

    - +IN 5

    - +IN 6

    - +IN 7

    - +IN 8

    - +IN 9

    -+

    U AUX

    -

     A

    B

    C

     A

    BC

    INTERFACE+

    IN 41-

     A 

    OUT 1

    B A 

    OUT 17

    B

    1 IN1A

    2 IN1B

    3 IN2A

    4 IN2B

    5 IN3A

    6 IN3B

    7 IN4A8 IN4B

    9 IN5A

    10 IN5B

    11 IN6A

    12 IN6B

    13 IN7A

    14 IN7B

    15 IN8A

    16 IN8B

    17 IN9A

    18 IN9B

    K5

    1 GND

    2 GND

    3 GND

    4 N/C

    5 N/C

    6 O1A

    7 O1B

    8 O2A

    9 O2B

    10 O3A

    11 O3B

    12 O4A

    13 O4B

    14 O5A

    15 O5B

    16 O6A

    17 O6B

    18 O6C

    K6

    1 GND

    2 GND

    3 IN9A

    4 IN9B

    5 IN10A

    6 IN10B

    7 IN11A

    8 IN11B

    9 IN12A

    10 IN12B

    11 IN13A

    12 IN13B

    13 IN14A

    14 IN14B

    15 IN15A

    16 IN15B

    17 IN16A

    18 IN16B

    K8

    1 N/C

    2 N/C

    3 ISA1

    4 ISA2

    5 ISB1

    6 ISB2

    7 ISC1

    8 ISC2

    9 ISN1

    10 ISN2

    K2

    1 IPA1

    2 IPA2

    3 IPB1

    4 IPB25 IPC1

    6 IPC2

    7 IPN1

    8 IPN2

    9 N/C

    10 N/C

    K1

    1 GND

    2 GND

    3 GND

    4 -VIN

    5 +VIN

    6 O1A

    7 O1B

    8 O2A

    9 O2B

    10 O3A

    11 O3B

    12 O4A

    13 O4B

    14 O5A

    15 O5B

    16 WA

    17 WB

    18 WC

    K4

    1 IN1A

    2 IN1B

    3 IN2A

    4 IN2B

    5 IN3A

    6 IN3B

    7 IN4A8 IN4B

    9 IN5A

    10 IN5B

    11 IN6A

    12 IN6B

    13 IN7A

    14 IN7B

    15 IN8A

    16 IN8B

    17 IN9A

    18 IN9B

    K3

    230 mm

    266 mm

    1 IN1A

    2 IN1B

    3 IN2A

    4 IN2B

    5 IN3A

    6 IN3B

    7 IN4A8 IN4B

    9 IN5A

    10 IN5B

    11 IN6A

    12 IN6B

    13 IN7A

    14 IN7B

    15 IN8A

    16 IN8B

    17 GND

    18 GND

    K7

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    12/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 12 / 14

    TPU TD410TPU TD410

    DIMENSIONS

     The TPU TD410 supports the double EuroCard dimensions, with 6U height and 42 HP width

    ELECTROMAGNETIC COMPABILITY (CLASSES)

    Immunity Tests

    1 MHz burst disturbanceIEC 60255-22-1

    Class III

    2.5 kV common mode

    1 kV differential mode

    Electrostatic dischargesIEC 60255-22-2

    Class IV

    8 kV contact

    15 kV air

    Electrostatic discharges EN 61000-4-24 kV contact

    8 kV air

    Electromagnetic fieldIEC 1000-4-3

    ENV 5014010 V/m 80 MHz – 1000 MHz

    Radiated electromagnetic field

    disturbanceIEC 801-3 10 V/m 27 MHz – 80 MHz

    Radiated electromagnetic field

    disturbanceENV 50140 / 50204 10 V/m 900 ±  5 MHz pulse modulated

    Power frequency magnetic fieldEN 61000-4-8

    Class V

    100 A/m cont. 50Hz

    1000 A/m 3s, 50 Hz

    Fast transientsIEC 60255-22-4

    Class IV4 kV 5/50 ns 5 kHz

    Fast transients EN 61000-4-4 2 kV 5/50 ns 5 kHz

    Conducted electromagnetic field

    disturbance

    EN 61000-4-6

    ENV 50141

    10V rms, 150 kHz – 80 MHz

     @ 1 kHz 80% am

    7

     

    7

    7

     

    7

     

    7

     

    265 m m

    4

    7

    266 m m

    245 m m

    84 m m

    84 m m

    14 m m

    6

     

    Sistemas de Electrónica, S.A.

    TPU - TD410TPU - TD410

    ONON

    LA NLA N

    CC

    00

    IILocalLocal

    RemoteRemote

    NormalNormal

    E mergE merg

    L/ RL/ R

    M/ AM/ A

    EE

    60 Hz In=5A60 Hz In=5A38-138 V=38-138 V=

    CL RCL R SE LSE L

    IR = 103.2 AIR = 103.2 A

    Corrente IRCorrente IR

    Corrente ISCorrente IS

    Corrente ITCorrente IT

    I0 TerraI0 Terra

    Tensão URTensão UR

    Tensão USTensão US

    Tensão UTTensão UT

    Tensão U0Tensão U0

    Tensão URSTensão URS

    Tensão USTTensão UST

    Tensão UTRTensão UTR

    FrequênciaFrequência

    P.P. Ac t iv aActiva

    Corrente IRCorrente IR

    LeituraL e it u ra d asd as m e di d asmedidas

    FRONTAL PANEL RIGHT PANEL

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    13/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 13 / 14

    TPU TD410TPU TD410

    Insulation Tests

    Insulation test IEC 60255-5

    2 kV ac 1min 50 Hz

    2,8 kV dc 1 min (power supply)

    1,5 kV ac 1 min (between output

    contacts)

    1 kV ac 1 min (between watch-dog

    contact)

    Impulse voltage test IEC 60255-5 5 kV 1,2/50 µs, 0,5 J

    Insulation resistance IEC 60255-5 > 100 MΩ @ 500 V dc

    Emission Tests

    Electromagnetic emission radiated EN 55011

    EN 5502230 – 1000 MHz class A

    CE Mark

    Immunity EN 50082-2

    Emissivity EN 50081-2

    Low voltage directive EN 60950 / EN 50178

  • 8/19/2019 Unitate de Protectie Transformator TPU TD410

    14/14

    Sistemas de Electrónica, S.A.Power Systems Automation and Telecontrol

    4DV002007 14 / 14

    TPU TD410TPU TD410

     TECHNICAL SPECIFICATIONS

    Rated values

    Frequency 50 Hz (60 Hz in option)

    Rated current 5 A (1 A option)Rated neutral current 1 A (0,2 A option)

    Supply

    Voltage supply 19-53; 38-138;

    90- 280 V dc

    Max. ripple at rated voltage < 12 %

    Power consumption 9 to 20 W

    Bridging time during loss of power

    supply