Upload
harshjindal
View
215
Download
0
Embed Size (px)
Citation preview
7/27/2019 Unit Iisvc2012
1/56
Objectives of shunt compensation
1. Mid point voltage regulation for line segmentation
Doubles the Pmax transmitted at the expense of increased reactive
power demand on the mid point compensator (and on the endgenerators)
2. End of line voltage support to prevent voltage instability.
3. Improvement of transient stability.
4. Power oscillation damping.
UNIT-II Shunt Compensation
7/27/2019 Unit Iisvc2012
2/56
Methods of controllable VAR generation
Static VAR generators vs Static VAR compensators
SVG : Is a self- sufficiently functioning device (unit) thatdraws controllable reactive current from an alternating power
source.
SVC : An SVG becomes an SVC when it is equipped withspecial system controls(external) which derive the necessary
reference for its input, from the operating requirements andprevailing variables of the power systems, to execute the desired
compensation of the transmission line.
7/27/2019 Unit Iisvc2012
3/56
Typical inputs to the SVG can be : The reactive current, impedance or power reference
signal that the SVG is to provide at its output.
Two broad categories of shunt connected SVGs
1) Variable impedance type SVGs
Eg : TCR, TSR, TSC, FC+TCR, TSC+TCR and
multilevel TSC and TCR banks
2) Switching converter type SVGs
Power converters (AC to DC or DC to AC) are operated as voltage and current
sources. These converters produce reactive power essentially without reactive energy
storage components by circulating alternating current among the phases of the AC
system (Static Synchronous Generators-SSG)
7/27/2019 Unit Iisvc2012
4/56
STATCOM (Static Compensator):
When an SSG is operated with an energy source, and with appropriate
controls to function as a shunt connected reactive compensator, it is known as
STATIC Synchronous Compensator (STATCOM)
Traditional methods of reactive power compensation:
1) Mechanically switched capacitor and/or inductor
2) Over or under excited synchronous m/c
3) Saturating reactors along with fixed capacitors
4) Semiconductor switch based VAR generators from 1970 onwards
7/27/2019 Unit Iisvc2012
5/56
FACTS controllers for shunt compensation
a) TSC
b) TCR
c) SVC (FC+TCR)d) SVC (TSC+TCR)
e) STATCOM
f) Hybrid compensators
7/27/2019 Unit Iisvc2012
6/56
a) Thyristor switched capacitor(TSC)
Switching surges
VAR control in steps
Switch closed when the Vin is equal
to the capacitor voltage
7/27/2019 Unit Iisvc2012
7/56
Simple control requirement (Fully in or fully out).
Response time around 2 cycles of input voltage.
VAR generated is proportional to the system voltage.
Large size & weight
No generation of harmonics
7/27/2019 Unit Iisvc2012
8/56
It consists of a fixed (usually air-core) reactor of
inductance L, and a bidirectional thyristor valve (or
switch) sw.
The current in the reactor can be controlled frommaximum (thyristor valve closed) to zero (thyristor
valve open) by the method of firing delay angle control.
That is, the closure of the thyristor valve is delayed
with respect to the peak of the applied voltage in each
half-cycle, and thus the duration of the current
conduction intervals is controlled.
b) THYRISTOR CONTROLLED REACTOR
(TCR)
7/27/2019 Unit Iisvc2012
9/56
Static VAR Compensator (SVC) or Fixed capacitor VAR compensator
(TCR+FC)
7/27/2019 Unit Iisvc2012
10/56
When =90o , L is fully in & hence there is no more controllability
In FC+TCR SVC, since
Smooth and step less control.
Complex control (Synchronization and presence of harmonics)
Low order harmonics are generated.
When =180o, L is out, current is zero
7/27/2019 Unit Iisvc2012
11/56
t
m
t
dttsinL
Vdi
00
1
min= 90o (w.r.t +ve zero crossing of Vs) => max IL1
& max = 180o
=> iL(t)=0 IL1=0.For < t < {ie 90 < < 180}
i.e. or
Brief analysis of TCR
ktL
Vi
m
cos1
7/27/2019 Unit Iisvc2012
12/56
Using Initial conditions,
At t=, i1=0.
=>
Boundary condition i1=0 at t=
=> =2- or +=2
V-I characteristics of TCR
With different firing angle
7/27/2019 Unit Iisvc2012
13/56
IL1=Fundamental component of Il
..Verify
Low efficiency.
Large passive elements.
)212
2(2
SinL
Vm
7/27/2019 Unit Iisvc2012
14/56
Conduction angle = -2
=90o to 180o measured from +ve zero crossing of Vin
7/27/2019 Unit Iisvc2012
15/56
L
Vm
2
)212
2(2
1)(
SinL
BL
IL1 () = fundamental component (peak) of iL ()
IL1 () varies from 0 at =180 to max at =90
BL () varies from 0 (at =180 to BL max at =90)
)2
12
2( SinL
Vm
Maximum RMS of inductor current (fundamental) is
Reactive admittance
7/27/2019 Unit Iisvc2012
16/56
Variation of normalised IL1() [or BL1() ] from 0 to 1p.u.
as a function of
7/27/2019 Unit Iisvc2012
17/56
Operating V-I area of (a) TCR (b) TSR TSR is identical (Similar) to TCR but is operated with fixed
firing angle, usually =90o or 180o
7/27/2019 Unit Iisvc2012
18/56
Harmonics with TCR:
where n=2k+1 & k=1,2,3etc
Triplen harmonics are
absent in delta balanced
connected system.
1
)()(4
)( 2n
nSinnCosnCosSin
nL
V
ILn
7/27/2019 Unit Iisvc2012
19/56
1. Multi-pulse TCR arrangement
By employing 12 pulse TCR arrangement 2 identical 3- TCRs, one fed
from a Y-connected winding (Transformer secondary) and the other
connected to a -connected secondary winding (of the same transformer
).
Harmonics generated in the two TCRs get cancelled due to the 30o
phase shift between the transformer secondaries.
Methods to reduce harmonics
7/27/2019 Unit Iisvc2012
20/56
2. Another method to reduce the harmonics is to employ Sequential
control of multiple TCR banks
7/27/2019 Unit Iisvc2012
21/56
Sequential control of multiple TCR banks
7/27/2019 Unit Iisvc2012
22/56
Case1. When v(wt)=vc0Then the current rises instantly to the steady
state value with infinite di/dt
Case2. When v(wt)vc0Then a large current flows to charge the
capacitor to bus voltage
In both cases, the SCRs fail to withstand the
stress.
Hence a small inductor is included in series.
7/27/2019 Unit Iisvc2012
23/56
7/27/2019 Unit Iisvc2012
24/56
L : is a small reactor to limit the surge current.
Let ; then
or
where
Peak(amplitude) of capacitor voltage is
Ignoring VL(t), the switch voltage is
Vsw=V-Vc (Varies from 0 to )
tSinVV m tCosLC
CVi m
21
tCosCn
nVti m )
1()(
2
2
L
C
X
X
LCn
21
2
1
12
2
n
nVV mC
12
2
2
n
nVm
7/27/2019 Unit Iisvc2012
25/56
Switching Transients with TSC
Typical cases of switching
b)Capacitor partially discharged
a)Capacitor fully discharged
7/27/2019 Unit Iisvc2012
26/56
Minimum transients if TSC is
switched ON at the instants when
capacitor residual voltage and the
applied AC voltages are equal.
Transient-free switching waveforms with TSC
7/27/2019 Unit Iisvc2012
27/56
Since the capacitor is normally discharged after the TSC is switched
OFF, the maximum possible delay in switching IN of the
TSC is one full cycle of the applied voltage.
7/27/2019 Unit Iisvc2012
28/56
Switching instants:
Case i: Vc < Vm
then the instant for the switching is when Vc = V i.e., Vsw = 0.
Case ii: If Vc > Vm
then the instant for the switching is when Vsw = min i.e., =0(min)
7/27/2019 Unit Iisvc2012
29/56
Fig : Operating V-I area
TCR OFF, TSC ON TCR ON, TSC OFF
BOTH OFF
Icmax ILmax0
7/27/2019 Unit Iisvc2012
30/56
Fixed Capacitor-Thyristor Controlled reactor FC TCR type SVG)
7/27/2019 Unit Iisvc2012
31/56
QL=VIL() ; Qc=VIc=Constant
QLmax = VIL(=90o)
Total (or net) reactive power Q=QL-Qc
Therefore Qmax
= VIL
(=90o) - VIc
Qmin= VIL(=180o) - VIc = -Qc
=0
7/27/2019 Unit Iisvc2012
32/56
for = 90o to 180o
212
2)( SinF
7/27/2019 Unit Iisvc2012
33/56
Inductor current control in TCR
7/27/2019 Unit Iisvc2012
34/56
FC TCR type SVG:
Dynamic response exhibits a time lag (due to firing delay
angle control) with respect to the input response.
The transfer function is of the form,
where k = Gain constant
Td = Transport lag (due to
control)
sTd
kesG
)(
7/27/2019 Unit Iisvc2012
35/56
Simplifying to a first order ,
Typically Tdmax = T/2 in a 1- case.
For a 6-pulse (3-) case,
Average Tdmax = T/6 for increasing current,
= T/3 for decreasing current.
sT
ksG
d
1)(
7/27/2019 Unit Iisvc2012
36/56
i. Capacitor Losses : small & constant
ii. Inductor losses : Vary as square of current
iii. Switching losses(scr) : Vary linearly with current
Losses in FC+TCR type SVG
7/27/2019 Unit Iisvc2012
37/56
Thus the total loss is small with higher capacitive VAR
output (as in case of pf correction in industry)
7/27/2019 Unit Iisvc2012
38/56
Effective, variable capacitive VAR (-Qc to +QL)
TSC-TCR type SVG (Single bank)
7/27/2019 Unit Iisvc2012
39/56
Multiple TSC and TCR(3-TSC 1-TCR type SVG)
Effective, variable capacitive VAR
(-3Qc to +QL)
7/27/2019 Unit Iisvc2012
40/56
Operation of the functional control scheme for (TSC-TCR) SVG
1. From the preset command of reactive power requirement
(+ve capacitive current of SVG), compute the inductive
current needed.
Therefore first estimate n since Ic = constant.
(Round up to next integer)
)(LFcref
Qref InIV
VARI
7/27/2019 Unit Iisvc2012
41/56
Then
Therefore control input to TCR control block is thus completed.
2. Transient-free , controlled switching IN of TSC bank(s).
Thyristors in TSC are switched ON when the voltage across them is
minimum.
3. TCR firing delay angle control.
CQrefLF nIII )(
7/27/2019 Unit Iisvc2012
42/56
Fig : Functional control scheme for (TSC-TCR) SVG
7/27/2019 Unit Iisvc2012
43/56
Fig : Transient- free switching strategy implementation
7/27/2019 Unit Iisvc2012
44/56
Vsw
= 1 when Vc
= V
PT = 1 when V = Vm
Vpol = 1 when
sign(V) = sign(Vc)
TSC turns ON if :
ON = 1 and Vsw = 1
or
ON = 1 and PT = 1 & Vpol = 1
7/27/2019 Unit Iisvc2012
45/56
Fig : Operating V-I area of TSC-TCR SVG with two TSC banks
7/27/2019 Unit Iisvc2012
46/56
With each switched-in
TSC bank, the losses
increase by a fixedamount.
7/27/2019 Unit Iisvc2012
47/56
Voltage control with SVC
SVC characteristics with voltage control
Slope or droop regulation
7/27/2019 Unit Iisvc2012
48/56
V-I characteristics of TCR with voltage control
7/27/2019 Unit Iisvc2012
49/56
V-I characteristics of FC-TCR with voltage control
7/27/2019 Unit Iisvc2012
50/56
Slope or Droop Regulation for Static VAr compensators
(SVC)
7/27/2019 Unit Iisvc2012
51/56
VRefLoad Line 1
Icmax ILmax
VsvcLoad Line 3
ILr
E2
Load Line 2
Icr
E1
Ic IL
BcmaxBLmax
Perfect Regulation or Flat characteristics implies
Poorly defined operating point
SVC overload limits are hit frequently for minor variation in operating voltage
Uneconomical load sharing when more devices are sharing load in parallel
7/27/2019 Unit Iisvc2012
52/56
Slope or Droop Regulation
In many applications ,the static compensator is not used as a perfect
terminal voltage regulator, but rather the terminal voltage is allowed to
vary in proportion with the compensating current. There are several
reasons for this.
1. The linear operating range of a compensator with a given maximum capacitive
and inductive ratings can be extended if a regulation droop is allowed .
2. Perfect regulation (zero droop or slope) could result in poorly operating point,
and a tendency of oscillation.
3. A regulation droop or slope enables automatic load sharing between staticcompensator as well as other voltage regulating devices connected in parallel.
7/27/2019 Unit Iisvc2012
53/56
1. Extended linear control range with Slope Regulation(K0)
VRefLoad Line 1
Icmax ILmax
Vsvc
Even for a range of E2 to E1, the SVC current range is reduced
with droop regulation
Ic IL
VLmaxV
cmax
VcmaxVLmax
ILmax
K=
Icmax
=
Load Line 2
Icr
E1
x
Load Line 3
ILr
E2
y
Bcmax BLmax
7/27/2019 Unit Iisvc2012
54/56
2. With Regulation Slope(K0)
Overload operation can be reserved for system disturbance conditions callingfor wider voltage range (E4 to E3) at the SVC bus. Thus the current limits are
not hit unduly
3 L d Sh i Wi h D R l i
7/27/2019 Unit Iisvc2012
55/56
3. Load Sharing With Droop Regulation
a) Two parallel connected SVCs at bus
b) Without droop same Vreffor both
two units operating at overload, countering
each other to maintain the same Vref (theoperation at A; is possible with SVC1 at B near
maximum and SVC2 at C on overload
c). With droopboth units are allowed to have
different Vreflevels
Both are well within their max limits, (for
operation at A, SVC1 is at B and SVC2 at C )
7/27/2019 Unit Iisvc2012
56/56