[email protected] Dhabi : +971 2 497 8600 Dubai : +971 4 381 9444
ULTRAFOG®HIGH PRESSURE WATER MIST SYSTEMGENERAL LAND APPLICATIONS
TABLE OF CONTENT
ABOUT US1. NOZZLE TYPES .................................................................................... 1.1 FM approved system.....................................................................................................
1.2 FM 5560..........................................................................................................................
1.3 OH1 - Office Building....................................................................................................
1.4 OH2 - Parking Garage...................................................................................................
1.5 OH3 - Store, Compact Storage and Rack Store.........................................................
1.6 OH4 - High Ceiling up to 12m.....................................................................................
1.7 Nursing Home................................................................................................................
2. SYSTEM SCHEMES ............................................................................. 2.1 MPU335 System.............................................................................................................
2.2 Micro Pump System.......................................................................................................
2.3 Master Pump System.....................................................................................................
2.4 MPU335 System driven by Batteries Pack..................................................................
2.5 MPU335 System driven by Diesel Generator.............................................................
2.6 System with Diesel Engine Pump................................................................................
2.7 Accumulator System......................................................................................................
2.8 Accumulator System for Deep Fat Fryer.....................................................................
2.9 Fire Hose Lance System................................................................................................
2.10 Fire Hose Lance with Foam System...........................................................................
2.11 Transformer Protection System (inside Building)....................................................
2.12 Turbine Enclosure Protection System.......................................................................
0304
05
06
07
08
09
10
1112
13
14
15
16
17
18
19
20
21
22
23
02.SIBCA - FIRE PUMPS
The sprinkler nozzle in Ultra Fog sprinkler system is used to create water mist from pressurised water. There are two main types of nozzle in the Ultra Fog system but common to both is the way the water mist is created. In the Ultra Fog nozzle the water is pressed through small grooves in a washer which create jets of water which collide, to create even smaller droplets and provide more effective fire extinguishing.
Both nozzle types are available in models that are to be mounted either with the piping inside a wall or ceiling or on the surface of a wall or ceiling. The nozzles can be coated or painted in almost any colour metallic finish. As standard, the nozzles are made of polished stainless steel. As an option nozzles are available in higher grades of stainless steel with increased (C5) corrosion resistance.
1. NOZZLE TYPES
03.SIBCA - FIRE PUMPS
1. NOZZLE TYPES
Occupancies Hazard Category 1 (HC-1)(Hotel, Hospital, Commercial Offices)
Features:
• Unique patented design with high performance for cooling effect and low consumption of water.• Easy to install and test for both commissioning and maintenance.• 603 nozzle body is supplied with an M20 thread for ease of installation.• Nozzle tools and spares are available for maintenance.• Working pressure – 65 bar.• A unique feature of Ultra Fog nozzles is that they can be tested, drained, and flushed without breaking the frangible glass bulb. No other manufacturer provide this feature.• Ultra Fog is the only company that can test the nozzle without breaking the frangible glass bulb. breaking the frangible glass bulb.• Standard FM 5560 LH Nozzle.• Approval number: 3043823 in progress. FM HC1 approved nozzle is 603-300-061-B-F, includes pump and section valves. and section valves.
Technical Data:
*The distance from the wall is about 1/2 of the spacing. Detailed instructions included in installation guidelines manual
603-300-061-B-F 4,5m * Up to 5m 21m2 Ceiling 3,61Flow at 65bar
29.1 L/min
NozzleType
Spacing(C-C)
CeilingHeight
CoveringArea Mounting K Value
(K=) Flow Rate
1.1 FM APPROVED SYSTEM
04.SIBCA - FIRE PUMPS
1. NOZZLE TYPES
Turbines and Machinery Enclosures(Engine Room, Generator Room,Turbine Generators)
Features:
• Unique patented design with high performance for cooling effect and low consumption of water.• Easy to install and test for both commissioning and maintenance.• 202 open nozzle, in high quality stainless steel.• Nozzle tools and spares are available for maintenance.• Working pressure – 100 bar.• FM 5560 Turbines and Machinery Enclosures.
Technical Data:
*The distance from the wall is about 1/2 of the spacing. Detailed instructions included in installation guidelines manual
202-073-0-F 4 5 260 100 0.73 7.3
202-073-0-F 3.3 5 500 100 0.73 7.3
202-209-0-F 5 11 1315 100 0.73 2.09
202-209-0-F 12Wall
mounted(horizontal)
1320 100 0.73 2.09
NozzleType
Spacing(C-C)
CeilingHeight
Max EnclosureVolume (m3)
WorkingPressure (bar)
K Value(K=) Flow Rate
1.2 FM 5560
05.SIBCA - FIRE PUMPS
1. NOZZLE TYPES
Features:
• Unique patented design with high performance for cooling effect and low consumption of water.• Easy to install and test for both commissioning and maintenance.• 603 nozzle body is supplied with an M20 thread for ease of installation.• Nozzle tools and spares are available for maintenance.• Working pressure – 82 bar.• A unique feature of Ultra Fog nozzles is that they can be tested, drained, and flushed without breaking the frangible glass bulb. No other manufacturer provide this feature.• Ultra Fog is the only company that can test the nozzle without breaking the frangible glass bulb. breaking the frangible glass bulb.• Standard EN-CEN/TS 14972:2011.• Fire test report reference number: DFL 140508-142
Technical Data:
*The distance from the wall is about 1/2 of the spacing. Detailed instructions included in installation guidelines manual
603-260-160-B 5,3m * 4m 28m2 Ceiling 4,2Flow at 80bar
38 L/min
NozzleType
Spacing(C-C)
CeilingHeight
CoveringArea Mounting K Value
(K=) Flow Rate
1.3 OH1 - OFFICE BUILDING
06.SIBCA - FIRE PUMPS
EXPLODED VIEW 1. NOZZLE TYPES
Occupancies Hazard Category 1 (HC-1)(Hotel, Hospital, Commercial Offices)
Features:
• Unique patented design with high performance for cooling effect and low consumption of water.• Easy to install and test for both commissioning and maintenance.• 603 nozzle body is supplied with an M20 thread for ease of installation.• Nozzle tools and spares are available for maintenance.• Working pressure – 100 bar.• A unique feature of Ultra Fog nozzles is that they can be tested, drained, and flushed without breaking the frangible glass bulb. No other manufacturer provide this feature.• Ultra Fog is the only company that can test the nozzle without breaking the frangible glass bulb. breaking the frangible glass bulb.• Standard IMO MSC1 Circ. 1272, CEN/TS 14972 Annex B.• Fire test report reference number: 01.16351.01.003
Technical Data:
*The distance from the wall is about 1/2 of the spacing. Detailed instructions included in installation guidelines manual
603-300-035-B 5m * Up to 2,5m 25m2 Ceiling 3,35Flow at 100bar
33.5 L/min
603-260-160-B 4m * Up to 5m 16m2 Ceiling 4,2Flow at 100bar
42 L/min
NozzleType
Spacing(C-C)
CeilingHeight
CoveringArea Mounting K Value
(K=) Flow Rate
1.4 OH2 - PARKING GARAGE
07.SIBCA - FIRE PUMPS
603-260-160-B 3,5m * 5m 13m2 Ceiling 4,2Flow at 100bar
42 L/min
603-260-230-B
Compact storage
Rack store 3,5m * 5m 13m2 Ceiling 4,9Flow at 100bar
49 L/min
NozzleTypeSettings Spacing
(C-C)CeilingHeight
CoveringArea Mounting K Value
(K=) Flow Rate
1. NOZZLE TYPES
(Shopping Centers)
Features:
• Unique patented design with high performance for cooling effect and low consumption of water.• Easy to install and test for both commissioning and maintenance.• 603 nozzle body is supplied with an M20 thread for ease of installation.• Nozzle tools and spares are available for maintenance.• Working pressure – 100 bar.• A unique feature of Ultra Fog nozzles is that they can be tested, drained, and flushed without breaking the frangible glass bulb. No other manufacturer provide this feature.• Ultra Fog is the only company that can test the nozzle without breaking the frangible glass bulb. breaking the frangible glass bulb.• VdS Schadenverhütung Draft Fire test Store OH3, Standard EN 12845, CAE 4001• Fire test report reference number: SWRI 01.16351.07.010
Technical Data:
*The distance from the wall is about 1/2 of the spacing, if the room is up to 13m2 the nozzle will be placed in the center of the room. Detailed instructions included in installation guidelines manual.
1.5 OH3 - STORE, COMPACT STORAGE AND RACK STORE
08.SIBCA - FIRE PUMPS
1. NOZZLE TYPES
(Cinemas, Theatres, TV Studios)
Features:
• Unique patented design with high performance for cooling effect and low consumption of water.• Easy to install and test for both commissioning and maintenance.• 603 nozzle body is supplied with an M20 thread for ease of installation.• Nozzle tools and spares are available for maintenance.• Working pressure – 100 bar.• A unique feature of Ultra Fog nozzles is that they can be tested, drained, and flushed without breaking the frangible glass bulb. No other manufacturer provide this feature.• Ultra Fog is the only company that can test the nozzle without breaking the frangible glass bulb. breaking the frangible glass bulb.• Standard EN-CNT/TS 14972-B, EN 12845, CEA 4001 OH4.• Fire Test report reference number: SWRI 01.16351.01.009.
Technical Data:
*The distance from the wall is about 1/2 of the spacing, if the room is up to 20m2 the nozzle will be placed in the center of the room. Detailed instructions included in installation guidelines manual.
603-260-160-B 4,5m * Up to 12m 20m2 Ceiling 4,2Flow at 100bar
42 L/min
NozzleType
Spacing(C-C)
CeilingHeight
CoveringArea Mounting K Value
(K=) Flow Rate
1.6 OH4 - HIGH CEILING UP TO 12M
09.SIBCA - FIRE PUMPS
1. NOZZLE TYPES
Features:
• Unique patented design with high performance for cooling effect and low consumption of water.• Easy to install and test for both commissioning and maintenance.• 603 nozzles are supplied with a star lock for easy mounting.• 603 nozzle body can be supplied as threaded M20 with optional nut• Nozzle tools and spares are available for maintenance.• Working pressure – 100 bar.• A unique feature of Ultra Fog nozzles is that they can be tested, drained, and flushed without breaking the frangible glass bulb. No other manufacturer provide this feature.• Ultra Fog is the only company that can test the nozzle without breaking the frangible glass bulb. breaking the frangible glass bulb.• Our system apply with INSTA 900 and the nozzle pass the fire test in according INSTA 900-3: 2012.• Fire test report reference number: DFL 140508-138.
Technical Data:
*The distance from the wall is about 1/2 of the spacing, if the room is up to 13m2 the nozzle will be placed in the center of the room. Detailed instructions included in installation guidelines manual.
**Can by higher.
603-08-B 3,5m * 2,5m ** 13m2 Ceiling 0,8Flow at 100bar
8 L/min
NozzleType
Spacing(C-C)
CeilingHeight
CoveringArea Mounting K Value
(K=) Flow Rate
1.7 NURSING HOME
10.SIBCA - FIRE PUMPS
EXPLODED VIEW02. SYSTEM SCHEMES
2.8 ACCUMULATOR SYSTEM FOR DEEP FAT FRYER
*For large Deep Fat Fryer system accumulators can be replaced with pump unit.**Power supply for Deep Fat Fryer will be disabled automatically by Control Box after system activation.
19.SIBCA - FIRE PUMPS
UNITED ARAB EMIRATESABU DHABI - HEAD OFFICE
P.O. Box 46944, Abu Dhabi, UAESIBCA Building Behind Etisalat T & A BuildingQuba Street - KhalidyaTel: +971 2 497 8600Fax: +971 2 497 8700Email: [email protected]
AL AINP.O. Box 19318, Al Ain, UAE403, Building No. 43, Oud Al Touba StreetTel: +971 3 751 8080Fax: +971 3 751 9280Email: [email protected]
DUBAIP.O. Box 55472, Dubai, UAE
nd Floor, Vision Tower, Business Bay.Tel: +971 4 381 9444Fax: +971 4 381 9445Email: [email protected]
2
SHARJAHP.O.Box 5608, Sharjah, UAE1004, Al Mulla Tower, Al Nahda.Tel: +971 6 502 8555Fax: +971 6 502 8500Email: [email protected]
MANAMAP.O. Box 5703Office 12, MSCEB Bldg. 123, Road 402,Manama 304, Kingdom of BahrainTel: +973 172 12639Fax: +973 172 12638Email: [email protected]
KINGDOM OF BAHRAINLumiere, Sasthamangalam,Thiruvananthapuram, Kerala
INDIA
AJMANP.O. Box 22563 , Ajman, UAE1901, D Block, Horizon TowerTel: +971 6 538 2117Email: [email protected]
UMM AL QUWAINP.O. Box 5608, Uaq, UAE2, Malik Faisal RoadTel: +971 6 539 5879Email: [email protected]
RAS AL KHAIMAHP.O. Box 12480, Rak, UAEAl Oraibi, Al Rams Road, Ras Al Khaimah, UAETel: +971 7 236 1003Fax: +971 7 228 0445Email: [email protected]
FUJAIRAHP.O. Box 22563, Fujairah, UAE1001, Emirates Islamic Bank BuildingTel: +971 9 222 1816Email: [email protected]
CONTACTUS
24.SIBCA - FIRE PUMPS