Upload
others
View
5
Download
0
Embed Size (px)
Citation preview
UG-1056 NPC eCAP-9040
User's Guide
December 2018
NPC eCAP-9040 User's Guide UG-1056
Copyright © 2017 by QEI
NPC eCAP-9040 User's Guide ALL RIGHTS RESERVED
NOTICE
The information in this document has been carefully checked and is believed to be accurate. However, no responsibility is assumed or implied for inaccuracies. Further-more, QEI, reserves the right to make changes to any products herein described to improve reliability, function or design. QEI does not assume liability arising the application or use of any product or circuit described herein; neither does it convey any license under its patent rights nor the rights of others.
This manual and all data contained constitutes proprietary information of QEI and shall not be reproduced, copied or disclosed to others, or used as the basis for manufacture without written consent of QEI.
45 Fadem Road Springfield, NJ 07081 Phone: (973) 379-7400 Fax: (973) 379-2138 Web Site: wwwqeiinc.com
http://www.cgautomationusa.com/
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Revisions i
Revisions
Revision Description Date
A Release July 2007
B Updated Formatting October 2012
C
D
Updated Formatting
Updated QEI Address
May 2017
December 2018
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Introduction 3
Contents
1. Introduction ..............................................................................4 1.1 Specifications ......................................................................... 5
1.1.1 Size ......................................................................... 5 1.1.2 Temperature Sensor ............................................... 5 1.1.3 Operation Counter .................................................. 5 1.1.4 Current Sensor ....................................................... 5 1.1.5 Capacitor Switch Relays ......................................... 5 1.1.6 Supply Voltage ........................................................ 5 1.1.7 Line Frequency ....................................................... 5 1.1.8 Local Switching Strategy ........................................ 5 1.1.9 Power Consumption ............................................... 5 1.1.10 Environment ............................................................ 5 1.1.11 Case ........................................................................ 5 1.1.12 Radio: ...................................................................... 6 1.1.13 Radio Power Supply ............................................... 6
2. Installation ................................................................................7 2.1 Making Connections .............................................................. 7 2.2 Grounding .............................................................................. 7 2.3 4-Wire System Installation ..................................................... 8 2.4 Line Current Measurement .................................................. 10 2.5 Meter Socket Mounting ........................................................ 11
3. Hardware Description ............................................................12 3.1 Front Panel Layout ............................................................... 12
3.1.1 Fuses and Fuseholders ........................................ 15 3.1.2 Battery ................................................................... 15 3.1.3 Clock ..................................................................... 15
4. Operation ................................................................................17 4.1 Navigating the LCD Display – an Example: ......................... 17 4.2 Live Values ........................................................................... 19 4.3 Local Switching Strategy Configuration ............................... 20 4.4 Other Configuration Settings ............................................... 22 Other Configuration Settings (contd.) ........................................... 23 Other Configuration Settings (contd.) ........................................... 24
5. Misc Technical Data ...............................................................25 5.1 Communications Board........................................................ 27
5.1.1 Jumpers - Factory Configuration .......................... 27 5.1.2 TX / RX LEDs ...................................................... 28 5.1.3 Setting the Baud Rate .......................................... 29
5.2 Radio Interface Board .......................................................... 29 5.2.1 DB9 RS-232 Cable: .............................................. 31
5.3 Local/Remote Front Panel Switch ....................................... 32
6. DNP3 Device Profile w/Point List ..........................................33 Version 1.0 .................................................................................... 33
NPC eCAP-9040 User's Guide UG-1056
4 Introduction Copyright © 2017 QEI
1. Introduction
The NPC eCAP-9040 is part of QEI’s family of Capacitor Bank Controllers. The eCAP contains a Telemetric DNP-RTM (Remote Telemetry Module). The SCADA analog, status, and control points are remotely accessible through this module.
The eCAP is designed to monitor the AC line voltage and current. Measurement data and controls are accessed via the Telemetric DNP-RTM and website. A local switching strategy is available via auto failover, should SCADA communications be interrupted. The local switching strategy includes a time schedule to switch the bank on or off-line, based on temperature, with high/low voltage overrides.
The eCAP can be commanded to switch the cap bank on or offline via the remote SCADA operation. The remote operation allows monitoring of many measured and calculated values. See the DNP profile document for further information.
eCAP contains a real-time clock/calendar, and a temperature sensor as standard equipment.
The eCAP keeps historical information in non-volatile memory. It maintains an operations log and a history of the measurements taken of the monitored circuit. The measurement history is optionally saved as 1, 2, 5, or 15 minute averages. Enough information is saved so that a complete operating history is available.
eCAP can be set up and operated via a serial link to a typical laptop computer (or other PC), running QEI=s ANPC SmartWare@ program.
The eCAP front panel has an AAuto/Manual@ switch and an AOpen/Close@ switch.
Five LED indicators are included. A yellow LED indicates Local Auto Mode (LED is on) or Remote Mode (LED is blinking) or Manual Mode (LED is off). A red LED indicates that the last Cap Bank operation was CLOSE (red LED is on), or OPEN (green LED is on). A flashing OPEN or CLOSE LED indicates a pending operation.
A panel mounted 9 pin female RS232 connector allows the eCAP to be connected to a laptop (or any PC with a standard 9-pin serial port) using a standard one-to-one 9-pin serial port cable. A switch labeled “Remote/Local” is used to place the eCAP under control of a laptop PC (Local) or under SCADA control (Remote). Two red LEDs indicate data transmit/receive (Tx/Rx) when the switch is in the “Remote” state.
Internal timers and logic in the eCAP protect user and equipment from undesired and non-secure operations. Using timers and logic, the controls can prevent unsafe operations. Internal timers also allow the user to initiate local operations and leave the vicinity of the control before the switching operation occurs. Emergency voltage overrides provides bypass of long timers.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Introduction 5
1.1 Specifications
1.1.1 Size
Height 12", Width 10", Depth 7.5"
1.1.2 Temperature Sensor
0 to 140F (-15 to 60C)
1.1.3 Operation Counter
Internal software counter
1.1.4 Current Sensor
Line Post Sensors: Fisher Pierce 1301-x1A, x7A, Lindsey TrueCT, Multicore (sensors not included with the control)
1.1.5 Capacitor Switch Relays
Electro-mechanical relays rated at 20 amps continuous duty at 240 VAC.
1.1.6 Supply Voltage
120 VAC. The supply voltage is also used to sense the line voltage.
1.1.7 Line Frequency
60 Hz
1.1.8 Local Switching Strategy
Time, Temperature, Voltage: defaults are as follows:
Between the hours of 9AM and 9PM, the control will operate the bank based on temperature (close at 95 degrees, open at 80 degrees) with voltage overrides of 116.0 volts and 126.0 volts.
1.1.9 Power Consumption
3 VA, not including communications transceiver.
1.1.10 Environment
-40F to 149F (-40C to 65C) Temperature; 95% Humidity (non-condensing)
1.1.11 Case
NEMA 4 rated, weatherproof outdoor type.
NPC eCAP-9040 User's Guide UG-1056
6 Introduction Copyright © 2017 QEI
1.1.12 Radio:
Telemetric DNP-RTM.
1.1.13 Radio Power Supply
Input: 90-264VAC 50/60Hz.
Output: +12Vdc @ 2.5 Amps.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Installation 7
2. Installation
2.1 Making Connections
The diagram below shows how to connect the eCAP to the capacitor bank switches, the 120VAC transformer, the line post current sensor, and Neutral Current CT. The 120VAC transformer furnishes the power to the eCAP and also serves as the voltage sensor for the control.
2.2 Grounding
Proper grounding is critical when wiring a QEI eCAP. The neutral of all elements (the capacitor switches, the 120VAC transformer, the Line Post Sensor, should be connected to a common point in a junction box on the near the top of the pole. A separate ground wire should run down the pole to a ground rod driven into the soil at
the base of the pole. The earth ground must not be connected at or through the
eCAP. The diagram on the next page illustrates the correct method of connecting the eCAP and grounding.
NPC eCAP-9040 User's Guide UG-1056
8 Installation Copyright © 2017 QEI
2.3 4-Wire System Installation
The installation block diagram for a 4-Wire system is shown below. Please note the following installation guidelines for proper installation of the eCAP units on a 4-Wire system.
The placement of the LPCS (Line Post Current Sensor) must be located in between the Source and Capacitor Bank for proper electrical VAR sensing.
All components must be star grounded at the Neutral Support Point shown in the 4-Wire System Installation Pictorial Diagram below.
Voltage and Current signals should come from the same phase on a 4-Wire System in order for the eCAP to indicate correct electrical value readings. If this is an inconvenience, please consult the factory for recommendations.
4-Wire System Block Diagram
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Installation 9
4-Wire Installation Pictorial
NPC eCAP-9040 User's Guide UG-1056
10 Installation Copyright © 2017 QEI
2.4 Line Current Measurement
The eCAP current measurement input accepts a line post current sensor (LPCS). The following types are supported: Fisher-Pierce Series 1301-x1A, x7A, Lindsey “TrueCT” or Lindsey “Multicore” (or any LPCS with a 60 amps/volt input to output ratio). The outputs from these devices are monitored directly by the eCAP control unit.
WARNING: Do not connect a CT to the eCAP-9040. Connecting a CT may result in unit damage.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Installation 11
2.5 Meter Socket Mounting
Verify that the eCAP unit matches the available socket on the utility pole. The sticker on the inside of the unit cover shows the required socket connections. The view on the sticker is looking into the meter socket on the pole.
Units should be secured in place with a locking collar (not provided) to prevent the eCAP from being removed from its socket by unauthorized personnel.
NPC eCAP-9040 User's Guide UG-1056
12 Hardware Description Copyright © 2017 QEI
3. Hardware Description
3.1 Front Panel Layout
The following two pages show the location of all front panel switches, indicators, and controls. A description of each item appears on the following pages.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Hardware Description 13
# ITEM DESCRIPTION
1 Display Contrast This control is used to adjust the contrast on the LCD Display. Turning the control clockwise makes the display contrast darker.
2 Two Line LCD
Display
This 2 line x 16-character display is used for a number of functions. It is used to enter switching algorithms, review and set configuration items and parameters, and to view actual operating conditions. The function of the display depends on the menu item selected. For more detailed information, consult the description of menu item functions.
3 UP / DOWN Switch This switch has several uses: When on a non-numeric item, it is used to select the desired setting. When on a numeric item, it increments or decrements the highlighted value.
4 x10 / ÷10 Switch This switch is used to multiply or divide a numeric value by 10 thereby shifting the value one digit to the left or right. This switch in conjunction with the Modify Up/Down switch is used to enter numeric values.
5 RIGHT/ LEFT Switch This switch has two uses: When the main menus are displayed, this switch moves forward and backward through the main menus. When a sub-menu item is displayed, this switch moves the cursor to the right or left on the display.
6 MENU/ ITEM Switch This switch is used to navigate around the eCAP displays. Use ITEM to navigate from any main menu selection to its’ associated sub-menus. Use MENU to navigate back to the main menu selection from the sub-menus. A main menu selection is any screen numbered “01>” through “23>”.
8 Operating Mode
LED (Yellow)
A yellow LED to the left of the AUTO switch indicates if the control is in auto or manual mode as follows:
ON (Continuous): Auto Mode (Local) ON (blinking): Remote Mode OFF: Manual mode
9 AUTO / MANUAL
Switch
This switch sets the local operating mode to AUTO or MANUAL. When in AUTO mode, the eCAP operates via SCADA control (Remote Mode) or via a settable local switching strategy if communications fails.
10 CLOSE / OPEN
Switch
This switch is used in local Manual mode to switch the capacitor bank on-line or off-line. Timers delay manual operation to allow the user to walk away from the bank after initiating a manual mode operation. The timer is 10 seconds for an OPEN operation, and 45 seconds for a CLOSE operation. A re-close block timer for cap discharge will delay the manual CLOSE operation for up to 5 minutes, immediately following an OPEN operation.
NPC eCAP-9040 User's Guide UG-1056
14 Hardware Description Copyright © 2017 QEI
# ITEM DESCRIPTION
11 Capacitor Bank
Switch State LEDs
These Red and Green LEDs adjacent to the Close/Open switch indicate the state of the capacitor bank switch:
Red LED On - The last operation performed was a CLOSE operation.
Red LED Blinking – A CLOSE operation is pending. The capacitor bank will be CLOSED after any delay timers have expired.
Green LED On - The last operation performed was an OPEN (Trip) operation.
Green LED Blinking – An OPEN operation is pending. The capacitor bank will be OPENED (tripped) after any delay timers have expired.
12 RS232 Port This 9-pin female D-sub connector is used to connect the eCAP to a laptop computer. Using Smartware, the user can change many of the eCAP settings, and view real-time data.
13 Line, Neutral,
Current, +12VDC,
Common
Test Jacks
These terminals are used connect the control to a meter that is used in checking the control. A multimeter set to 200VAC scale between the NEUTRAL and VOLTAGE test points measures the actual AC line voltage. A multimeter set to 20 VAC scale between NEUTRAL and CURRENT measures the actual output of the line post sensor into the eCAP (1Vrms in = 60 Amps of primary phase current).
14 Temperature Sensor An external temperature sensor is mounted at the bottom of the eCAP. The sensor allows for the unit to switch the Cap Bank OPEN or CLOSED based on environmental temperature. Range = 0 to 140F.
15 Local/Remote
Switch LOCAL - When the switch is in this position, a laptop
PC can be connected to the front panel RS232 port to configure, monitor, or control the eCAP (Using QEI’s “SmartWare” software.)
REMOTE – When the switch is in this position, the eCAP is monitored and controlled via SCADA communications (through the Telemetric DNP-RTM.) The front panel RS232 port should not be used when the switch is in this position.
16 TX/RX LEDs These LEDS indicated SCADA communication status. TX= data transmitted from the eCAP. RX= data received by the eCAP.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Hardware Description 15
3.1.1 Fuses and Fuseholders
There are three fuses associated with the eCAP. A 10 Amp Slo-Blo type 1-1/4 inch cylinder fuse (QEI No. 10-003669-028) is located in the front panel fuseholder (item 17 in the front panel pictorial). Another fuse is a ¼ Amp 5 x 20mm slo-blo type fuse (QEI No. 10-003669-044, Littlefuse 218.250) on the lower (larger) printed circuit board located underneath the front panel. If the control were inoperative, one of the first steps would be to verify that either of these fuses is not blown. A third fuse is a 2 Amp 5 x 20mm located on AC input of the internal +12VDC radio power supply. Both of the 5 x 20mm fuses are accessed by opening the hinged front panel of the eCAP.
3.1.2 Battery
Each of the two eCAP circuit boards has a +3 VDC lithium battery installed. The batteries maintain the clock, and trending (historical data) memory, when power is removed from the eCAP. The circuit boards are accessed by opening the hinged front panel of the eCAP, so that the rear of the front panel is viewed. On the lower (larger) circuit board , there is one battery labeled B1, and it is installed in the upper left corner of the board. The second battery is located on the upper (smaller) printed circuit board. This battery is labeled BH1 and is located in the upper right corner. The maximum life expectancy of the lithiums in-circuit is 4 years, when the eCAP is in a non-powered state, and 10 years in a powered state. Customer may request for replacement from the factory. The manufacturer and model of the batteries is:
Manufacturer: Renata
Model Number: CR1225
3.1.3 Clock
The eCAP has a battery backed internal clock/calendar, which can automatically adjust for daylight savings time. The battery keeps the clock running when the unit is in a non-powered state.
NPC eCAP-9040 User's Guide UG-1056
16 Copyright © 2017 QEI
The eCAP has a front panel RS-232 port, which can be connected to a laptop PC (with QEI’s “SmartWare” software installed and running on the PC) for configuration of the eCAP-9040, and for viewing measurements, etc. in real-time.
Additionally, the eCAP has a Hardware Interface, which is a set of four toggle switches and an LCD Display. The Hardware Interface can be used to set up many of the operating parameters directly from the front panel, without the use of a computer. This may allow for easier setup in the field.
The toggle switches are used to navigate the various configuration menus, and to view the measured/calculated values (i.e., Volts, current, kVAr, kW, etc.) in real time.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Operation 17
4. Operation
4.1 Navigating the LCD Display – an Example:
1) Making sure that the eCAP AUTO/MANUAL switch is set to MANUAL, apply power to the eCAP.
2) Two self tests run (visible on display): one for Flash Memory, another for RAM. The Auto/Manual (Yellow) and the Open/Close (Green/Red) Leds will turn on and off (lamp test) during the self-tests. After the self tests complete, the startup banner appears on the eCAP-9040 display. After the self-tests complete, a start up banner will appear, indicating the firmware version, current sensor type, and maximum line current.
QEI ECap NPC:1.0
FLPS 0-180 Amps
3) Press the MENU switch once to go the main menus (numbered “01>” thru “23>”.
01>Live Values
Voltage, Current
4) Press the RIGHT switch 8 times to navigate to the following main menu selection:
09>Hrdwre Config
Line Volts/Freq
5) Press the ITEM switch to navigate to the Line Volts/Freq sub-menu: V Sec. Freq 120 60
NPC eCAP-9040 User's Guide UG-1056
18 Operation Copyright © 2017 QEI
6) Notice that the cursor is now flashing over “120”. This indicates that the value can be changed. In any sub-menu, if the cursor is not blinking, the value is fixed, and cannot be changed.
7) Press the RIGHT switch to move the cursor to the right.
8) Notice that the cursor has moved over to “60”, and is blinking. This indicates the value can be changed.
9) Use the LEFT and RIGHT switches to move the cursor back and forth between “120” and 60”. Stop back at “60”
9) Use the UP switch to change the frequency from 60Hz to 50 Hz.
10) Use the DOWN switch to set the frequency back to 60 Hz (The UP switch would also work to change the value back, since there are only two choices (50 or 60Hz).
11) Use the LEFT switch to move back to “120”.
12) Use the DOWN switch twice to set the voltage to “240”, then back to “120” (the UP switch, would work here to change the value back, since there are only two choices (120 or 240Volts).
13) Use the MENU switch to navigate back to the main menus.
14) Press the RIGHT switch 11 times (or the LEFT switch 12 times to go to the following main menu selection:
20>Misc. Config
Unit ID
15) Press the ITEM switch to navigate to the Unit ID sub-menu: Unit ID Number 1 16) Press the UP switch 3 times to change the ID number from 1 to 4. 17) Press the X10 switch twice to increase the unit ID from 4 to 400. 17) Press the ÷10 switch twice to change the number from 400 to 4. 18) Press the DOWN switch 3 times to change the number from 4 to 1. 19) Press the MENU switch to go back to the main menus, then use the RIGHT or LEFT switch to browse the various main menu selections (numbered “01>” through “”23>”). The example above gives a general idea of navigation. Some main menu selections contain multiple sub-menus. In that case, a sub-menu may contain a “>>” symbol. This indicates that another sub-menu is located below the present sub-menu. Use the ITEM switch to go from the present sub-menu display, down to the next sub-menu display.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Operation 19
4.2 Live Values
The eCAP-9040 monitors the line voltage, phase current, phase angle and ambient temperature. Using the voltage, current, and phase angle, it computes kW, kVAr, PF (power factor) etc. Many of the monitored and computed values are visible through the front panel LCD display, accessible from menus labeled “01>” through “08>”, and called “Live Values”. The table below list the displays, and gives an explanation of each.
Menu Item Submenu Item Format Comments
QEI ECap NPC:1.0
FLPS 0 - 180 Amps
Startup Banner, appears at power up.
01>Live Values
Voltage, Current Volts VCor Cur 124.5 125.5 50
Real-time voltage and current. The VCor value (Voltage Corrected) is the predicted voltage rise (or drop) with a 25% margin used by the eCAP for voltage override purposes.
02>Live Values
kW, kVAr, PF kW kVAr PF 2485 514 98
Real-time kilowatts, kVAr, and power factor .
03>Live Values
Temperature Ambient Temp 82 F
Real-time measured temperature from sensor at bottom of enclosure.
04>Live Values
Switch Status Status Pending Closed Open
“Status” shows last operation performed. “Pending” shows any operation that is in progress, but hasn’t yet occurred.
05>Live Values
Operating Mode Comm Local Auto Manual
“Comm” shows the SCADA set operating mode (Auto or Remote). Local shows the state of the front panel Auto/Manual toggle switch.
06>Live Values
Operations Count Today Op Count 4 122
“Today” shows the daily count (resets at midnight). “Op count” is total count since installation (can be reset via SCADA.
07>Live Values
Reason Last Op Last Operation Temp Lo Open
Shows the operation performed (Close or Open) and the reason.
NPC eCAP-9040 User's Guide UG-1056
20 Operation Copyright © 2017 QEI
4.3 Local Switching Strategy Configuration
A local switching strategy is entered into the eCAP. The strategy is in effect whenever the eCAP has no SCADA communications. If the eCAP has SCADA communications, it can be set via SCADA to operate in Remote Mode (eCAP under SCADA control), or in Auto mode (use the local switching strategy). Additionally, if in Remote Mode and SCADA communications fails, the eCAP can be set to automatically failover to the local switching strategy.
Menu Item Submenu Item Format Comments
08>Switch Mode
Switching Setup
Switch On Volts, Tmp, Time >>
Selects the desired switching strategy. Can be set to “Volts, Tmp Time”, “Tmp, Time”, or “Volts, Time”.
Volt Lo Volt Hi 116.0 126.0 >>
Sets the low (close) and high (open) voltage limits used in the switching strategy.
Volt Lo Volt Hi Yes Yes >>
Separate enables for low and high voltage limits.
EOVR Lo EOVR Hi 115.0 129.0 >>
Emergency low and high voltage overrides . These limits bypass the long interval timer that would normally be in effect for the voltage limits in Auto Mode (10-60 minutes, configurable). If enabled these limits are in effect regardless of the time schedule or other switching strategy settings.
Emer. Voltage OR Enabled >>
Enable for emergency voltage override feature.
Time1 Time2 09:00 21:00
Defines the start time and end times for the time schedule.
Not Time Period Stay: Open >>
“Stay:” indicates the cap bank position that will be set when the switching strategy time schedule is not active (i.e., when the present time is outside of the scheduled time period).
The voltage limits (if enabled) will prevent switching when entering or leaving the scheduled time period, if opening the bank would cause the voltage to fall too low, or closing would cause the voltage to rise too high.
Temp: Open Close 80 95
Sets the low (open) and high (close) temperature limts used in the switching strategy.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Operation 21
Three local switching strategies are available:
1) Volts, Temperature, Time – When the present time is within the scheduled time period, switch the bank based on low/high temperature limits, with low/high voltage override.
2) Volts, Time -- When the present time is within the scheduled time period, switch the bank based on low/high voltage limits.
3) Temp, Time -- When the present time is within the scheduled time period, switch the bank based on temperature.
For all three switching strategies, the EOVR (emergency voltage overrides) are in effect (if enabled). The emergency overrides bypass the 60 minute Anti-Hunt timer (see main menu selection “19>Misc. Config, Max Ops per Day” ).
The local switching strategy voltage limits (if enabled) also function when in SCADA remote mode. In this case, the limits will override SCADA commands, and prevent the bank from being switched remotely, if closing the bank would cause the voltage to rise above the high limit, or opening the bank would cause the voltage to fall below the low limit.
NPC eCAP-9040 User's Guide UG-1056
22 Operation Copyright © 2017 QEI
4.4 Other Configuration Settings
Menu Item Submenu Item Format Comments
09>Hrdwre Config
Line Volts/Freq
VSec. Freq 120 60
Sets the line voltage (120/240V) and line frequency (50/60Hz).
10>Hrdwre Config
Power Direction
Power Direction Always Positive
Sets the sign associated with forward and reverse power flow. Can be “Always Positive” or “Normal” (reverse power flow will be indicated with a negative sign).
11>Hrdwre Config
Current Sensor
Curr Sensor Type FP 1301 x7A >>
Selects LPS (Line Post Sensor) mfgr and model. Can be set to: Lindsey TrueCT/ Multicore. Fisher Pierce: 1301 x7A (-17A, -47A, -27A) 1301 x1A (-11A, -41A, -21A). Generic LPS or CT. Note: Do NOT use a CT with this eCAP model, or damage may result.
Amps/V Phase 60 90 >>
Amps/V and phase shift settings. These are fixed, and depend on the sensor model. These settings can be changed if “Generic LPS” is chosen for the sensor model above.
Harmonic Comp Enabled
LPS harmonic compensation circuit status (enabled/disabled) This is fixed, depending on the sensor model. Can be changed if “Generic LPS” is selected.
12> Hrdwre Config
Maximum Current
Maximum Current 180 Amps
Sets the maximum measurable current in the eCAP. Settable in sixteen steps from 180 to 1530 Amps. Lower settings help resolution at lower currents. Choose a number that is 20% higher than the maximum expected phase current.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Operation 23
Other Configuration Settings (contd.)
Menu Item Submenu Item Format Comments
13>Hrdwre Config
Switching DeltaV
Learn ClsV OpnV Yes 2.0 2.0
Values used to provide the predicted VCor deadbands (hysteresis) for the voltage limits. ClsV is rise in voltage after closing. OpnV is drop in voltage after opening. Values can be set manually (Learn = No) or the eCAP will learn them as it switches the bank (Leran=Yes). The DeltaV values are added to, or subtracted from the measured voltage (depending on the operation) to arrive at the VCor value. The VCor value also includes a 25% margin for hysteresis.
14>Hrdwre Config
Config Constants
Volts Amps Deg 7200 60 152
Volts = Settable Primary Phase-Neutral Voltage. Amps, Deg = fixed settings, depending on the LPS sensor settings.
15> Misc. Config
Sw Error Check
Delta Err. Check Disabled
If enabled, the measured line voltage rise (or drop) after a bank operation, must be 25% or more of the ClsV (or OpnV) values. If the 25% minimum change is not observed for three consecutive operations, a “Switching Voltage Delta Error” is returned via SCADA.
16> Misc. Config
Tracking Delays
Delay Emer Volt Secs 120 120
“Emer” = emergency voltage tracking delay, “Volt” = voltage limit tracking delay. Both are settable from 1 to 300 seconds. These delays prevent short transient voltage spikes from triggering a cap bank operation.
17> Misc. Config
Sw. Oper. Time
Opn Operate Time 7 Secs >>
“Open” output relay energization time. Settable from 1 to 100 secs.
Cls Operate Time 7 Secs
“Close” output relay energization time. Settable from 1 to 300 secs.
18> Misc. Config
Discharge Time
Discharge Time 300 Secs (5 Min)
Re-close block of 5 minutes to allow the cap bank to discharge after an open operation. Settable to 300 (5 Min) or 600 Secs (10 Min).
NPC eCAP-9040 User's Guide UG-1056
24 Operation Copyright © 2017 QEI
Other Configuration Settings (contd.)
Menu Item Submenu Item Format Comments
19> Misc. Config
Max Ops Per Day
Max Ops Enable Enabled >>
Maximum number of open/close cycles allowed during a single day (24 hours). Can be enabled or disabled. When the count is exceeded, no further operations are allowed until the following day (beginning after midnight).
Time Count 60 Mins 10
“Time” = Anti-Hunt delay time between consecutive auto operations. Settable from 10 to 60 Minutes. “Count” = number of open/close cycles allowed per day. Settable from 4 to 25 counts, or No Limit. The cycle count resets at midnight of each day.
20> Misc. Config
Unit ID
Unit ID Number 1
Unit ID number. Settable from 1 to 32767.
21> Misc. Config
Date
Date: Yr/Mo/Dy is 07/05/24
Sets/displays the date. To set the date, see the time setting instructions below.
22> Misc. Config
Time
Time: Hr:Mn DOW is: 06:25 5Fr
Sets/displays the time of day (Format: HH:MM) and DOW (day-of-week) To set time, make sure the cursor is over the word “is”. Press the UP switch until “is” says “Ent”. Next use the RIGHT switch to move the cursor to the right until it is over the hour. Use the UP/DN switch to set the hour, then use the RIGHT switch again to move the cursor over the minutes. Use the UP/DN switch to set the minutes. Use the RIGHT switch again to move the cursor over the day-of-week. Use the UP/DN switch to set the Day (1 = Monday thru 7 = Sunday). Now use the LEFT switch multiple times to move the cursor back to “Ent”. Press the UP switch once, and verify that “Ent” changes to “Set”, then to “is”.
23> Misc. Config
DST Config
DST Hemisph * Enabled North >>
Daylight Savings Time compensation. When enabled, clock is advanced one hour in the spring (Month1), and set back one hour in the fall (Month2). Settable for North (US) or South Hemispheres. If South Hemisph is selected, the time will be set back in the spring, and advanced in the fall. Asterisk = in DST period.
Month1 Month2 3 11
Month1 = Beginning of DST (the time will be advanced by 1 hour) Month2 = end of DST (the time will be set back by 1 hour).
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Misc Technical Data 25
5. Misc Technical Data
DB9
Pin
To Radio
Intf Board
Description
Pin 2 RX Data received by the radio and sent to the eCAP.
Pin 3 TX Data transmitted out by the eCAP.
Pin 5 GND Signal ground.
NPC eCAP-9040 User's Guide UG-1056
26 Misc Technical Data Copyright © 2017 QEI
Cable DB9M QEI No. 40-057808-001
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Misc Technical Data 27
5.1 Communications Board
The eCAP is designed for communications in a SCADA system, and the communications board is designed as the eCAP interface to the SCADA Master Station via a data-radio or modem. The communications board talks to the eCAP microprocessor board on PORT 1 (connector P3). It talks to the data radio through the Radio Interface Board that is mounted on the communications board on PORT 2 (connector P4). Communications protocol is DNP3. Communications parameters to the radio are No parity, 8 data bits, one stop bit. Baud rate is jumper configurable on the communications board.
5.1.1 Jumpers - Factory Configuration
The eCAP communications board contains pluggable configuration jumpers. Certain jumpers are relevant to the communications configuration. Other jumpers were preset at the factory before shipment. The factory configuration for all jumpers is as follows:
OS3-CD = IN OS7-ROM60 = IN
OS4-AB = IN 0S7-ROM80 = IN
OS6-AC = IN OS7-ROMA0 = IN
OS6-BD = IN OS7-ROMC0 = IN
OS7-RAM20 = IN 0S9-CD = IN
OS7-RAM40 = IN
Any jumpers not listed in the table above were not installed at the factory (the jumper would be considered OUT). The factory configuration listed in the table above configures the communications board for 9600 bps. An illustration of the jumper locations for the communications board appears on the following page.
Changing any other jumpers on the board is not recommended, and may result in
rendering the board inoperative. If a jumper is accidentally changed, refer to the table above to restore the factory settings. The drawing that follows shows the location of jumpers (and LEDs) on the communications board.
NPC eCAP-9040 User's Guide UG-1056
28 Misc Technical Data Copyright © 2017 QEI
Pictorial of Jumper locations for eCAP communications board.
5.1.2 TX / RX LEDs
Two LEDs on the communications board indicate data transfer to/from the eCAP microprocessor board. The red LED (TX1) indicates data is being sent TO the eCAP microprocessor board. The green LED (RX1) indicates data is being received FROM the eCAP microprocessor board.
Two LEDs on the eCAP front panel indicate data transfer between the communications board and the data radio. TX indicates data is being sent TO the radio, and RX indicates data received FROM the radio.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Misc Technical Data 29
5.1.3 Setting the Baud Rate
Use jumper OS3 to change the baud rate.
The communications board is configurable for the following baud rates: 1200, 2400, 4800, 9600, 19200. Baud rate is configured via pluggable jumpers. For all baud rates, insure that jumper OS4-AB is IN, while jumper OS4-BC is OUT. Otherwise, none of the baud rates will function correctly.
Factory default for the jumper OS3 is CD = IN = 9600 baud. Refer to the following table to configure jumper OS3 for the required baud rate:
BAUD RATE JUMPERS
1200 2400 4800 9600 19200
OS3-JK IN OUT OUT OUT OUT
OS3-GH OUT IN OUT OUT OUT
OS3-EF OUT OUT IN OUT OUT
OS3-CD OUT OUT OUT IN OUT
OS3-AB OUT OUT OUT OUT IN
5.2 Radio Interface Board
The RS-232 Radio Interface Board provides an isolated RS-232 interface between the SCADA Communications Board and the data radio:
eCAP CPU
BOARD
SCADA COMM
BOARD
RS-232 RADIO
INTFACE BDDATA RADIO
FIBER
OPTICAL
RS-232
ANTENNA
(CUSTOMER SUPPLIED)
NPC eCAP-9040 User's Guide UG-1056
30 Misc Technical Data Copyright © 2017 QEI
The Radio Interface Board contains a 4 position terminal block (J1) for connection of the above RS-232 data cables. The board is marked next to the terminal block with the legends “RX”, “TX”, “+12V”, and “GND”:
RADIO INTERFACE
BOARD, J1
TERMINAL BLOCK
CONNECTED
WIRE COLOR
DESCRIPTION
RX BLUE Incoming data from the radio
TX ORANGE Outgoing data transmitted by the eCAP
+12V RED Power (from radio power supply)
GND BLACK Power supply return, and data common.
The drawing below shows a closeup view of the Radio Interface Board:
The jumpers for JP1 must always be oriented as shown in the Radio Interface Board drawing above (the jumpers are parallel to the “long” side of this board as shown). The Radio Interface Board part number is 40-057807-001.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI Misc Technical Data 31
The Radio Interface Board is “piggy-backed” onto the SCADA Communications Board, and has plastic optical fiber (1000 micron) running from it’s two fiber connectors to the fiber connectors on the SCADA Board.
The illustration above (right) shows the wiring of the RS-232 cable to the Radio Interface Board Terminal Block (J1). Two RS-232 cables are supplied with the eCAP: a 9-pin and 25-pin cable. Use the appropriate cable based on the type of radio.
5.2.1 DB9 RS-232 Cable:
Orange wire: Connected to “TX” on the Radio Interface Board terminal block, goes to pin 3 of the DB9 connector. This is data to be sent from the eCAP to the radio.
Blue wire: Connected to “RX” on the Radio Interface Board terminal
block, goes to pin 2 of the DB9 connector. This is data received from the radio to the eCAP.
Black wire: Connected to “GND” on the Radio Interface Board terminal
block (GND) goes to pin 5 of the DB9 connector. This is the data common connection, and also goes to the radio power supply common.
NPC eCAP-9040 User's Guide UG-1056
32 Misc Technical Data Copyright © 2017 QEI
5.3 Local/Remote Front Panel Switch
In order to use SCADA communications, the front panel LOCAL/REMOTE switch must be in the REMOTE position. When in the REMOTE position, the eCAP communicates with a SCADA system using a data radio or modem, etc. When the switch is in the LOCAL position, the eCAP communicates with a Laptop PC through the RS-232 port on the front panel. The PC must be running QEI’s “SmartWare” software. Note that when the switch is in REMOTE position, the front panel RS-232 port is disabled, and when it is in LOCAL position, SCADA communications via data radio is disabled.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI DNP3 Device Profile w/Point List 33
6. DNP3 Device Profile w/Point List
Version 1.0
Date: 06/21/2007
DNP V3.00 DEVICE PROFILE DOCUMENT
This document must be accompanied by a table having the following headings: Object Group Request Function Codes Response Function Codes Object Variation Request Qualifiers Response Qualifiers Object Name (optional)
Vendor Name: QEI
Device Name: NPC eCAP Capacitor Controller
Highest DNP Level Supported: For Requests 2 For Responses 2
Device Function: Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the attached table): The read function code for Object 50 (Time and Date), variation 1, is supported.
Maximum Data Link Frame Size (octets): Transmitted 292 Received 292
Maximum Application Fragment Size (octets): Transmitted 2048 Received 2048
Maximum Data Link Re-tries: None Fixed at Configurable, range None to 10
Maximum Application Layer Re-tries: None Configurable, range None to 10 (Fixed is not permitted)
NPC eCAP-9040 User's Guide UG-1056
34 DNP3 Device Profile w/Point List Copyright © 2017 QEI
Requires Data Link Layer Confirmation: Never Always Sometimes: For multi-frame messages. Configurable
Requires Application Layer Confirmation: Never Always (not recommended) When reporting Event Data (Slave devices only) When sending multi-fragment responses (Slave devices only) Sometimes Configurable
Time-outs while waiting for: Data Link Confirm None Fixed at Variable Configurable Complete Appl. Fragment None Fixed at Variable Configurable Application Confirm None Fixed at 5 sec Variable Configurable Complete Appl. Response None Fixed at Variable Configurable Others: Transmit Enable (Time to 1st char after CTS) configurable by A/O (see Table) CTS Override Tim to 1st char after RTS if no CTS) configurable by A/O (see Table) Transmit Disable(Hold time: RTS after last char) configurable by A/O (see Table)
Executes Control Operations: WRITE Binary Outputs Never Always Sometimes Configurable SELECT/OPERATE Never Always Sometimes Configurable DIRECT OPERATE Never Always Sometimes Configurable DIRECT OPERATE - NO ACK Never Always Sometimes Configurable Count > 1 Never Always Sometimes Configurable Pulse On Never Always Sometimes Configurable Pulse Off Never Always Sometimes Configurable Latch On Never Always Sometimes Configurable Latch Off Never Always Sometimes Configurable Queue Never Always Sometimes Configurable Clear Queue Never Always Sometimes Configurable Latch On, Latch Off operate all CROBs except Cap Bank Trip/Close when not in Local.
In addition, unit must be in Remote mode to operate Cap Bank Trip/Close.
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI DNP3 Device Profile w/Point List 35
FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY:
Expects Binary Input Change Events: Either time-tagged or non-time-tagged for a single event Both time-tagged and non-time-tagged for a single event Configurable (attach explanation)
FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY:
Reports Binary Input Change Events when no specific variation requested: Never Only time-tagged Only non-time-tagged Configurable
Reports time-tagged Binary Input Change Events when no specific variation requested: Never Binary Input Change With Time Binary Input Change With Relative Time Configurable (attach explanation)
Sends Unsolicited Responses: Never Configurable (attach explanation) Only certain objects Sometimes (attach explanation)
Sends Static Data in Unsolicited Responses: Never When Device Restarts When Status Flags Change No other options are permitted.
Default Counter Object/Variation: No Counters Reported Configurable (attach explanation) Default Object 20 Default Variation 04
Point-by-point list attached
Counters Roll Over at: No Counters Reported Configurable (attach explanation) 16 Bits 32 Bits Other Value _____________ Point-by-point list attached
Sends Multi-Fragment Responses: Yes No
NPC eCAP-9040 User's Guide UG-1056
36 DNP3 Device Profile w/Point List Copyright © 2017 QEI
DNP 3.0 Implementation Table for eCAP
OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse) Obj
Var
Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
1
0
Binary Input - All Variations
1
06
1
1
Binary Input
129
00, 01
1
2
Binary Input with Status
129
00, 01
2
0
Binary Input Change - All Variations
1
06,07,08
2
1
Binary Input Change without Time
1
06,07,08
129
17, 28
2
2
Binary Input Change with Time
1
06,07,08
129
17, 28
2
3
Binary Input Change with Relative Time
1
06,07,08
129
17, 28
10
0
Binary Output - All Variations
1
06
10
1
Binary Output
10
2
Binary Output Status
129
00, 01
12
0
Control Block - All Variations
12
1
Control Relay Output Block
3, 4, 5, 6
17, 28
129
echo of
request
12
2
Pattern Control Block
12
3
Pattern Mask
20
0
Binary Counter - All Variations
1, 7, 8, 9, 10
06
20
1
32-Bit Binary Counter
129
00, 01
20
2
16-Bit Binary Counter
129
00, 01
20
3
32-Bit Delta Counter
129
00, 01
20
4
16-Bit Binary Counter
129
00, 01
20
5
32-Bit Binary Counter without Flag
129
00, 01
20
6
16-Bit Binary Counter without Flag
129
00, 01
20
7
32-Bit Delta Counter without Flag
129
00 ,01
20
8
16-Bit Delta Counter without Flag
129
00 ,01
21
0
Frozen Counter - All Variations
1
06
21
1
32-Bit Frozen Counter
129
00, 01
21
2
16-Bit Frozen Counter
129
00, 01
21
3
32-Bit Frozen Delta Counter
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI DNP3 Device Profile w/Point List 37
OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse) Obj
Var
Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
21
4
16-Bit Frozen Delta Counter
21
5
32-Bit Frozen Counter with Time of Freeze
21
6
16-Bit Frozen Counter with Time of Freeze
21
7
32-Bit Frozen Delta Counter with Time of Freeze
21
8
16-Bit Frozen Delta Counter with Time of Freeze
21
9
32-Bit Frozen Counter without Flag
129
00, 01
21
10
16-Bit Frozen Counter without Flag
129
00, 01
21
11
32-Bit Frozen Delta Counter without Flag
21
12
16-Bit Frozen Delta Counter without Flag
22
0
Counter Change Event - All Variations
1
06,07,08
22
1
32-Bit Counter Change Event without Time
129
17, 28
22
2
16-Bit Counter Change Event without Time
129
17, 28
22
3
32-Bit Delta Counter Change Event without Time
22
4
16-Bit Delta Counter Change Event without Time
22
5
32-Bit Counter Change Event with Time
22
6
16-Bit Counter Change Event with Time
22
7
32-Bit Delta Counter Change Event with Time
22
8
16-Bit Delta Counter Change Event with Time
23
0
Frozen Counter Event - All Variations
23
1
32-Bit Frozen Counter Event without Time
23
2
16-Bit Frozen Counter Event without Time
23
3
32-Bit Frozen Delta Counter Event without Time
23
4
16-Bit Frozen Delta Counter Event without Time
23
5
32-Bit Frozen Counter Event with Time
23
6
16-Bit Frozen Counter Event with Time
23
7
32-Bit Frozen Delta Counter Event with Time
23
8
16-Bit Frozen Delta Counter Event with Time
30
0
Analog Input - All Variations
1
06
30
1
32-Bit Analog Input
129
00, 01
30
2
16-Bit Analog Input
129
00, 01
30
3
32-Bit Analog Input without Flag
129
00, 01
NPC eCAP-9040 User's Guide UG-1056
38 DNP3 Device Profile w/Point List Copyright © 2017 QEI
OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse) Obj
Var
Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
30
4
16-Bit Analog Input without Flag
129
00, 01
31
0
Frozen Analog Input - All Variations
31
1
32-Bit Frozen Analog Input
31
2
16-Bit Frozen Analog Input
31
3
32-Bit Frozen Analog Input with Time of Freeze
31
4
16-Bit Frozen Analog Input with Time of Freeze
31
5
32-Bit Frozen Analog Input without Flag
31
6
16-Bit Frozen Analog Input without Flag
32
0
Analog Change Event - All Variations
1
06,07,08
32
1
32-Bit Analog Change Event without Time
129
17,28
32
2
16-Bit Analog Change Event without Time
129
17,28
32
3
32-Bit Analog Change Event with Time
32
4
16-Bit Analog Change Event with Time
33
0
Frozen Analog Event - All Variations
33
1
32-Bit Frozen Analog Event without Time
33
2
16-Bit Frozen Analog Event without Time
33
3
32-Bit Frozen Analog Event with Time
33
4
16-Bit Frozen Analog Event with Time
40
0
Analog Output Status - All Variations
1
06
40
1
32-Bit Analog Output Status
40
2
16-Bit Analog Output Status
129
00, 01
41
0
Analog Output Block - All Variations
41
1
32-Bit Analog Output Block
41
2
16-Bit Analog Output Block
3, 4, 5, 6
17, 28
129
echo of request
50
0
Time and Date - All Variations
50
1
Time and Date
1,2
07 where quantity = 1
50
2
Time and Date with Interval
51
0
Time and Date CTO - All Variations
51
1
Time and Date CTO
129
07, quantity=1
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI DNP3 Device Profile w/Point List 39
OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse) Obj
Var
Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
51 2 Unsynchronized Time and Date CTO 129 07, quantity=1
52
0
Time Delay - All Variations
52
1
Time Delay Coarse
129
07, quantity=1
52
2
Time Delay Fine
129
07, quantity=1
60
0
60
1
Class 0 Data
1
06
60
2
Class 1 Data
1
06,07,08
60
3
Class 2 Data
1
06,07,08
60
4
Class 3 Data
1
06,07,08
70
1
File Identifier
80
1
Internal Indications
2
00
index=7
81
1
Storage Object
82
1
Device Profile
83
1
Private Registration Object
83
2
Private Registration Object Descriptor
90
1
Application Identifier
100
1
Short Floating Point
100
2
Long Floating Point
100
3
Extended Floating Point
101
1
Small Packed Binary-Coded Decimal
101
2
Medium Packed Binary-Coded Decimal
101
3
Large Packed Binary-Coded Decimal
No Object
13
No Object
23 (see 4.14)
NPC eCAP-9040 User's Guide UG-1056
40 DNP3 Device Profile w/Point List Copyright © 2017 QEI
Basic Input Data Registers – Analog Points
Object /
Variation
/ Class Parameter
Point
Address Units Range
30/4/0 OR 32/2/2 Secondary Voltage (1 phase) 0 0.1 Volts
30/4/0 OR 32/2/2 Voltage w/ Correction (1 phase) 1 0.1 Volts
30/4/0 OR 32/2/2 Current (1 phase) 2 Amps
30/4/0 OR 32/2/2 KW (1 phase x3) 3 KW
30/4/0 OR 32/2/2 kVAr (1 phase x3) 4 kVAr
30/4/0 OR 32/2/2 kVA (1 phase x3) 5 kVA
30/4/0 OR 32/2/2 Power Factor 6 0.1 %
30/4/0 OR 32/2/2 Phase Angle 7 Degrees
30/4/0 OR 32/2/2 Spare1 8 Always 0
30/4/0 OR 32/2/2 Ambient Temperature 9 Degrees F
30/4/0 OR 32/2/2 Operations Counter 10 # of Operations 0 to 32767
30/4/0 OR 32/2/3 Operations Counter Today 11
# of Operations
Since Midnight
30/4/0 OR 32/2/3 Reason for Last Switch Operation 12 See Note 1.
30/4/0 OR 32/2/3 ECap Firmware Version 13 100 = Ver:1.00
30/4/0 OR 32/2/3 NPC Identification Serial number 14 ECap Unit ID 0 to 32767
30/4/0 OR 32/2/2 Last SCADA Command Received 15 See Note 2.
30/4 Last SCADA Point Number 16 SCADA Point #
30/4 Last SCADA Set Point Value 17 Set Point Value
Note 1: Reason for the Last Switch Operation Value Description
0 No Operation 1 Manual Operation 2 Remote (SCADA) Operation 3 Out of Time Period 4 Temperature High 5 Temperature Low 6 Under-Voltage 7 Over-Voltage 8 Emergency Under-Voltage 9 Emergency Over Voltage
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI DNP3 Device Profile w/Point List 41
Note 2: Last SCADA Command Received Value Description
0 No Command Received 1 Open/Trip 2 Close 3 Set Point
NPC eCAP-9040 User's Guide UG-1056
42 DNP3 Device Profile w/Point List Copyright © 2017 QEI
Basic Input Data Registers – Status Points
Object/
Variation/
Class Point Name
Point
Address Description
01/1/0 OR 02/2/1 Cap Bank Switch – Open / Close 0 0 = Open, 1 = Closed
01/1/0 OR 02/2/1 Remote Mode 1 0 = Auto, 1 = Remote
01/1/0 OR 02/2/1 Delta Voltage Learn 2 0 = Disabled, 1 = Enabled
01/1/0 OR 02/2/1 Spare1 3 Always 0
01/1/0 OR 02/2/1 Max Number Operations Daily 4 0 = Disable, 1 = Enabled
01/1/0 OR 02/2/1 Auto-Manual Switch 5
Sets IIN Local bit.
0 = Auto, 1 = Manual
01/1/0 OR 02/2/1 Spare2 6 Always 0
01/1/0 OR 02/2/3 Spare3 7 Always 0
01/1/0 OR 02/2/3 Auto-Remote Timeout Timer Enable 8 0 = Disabled, 1 = Enabled
01/1/0 OR 02/2/3
Under/Over-Voltage SCADA Override Enable 9 0 = Disabled, 1 = Enabled
01/1/0 OR 02/2/3 SCADA Override Active 10 0 = Inactive, 1 = Active
01/1/0 OR 02/2/3 Open Operation is Pending 11 0 = No Open Pending, 1 = Open
01/1/0 OR 02/2/3 Close Operation is Pending 12 0 = No Close Pending, 1 = Close
01/1/0 OR 02/2/3 Switch State (Open/Closed) Unknown 13 0 = OK, 1 = State is Unknown
01/1/0 OR 02/2/3 Under-Voltage Override 14 0 = Disabled, 1 = Enabled
01/1/0 OR 02/2/3 Under-Voltage Override Active 15 0 = Inactive, 1 = Active
01/1/0 OR 02/2/3 Over-Voltage Override 16 0 = Disabled, 1 = Enabled
01/1/0 OR 02/2/3 Over-Voltage Override Active 17 0 = Inactive, 1 = Active
01/1/0 OR 02/2/3 Emergency UV Override 18 0 = Inactive, 1 = Active
01/1/0 OR 02/2/3 Emergency OV Override 19 0 = Inactive, 1 = Active
01/1/0 OR 02/2/3 Under/Over-Voltage Control 20 0 = Disabled, 1 = Active
01/1/0 OR 02/2/3 Emergency Under/Over Voltage Control 21 0 = Disabled, 1 = Active
01/1/0 OR 02/2/3 Switching Delta Voltage Error 22 0 = No Error, 1 = Error Occurred
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI DNP3 Device Profile w/Point List 43
Basic Output Data Registers – Control Points
Object /
Variation Point Name
Point
Address
Operation
Type Description
Operation
Conditions
12/1 Cap Bank Switch Trip/Close 0 Latched Off = Trip
On = Close
Auto-Remote mode (Status Input 1) must be 1 (Remote). Auto-Manual (Status Input 5) must be 0 (Auto)
12/1 Remote Mode / Auto Mode 1 Latched Off = Auto
On = Remote
None.
12/1 Delta Voltage Learn 2 Latched Off = Disable
On = Enable
None.
12/1 IEEE Cap Discharge Delay – 10/5 minutes
3 Latched Off = 10 minutes
On = 5 minutes
None.
12/1 Maximum Daily Operations 4 Latched Off = Disable
On = Enable
None.
12/1 Auto-Remote Timeout Enable 5 Latched Off = Disable
On = Enable
None.
12/1 Under/Over-Voltage SCADA Override
6 Latched Off = Disable
On = Enable
None.
12/1
Under-Voltage Override 7 Latched Off = Disable
On = Enable
None.
12/1
Over-Voltage Override 8 Latched Off = Disable
On = Enable
None.
12/1
Voltage Control 9 Latched Off = Disable
On = Enable
None.
12/1
Emergency Voltage Control 10 Latched Off = Disable
On = Enable
None.
12/1
Clear Operations Counter 11 Latched Off = Clear
On = Clear
None.
NPC eCAP-9040 User's Guide UG-1056
44 DNP3 Device Profile w/Point List Copyright © 2017 QEI
Analog Outputs
Object /
Variation Parameter
Point
Address Units Default Range
41 / 2 Auto/Remote Timeout Time 0 Seconds 300
41 / 2 Under-Voltage Close/Override Value 1
1201 = 120.1 Volts 1160
41 / 2 Over-Voltage Close/Override Value 2
1201 = 120.1
Volts 1260
41 / 2 UV/OV Tracking Time 3 Seconds 120
41 / 2 Emergency Under-Voltage Close Value 4
1201 = 120.1 Volts 1150
41 / 2 Emergency Over-Voltage Open Value 5
1201 = 120.1 Volts 1290
41 / 2 Emergency UV/OV Tracking Time 6 Seconds 120
41 / 2 Time Period Start Time 7 See Note 1. 2304
41 / 2 Time Period End Time 8 See Note 1. 5376
41 / 2 Outside Time Period Remain 9
0 = Open, 1 = Closed 0 0 to 1
41 / 2 Low Temperature (Trip) 10 Degrees F 80
41 / 2 High Temperature (Open) 11 Degree F 95
41 / 2 Open Delta Voltage 12 201 = 2.01 Volts 200
41 / 2 Close Delta Voltage 13 201 = 2.01 Volts 200
41 / 2 Max Daily Operations 14 1 10
UG-1056 NPC eCAP-9040 User's Guide
Copyright © 2017 QEI DNP3 Device Profile w/Point List 45
Analog Output Status
Object /
Variation Parameter
Point
Address Units Default Range
40 / 2 Auto/Remote Timeout Time 0 Seconds 300
40 / 2 Under-Voltage Close/Override Value 1
1201 = 120.1 Volts 1160
40 / 2 Over-Voltage Close/Override Value 2
1201 = 120.1
Volts 1260
40 / 2 UV/OV Tracking Time 3 Seconds 120
40 / 2 Emergency Under-Voltage Close Value 4
1201 = 120.1 Volts 1150
40 / 2 Emergency Over-Voltage Open Value 5
1201 = 120.1 Volts 12900
40 / 2 Emergency UV/OV Tracking Time 6 Seconds 120
40 / 2 Time Period Start Time 7 See Note 1. 2304
40 / 2 Time Period End Time 8 See Note 1. 5376
40 / 2 Outside Time Period Remain 9
0 = Open, 1 = Closed 0 0 to 1
40 / 2 High Temperature (Close) 10 Degrees F 95
40 / 2 Low Temperature (Open) 11 Degree F 80
40 / 2 Open Delta Voltage 12 201 = 2.01 Volts 200
40 / 2 Close Delta Voltage 13 201 = 2.01 Volts 200
40 / 2 Max Daily Operations 14 1 10
Note 1: Time Values
Time = (Hour X 256) + Minutes
Example: 14:30 = (14 X 256) + 30 = 3614