    DynaVar

    Distribution Class Riser Pole (PVR) Surge Arresters

    2M GEN 3/08

  • 7/30/2019 U-100 catalog

    2/8

    MARCH 2008 OHIO BRASS AIKEN, SC

    U-100-2

    POWER SYSTEMS, INC.

    NOTE: Because Hubbell has a policy o continuous product improvement, we reserve the right to change design and specifcations without notice.

    Warranty - MaterialHubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as suchterm is defned in the Uniorm Commercial Code) and to be ree rom deects in material and

    workmanship. Buyer must notiy the Company promptly o any claim under this warranty. The

    Buyers exclusive remedy or breach o this warranty shall be the repair or replacement, F.O.B.actory, at the Companys option, o any product deective under the warranty which is returned

    to the Company within one year rom the date o shipment. NO OTHER WARRANTY, WHETHER

    EXPRESS OR ARISING BY OPERATION OF LAW, COURSE OF DEALING, USAGE OFTRADE OR OTHERWISE IMPLIED, SHALL EXIST IN CONNECTION WITH THE COMPANYS

    PRODUCTS OR ANY SALE OR USE THEREOF. The Company shall in no event be liable orany loss o profts or any consequential or special damages incurred by Buyer. The Companys

    warranty shall run only to the frst Buyer o a product rom the Company, rom the Companys

    distributor, or rom an original equipment manuacturer reselling the Companys product, and isnon-assignable and non-transerable and shall be o no orce and eect i asser ted by any per-

    son other than such frst Buyer. This warranty applies only to the use o the product as i ntended

    by Seller and does not cover any misapplication or misuse o said product.

    Warranty - ApplicationHubbell Power Systems, Inc. does not warrant the accuracy o and results rom product orsystem perormance recommendations resulting rom any engineering analysis or study. This

    applies regardless o whether a charge is made or the recommendation, or i it is provided reeo charge.

    Responsibility or selection o the proper product or application rests solely with the purchaser. In

    the event o errors or inaccuracies determined to be caused by Hubbell Power Systems, Inc. , itsliability will be limited to the re-perormance o any such analysis or study.

    Table o ContentsPage

    Warranty ................................................................................... U-100-2

    Introduction .............................................................................. U-100-3

    Basic Construction ................................................................... U-100-3

    Tests Verify PVR Arrester Design .............................................. U-100-4

    Full Scale Fault Current Tests ............................................... U-100-4

    Design Test Report Summary ............................................... U-100-4

    Selection Considerations ......................................................... U-100-5

    Temporary Overvoltage .............................................U-100-5, U-100-6

    Tightening Torques for PVR Arrester Fasteners ....................... U-100-6

    PVR Electrical Characteristics .................................................. U-100-7

    Typical Mounting Congurations

    and Hardware ....................................................................... U-100-8

    Copyright 2008 Hubbell 210 North Allen Street Centralia, MO 65240

  • 7/30/2019 U-100 catalog

    3/8

    MARCH 2008

    U-10

    OHIO BRASS AIKEN, SC

    POWER SYSTEMS, INC.

    Basic Construction

    In Ohio Brass arresters, the Varistors are locked in

    place with tightly wound layers of berglass lament

    impregnated with epoxy resin. The arrester housingis made from our proprietary blend of ESP silicone

    alloy. In addition to ESPs exceptional performance

    as an insulator material, ESPs properties have been

    conrmed in a series of performance tests which

    include tracking resistance, contamination, aging, and

    seal design.

    PVR arresters are used with all standard mounting

    arms and brackets. They come with all the necessary

    fasteners, isolators, and terminal attachments. A

    specially designed glass-lled polyester insulating

    bracket, with integrated disconnector, along withoptional mounting brackets such as the cross arm or

    transformer bracket, enable mounting the arrester in a

    way which best suits each individual customer.

    Cutaway View o Typical PVR Unit

    Introduction

    Ohio Brass PVR arresters target cable applications

    where low discharge voltages promote longer cable

    life.

    Stainless SteelTerminal Stud

    Stainless Steel Cap

    End Terminal

    Live Silicone Interface

    Alloy ESP Rubber Housing

    Metal Oxide Varistor

    Belleville Washer

    Epoxy-Fiberglass Wrap

    Metal Oxide Varistor

    UNDERGROUND PRODUCTS

  • 7/30/2019 U-100 catalog

    4/8

    MARCH 2008 OHIO BRASS AIKEN, SC

    U-100-4

    POWER SYSTEMS, INC.

    Tests Veriy PVR Arrester Design

    Full Scale Fault Current Tests

    Short circuit design tests were performed on PVR arrest-ers in accordance with Section 8.18 of IEEE C62.11-2004Standard. Eight arresters were tested. Per the standard, foursamples were tested at the claimed high current withstandcapability. Two of these samples were assembled withinternal fuse wires. The other two were good arresters whichwere subjected to an overvoltage condition, which failed thearrester (with a weak source). The arrester was immediatelysubjected to the claimed high current fault current. Two addi-tional arresters were subjected to fault currents approximate-ly half of the claimed high current value. The fault currentduration for all high current tests was 12 cycles. Finally, twoarresters were subjected to a nominal 600 amp, 1 secondfault current test. All test arresters were 17 kV MCOV, thelongest single module conguration used for each arrestertype. Tests were performed at full voltage (17 kV rms).

    Successful performance was demonstrated when the epoxy-berglass wrapped arrester modules burned through torelieve internal pressures associated with the fault currentarcing. In all cases, the arrester remained intact, except at

    the high current levels which caused polymer housing frag-mentation, which is acceptable.

    The following table summarizes the claimed short circuitcapabilities for the arresters.

    PVR Design Test Report Summary

    There is no standard for PVR arresters so they were testedper the heavy duty requirement.

    The table below summarizes the capabilities of PVR Arrest-ers.

    The above is merely a summary of a portion of the design tests per-formed on PVR arresters. Contact your Ohio Brass territory managerfor complete test reports.

    Arrester Type Short Circuit Test

    Current Arms

    Short Circuit Test

    Duration-Sec.

    PVR 20,000 .20

    PVR 10,000 .20

    PVR 500 1.0

    Test Heavy DutyRiser Pole PVR

    High Current-Short Duration

    2 - 100 kADischarges

    Low CurrentLong Duration

    20 - 250A x 2000sec Discharges

    Duty Cycle 20 - 10 kA

    plus 2 - 40 kADischarges

  • 7/30/2019 U-100 catalog

    5/8

    MARCH 2008

    U-10

    OHIO BRASS AIKEN, SC

    POWER SYSTEMS, INC.

    Eectively

    Grounded

    Neutral Circuits

    2.55

    7.65

    7.65

    8.4

    8.4

    12.7

    15.3

    15.322.0

    Maximum

    2.54

    4.4

    5.08

    7.26

    12.7

    13.2

    13.97

    14.52

    22.0

    24.2

    24.34

    26.436.5

    Nominal

    2.4

    4.16

    4.8

    6.9

    12.0

    12.47

    13.2

    13.8

    20.78

    22.86

    23.0

    24.9434.5

    ImpedanceGrounded

    and Ungrounded

    Circuits

    2.55

    5.1

    5.1

    7.65

    12.7

    15.3

    22.0

    22.0

    22.0

    Arrester MCOV-kVSystem L-L VoltagekV

    NORMALLY RECOMMENDED PVR

    MCOV FOR VARIOUS SYSTEM VOLTAGESSelection of arrester size is based upon the maximum

    continuous operating voltage (MCOV) that is ap-

    plied across the arrester in service (line-to-ground).

    For arresters on effectively grounded systems, this isnormally the maximum line-to-ground voltage -- e.g.,

    7.65 kV on a 12.47 kV multi-grounded system. For

    ungrounded or impedance-grounded systems, the

    MCOV should be at least 90 percent of maximum

    phase-to-phase voltage. Smaller arresters than shown

    may be used, contact your Ohio Brass representative

    for details.

    For convenience, the data shown in this catalog in-

    cludes the traditional duty-cycle voltage rating associ-

    ated with the MCOV of each arrester.

    The selection of the actual type will be primarily gov-

    erned by the insulation being protected.

    Selection Considerations

    MOV arresters by nature are voltage sensitive devices.

    At normal line to ground voltages, the arrester is en-

    ergized at its MCOV (Maximum Continuous Operating

    Voltage) and conducts very little current. During distur-

    bances on the system, the arrester can see elevated

    voltages and therefore higher 60Hz current through the

    Temporary Overvoltage

    unit. The magnitude and duration of the system-gen-

    erated temporary over voltage (TOV) that the arrester

    can withstand is best expressed graphically. The curve

    on the next page shows the TOV capability versus time

    for OB PVR arresters.

  • 7/30/2019 U-100 catalog

    6/8

    MARCH 2008 OHIO BRASS AIKEN, SC

    U-100-6

    POWER SYSTEMS, INC.

    RecommendedTightening Torque

    20 foot pounds

    20 foot pounds

    20 foot pounds

    Fastener3

    8inch line terminal

    38

    inch ground terminal1

    2inch fastener connecting

    base bracket to crossarm ortransformer sidewall bracket

    RECOMMENDED TIGHTENING TORQUES FORPVR ARRESTER FASTENERS

  • 7/30/2019 U-100 catalog

    7/8

    MARCH 2008

    U-10

    OHIO BRASS AIKEN, SC

    POWER SYSTEMS, INC.

    Riser-PoleDynaVar PVR

    Electrical Characteristics

    Rated 0.5 sec 500 AVoltage MCOV Catalog 10kA Maximum Switching Surge

    kV kV Number IR-kV(1) Maximum IR-kV(2) 1.5 kA 3 kA 5 kA 10 kA 20 kA 40 kA

    03 02.55 221603 9.9 6.6 7.2 7.8 8.2 9.1 10.4 12.3 06 5.1 221605 20.0 13.3 14.6 15.7 16.6 18.3 21.0 24.8 09 7.65 221608 26.8 17.8 19.5 21.0 22.2 24.5 28.1 33.2

    10 8.4 221609 29.5 19.6 21.5 23.1 24.4 27.0 31.0 36.612 10.2 221610 35.5 23.6 25.9 27.9 29.4 32.5 37.3 44.015 12.7 221613 44.2 29.4 32.2 34.7 36.7 40.5 46.5 54.818 15.3 221615 53.4 35.5 38.9 41.9 44.3 48.9 56.1 66.221 17.0 221617 60.7 40.3 44.3 47.6 50.3 55.6 63.8 75.324 19.5 221620 70.9 47.1 51.7 55.6 58.7 64.9 74.4 87.927 22.0 221622 78.6 52.2 57.3 61.7 65.2 72.0 82.6 97.530 24.4 221624 88.5 58.7 64.5 69.4 73.3 81.0 92.9 110.036 29.0 221629 105.0 69.7 76.5 82.4 87.0 96.1 110.0 130.0

    8/20 Maximum Discharge Voltage - kV

    All Ohio Brass Arresters are fully compliant with ANSI/IEEE C62.11 Standard

    (1) Maximum discharge voltage for a 10-kA impulse current wave which produces a voltage wave cresting in 0.5 s. This can be used for

    coordination where front-of-wave sparkover was formerly used.

    (2) Based on a 500A surge of 45-s time to crest.

    Riser PoleDynaVar PVR

    (1) Center line to center line is equivalent to phase-to-phase; center line to ground is equivalent to phase-to-ground. These are recommended minimum clear-

    ances only and as such are not intended to take precedence over existing construction codes or specications.

    For appropriate packed weight, add 0.5 lb. per arrester.

    Mounting Clearance (1) Approx. Net Weights

    Unit withInsulating Bracket,

    Isolator andNEMA Bracket

    pounds

    5.8

    6.66.6

    6.6

    6.8

    8.0

    8.6

    8.6

    9.9

    12.1

    12.1

    13.3

    Unit with Insu-lating

    Base Bracketpounds

    3.3

    4.14.1

    4.1

    4.3

    5.5

    6.1

    6.1

    7.4

    9.6

    9.6

    10.8

    UnitOnly

    pounds

    2.3

    3.13.1

    3.1

    3.3

    4.5

    5.1

    5.1

    6.1

    8.3

    8.3

    9.5

    CenterLine toGroundinches

    3.0

    3.33.8

    4.0

    5.3

    6.3

    7.2

    7.7

    9.6

    10.5

    11.5

    14.0

    CenterLine to

    Center Lineinches

    5.0

    5.35.8

    6.0

    7.3

    8.3

    9.2

    9.7

    11.6

    12.5

    13.5

    16.0

    LeakageDistanceTerminalto Baseinches

    8.0

    15.415.4

    15.4

    15.4

    26.0

    26.0

    26.0

    30.8

    52.0

    52.0

    52.0

    MCOVkV

    2.55

    5.17.65

    8.4

    10.2

    12.7

    15.3

    17.0

    19.5

    22.0

    24.4

    29.0

    RatedVoltage

    kV

    3

    69

    10

    12

    15

    18

    21

    24

    27

    30

    36

    XOverallHeightinches