9 TECHNICAL CHARACTERISTICS Because of changes in standards and equipment, the characteristics given in the text and the illustrations in this document are not binding unless confirmed by Delta Dore. Field of application: Wireless alarm equipment - Radio range: outside: 200 to 300 m depending on environment inside: depending on environment - Radio frequencies: 434 and 868 MHz bands, class I - Power supply: One 6LR61 type 9 Vdc alkaline battery - Autonomy: 2 years for normal use - Dimensions with the base (mm): φ 120 x 55 (h) - Voltage of the low battery warning: 6.7 Volts +/- 0.1 V - Operating temperature: +5°C / +55°C - Weight (with batteries): 220 g 7 CLEANING 8 LIMITS OF USE The following operations must be performed once per year. After removing the detector: Clean the slots on the side of the side of the detector using a vacuum cleaner and a soft brush. Clean the outside of the cover using a damp cloth. The smoke alarm detector is a device that gives a rapid warning of any outbreak of fire at a reasonable cost. However, residential fires can break out in different ways and are often unpredictable. Yet it can fail to warn you of a fire if: - The battery is low or the wrong type. - The detector is not clean. - It is mounted in the wrong place or the smoke does not reach it. - The operational test is not regularly done. It is advisable to replace this detector after 5 years. Cleaning your detector is essential for your safety. If your detector is positioned in a dirty area, you must clean it more frequently in order to ensure that it operates efficiently. The DOFX helps save lives, but does not exempt you from taking out insurance to protect persons and property. 1 PRESENTATION The DOFX wireless smoke detector is desi- gned to detect the start of a slow burning fire. The detection of smoke particles is indi- cated by a radio message to the TYXAL control unit which then triggers the alarm. It is suitable for 24 hour per day surveillance of private homes (house, apartments, mobi- le home, caravan, etc.). Any presence of smoke is indicated by the flashing red LED and the sounding of the audible alarm. Whatever the state of the system (sur- veillance On / Off), when smoke is detected: - The CSX control unit emits warning beeps (beep, beep, beep, etc. for 45 seconds if the fault is no longer present, or 4 cycles of 45 seconds if the fault is continuous). The fault will be indicated by the “alarm” LED 1. - A telephone call cycle is triggered. It will indicate “fire alarm, press on star”, and your personal message. - On a control keypad with display, “technical detector” appears on the screen, followed by its identity (to be personalized). Note: The system siren does not sound because it is a “technical alarm”. 2 FITTING RECOMMENDATIONS The detector must preferably be attached to the ceiling in the centre of the room or: - more than 20 cm from any obstacle (wall, beam, etc.). - more than 60 cm from any corner in the room. If this is not possible, mount the detector on the wall at a distance of 15 to 25 cm from the ceiling. Contents: - a wireless smoke detector, - an installation and user guide, - a packet of screws. DELTA DORE Bonnemain - 35270 COMBOURG - France E-mail : [email protected] This does not detect gas. Minimum 60 cm between 15 cm and 25 cm Acceptable location Best location TEST button LED Base TYXAL Wireless alarm range Wireless smoke detector DOFX Installation and User Guide For very inclined ceilings, install the detector at a horizontal distance between 20 and 90 cm from the vertical passing through the highest point between 20 cm and 90 cm Device complying with the requirements of the R&TTE 1999/5/EC directives *2701916_rev1*

TYXAL Wireless smoke detector DOFX 7 9 ... - DELTA … · 9 TECHNICAL CHARACTERISTICS Because of changes in standards and equipment, the characteristics given in the text and the

Embed Size (px)

Citation preview

Page 1: TYXAL Wireless smoke detector DOFX 7 9 ... - DELTA … · 9 TECHNICAL CHARACTERISTICS Because of changes in standards and equipment, the characteristics given in the text and the

9 TECHNICALCHARACTERISTICS

Because of changes in standards and equipment, the characteristics given in the text and the illustrations in this document are not binding unless confirmed by Delta Dore.

Field of application: Wireless alarm equipment

- Radio range: outside: 200 to 300 m depending on environment

inside: depending on environment- Radio frequencies: 434 and 868 MHz

bands, class I- Power supply: One 6LR61 type 9 Vdc

alkaline battery- Autonomy: 2 years for normal use- Dimensions with the base (mm): φ 120 x 55

(h)- Voltage of the low battery warning:

6.7 Volts +/- 0.1 V- Operating temperature: +5°C / +55°C- Weight (with batteries): 220 g

7 CLEANING

8 LIMITS OF USE

The following operations must be performedonce per year. After removing the detector:

� Clean the slots on the side of the side ofthe detector using a vacuum cleaner and asoft brush.�Clean the outside of the cover using a

damp cloth.

The smoke alarm detector is a device thatgives a rapid warning of any outbreak of fireat a reasonable cost. However, residentialfires can break out in different ways and areoften unpredictable.

Yet it can fail to warn you of a fire if:- The battery is low or the wrong type.- The detector is not clean.- It is mounted in the wrong place or the

smoke does not reach it.- The operational test is not regularly done.

It is advisable to replace this detector after 5 years.

Cleaning your detector is essentialfor your safety. If your detector ispositioned in a dirty area, you mustclean it more frequently in order toensure that it operates efficiently.

The DOFX helps save lives, butdoes not exempt you from takingout insurance to protect personsand property.

1 PRESENTATION

The DOFX wireless smoke detector is desi-gned to detect the start of a slow burningfire. The detection of smoke particles is indi-cated by a radio message to the TYXALcontrol unit which then triggers the alarm.

It is suitable for 24 hour per day surveillanceof private homes (house, apartments, mobi-le home, caravan, etc.).

Any presence of smoke is indicated by theflashing red LED and the sounding of theaudible alarm.

Whatever the state of the system (sur-veillance On / Off), when smoke is detected:

- The CSX control unit emits warning beeps(beep, beep, beep, etc. for 45 seconds ifthe fault is no longer present, or 4 cycles of45 seconds if the fault is continuous).The fault will be indicated by the “alarm”LED 1.

- A telephone call cycle is triggered.It will indicate “fire alarm, press on star”,and your personal message.

- On a control keypad with display, “technicaldetector” appears on the screen, followedby its identity (to be personalized).

Note: The system siren does not soundbecause it is a “technical alarm”.

2 FITTINGRECOMMENDATIONS

The detector must preferably be attached tothe ceiling in the centre of the room or:- more than 20 cm from any obstacle

(wall, beam, etc.).- more than 60 cm from any corner in the

room.If this is not possible, mount the detector onthe wall at a distance of 15 to 25 cm from theceiling.

Contents:- a wireless smoke detector,- an installation and user guide,- a packet of screws.

DELTA DORE Bonnemain - 35270 COMBOURG - France

E-mail : [email protected]

This does not detect gas.

Minimum

60 cm

between15 cm

and25 cm

Acceptablelocation

Best location

TESTbutton

LED

Base

TYXALWireless alarm range

Wireless smoke detector DOFXInstallation and User Guide

For very inclined ceilings, install the detector at a horizontal distance between20 and 90 cmfrom the verticalpassing throughthe highest point

between20 cm

and 90 cm

Device complying with the requirements of the R&TTE 1999/5/EC directives

*2701916_rev1*

Page 2: TYXAL Wireless smoke detector DOFX 7 9 ... - DELTA … · 9 TECHNICAL CHARACTERISTICS Because of changes in standards and equipment, the characteristics given in the text and the

- When operating normally, DOFX emits ared flash of light once a minute.

You must fully test your detector once amonth or each time the battery is changed,or prior to each long period of absence.

To test the detector::

- Press the “TEST” but-ton located on thecover.

The LED flashes,- After around ten

seconds the alarmemits a piercing sound.

- Releasing the button will stop the alarmimmediately.

6 OPERATIONALTEST5 LEARNING

- Press the detector's “test” button until thecontrol unit emits a beep.

The control unit LED “1” (detector) lights up.

12

34

56

7

BeeeP

1

2

3

4

5

alarm

tamper alarm

battery

supervision

open door/window

remove test

2

This LED is already lit if a detection elementhas already been recorded.

- Close the battery cover of the controlunit.

Stand at a reasonable distancefrom the detector to protect yourhearing from the loud alarm.

Do not try to trigger an alarm byany other means (by using a lighter,etc.). You could damage the detec-tor.

4 REPLACING THE BATTERY

- Remove the detectorfrom the base by turningit anticlockwise.

- Pierce at the indicatedplace and mount the baseusing the 2 attachmentscrews and pins provided(∅ 5 mm).

- Fit a 6LR61 type 9 Voltbattery (see section § 4).

- Secure the detector ontothe base by turning itclockwise.

3 INSTALLATION

The DOFX is equipped with a safety device that prevents it frombeing secured without the battery.

Do not install the detector:

- Less than 1 m from heating, cooling, oraeration vents.

- In a location where the temperature maygo below 0°C or above 50°C; the detectormay malfunction.

- In a location where there is a lot ofcondensation (bathroom, laundry room) orgrease (oven, boiler), in a location wheresmoke may be produced (kitchen or agarage which is not aired), or in a dustyplace.

Never throw away the used battery. It mustbe taken back to the point of purchase.

We recommend that you change the batte-ry once a year.

Never use a rechargeable battery

Low battery indication:

The detector will emit an audible beep everyminute when the battery is low. You musttherefore replace the battery as follows:- Remove the detector from the base by

turning it anticlockwise.- Remove the used battery.- Fit a new 6LR61 type 9 Vdc alkaline

battery respecting the indicated polarityand replace it in its compartment.

- Secure the detector onto the base by turning it clockwise.

- Check that the detector is operating correctly (section § 6).

For mobile homes:- For recent mobile homes designed with

adequate insulation, install the detectors onthe ceiling.

- For poorly insulated mobile homes, a ther-mal barrier may form on the ceiling, installthe detector on a wall.

2 3

The Tyxal control unit must be inMaintenance mode (press the ON and OFFbuttons simultaneously for 5 seconds on analready recognized control device and openthe battery cover on the control unit).

Declare the DOFX detector to the controlunit:

- Press the “ON” button for more than 5 sec.on a control device,

The control unit emits a beep and the frontpanel LED is steady.

5 sec.

12

34

56

7

BeeeP

1