ComAp, spol s.r.o.Kundratka 2359/17 180 00, Praha 8 Czech Republic
InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013 1 InteliNano-NT-MRS-1.4-Fast User Guide.pdf
CAN INTERFACE
GENERATOR VOLTAGE MEASUREMENT
T16 = NeutralT17 = Phase 1T18 = Phase 2T19 = Phase 3
USB interface
LCOM
H
INTPUT TERMINALST10 = COM for analog inputsT11 = binary inputT12 = binary inputT13 = binary/analog input – Low Fuel LevelT14 = binary/analog input – Coolan TemperatureT15 = binary/analog input – Oil Pressure
OUTPUT TERMINALST04 = binary output – Starter (6A)T05 = binary output - Fuel Solenoid (6A)T06 = binary output (500 mA)T07 = binary input/output (500 mA)
POWER SUPPLY, D+T01 = BATT -T02 = D+T03 = BATT +
GECU
DIESEL / GASOLINE ENGINE GENERATOR
LOAD
Fue
l Sole
no
id
Batte
ry
Sarter
Fue
l Leve
l An
alog
Co
olan
t Tem
pe
rature
An
alog
Oil P
ressu
re A
nalo
g
D+
-+
Alarm
Re
ady To
Load
Fue
l Sole
no
idStarte
r
CO
MR
em
ote
Start An
d Lo
adEm
erge
ncy Sto
p
CA
NL C
OM
HUSB
Batte
ry +
Batte
ry -D
+
PC
L1
L2
L3
N
InteliNano NT MRS Fast User Guide
Typical wiring diagram
Accessing the setup mode
Ensure the engine is stopped and the controller is in Manual mode (green LED above button Auto is turned off). If you have not configured the custom initialization (init) screen then press and hold Stop button, then briefly press ▲ button and then Auto .If you have already created your own init screen then press and hold Stop button and then briefly press ▲, the custom init screen will appear, keep holding the Stop
button. Then press ▼ to switch LCD to default init screen, and then press Auto.To move up and down in the setup menu use ▲ and ▼ buttons. Press Start button to select or Stop button for exit.
Basic settings Input settings
Engine parameters and protections ECU setting
Generator protections Info
Output settings
Outputs and inputs
Output code
Output source Type Terminal assignment
O00 Not Used binary T04, T05, T06, T07 O01 Starter binary T04 O02 Fuel Solenoid binary T04, T05, T06, T07 O03 Stop Solenoid binary T04, T05, T06, T07 O04 Alarm binary T04, T05, T06, T07 O07 Ready To Load binary T04, T05, T06, T07 O08 Prestart binary T04, T05, T06, T07 O09 ECU Power Relay binary T04, T05, T06, T07 O10 Choke binary T04, T05, T06, T07 O11 Glow Plugs binary T04, T05, T06, T07
Normally Open Contact – output Normally Open Contact - input button
Normally Closed Contact – output Normally Closed Contact – input button
User curves
I21 I23 I25
VDO Level % VDO 5 Bar VDO 40-120 °C
Datcon Level % VDO 10 Bar VDO 50-150 °C
Datcon 5 Bar Datcon High °C
Datcon 7 Bar Datcon Low °C
Datcon 10 Bar
Not selected Not selected Not selected
Input code
Input source Type Terminal assignment
I00 Not Used binary T07, T11, T12, T13, T14, T15I01 Emergency Stop binary T07, T11, T12, T13, T14, T15I02 Remote Start/Stop binary T11 I03 Remote Start And Load binary T11 I04 Access Lock binary T07, T11, T12, T13, T14, T15 I07 GCB Feedback binary T07, T11, T12, T13, T14, T15I10 External Warning 1 binary T07, T11, T12, T13, T14, T15I11 External Warning 2 binary T07, T11, T12, T13, T14, T15I12 External Warning 3 binary T07, T11, T12, T13, T14, T15I13 External Shutdown 1 binary T07, T11, T12, T13,T14, T15I14 External Shutdown 2 binary T07, T11, T12, T13, T14, T15I15 External Shutdown 3 binary T07, T11, T12, T13, T14, T15I20 Low Fuel Level binary T07, T11, T12, T13, T14, T15I21 Fuel Level Analog analog T13, T14, T15 I22 Low Oil Pressure binary T07, T11, T12, T13, T14, T15I23 Oil Pressure Analog analog T13, T14, T15 I24 High Coolant Temperature binary T07, T11, T12, T13, T14, T15I25 Coolant Temperature Analog analog T13, T14, T15
Dimensions
Case dimensions: 118mm x108mm x 40mmPanel Cutout: 96mm x 96mm
WARNING!
If D+ is not used, connect this terminal to battery positive!
80018963
Not for
Rep
roduc
tion
ComAp, spol s.r.o. Kundratka 2359/17 180 00, Praha 8 Czech Republic
InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013 2 InteliNano-NT-MRS-1.4-Fast User Guide.pdf
Setpoints
Use ▲ and ▼ buttons to move or change value. Start button to select setpoint or confirm changes and Stop button to go back.
Basic settings
Setpoint code
Setpoint name
B01 Nominal Voltage Ph-N 80 – 480 V
B02 Nominal Voltage Ph-Ph 80 – 600 V
B03 Nominal Frequency 50 Hz (1), 60 Hz (2)
B04 Connection Type Mono Phase (1), SplitPhase (2), 3Ph3Wire (3), 3Ph4Wire (4)
B05 Units Format Metric unit format (1), US unit format (2)
B07 Zero Power Mode Delay 0-360 min
B08 Light Tower Mode Disable (1), Enable (2)
B09 Nominal RPM 100-4000
Engine parameters and protections
Setpoint code
Setpoint name
E01 Prestart Time 0-600 s
E02 Maximum Cranking Time 0-60 s
E03 Cooling Time 0-3600 s
E04 Oil Pressure Shutdown 0-10 Bar E05 Coolant Temperature Shutdown 0 -150 °C E06 Battery Undervoltage 8 – 40 V
E07 Warning Maintenance 0 – 10000 h
E08 Oil Pressure Starter Disengagement Disable (1), Enable (2) E09 Choke Time 0 – 3600 s
E10 Minimal Stabilization Time 1 – 300 s
Generator protections
Setpoint code
Setpoint name
G01 Generator Overvoltage Shutdown G02 – 200 % G02 Generator Undervoltage Shutdown 0 - G01 % G03 Generator Overfrequency Shutdown G04 – 130 % G04 Generator Underfrequency Shutdown 0 – G03 %
To apply all changes return to the main setup menu and restart the controller by pressing the Stop button.
Alarms and Events
Events
Manual Start
Remote Start
Manual Stop
Remote Stop
Auto On
Auto Off
Power On
Island Operation
Warnings
Warning Maintenance
Low Battery
Low Fuel Level
External Warning 1
External Warning 2
External Warning 3
ECU Communication Error
Shutdowns
Emergency Stop
Overspeed
Underspeed
Low Oil Pressure
High Coolant temperature
External Shutdown 1
External Shutdown 2
External Shutdown 3
GCB Fail
Generator Overvoltage
Generator Undervoltage
Generator Overfrequency
Generator Underfrequency
Generator CCW Rotation
Start Fail
Stop Fail
Battery Flat
ECU
For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide. Technical data
Power supply range 6-36 VDC Power supply drop-out immunity 100 ms Power consumption 35 – 295 mA Zero Power Mode consumption 52 - 344 µA
Operating temperature -20... 70 °C Operating humidity 95% non-condensing (IEC/EN 60068-2-30)
Protection degree (front panel) IP65 with GASKET 4x405 only IP50 without gasket
Storage temperature -30... 80 °C
Binary outputs (up to 4) Low current outputs (2) 500 mA High current output (2) 6 A (long term) / 10 A (short term) Total output current 10 A (long term) / 16 A (short term)
Binary inputs (up to 6) Input resistance 1,5 kΏ Closed contact voltage <2 V Open contact voltage >3,5 V
Analog inputs (up to 3) Galvanic insulation Not insulated Electrical range 0 - 2500 kΏ Resolution 0,1 Ώ Precision 2 % ± 3 Ώ
Charging alternator preexcitation circuit Excitation current 100 mA Charging fail threshold 80 %
Generator/Mains measurements Measurement input 3ph generator voltage Measurement type True RMS Voltage range 480 V Ph-Ph (277 V Ph-N) Max. measured voltage 340 V Ph-N Voltage accuracy 1% Frequency range 40 – 70 Hz Frequency accuracy 1 %
Not for
Rep
roduc
tion
ComAp, spol s.r.o. Kundratka 2359/17 180 00, Praha 8 Czech Republic
InteliNano-NT MRS, SW version 1.1, ©ComAp – February 2012 1 InteliNano-NT-MRS-1.1-Fast User Guide.pdf
GECU
DIESEL / GASOLINE ENGINE GENERATOR
LOAD
Fue
l Sole
no
id
Batte
ry
Sarter
Fue
l Leve
l An
alog
Co
olan
t Tem
pe
rature
An
alog
Oil P
ressu
re A
nalo
g
D+
-+
Alarm
Re
ady To
Load
Fue
l Sole
no
idStarte
r
CO
MR
em
ote
Start An
d Lo
adEm
erge
ncy Sto
p
CA
NL C
OM
HUSB
Batte
ry +
Batte
ry -D
+
PC
L1
L2
L3
N
INTERFAZ CAN
MEDIDA DE TENSION DE GENERADOR
T16 = NeutroT17 = Fase 1T18 = Fase 2T19 = Fase 3
Interfaz USB
LCOM
H
TERMINALES DE ENTRADAST10 = COM para entradas analógicasT11 = entrada binariaT12 = entrada binariaT13 = Entrada bin./anal. – Bajo nivel de combT14 = Entrada bin./anal. – Temperatura motorT15 = Entrada bin./anal. – Presion aceite
TERMINALES DE SALIDAST04 = salida binaria – Arranque (6AT05 = salida binaria - Solenoide comb (6A) T06 = salida binaria (500 mA)T07 = entrada/salida binaria (500mA)
ALIMENTACIÓN, D+T01 = BAT -T02 = D+T03 = BAT +
InteliNano NTMRS
Guia rápida de usuario
Esquema típico
Accediendo al modo programación
Asegurese de que el motor está parado y en controlador en modo Manual (el LED verde sobre el botón Auto está apagado). Si no ha configurado la pantalla inicial personalizada, mantenga presionado el botón Stop, pulse brevemente el botón ▲ y entonces pulse Auto.
Si ha creado su popia pantalla inicial, mantenga presionado el botón Stop y entonces pulse brevemente ▲, aparecerá la pantalla personalizada, mantenga presionado el botón Stop. Entonces pulse ▼ para cambiar a la pantalla por defecto, y por último presione Auto.
Para desplazarse por el menú utilice los botones ▲ y ▼. Pulse Start para seleccionar o Stop para salir.
Basic settings (Parámetros básicos) Input settings (Ajustes de entradas)
Engine parameters and protections (Parámetros y protecciones
de motor) ECU setting (Ajustes ECU)
Generator protections (Protecciones de generador) Info (Información)
Output settings (Ajuste de salidas)
Entradas y salidas
Salidas código
Fuente de la salida Tipo Asignación del terminal
O00 No Usado binario T04 , T05, T06, T0 O01 Arranque binario T04 O02 Solenoide combustible binario T05 O03 Solenoide parada binario T05 O04 Alarma binario T04, T05, T06, T07 O07 Preparado para meter carga binario T04, T05, T06, T07 O08 Prearranque binario T04, T05, T06, T07 O09 Relé de Potencia ECU binario T04, T05, T06, T07
Contacto NC – salida Contacto NA - entrada
Contacto NA – salida Contacto NC – entrada
User curves
I21 I23 I25
VDO Nivell % VDO 5 Bar VDO 40-120 °C
Datcon Nivel % VDO 10 Bar VDO 50-150 °C
Datcon 5 Bar Datcon High °C
Datcon 7 Bar Datcon Low °C
Datcon 10 Bar
No seleccionado No seleccionado No seleccionado
Input code
Input source Type Terminal assignment
I00 Not Used binary T07, T11, T12, T13, T14, T15 I01 Emergency Stop binary T07, T11, T12, T13, T14, T15 I02 Remote Start/Stop binary T11 I03 Remote Start And Load binary T11 I04 Access Lock binary T07, T11, T12, T13, T14, T15 I07 Estado GCB binary T07, T11, T12, T13, T14, T15 I10 Aviso Externo 1 binary T07, T11, T12, T13, T14, T15 I11 Aviso Externo 2 binary T07, T11, T12, T13, T14, T15 I12 Aviso Externo 3 binary T07, T11, T12, T13, T14, T15 I13 Parada Externa 1 binary T07, T11, T12, T13,T14, T15 I14 Parada Externa 2 binary T07, T11, T12, T13, T14, T15 I15 Parada Externa 3 binary T07, T11, T12, T13, T14, T15 I20 Bajo Nivel de Combustible binary T07, T11, T12, T13, T14, T15 I21 Nivel de Combustible Analog. analog T13, T14, T15 I22 Baja Presión de Aceite binary T07, T11, T12, T13, T14, T15 I23 Presión de Aceite Analog. analog T13, T14, T15 I24 Alta Temperatura Refrigerante binary T07, T11, T12, T13, T14, T15 I25 Temperatura Refrig. Analog analog T13, T14, T15
Dimensiones Dimensiones de caja:118mm x108mm x40mm
Corte panel: 96mm x 96mm
AVISO! Si no se utilize el D+, conectar este terminal al positivo de batería!
Not for
Rep
roduc
tion
ComAp, spol s.r.o. Kundratka 2359/17 180 00, Praha 8 Czech Republic
InteliNano-NT MRS, SW version 1.1, ©ComAp – February 2012 2 InteliNano-NT-MRS-1.1-Fast User Guide.pdf
Setpoints
Utillice los pulsadores ▲ y ▼ para moverse o cambiar valores. El pulsador Start para seleccionar el parámetro o confirmar los cambios y el Stop para salir.
Basic settings
Ajuste código
Nombre parámetro
B01 Tension Nominal F-N 80 – 480 V
B02 Tensión Nominal F-F 80 – 600 V
B03 Frecuencia Nominal 50 Hz (1), 60 Hz (2)
B04 Tipo Conexión Monofásica (1),Doble delta (2), 3F3Hilos (3), 3F4Hilos (4)
B05 Formato Unidades Formato Metrico (1), formato US (2)
B07 Retardo Modo Zero Consumo 0-360 min
Engine parameters and protections
Ajuste código
Nombre parámetro
E01 Tiempo Prearranque 0-600 s
E02 Máximo Tiempo Arranque 0-60 s
E03 Tiempo Enfriamiento 0-3600s
E04 Parada Presion Aceite 0-10 Bar E05 Parada Temperatura Refrigerante 0 -150 °C E06 Baja tension Batería 8 – 40 V
E07 Aviso Mantenimiento 0 – 10000 h
E08 Detección de arranque por presión Disable (1), Enable (2)
Generator protections
Ajuste código
Nombre parámetro
G01 Parada Sobretensión de generador G02 – 200 % G02 Parada Baja tension de generador 0 - G01 % G03 Parada Sobrefrecuencia de generador G04 – 130 % G04 Parada Baja frecuencia de generador 0 – G03 %
Para que se apliquen todos los cambios, vuelva a la manu principal de programación y reinicie el controlador pulsando el botón Stop.
Alarmas y Eventos
Events
Arranque Manual
Arranque Remoto
Parada Manual
Parada Remota
Auto On
Auto Off
Encendido
Operación en Isla
Warnings
Aviso Mantenimiento
Batería Baja
Bajo Nivel Combustible
Aviso Externo 1
Aviso Externo 2
Aviso Externo 3
ECU Error Comunicación
Shutdowns
Parada Emergencia
Sobrevelocidad
Baja velocidad
Baja presión de Aceite
Alta Temperatura motor
Parada Externa 1
Parada Externa 2
Parada Externa 3
Fallo GCB
Sobretensión Generador
Baja Tensión Generador
Alta frecuencia Generador
Baja frecuencia Generador
Sentido Giro Generador
Fallo de Arranque
Fallo de Parada
Batería descargada
ECU
Para la configuración ECU utilice el software para PC NanoEdit. Para más detalles vea ‘InteliNano AMF Reference Guide’. Información Técnica
Rango de alimentación 6-36VDC Inmunidad caida de tensión 100ms Consumo 35 – 295mA Consumo en modo Zero Consumo 52 - 344 µA
Temperatura de funcionamiento -20... 70°C Humedad de funcionamiento 95% no-condensado (IEC/EN 60068-2-30) Grado de protección (frente panel) IP65 Temperature almacenamiento -30... 80°C
Salidas binarias (hasta 4) Salidas de bajo corriente (2) 500mA Salidas de alta corriente (2) 6A (permanente) / 10A (puntual) Corriente de Salida Total 10A (permanente) / 16A (puntual)
Entradas binarias (hasta 6) Resistencia de Entrada 1,5 kΏ Tensión contacto cerrado <2V Tensión contacto abierto >3,5V
Entradas Analógicas (hasta 3) Aislamiento Galvánico No aislado Rango eléctrico 0 - 2500kΏ Resolución 0,1 Ώ Precisión 2% ± 3Ώ
Circuito de preexcitación del Alternador Cargabaterías Corriente de Excitación 100mA Umbral fallo de carga 80%
Medidas Generador/Red Medida entrada Tension de generador 3f, tensión de red 3f Tipo medición RMS verdadero Rango de tensión 480V F-F (277V F-N) Max. tension medida 340V F-N Preción de tensión 1% Rango de frecuencia 40 – 70 Hz Precisión de frecuencia 1%