Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
REFRIGERATION AND AIR CONDITIONING
Technical leaflet
Solenoid valves Type EVUfor fluorinated Refrigerants
2 DKRCC.PD.BD0.A3.02-520H1735 Danfoss A/S (AC-AKC / frz),11-2008
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
Danfoss A/S (AC-AKC /frz),11-2008 DKRCC.PD.BD0.A3.02-520H1735 3
Contents Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Accessories / Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-14
Design/ Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Material specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Dimensions and weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
CE
EVU 1 0.00 24 3) 19 −40→ 105 70 0.1
EVU 2 0.02 36 28 −40→ 105 70 0.2
EVU 3 0.02 36 28 −40→ 105 70 0.3
EVU 4 0.02 36 28 −40→ 105 70 0.5
EVU 5 0.02 36 28 −40→ 105 70 0.65
EVU 6 0.02 36 28 −40→ 105 70 0.8
EVU 8 0.02 36 25 −40→ 105 70 1.0
4 DKRCC.PD.BD0.A3.02-520H1735 Danfoss A/S (AC-AKC / frz),11-2008
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
Type Opening differential pressurewith standard coil
∆p bar
Temperatureof medium
°C
Max. workingpressure
PB
bar
kv-value 1)
m3/h
Min. Max. (=MOPD) liquid 2)
Min. 6 W a.c. 14 W d.c.
Introduction
The EVU solenoid valve series has been developed and constructed for soldering into semi-hermetically sealed refrigeration plant and where demands on small physical dimensions are essential. EVU 1 to 8 are compact hermetically sealed sevo operated solenoid valves for liquid, suction, and hot gas lines with fluorinated refrigerants.
EVU can be used in many different refrigeration systems and is especially designed for:
Traditional refrigeration systems
Liquid coolers
Ice cube machines
Mobile refrigeration systems
Heat pump plant
Air conditioning units
Features Compact construction small dimensions, low weight for both valve and coil.
Hermetic construction. Metallic sealing between armature tube and valve body. Bimetal connections to the brass housing Causes:
− high strength of joints and high vibration resistance
− maximum external tightness within the whole temperature and pressure operation range
Bimetal connections simple, fast soldering without the need of wet cloth or refrigration pliers
Direct and servo operated mini pistoncompact solenoid valve
Universal application for − liquid, suction, and hot gas applications − reduced power consumption
Simple and fast mounting of coil − clip-on/off
Small encapsulated coils with long life time under extreme conditions
Refrigerants R22, R134a, R404A, R507, R407C, R410A, R744 and future refrigerants
Large MOPD range − up to 36 bar
Approvals Underwriter laboratoriesPED (97/23/EC A3.P3)The Low Voltage Directive 73/23/EC with amendments EN 60730-2-8
Technical data RefrigerantsCFC, HCFC, HFC, CO2
Temperature of medium−40 → +105°C max. 130ºC during defrosting
Ambient temperature−40 → +60°C
MOPD operating range0.02 bar up to 36 bar
1) The kv value is the water flow in m3/h at a pressure drop across the valve of 1 bar, ρ = 1000 kg/m3.2) MOPD for media in gas form is approx. 8 bar higher. 3) For coil 208-240V, 60 Hz, MOPD is 17 bar.MOPD is measured with highest media and ambient temperature and 15% below nominal voltage.
EVU is supplied as straightway and angleway solder version. The valve cannot be serviced. The standard coil is available with a 3-core cable connection, DIN plug and 0.25 in. US spade. EVU valves are supplied as separate components, i.e. valve body and coil separately in industrial pack.
EVU 1 bis 6
EVU 8
EVU 1 2.01 1.85 1.40 1.89 2.01 0.23 0.16 0.20 0.21 0.29 0.93 0.73 0.75 0.99 1.40
EVU 2 4.02 2.96 2.24 3.02 3.22 0.45 0.33 0.40 0.43 0.58 1.85 1.47 1.51 1.98 2.79
EVU 3 6.03 5.55 4.2 5.67 6.03 0.68 0.49 0.60 0.64 0.87 2.78 2.2 2.26 2.96 4.19
EVU 4 10.05 9.25 7.0 9.45 10.05 1.30 0.82 1.00 1.07 1.45 4.63 3.67 3.77 4.94 6.99
EVU 5 13.07 12.03 9.1 12.29 13.07 1.46 1.06 1.30 1.39 1.89 6.01 4.77 4.9 6.42 9.81
EVU 6 16.08 14.8 11.2 15.12 16.08 1.80 1.30 1.60 1.70 2.32 7.40 5.86 6.02 7.90 11.18
EVU 8 20.10 18.50 14.00 18.90 20.10 2.25 1.63 2.00 2.13 2.90 9.25 7.33 7.53 9.88 13.97
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
Danfoss A/S (AC-AKC /frz),11-2008 DKRCC.PD.BD0.A3.02-520H1735 5
Type Rated capacity kW
Liquid Suction vapour Hot gas
R22 R134a R404A/R507
R407C R410A R22 R134a R404A/R507
R407C R410A R22 R134a R404A/R507
R407C R410A
TypeConnection Code no.
in. mm in. mm
EVU 1 ¼ 6 032F7005 032F7004
EVU 2 ¼ 6 032F5043 032F5053
EVU 3¼ 6 032F5024 032F50253/8 10 032F5026 032F5027
EVU 4
¼ 6 032F5034 032F50353/8 10 032F5036 032F5037
½ 12 032F5039 032F5038
EVU 53/8 10 032F7000 032F7001
½ 12 032F7002 032F7003
EVU 63/8 10 032F5046 032F5047
½ 12 032F5049 032F5048
EVU 8 ½ 12 032F7008 032F8009
Type Voltage
V
Frequency
Hz
Code no. Industrial pack
(40 pcs.) with DIN plug1)
IP 65
Code no.single pack
Powerconsumption
EVU 1,2,3,4,5,6 and 8
24
50/60
042N8608 042N7608 Holding:6W
12VAInrush
indkobling:26VA
48 042N8609 042N7609
115 042N8612 042N7612
230 042N8601 042N7601
240 042N8602 042N7602
Type Voltage
V
Frequency
Hz
Code no. Industrial pack
(40 pcs.)with1 m cable and
DIN plugIP 67
Code nosingle pack
Powerconsumption
EVU 1,2, 3, 4, 5,6 and 8
24
50/60
042N8658 042N7658Holding
6W12VA
Inrush:26VA
48 042N8659 042N7659
115 042N8662 042N7662
230 042N8651 042N7651
240 042N8652 042N7652
100*) 042N8671 042N7671
200*) 042N8674 042N7674
Rated liquid and suction capacity is based on evaporating temperature te = −10°C, liquid temperature ahead of the valve tl = 25°C, pressure drop in valve ∆p = 0.15 bar.
Rated hot gas capacity is based on condensing temperature tc = 40°C, pressure drop across valve ∆p = 0.8 bar, hot gas temperature th = 65°C and subcooling of refrigerant ∆tsub = 4 K.
Ordering valveNormally closed NC
OrderingCoils
Alternating current a.c.
*) 0.5 m cable with 2 x 0,75 wire
Alternating current a.c.
1) The three pins on the coil can be fitted with spade tabs, 6.3 mm wide (to DIN 46247). The two current carrying pins can also be fitted with spade tabs, 4.8. mm wide. Max. lead cross section: 1.5 mm2.
If DIN plug is used (DIN 43650) the leads must be connected in the socket. The socket is fitted with a Pg 11 screwed entry for 6 to 12 mm.
Capacity R744 CO2
Due to the fact that EVU only can be used for sub critical CO2 application, capacity tables are not illustrated in this technical leaflet. For capacity dimension please refer to DIR-Calc or contact your local Danfoss office.
6 DKRCC.PD.BD0.A3.02-520H1735 Danfoss A/S (AC-AKC / frz),11-2008
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
DIN
DIN
Type VoltageV
FrequencyHz
Code no. Indust. pack 40-off
Code no.Single pack
Powerconsumption
EVU1,2, 3, 4, 5, 6 and 8
208-240
50/60
042N8201 042N4201 Holding: 7 W14 VA
Inrush: 28 VA110-120 042N8202 042N4202
24 042N8203 042N4203
Type VoltageV
FrequenyHz
Code no.Indust. pack (40 -off)
Code no. Single pack
Powerconsumption
EVU1,2, 3, 4, 5, 6 and 8
208-240
50/60
042N8211 042N4211 Holding: 7 W14 VA
Inrush: 28 VA110-120 042N8212 042N4212
24 042N8213 042N4213
Ordering Coils (continued)
Alternating current a.c.
0,25" US spade
Alternating current a.c.
Direct current d.c.
DC coils with 0.25" US spade can be supplied on request.
Accessories / Spare parts
DIN plug, code no. 042N0156
O-ring for sealing the coil. Industrial pack (50 pcs.) Code no. 032F6115
NB: valve body supplied with O-ring from new.
Type Voltage
V
Code no.Industr. pack 40-off
With 1 m cable IP 67
Code no. Single pack
Power consumption
EVU1,2, 3, 4, 5, 6 and 8
12 042N8696 042N769614 W
24 042N8697 042N7697
Direct current d.c.Type Voltage
V
Code no.Industr. pack 40-off
With DIN plugIP 65
Code no. Single
marking
Power consumption
EVU1,2, 3, 4, 5, 6 and 8
12 042N8686 042N768614 W
24 042N8687 042N7687
Bracket for fixing of valve.Industrial pack 40-offCode number 032F8036
EVU 1 1.64 2.01 2.33 2.85 3.29 3.68
EVU 2 3.28 4.02 4.66 5.7 6.58 7.36
EVU 3 4.92 6.03 6.99 8.55 9.87 11.04
EVU 4 8.2 10.05 11.65 14.25 16.45 18.4
EVU 5 10.66 13.07 15.15 18.53 21.39 23.92
EVU 6 13.12 16.08 18.65 22.8 26.32 29.44
EVU 8 16.4 20.1 23.3 28.5 32.9 36.8
EVU 1 1.52 1.85 2.14 2.63 3.03 3.39
EVU 2 2.43 2.96 3.42 4.21 4.85 5.42
EVU 3 4.56 5.55 6.42 7.89 9.09 10.17
EVU 4 7.6 9.25 10.7 13.15 15.15 16.95
EVU 5 9.88 12.03 13.91 17.10 19.70 22.04
EVU 6 12.16 14.8 17.12 21.04 24.24 27.12
EVU 8 15.2 18.5 21.4 26.3 30.30 33.9
EVU 1 1.52 1.4 1.62 1.99 2.29 2.57
EVU 2 1.84 2.24 2.59 3.18 3.66 4.11
EVU 3 3.45 4.2 4.86 5.97 6.87 7.71
EVU 4 5.75 7.0 8.1 9.95 11.45 12.85
EVU 5 7.48 9.10 10.53 12.94 14.89 16.71
EVU 6 9.2 11.2 12.96 15.92 18.32 20.56
EVU 8 11.5 14.0 16.2 19.9 22.9 25.7
EVU 1 1.52 1.89 2.18 2.68 3.09 3.46
EVU 2 2.48 3.02 3.49 4.29 4.94 5.54
EVU 3 4.65 5.67 6.54 8.04 9.27 10.38
EVU 4 7.75 9.45 10.9 13.4 15.45 17.3
EVU 5 10.08 12.29 14.17 17.42 20.09 22.49
EVU 6 12.4 15.12 17.44 21.44 24.72 27.68
EVU 8 15.4 18.9 21.8 26.80 30.90 34.60
EVU 1 1.52 2.01 2.33 2.85 3.29 3.68
EVU 2 2.62 3.22 3.73 4.56 5.26 5.89
EVU 3 4.92 6.03 6.99 8.55 9.87 11.04
EVU 4 8.2 10.05 11.65 14.25 16.45 18.4
EVU 5 10.66 13.07 15.15 18.53 21.39 23.92
EVU 6 13.12 16.08 18.64 22.8 26.32 29.44
EVU 8 16.40 20.10 23.30 28.50 32.90 36.80
tv°C −10 0 10 15 20 25 30 35 40 45 50R22 0.76 0.82 0.88 0.92 0.96 1.0 1.05 1.1 1.16 1.22 1.3R134a 0.73 0.79 0.86 0.9 0.95 1.0 1.06 1.12 1.19 1.27 1.37R404A 0.65 0.72 0.81 0.86 0.93 1.0 1.09 1.2 1.33 1.51 1.74R507 0.65 0.73 0.81 0.87 0.93 1.0 1.08 1.19 1.31 1.47 1.69R407C 0.71 0.78 0.85 0.89 0.94 1.0 1.06 1.14 1.23 1.33 1.46R410A 0.73 0.79 0.86 0.9 0.95 1.0 1.06 1.14 1.23 1.33 1.47
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
Danfoss A/S (AC-AKC /frz),11-2008 DKRCC.PD.BD0.A3.02-520H1735 7
R22
R134a
R404A/R507
R407C
R410A
Type Liquid capacity Qo kW at pressure drop across valve ∆p bar
0.1 0.15 0.2 0.3 0.4 0.5
Type Liquid capacity Qo kW at pressure drop across valve ∆p bar
0.1 0.15 0.2 0.3 0.4 0.5
Type Liquid capacity Qo kW at pressure drop across valve ∆p bar
0.1 0.15 0.2 0.3 0.4 0.5
Type Liquid capacity Qo kW at pressure drop across valve ∆p bar
0.1 0.15 0.2 0.3 0.4 0.5
Type Liquid capacity Qo kW at pressure drop across valve ∆p bar
0.1 0.15 0.2 0.3 0.4 0.5
Capacity Liquid capacity Qo kW
Liquid capacity Qo kW
Liquid capacity Qo kW
Liquid capacity Qo kW
Liquid capacity Qo kW
Capacity is based on liquid temperature tl = + 25°C ahead of valve, evaporating temperature te = –10°C superheat 0 K.
Correction factorsWhen sizing valves, the plant capacity must be multiplied by a correction factor depending on
Correction factor for liquid temperature tl
liquid temperature tl ahead of valve/evaporator. When the corrected capacity is known, the selection can be made from the table.
EVU 10.10.150.2
0.090.110.12
0.110.140.16
0.150.180.20
1.190.230.25
0.230.280.31
0.260.330.38
EVU 20.10.150.2
0.180.220.24
0.240.280.33
0.300.350.40
0.380.450.50
0.450.550.63
0.530.650.75
EVU 30.1 0.150.2
0.270.330.37
0.350.410.49
0.450.530.6
0.560.680.75
0.680.830.94
0.790.98 1.13
EVU 40.1 0.150.2
0.460.550.61
0.590.690.82
0.750.881.0
0.941.131.25
1.131.381.57
1.321.63 1.88
EVU 50.1 0.150.2
0.590.710.79
0.770.901.06
1.351.571.79
1.221.461.63
1.461.792.04
1.712.112.44
EVU 60.1 0.150.2
0.730.870.98
0.941.11.3
1.21.41.6
1.51.82.0
1.82.22.5
2.12.63.0
EVU 80.10.150.2
0.911.091.22
1.181.381.63
1.501.752.00
1.882.252.50
2.252.753.13
2.633.253.75
EVU 10.10.150.2
0.080.090.10
0.100.120.14
0.140.160.18
0.160.200.23
0.200.250.29
0.250.300.35
EVU 20.10.150.2
0.160.180.21
0.200.240.28
0.280.330.35
0.330.400.45
0.400.500.58
0.500.600.70
EVU 30.1 0.150.2
0.230.270.31
0.30.360.41
0.410.490.53
0.490.60.68
0.60.750.86
0.750.91.1
EVU 4 0.10.150.2
0.390.460.52
0.50.610.69
0.690.820.88
0.821.01.13
1.01.251.44
1.251.51.75
EVU 50.10.150.2
0.510.590.67
0.650.790.90
0.901.061.14
1.061.31.46
1.31.621.87
1.621.952.27
EVU 60.1 0.150.2
0.62 0.73 0.82
0.80.971.10
1.101.301.4
1.301.61.8
1.62.02.30
2.02.42.8
EVU 80.10.150.2
0.780.911.03
1.001.211.38
1.381.631.75
1.632.002.25
2.002.502.88
2.503.003.50
EVU 10.10.150.2
0.060.070.07
0.080.090.11
0.110.130.14
0.140.160.19
0.180.210.24
0.210.250.30
EVU 20.10.150.2
0.120.130.15
0.160.190.22
0.210.250.28
0.280.330.38
0.350.430.48
0.430.500.60
EVU 30.1 0.150.2
0.170.2 0.22
0.240.280.33
0.320.380.41
0.410.490.56
0.530.640.71
0.640.750.9
EVU 40.1 0.150.2
0.29 0.33 0.37
0.40.470.55
0.530.630.69
0.690.820.94
0.881.071.19
1.071.251.5
EVU 50.1 0.150.2
0.380.430.47
0.510.600.71
0.680.810.90
0.901.061.22
1.141.381.55
1.381.631.95
EVU 60.1 0.150.2
0.450.530.58
0.630.740.87
0.841.01.10
1.101.301.50
1.41.701.90
1.702.0 2.4
EVU 80.10.150.2
0.580.660.73
0.790.931.09
1.051.251.38
1.381.631.88
1.752.132.38
2.132.503.00
8 DKRCC.PD.BD0.A3.02-520H1735 Danfoss A/S (AC-AKC / frz),11-2008
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
R22
R134a
R404A/R507
Type Pressure dropacross valve
∆p bar
Suction vapour capacity Qe kW at evaporating temperature te °C
–40 –30 –20 –10 0 +10
Type Pressure dropacross valve
∆p bar
Suction vapour capacity Qe kW at evaporating temperature te °C
–40 –30 –20 –10 0 +10
Type Pressure dropacross valve
∆p bar
Suction vapour capacity Qe kW at evaporating temperature te °C
–40 –30 –20 –10 0 +10
Capacity(continued)
Suction vapour capacity Qe kW
Suction vapour capacity Qo kW
Suction vapour capacity Qo kW
Capacities are based on liquid temperature tl = +25°C ahead of evaporator. The table values refer to the evaporator capacity and are given as a function of evaporating temperature te and pressure drop ∆p across valve. Capacities are based on dry, saturated vapour ahead of valve.During operation with superheated vapour ahead of valve, the capacities are reduced by 4% for each 10K superheat.
EVU 10.10.150.2
0.060.090.10
0.100.120.14
0.140.160.18
0.810.210.23
0.210.260.30
0.250.310.36
EVU 20.10.150.2
0.120.180.20
0.200.240.28
0.280.330.35
0.350.430.45
0.430.530.60
0.500.630.73
EVU 30.10.150.2
0.180.270.30
0.300.360.41
0.410.490.53
0.530.640.68
0.640.790.90
0.750.941.09
EVU 40.10.150.2
0.310.450.51
0.510.60.69
0.690.820.88
0.881.071.13
1.071.321.5
1.251.571.82
EVU 50.10.150.2
0.400.580.66
0.660.770.90
0.901.061.14
1.141.381.46
1.381.711.95
1.622.032.36
EVU 60.10.150.2
0.490.720.81
0.810.951.10
1.101.301.40
1.401.701.80
1.702.102.40
2.02.502.90
EVU 80.10.150.2
0.610.901.01
1.011.191.38
1.381.631.75
1.752.132.25
2.132.633.00
2.503.133.63
EVU 10.10.150.2
0.120.150.17
0.160.180.22
0.200.230.26
0.240.290.32
0.290.350.40
0.330.410.47
EVU 20.10.150.2
0.250.30.3
0.310.370.44
0.390.460.52
0.480.580.65
0.570.70.8
0.660.820.95
EVU 30.10.150.2
0.370.450.51
0.470.550.65
0.590.680.79
0.720.870.97
0.861.051.19
0.991.231.42
EVU 40.10.150.2
0.620.750.86
0.780.921.09
0.981.141.31
1.211.451.62
1.431.751.99
1.662.052.37
EVU 50.10.150.2
0.810.981.11
1.011.201.42
1.271.481.70
1.571.882.1
1.862.272.59
2.152.663.07
EVU 60.10.150.2
0.991.21.37
1.251.471.74
1.561.822.1
1.932.322.58
2.292.793.18
2.653.283.78
EVU 80.10.150.2
1.241.501.71
1.561.842.18
1.952.282.62
2.412.903.23
2.863.493.98
3.314.104.73
tv°C 10 15 20 25 30 35 40 45 50
R22 0.9 0.93 0.96 1.0 1.04 1.08 1.13 1.18 1.24
R134a 0.88 0.92 0.96 1.0 1.05 1.1 1.16 1.23 1.31
R404A 0.84 0.89 0.94 1.0 1.07 1.16 1.26 1.4 1.57
R507 0.84 0.89 0.94 1.0 1.07 1.16 1.26 1.39 1.57
R407C 0.88 0.91 0.95 1.0 1.05 1.11 1.18 1.26 1.35
R410A 0.89 0.92 0.96 1.0 1.05 1.11 1.18 1.26 1.37
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
Danfoss A/S (AC-AKC /frz),11-2008 DKRCC.PD.BD0.A3.02-520H1735 9
R410AType Pressure drop
∆p bar
Suction vapour capacity Qe kW at evaporating temperature te °C
–40 –30 –20 –10 0 +10
Type Pressure drop
∆p bar
Suction vapour capacity Qo kW at evaporating temperature te °C
–40 –30 –20 –10 0 +10
R407CCapacity(continued)
Suction vapour capacity Qo kW
Capacities are based on liquid temperature tl = +25°C ahead of evaporator. The table values refer to the evaporator capacity and are given as a function of evaporating temperature te and pressure drop ∆p across valve. Capacities are based on dry, saturated vapour ahead of valve.During operation with superheated vapour ahead of valve, the capacities are reduced by 4% for each 10 K superheat.
Correction factorsWhen sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid temperature tl ahead of valve/evaporator. When the corrected capacity is known, the selection can be made from the table.
Correction factors for liquid temperature tl
Suction vapour capacity Qo kW
EVU 1
0.10.20.40.81.6
0.300.430.600.831.16
0.310.450.640.851.24
0.330.460.660.931.30
0.340.430.690.991.35
0.350.490.700.991.36
EVU 2
0.10.20.40.81.6
0.600.851.201.652.33
0.630.901.281.702.48
0.650.931.331.851.60
0.680.851.381.982.70
0.700.981.401.982.73
EVU 3
0.10.20.40.81.6
0.91.281.8
2.48 3.49
0.941.351.912.553.71
0.981.391.992.783.9
1.011.282.062.964.05
1.051.462.12.964.09
EVU 4
0.10.20.40.81.6
1.52.133.04.135.82
1.572.253.194.256.19
1.632.323.324.636.5
1.692.133.444.946.75
1.752.443.54.946.82
EVU 5
0.10.20.40.81.6
1.952.763.95.367.56
2.032.924.155.528.05
2.113.014.316.018.45
2.22.764.476.428.77
2.273.174.556.428.86
EVU 6
0.10.20.40.81.6
2.43.44.86.6
9.3
2.53.65.16.89.9
2.63.75.37.4
10.4
2.73.45.57.9
10.8
2.83.95.67.9
10.9
EVU 8
0.10.20.40.81.6
3.004.256.008.25
11.63
3.134.506.388.50
12.38
3.254.636.639.25
13.00
3.384.256.889.88
13.50
3.504.887.009.88
13.63
EVU 1
0.10.20.40.81.6
0.240.340.470.660.95
0.250.360.510.701.01
0.260.370.530.731.05
0.260.380.540.771.07
0.260.370.530.761.03
EVU 2
0.10.20.40.81.6
0.470.670.931.321.90
0.50.711.021.412.01
0.520.741.061.472.09
0.530.751.071.542.13
0.520.741.061.522.12
EVU 3
0.10.20.40.81.6
0.701.011.41.982.85
0.751.071.532.113.02
0.781.111.582.23.12
0.791.131.612.313.2
0.781.111.592.283.17
EVU 4
0.10.20.40.81.6
1.181.682.333.314.76
1.251.782.553.525.03
1.31.852.643.675.23
1.321.882.683.855.33
1.311.862.653.85.29
EVU 5
0.10.20.40.81.6
1.532.183.034.36.18
1.622.313.324.576.54
1.682.43.434.776.8
1.722.443.485.006.92
1.72.413.444.946.88
EVU 6
0.10.20.40.81.6
1.88 2.69 3.735.29
7.61
1.992.844.085.68.05
2.072.954.285.868.37
2.113.04.286.168.52
2.092.974.236.088.46
EVU 8
0.10.20.40.81.6
2.353.364.666.619.51
2.493.555.107.03
10.06
2.593.695.287.33
10.46
2.643.755.357.70
10.65
2.613.715.297.60
10.58
10 DKRCC.PD.BD0.A3.02-520H1735 Danfoss A/S (AC-AKC / frz),11-2008
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
R22
R134a
Type Pressure dropacross valve
∆p bar
Hot gas capacity Qh kWEvaporating temp. te = -10°C. Hot gas temp. th = tc +25°C. Subcooling ∆tsub = 4 K
Condensing temperature tc °C
+20 +30 +40 +50 +60
Type Pressure dropacross valve
∆p bar
Hot gas capacity Qh kWEvaporating temp. te = -10°C. Hot gas temp. th = tc +25°C. Subcooling ∆tsub = 4 K
Condensing temperature tc °C
+20 +30 +40 +50 +60
Capacity(continued)
Hot gas capacity Qh kW
Hot gas capacity Qh kW
An increase in hot gas temperature th of 10 K, based on th = tc +25°C, reduces valve capacity approx. 2% and vice versa.A change in evaporating temperature te changes valve capacity; see correction factor table, page 12.
EVU 1
0.10.20.40.81.6
0.270.380.540.741.05
0.270.390.550.761.07
0.270.380.540.751.05
0.260.360.520.741.01
0.230.330.470.670.90
EVU 2
0.10.20.40.81.6
0.540.761.091.492.09
0.550.771.11.512.13
0.540.761.091.512.11
0.510.731.031.482.03
0.470.660.941.341.80
EVU 3
0.10.20.40.81.6
0.811.141.632.233.14
0.821.161.642.273.2
0.811.141.632.263.16
0.771.091.552.223.04
0.70.991.41 2.012.7
EVU 4
0.10.20.40.81.6
1.351.92.723.725.23
1.371.932.743.785.33
1.351.912.723.775.17
1.281.822.583.75.07
1.171.652.353.364.5
EVU 5
0.10.20.40.81.6
1.752.463.534.836.8
1.772.503.564.916.93
1.752.503.564.916.92
1.662.363.354.816.56
1.512.143.054.365.85
EVU 6
0.10.20.40.81.6
2.163.034.345.948.37
2.183.084.386.058.52
2.153.054.356.028.43
2.052.904.135.928.10
1.862.643.765.377.2
EVU 8
0.10.20.40.81.6
2.703.795.437.43
10.46
2.733.855.487.56
10.65
2.693.815.447.53
10.54
2.563.635.167.40
10.13
2.333.304.706.709.00
EVU 1
0.10.20.40.81.6
0.270.380.540.741.05
0.270.390.550.761.07
0.270.380.540.751.05
0.260.360.520.741.01
0.230.330.470.670.90
EVU 2
0.10.20.40.81.6
0.680.951.351.852.60
0.701.001.401.882.73
0.701.001.431.982.78
0.700.951.432.052.80
0.680.951.381.932.68
EVU 3
0.10.20.40.81.6
1.011.432.032.783.9
1.051.52.12.814.09
1.051.52.142.964.16
1.051.432.143.084.2
1.011.432.062.894.01
EVU 4
0.10.20.40.81.6
1.692.383.384.636.5
1.752.53.54.696.82
1.752.53.574.946.94
1.752.383.575.137.0
1.692.383.444.826.69
EVU 5
0.10.20.40.81.6
2.23.094.396.018.45
2.273.254.556.18.86
2.273.254.646.429.02
2.273.094.636.669.10
2.23.094.476.268.7
EVU 6
0.10.20.40.81.6
2.703.85.47.410.4
2.84.05.67.5010.90
2.84.05.707.9011.10
2.83.85.708.211.2
2.703.85.507.7010.70
EVU 8
0.10.20.40.81.6
3.44.86.89.313.0
3.55.07.09.413.6
3.55.07.19.913.9
3.54.87.110.314.0
3.44.86.99.613.4
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
Danfoss A/S (AC-AKC /frz),11-2008 DKRCC.PD.BD0.A3.02-520H1735 11
R404A/R507
R407C
Type Pressure dropacross valve
∆p bar
Hot gas capacity Qh kW
Evaporating temp. te = -10°C. Hot gas temp. th = tc +25°C. Subcooling ∆tsub = 4 K
Condensing temperature tc °C
+20 +30 +40 +50 +60
Type Pressure dropacross valve
∆p bar
Hot gas capacity Qh kWEvaporating temp. te = -10°C. Hot gas temp. th = tc +25°C. Subcooling ∆tsub = 4 K
Condensing temperature tc °C
+20 +30 +40 +50 +60
An increase in hot gas temperature th of 10 K, based on th = tc +25°C, reduces valve capacity approx. 2% and vice versa.A change in evaporating temperature te changes valve capacity; see correction factor table, page 12.
Hot gas capacity Qh kWCapacity(continued)
Hot gas capacity Qh kW
EVU 1
0.10.20.40.81.6
0.470.670.951.301.84
0.490.700.991.321.92
0.490.701.001.401.96
0.490.621.001.431.96
0.470.660.951.331.84
EVU 2
0.10.20.40.81.6
0.951.341.92.613.68
0.971.41.992.643.84
0.981.42.02.793.93
0.981.232.02.853.92
0.951.321.892.673.68
EVU 3
0.10.20.40.81.6
1.422.022.843.015.51
1.462.092.972.955.76
1.472.13.004.195.89
1.471.852.994.35.87
1.421.982.844.005.52
EVU 4
0.10.20.40.81.6
2.373.364.746.529.19
2.433.494.956.599.6
2.463.55.016.999.82
2.453.084.997.179.79
2.373.34.736.679.2
EVU 5
0.10.20.40.81.6
3.08 4.37 6.16
8.4711.95
3.154.546.438.57
12.47
3.194.546.519.08
12.76
3.184.006.499.31
12.73
3.074.286.148.67
11.96
EVU 6
0.10.20.40.81.6
3.795.387.58
10.4314.70
3.885.587.91
10.5415.35
3.935.598.01
11.1815.70
3.924.937.98
11.4615.66
3.785.277.56
10.6714.72
EVU 8
0.10.20.40.81.6
4.746.759.48
13.0418.38
4.856.986.98
13.1819.19
4.916.99
10.0113.9719.63
4.906.169.98
14.3319.58
4.736.599.45
13.3418.40
to °C −40 −30 −20 −10 0 +10R22 0.92 0.95 0.98 1.0 1.02 1.04R134a 0.88 0.92 0.96 1.0 1.04 1.08R404A 0.85 0.9 0.95 1.0 1.05 1.09R507 0.84 0.89 0.95 1.0 1.05 1.1R407C 0.89 0.93 0.96 1.0 1.03 1.07R410A 0.92 0.95 0.98 1.0 1.02 1.03
EVU 1
+90
+25+35+45
0.0030.0040.004
0.0050.0050.006
0.0060.0070.008
0.0070.0080.010
0.0070.0090.011
0.0070.0090.011
0.0070.0100.012
0.0070.0100.012
0.0070.0100.012
EVU 2+25+35+45
0.0070.0080.009
0.0090.0110.012
0.0120.0140.017
0.0140.0170.020
0.0150.0180.022
0.0150.0190.023
0.0150.0190.024
0.0150.0190.024
0.0150.0190.024
EVU 3+25+35+45
0.0100.0120.023
0.0140.0160.018
0.0180.0210.025
0.0210.0250.029
0.0220.0270.032
0.0220.0280.035
0.0220.0290.036
0.0220.0290.036
0.0220.0290.037
EVU 4+25+35+45
0.0170.0190.022
0.0230.0270.031
0.0310.0360.042
0.0350.0420.049
0.0370.0450.054
0.0370.0470.058
0.0370.0480.060
0.0370.0480.061
0.0370.0480.061
EVU 5+25+35+45
0.0220.0250.028
0.0300.0350.040
0.0400.0460.054
0.0450.0550.064
0.0470.0590.070
0.0480.0610.075
0.0480.0620.077
0.0480.0620.079
0.0480.0620.079
EVU 6+25+35+45
0.0270.0310.035
0.0370.0430.049
0.0490.0570.066
0.0550.0670.078
0.0580.0720.086
0.0590.0750.092
0.0590.0770.095
0.0590.0770.097
0.0590.0770.098
EVU 8+25+35+45
0.0340.0390.043
0.0460.0540.061
0.0610.0710.083
0.0690.0840.098
0.0730.0900.108
0.0740.0920.115
0.0740.0960.119
0.0740.9690.121
0.0740.0960.122
12 DKRCC.PD.BD0.A3.02-520H1735 Danfoss A/S (AC-AKC / frz),11-2008
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
R410A
R22
Type Pressure drop across valve
∆p bar
Hot gas capacity Qh kWEvaporating temp. te = -10°C. Hot gas temp. th = tc +25°C. Subcooling ∆tsub = 4 K
Condensing temperature tc °C tk °C
+20 +30 +40 +50 +60
Type Hot gastemp.th °C
Cond.temp.tc °C
Hot gas capacity Gh kg/s at pressure drop across valve ∆p bar
0.5 1 2 3 4 5 6 7 8
Capacity(continued)
Hot gas capacity Qh kW
An increase in hot gas temperature th of 10 K, based on th = tc +25°C, reduces valve capacity approx. 2% and vice versa.A change in evaporating temperature te changes valve capacity; see correction factor table below.
Corrections factorWhen sizing valves, the table value must be
Correction factors for evaporating temperature te
An increase in hot gas temperature of 10 K, reduces valve capacity approx. 2% and vice versa.
Hot gas capacity Gh kg/s
multiplied by a correction factor depending on evaporating temperature te.
EVU 1
+90
+25+35+45
0.0030.0040.004
0.0040.0050.006
0.0050.0060.007
0.0050.0070.009
0.0050.0070.009
0.0070.009
0.0070.009 0.009 0.009
EVU 2+25+35+45
0.0060.0070.008
0.0080.0100.011
0.0100.0120.015
0.0100.0140.017
0.0100.0140.018
0.0140.018
0.0140.018 0.018 0.018
EVU 3+25+35+45
0.0090.0110.012
0.0120.0140.017
0.0150.0180.022
0.0150.0210.026
0.0150.0210.027
0.0210.027
0.0210.027 0.027 0.027
EVU 4+25+35+45
0.0150.0180.020
0.0200.0240.028
0.0250.0310.037
0.0260.0350.043
0.0260.0350.045
0.0350.046
0.0350.046 0.046 0.046
EVU 5+25+35+45
0.0200.0230.026
0.0260.0310.036
0.0330.0400.048
0.0330.0450.055
0.0330.0460.059
0.0460.059
0.0460.059
0.059
0.059
EVU 6+25+35+45
0.0240.0280.032
0.0320.0380.045
0.0400.0490.059
0.0410.0550.068
0.0410.0560.072
0.0560.073
0.0560.073 0.073 0.073
EVU 8+25+35+45
0.0300.0350.040
0.0400.0480.056
0.0500.0610.074
0.0510.0690.085
0.0510.0700.090
0.0700.091
0.0700.091 0.091 0.091
EVU 1
+90
+25+35+45
0.0040.0050.005
0.0060.0070.008
0.0080.0090.010
0.0090.0110.012
0.0100.0120.014
0.0100.0120.015
0.0100.0130.015
0.0100.0130.016
0.0100.0130.016
EVU 2+25+35+45
0.0090.0100.011
0.0120.0140.015
0.0160.0180.020
0.0180.0210.024
0.0190.0230.027
0.0200.0250.029
0.0200.0250.031
0.0200.0250.032
0.0200.0250.032
EVU 3+25+35+45
0.0130.0140.016
0.0120.0200.023
0.0230.0270.030
0.0270.0310.036
0.0290.0350.041
0.0300.0370.044
0.0300.0380.046
0.0300.0380.047
0.0300.0380.048
EVU 4+25+35+45
0.0220.0240.027
0.0300.0340.038
0.0390.0450.051
0.0450.0530.060
0.0480.0580.068
0.0500.0620.073
0.0500.0630.077
0.0500.0630.079
0.0500.0630.080
EVU 5+25+35+45
0.0280.0310.035
0.0380.0440.049
0.0510.0590.066
0.0590.0690.079
0.0620.0750.088
0.0640.0800.094
0.0650.0820.099
0.0650.0820.103
0.0650.0820.104
EVU 6+25+35+45
0.0340.0380.043
0.0470.0540.061
0.0620.0720.082
0.0720.0850.097
0.0770.0930.108
0.0790.0980.116
0.0800.1010.122
0.0800.1010.126
0.080 0.1010.128
EVU 8+25+35+45
0.0430.0480.054
0.0590.0680.076
0.0780.0900.102
0.0900.1060.121
0.0960.1160.135
0.0990.1230.145
0.1000.1260.153
0.1000.1260.158
0.1000.1260.160
EVU 1
+90
+25+35+45
0.0040.0050.005
0.0050.0060.007
0.0070.0080.009
0.0080.0090.011
0.0080.0100.012
0.0081.0100.013
0.0080.0110.013
0.0080.0100.014
0.0080.0100.014
EVU 2+25+35+45
0.0070.0080.010
0.0100.0120.013
0.0130.0160.018
0.0150.0180.021
0.0160.0200.024
0.0160.0210.025
0.0160.0210.026
0.0160.0210.027
0.0160.0210.027
EVU 3+25+35+45
0.0110.0120.014
0.0150.0170.020
0.0200.0230.027
0.0230.0270.032
0.0240.0290.035
0.0240.0310.038
0.0240.0310.039
0.0240.0310.041
0.0240.0310.041
EVU 4+25+35+45
0.0180.0210.024
0.0250.0290.033
0.0330.0390.045
0.0380.0460.053
0.0400.0490.059
0.0410.0520.063
0.0410.0530.066
0.0410.0520.068
0.0410.0520.068
EVU 4+25+35+45
0.0230.0270.031
0.0330.0380.043
0.0430.0510.058
0.0490.0590.069
0.0510.0640.077
0.0530.0680.082
0.0530.0690.085
0.0530.0670.088
0.0530.0670.088
EVU 6+25+35+45
0.0290.0330.038
0.0400.0460.053
0.0530.0620.071
0.0600.0730.085
0.0630.0780.094
0.0650.0830.101
0.0650.0850.105
0.0650.0820.108
0.0650.0820.109
EVU 8+25+35+45
0.0360.0410.048
0.0500.0580.066
0.0660.0780.089
0.0750.0910.106
0.0790.0980.118
0.0810.1040.126
0.0810.1060.131
0.0810.1030.135
0.0810.1030.136
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
Danfoss A/S (AC-AKC /frz),11-2008 DKRCC.PD.BD0.A3.02-520H1735 13
R134a
R404A/R507
R407C
Type Hot gastemp.th °C
Cond.temp. tc °C
Hot gas temperature Gh kg/s at pressure drop across valve ∆p bar
0.5 1 2 3 4 5 6 7 8
Type Hot gastemp.th °C
Cond.temp. tc °C
Hot gas temperature Gh kg/s at pressure drop across valve ∆p bar
0.5 1 2 3 4 5 6 7 8
Type Hot gastemp.th °C
Cond.temp. tc °C
Hot gas temperature Gh kg/s at pressure drop across valve ∆p bar
0.5 1 2 3 4 5 6 7 8
Capacity(continued)
Hot gas capacity Gh kg/s
Hot gas capacity Gh kg/s
Hot gas capacity Gh kg/s
An increase in hot gas temperature of 10 K, reduces valve capacity approx. 2% and vice versa.
14 DKRCC.PD.BD0.A3.02-520H1735 Danfoss A/S (AC-AKC / frz),11-2008
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
R410A
Design / Function
1. & 5. Solder connection 2. & 4. Solder ring 3. Valve housing 6. Union nut 7. Armature tube 8. Return spring 9. Armature 10. Support ring 11. Pilot plate (servo) 12. Seat plate (servo) 13. Piston (servo)
When current is applied to the coil, the armature (9) is drawn up into the magnetic field and thus lifts the pilot plate (11) and opens for the pilot orifice so that the deenergising of the servo chamber (A) starts and the pressure is relieved to the level of the outlet side. As the inlet pressure that acts on the bottom of the piston (13) now is higher than the pressure in the servo chamber (A), the piston is moved upwards and lifts both the pilot plate (11) and the seat plate (12). When the seat plate is lifted, the main orifice opens for full flow. Therefore a minimum differential pressure of 0.02 bar is necessary to open the valve and keep it open.When the current to the coil is switched off, the spring (8) and armature (9) are pressed down to-wards the pilot plate (11). The pressure in the servo chamber (A) increases and the piston will no longer be able to hold the seat plate (12) in lifted position, by which the main orifice closes. The armature (9) continues its downwards movement untill the pilot orifice on the pilot plate (11) is fully closed.
Hot gas capacity Gh kg/sCapacity(continued) Type Hot gas
temp.th °C
Cond.temp. tc °C
Hot gas temperature Gh kg/s at pressure drop across valve ∆p bar
0.5 1 2 3 4 5 6 7 8
EVU 1
+90
+25+35+45
0.0050.0060.007
0.0070.0080.010
0.0100.0120.014
0.0130.0150.017
0.0150.0170.019
0.0171.0190.021
0.0180.0210.024
0.0180.0220.025
0.0180.0220.027
EVU 2+25+35+45
0.0080.0090.010
0.0110.0130.014
0.0160.0180.020
0.0190.0220.025
0.0220.0250.029
0.0250.0280.032
0.0270.0310.035
0.0270.0330.038
0.0270.0330.041
EVU 3+25+35+45
0.0120.0130.015
0.0170.0190.022
0.0230.0270.030
0.0290.0330.037
0.0330.0380.043
0.0370.0420.048
0.0400.0460.053
0.0400.0500.057
0.0400.0500.061
EVU 4+25+35+45
0.0200.0220.025
0.0280.0310.036
0.0390.0440.051
0.0480.0540.062
0.0550.0630.072
0.0620.0700.080
0.0670.0770.088
0.0670.0830.095
0.0670.0830.101
EVU 4+25+35+45
0.0260.0290.033
0.0360.0410.047
0.0510.0580.066
0.0620.0710.081
0.0720.0820.093
0.0800.0910.104
0.0870.1000.114
0.0870.1080.123
0.0870.1080.132
EVU 6+25+35+45
0.0310.0360.041
0.0440.0500.057
0.0630.0710.081
0.0770.0870.099
0.0880.1010.115
0.0990.1120.128
0.1070.1230.140
0.1070.1330.152
0.1070.1330.162
EVU 8+25+35+45
0.0390.0440.051
0.0550.0630.072
0.0780.0890.101
0.0960.1090.124
0.1110.1260.143
0.1240.1410.160
0.1340.1540.176
0.1340.1660.190
0.1340.1660.203
Servo operated Direct operated
Direct operatedEVU 1 is direct operated. The valve opens direct for full flow when the armature (9) moves up into the magnetic field of the coil.This means that the valve operates with a min. differential pressure, spring force and the weight of the armature. Thus, inlet pressure, spring force and the weight of the armature act to close the valve when the coil is currentless.
Servo operatedEVU 2, to 8 are servo operated solenoid valves with a "floating" piston. Piston and seat plate are here separated and can be moved independent from each other. This servo principle results in a fast operating and compact valve that is able to open against a high differential pressure. The valve closes rather soft, because the pilot system does not fully close before the main orifice has closed. This reduces force effect and wear of material in the valve.When the coil is currentless, the main orifice, seat plate (12) and pilot orifice (on the pilot plate (11)) are closed. The pilot orifice and main orifice are held closed by the armature weight, the armature spring force and the differential pressure between inlet and outlet sides.
EVU 1-6
EVU 8
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants
Danfoss A/S (AC-AKC /frz),11-2008 DKRCC.PD.BD0.A3.02-520H1735 15
Standard
No. Description Material Alloys Mat. no. W.no. DIN EN
1&5 Bi-metallic tube Stainless steel/ Cu
2 & 4 Solder ring Silver L-Ag 15P CP102 1044 1044
3 Valve body Brass CuZn40Pb2 CW617N 2.0402 17672-1 12165
6 Union nut Brass CuZn39Pb2 CW612N 2.0380 17672-1 12164
7 Armature tube Stainless steel X6CrMoS17 1.4105 10088
8 Spring Spring wire stainless X10CrNi18-8 1.4310 10088
9 Armature Stainless steel X4CrMoS18 1.410SIL 10088
10 Support ring Teflon PTFE
11 Pilot plate Thermoplast PEEK
12 Seat plate Teflon PTFE
13 Piston Brass CuZn39Pb2 CW612N 2.0380 17672-1 12164
Material specifications
Dimensions and weight
EVU 1-6, mounted with coil for DIN connection
Weight of coil6 W: approx. 0.1 kg
Weight of coil with cable approx. 0.15 kgWeight of valve
approx. 0.1 kg
16 DKRCC.PD.BD0.A3.02-520H1735 Danfoss A/S (AC-AKC / frz),11-2008
Technical leaflet Solenoid valves, type EVU for fluorinated refrigerants