36
TYM-VS2 Slide Gate Operator Installation & Owner’s Manual Operator models contained in this manual conform to UL325 standard for use in Class I, II, III, and IV applications Tymetal Corp. Greenwich, NY • Pearland, TX Phone (800) 328-GATE Fax (518)692-9404 Email [email protected] www.tymetal.com JDE Item # 41274 Revision 1, 102012

TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2Slide Gate Operator

Installation & Owner’s Manual

Operator models contained in this manualconform to UL325 standard for use in

Class I, II, III, and IV applications

Tymetal Corp.Greenwich, NY • Pearland, TXPhone (800) 328-GATEFax (518)692-9404Email [email protected]

JDE Item # 41274 Revision 1, 102012

Page 2: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

Table of ContentsPre-installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Before You Begin... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1Always Check the Gate’s Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Gate Operator Classifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Approved Obstruction Detection Devices . . . . . . . . . . . . . . . . . . . . .1

Safety Information and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1Regulatory Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Wiring Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2AC Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2DC Control and Accessory Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Mounting Pad Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3Gate Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3Mounting Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Operator Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Vent Plug Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Gate Bracket and Chain Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Chain Supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

Operator Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Controller Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Manual Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5AC Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Earth Ground. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Open and Close Limit Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . .6Limit Nuts Rough Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Limit Nuts Fine Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Setting Speeds using LSO-2 & LSC-2 . . . . . . . . . . . . . . . . . . . . . . .6Torque Limiter Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Indicator Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

Terminal Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

Operator Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Basic Controller Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Programming Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Entering Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Exiting Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Programming Keystrokes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Left or Right Hand Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Dual Gate Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Auto Close Timer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Run Alarm and Pre-start Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Maximum Open Direction Current Setting. . . . . . . . . . . . . . . . . . . .13Maximum Close Direction Current Setting . . . . . . . . . . . . . . . . . . .13

Advanced Controller Programming . . . . . . . . . . . . . . . . . . . . . . . . . . .14Entering Advanced Programming Mode . . . . . . . . . . . . . . . . . . . . .14Maximum Run Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Single Button Input Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Stagger Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Stagger Delay Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Auxiliary Relay Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Reverse Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Brake Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Constant Pressure Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Shadow Loop Open Prevention . . . . . . . . . . . . . . . . . . . . . . . . . . .15Reset Cycle Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Maintenance Alert Trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Mid-travel Stop Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Anti-tailgate Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Radio Enable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Antenna Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Radio Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Radio Transmitter Delete. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17MGT Obstacle Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . . .17MGT Obstacle Transmitter Delete. . . . . . . . . . . . . . . . . . . . . . . . . .17Motor Type Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Reset Controller to Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . .17

APeX v1.4 Gate Controller Quick Programming Guide . . . . . . . . . . .18

Loop Layout Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

Safety Edge Layout Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

Photoeye Installation Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

Picket Gate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

Dual Gate Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

Optional In-Cabinet Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

Gate Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Open Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Close Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Stop Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Reset Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Single Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Fire Department Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Open Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

Open Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Close Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Reverse Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Open Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Reverse Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Shadow/Reset Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

Operation Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Power-up Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Idle Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Last Gate Position/Condition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Pre-start Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Reverse Delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Run Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26Entrapment or Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26COMM LINK Connection Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . 26MGT Obstacle Transmitter Trouble . . . . . . . . . . . . . . . . . . . . . . . . .26Maximum Run Time Exceeded . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27Contacting Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27Operator fails to start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27Motor operates, but gate does not move. . . . . . . . . . . . . . . . . . . . .27Motor sounds like it is working harder than normal . . . . . . . . . . . . .27Limit switch getting out of time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Gate stopping part way open or closed. . . . . . . . . . . . . . . . . . . . . .27Gate staying open with automatic system. . . . . . . . . . . . . . . . . . . .27How to Order Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Model TYM-VS2 Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Controller Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316-Month Preventative Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . 31

FCC Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

Variable Speed Drive Programming. . . . . . . . . . . . . . . . . . . . . . . . . . .32Programming the Hitachi Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Gate Operator Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . 34

ONLY QUALIFIED TECHNICIANSSHOULD WORK ON

TYMETAL SLIDE GATEOPERATORS

CONTROLS INTENDED FOR USER ACTIVATION MUST BELOCATED AT LEAST SIX FEET (6’) AWAY FROM ANY MOVINGPART OF THE GATE AND WHERE THE USER IS PREVENTEDFROM REACHING OVER, UNDER, AROUND OR THROUGH THEGATE TO OPERATE THE CONTROLS. OUTDOOR OR EASILYACCESSIBLE CONTROLS SHALL HAVE A SECURITY FEATURETO PREVENT UNAUTHORIZED USE.

Page 3: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 1 - Revision 1, 102012

Pre-installation Information

Before You Begin...Before unpacking, inspect the carton for exterior damage.If you fi nd damage, advise the delivery carrier of a potential claim. Inspect your package carefully. You can check youraccessory box parts with the enclosed packing slip for yourconvenience. Claims for shortages will be honored for only30 days from the date of shipment.

Before installing the operator, read this manual completely to ensure allrequirements for proper installation are present. Verify that the voltage to beused matches the voltage of the operator.

If you have any questions about the requirements for properinstallation of this gate operator contact technical support at800-328-4283.

Always Check the Gate’s ActionIt’s very important before installing the gate operatorto make sure the gate slide is free and level throughoutthe entire opening distance. If the gate does not seem tooperate properly, it may affect the operator performanceor greatly shorten the life of the unit.

Gate Operator Classifi cations

All gate operators can be divided into one of four differentclassifi cations, depending on their design and usage. Install this gate operator only when the operator is appropriate forthe construction and usage class as defi ned below:

• Class I Residential Vehicular Gate OperatorA vehicular gate operator intended for use in a home or for oneto four single family dwellings with a common garage or parkingarea associated with these dwellings.

• Class II Commercial / General Access Vehicular Gate OperatorA vehicular gate operator intended for use in a commerciallocation or building such as a multi-family housing unit of fi ve or more single family units, hotel, retail store or other buildingservicing the general public.

• Class III Industrial / Limited Access Vehicular Gate OperatorA vehicular gate operator intended for use in an industriallocation or building such as a factory or loading dock area orother location not intended to service the general public.

• Class IV Restricted Access Vehicular Gate OperatorA vehicular gate operator intended for use in a guarded industriallocation or building such as an airport security area or otherrestricted access locations not servicing the general public,in which unauthorized access is prevented via supervision bysecurity personnel.

Approved Obstruction Detection DevicesThe following contact or non-contact obstruction detectiondevices have been approved for use with this slide gateoperator as part of a UL325 compliant installation:

• Contact EdgesMiller Edge Models MGO20, MGR20, MGS20, ME120

• PhotoeyesMMTC Model IR-55 (165’ range - P/N 2520-441)MMTC Model E3K (28’ range - P/N 2520-031)

Safety Information and Warnings

Regulatory WarningsRead the following before beginning to install this slide gateoperator:

THE FOLLOWING FORMATS ARE USED FOR SAFETYNOTES IN THESE INSTRUCTIONS.

WARNINGThis type of warning note is used to indicate possiblemechanical hazards that may cause serious injuries ordeath.

CAUTIONThis type of warning note is used to indicate the possibilityof damage to the gate or gate operator.

WARNINGThis type of warning note is used to indicate possibleelectrical shock hazards that may cause serious injuries ordeath.

IMPORTANT INSTALLATION SAFETYINSTRUCTIONS

WARNINGTO REDUCE THE RISK OF SEVEREINJURY OR DEATH TO PERSONS,

REVIEW THESE INSTALLATION SAFETYSTEPS BEFORE PROCEEDING

1. READAND FOLLOWALLINSTALLATION INSTRUCTIONS.2. Read the yellow “Safety Instructions” brochure enclosed

with the packet of information. If any pages are missing orare unreadable, or you do not have the safety instructions,please call Tymetal at 1-800-328-4283 to request additionalcopies.

3. ALL ELECTRICAL CONNECTIONS TO THE POWERSUPPLY MUST BE MADE BY A LICENSED ELECTRICIANAND MUST OBSERVE ALL NATIONAL AND LOCALELECTRICAL CODES.

4. A separate power-disconnect switch should be located nearthe operator so that primary power can be turned off whennecessary.

5. Install the enclosed warning signs on both sides of the gate.A minimum of two (2) WARNING SIGNS shall be installed,one on each side of the gate where easily visible.

6. Never reach between, through or around the fence tooperate the gate.

7. Never connect a button station within reach of the gate or onthe side of the gate operator.

8. Do not adjust the operator controller’s current sensingfeature too high. It should be adjusted high enough to keepthe gate from falsely triggering the sensing, but no higherthan necessary for the gate to operate. DO NOT DEFEATTHE PURPOSE OF THIS FUNCTION!

9. You must install all required safety equipment.10. UL325 Compliance requires the use of contact edges or

photoelectric controls on all automatic or remotely-controlledgate operators.

11. The operator is intended for installation only on gates usedfor vehicles. Pedestrians must be supplied with a separateaccess opening. The pedestrian access opening shall bedesigned to promote pedestrian usage. Locate the gate suchthat persons will not come into contact with the vehiculargate during the entire path of travel of the vehicular gate.

Page 4: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 2 - Revision 1, 102012-

Wiring Specifi cations

Refer to the following steps for details on power and accessory wiringfor the operator.

AC Power Wiring

1. Find the listing on this page corresponding to the model, voltagehorsepower, and amperage rating of your operator.

2. The distance shown in the table is measured in feet from the operatorto the power source. DO NOT EXCEED THE MAXIMUMDISTANCE. These calculations have been based on standard230 V supplies with a 10% drop allowable. If your supply is underthe standard rating, the runs listed may be longer than what yourapplication will handle, and you should not run wire too near themaximum distance for the gauge of wire you are using.

3. When large-gauge wire is used, a separate junction box (notsupplied) may be needed for the operator power connection.

4. Wire length calculations are based on the National Electrical Code,Article 430 and have been carefully determined based on motorinrush, brake solenoids, and operator requirements.

5. Connect power in accordance with local codes. The greenground wire must be properly connected.

6. Wire insulation must be suitable to the application.

7. LOCAL EARTH GROUND REQUIRED (See Figure 1 andPage 5).

DC Control and Accessory Wiring1. Choose an accessory device that is compatible with 24 VDC supply

power available at APeX controller (DC+, DC-).

2. Gate control devices (push button, keypad, card reader, etc.) use“dry contacts” handling 5VDC (from open, close, stop, and commonterminals).APeX controller provides 5 VDC supply for OPEN-CLOSE-STOP that is operational for up to 2500 ft with 20 ga. stranded wireand up to 5000 ft with 18 ga. stranded wire. In any case, wire shouldbe properly sized as per NEC standards. Long Distance Module isnot required.

3. Control wiring must be run in a separate conduit from power wiring.Running them together may cause interference and faulty signals insome accessories.

4. A three-wire shielded conductor cable is required to connect twooperators together for dual operation. You must use Belden 8760Twisted Pair Shielded Cable (or equivalent) only – P/N 2500-1982,per foot). See Page 24 for details of this connection. Note: Theshield wire should be connected in both the operators.

Control VoltageGenerally, access control and safety accessories powered from theoperator have a better tolerance for higher control voltages rather thanlower. For this reason, the 208/230 operator is manufactured with the 24Vcontrol power derived from the 230V transformer tap. The transformer islocated behind the APeX control board.

If you experience inaqequate voltage for your accessories due to lowsupply voltage, the control power source can be moved to the 208Vtransformer tap to boost the control voltage.

WARNINGALLAC ELECTRICAL CONNECTIONS TO THE POWERSOURCE AND THE OPERATOR MUST BE MADE BY ALICENSED ELECTRICIAN AND MUST OBSERVE ALLNATIONAL AND LOCAL ELECTRICAL CODES.

USE COPPER WIRE ONLY!

MODEL TYM-VS2 SINGLE PHASE POWER WIRING

VOLTS, HP &AMPERAGE

MAXIMUM DISTANCE(FEET)

WIREGAUGE

SINGLE DUAL

208 VOLTS1-HP, 10A

544 272 12864 432 101374 686 82184 1092 63476 1738 4

208 VOLTS2-HP, 16A

272 136 12432 216 10687 343 81092 546 61738 869 4

230 VOLTS1-HP, 10A

640 320 121016 508 101616 808 82570 1285 64090 2045 4

230 VOLTS2-HP, 16A

320 160 12508 254 10808 404 81285 642 62045 1022 4

MODEL TYM-VS2 THREE PHASE POWER WIRING

VOLTS, HP &AMPERAGE

MAXIMUM DISTANCE(FEET)

WIREGAUGE

SINGLE DUAL

208 VOLTS1-HP, 6A

714 357 121136 568 101804 902 8

208 VOLTS2-HP, 9A

357 178 12568 284 10902 451 8

230 VOLTS1-HP, 6A

840 420 121336 668 102124 1062 8

230 VOLTS2-HP, 9A

420 210 12668 334 101062 531 8

460 VOLTS1-HP, 3A

2689 1345 124274 2437 106798 3399 8

460 VOLTS2-HP, 6A

1345 672 122437 1218 103399 1699 8

Figure 1. Earth Ground

Page 5: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 3 - Revision 1, 102012

Mounting Pad InstallationThe gate operator mounts to posts secured in concretefootings. The posts support the operator and prevent it frommoving during operation, as shown in Figure 2.

Gate PreparationBefore installing, make sure the gate rolls or slides freely,and that all exposed rollers are properly covered. The gatemust be covered with fabric with openings no larger than2-1/4” in size, to a minimum height of 72” above groundlevel. On picket-style gates, if pickets are spaced less than2-1/4” apart, mesh is optional.

Mounting Specifi cationsUse two 4” OD galvanized posts and secure with concretefootings as shown, length to be determined by local codes,frost line depth and soil conditions.

Attach the operator with the hardware provided.

To assemble the drive chain and chain support brackets,refer to Pages 4 and 5. Make sure that the chain sag doesnot exceed recommended dimensions and that the chaindoes not come into contact with the moving parts of the gateor ground.

WARNINGThe operator is intended for installation only on gatesused for vehicles. Pedestrians must be supplied witha separate access opening. The pedestrian accessopening shall be designed to promote pedestrianusage. Locate the gate such that persons will notcome into contact with the vehicular gate during theentire path of travel of the vehicular gate.

WARNINGThe gate must be installed in a location so that enoughclearance is supplied between the gate and adjacentstructures when opening and closing to reduce therisk of entrapment.

Operator Preparation

Vent Plug InstallationIn order to keep gear oil from spilling out during shipping,gear reducers used in gate operators have either a solidplug, or a sealed vent plug, installed at the factory.

For operators with a solid plug, replace the solid plug withthe vent plug provided (see Figure 3).

With the vent plug installed, remove the vent plug’s breatherpin to allow the gear box to vent (see Figure 3)

Figure 3. Vent Plug Installation

Figure 2. Operator Elevations and Dimensions

Page 6: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 4 - Revision 1, 102012-

Figure 4a. Chain Path

Figure 4. Chain to Bracket Assembly

Figure 5. Standard

Figure 5a. Ornamental

Figure 3. Mounting Gate Bracket to Gate

5/16”-18 HEX LOCK NUT JDE# 3580

5/16”-18 x 3” HEX BOLTJDE# 3618

GATE FRAME

CHAIN MOUNTING BRACKETJDE# 3439

5/16” FLAT WASHERJDE# 3582

DRILL 11/32” THROUGHBOTH SIDES, 2 PLACES

Gate Bracket and Chain Assembly

q NOTE: The item numbers shown in these illustrationsare for reference only. For the actual part numbers, referto the parts lists in the rear of this manual.

Your gate should be hung level and move freely by hand inboth directions before attaching the operator drive chain.

Slide the gate to the fully open position. Line up the slotin the chain mounting bracket with the bottom of the idlerwheel on the operator. Mark the leading edge of the gateframe using the chain mounting bracket as a template. Drilland mount the chain mounting bracket as shown in fi gure 3.

Slide the gate to the fully closed position and mount theother chain mounting bracket to the rear edge of the gateframe in the same way.

Attach the chain to both chain mounting brackets as shownin fi gure 4, then route the chain through the operator as shown in fi gure 4a.

Install chain support brackets as shown in fi gure 5 and 5a. Brackets should support the chain but must not hit theoperator. See fi gure 2. Adjust the chain to have 1-2” of sag between the chain supports, as shown in Figure 6.

Page 7: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 5 - Revision 1, 102012

Figure 6. Operator Placement

Operator Setup

Controller AccessThe Controller is protected by a plastic dust cover. Toremove the dust cover, loosen the cover’s wing-screw andlift the cover off (see Figure 7).

AC Power ConnectionAll Tymetal gate operators are supplied with a powerdisconnect switch to turn on and off the power availableto the operator. Following wiring specifi cations on Page 2, incoming power should be brought into the operator andconnected to the labeled pigtails from the disconnect box.A wiring connections print can also be found on the labelinside the cover of the operator. See Figure 8.

Proper thermal protection is supplied with the operator. Themotor contains a thermal overload protector to guard fromoverheating the motor due to overload or high-frequency

Figure 7. Controller Access

operation. This overload protector will reset automatically

after the motor cools down.

Earth GroundInstall a ground rod and connect it to the operator’s framein every gate operator installation. A good earth groundis necessary to allow the Controller’s built-in surge andlightning protection circuitry to work effectively. The physicalbolting of the operator to the mounting posts is not suffi cient for a good earth ground. See Figure 1.

NOTE: Do not splice the ground wire. Use a single piece of solidcopper 12 AWG wire between the ground rod and the operator.

1. Install an 8-foot long copper ground rod next to the operator mountingpad within three feet of the operator.

2. Use a clamp to connect a solid copper 12 AWG ground wire to theground rod.

3. Route the ground wire to the operator.

4. Connect the ground wire to the operator’s frame.

Figure 8. Power Disconnect Box Wiring

L1

L2

Page 8: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 6 - Revision 1, 102012-

Open and Close Limit Adjustment

The limit nuts are NOT PRESET at the factory and must beadjusted for the gate in each installation. The limit switchesare activated by two threaded nylon rotary limit nuts whichare attached to a threaded limit shaft driven by a chainand sprockets from the main drive shaft. REMOVE THECARDBOARD FILLER BEFORE ADJUSTING THE LIMITNUTS.

The Controller is factory setup for right-hand installations.The OPEN limit switches are the ones closer to the frontof the operator. In left-hand installations, the CLOSE limitswitches are the ones closer to the front of the operator (seeFigures 10 & 11).

Limit Nuts Rough Adjustment

Before running the operator, set the limit nuts as follows:

1. With the gate connected to the gate operator in a mid-travel position,turn the power disconnect switch OFF.

2. To adjust the limit nuts, press down on the detent plate and rotate thelimit nut along the threaded shaft (see Figure 12).

3. Adjust the OPEN limit nut until it is about 1/2” from activating theLSO-2 OPEN limit switch.

4. Adjust the CLOSE limit nut until it is about 1/2” from activating theLSC-2 CLOSE limit switch.

CAUTIONIf the operator is installed in a left-hand installation.Set the Controller to left-hand operation BEFORErunning the operator for the fi ne setting of the limit cams. Failure to do so will result in over-shooting thelimit switches, and may cause damage to the operatorand/or gate. Refer to programming on Page 12.

Operator Setup cntd.

Manual DisconnectThe manual disconnect shifter lever and the locking lever isillustrated in Figure 9. They can be found at the center andto the left inside the operator cabinet. (The handle of eachhas been fi nished in easy to spot red fi rm-grip coating.)

To disconnect the unit for manual operation, grasp thehandle of the spring-loaded shifter lever and pull it directlytoward you until the spring-loaded locking lever snaps intoplace behind it. This action disengages the pinned shifterblock from the drive mechanism and holds the block in thedisengaged position.

To re-engage the operator, move the locking lever to theright, releasing the spring-loaded shifter lever to snap backinto the engaged position.

Manual Hand CrankTYM-VS2 is equipped with a manual hand crank to operatethe gate as an emergency means when no utility power ispresent.

1. Turn off Power

2. Put operator in manual mode using the disconnect shiftlever.

3. Remove hand crank from safety switch/holder assemblylocated in the upper right corner of the operator cabinetand unfold handle. See Figure 9a.

4. Place hand crank over hex clutch disc.

5. Turn the handle in the desired direction for gatemovement.

6. Reverse these steps to return operator to normaloperation.

□ NOTE: Removal of the crank handle from the safetyswitch holder will disable the gate operator. The crankhandle must be properly placed in the safety switchholder to allow gate operator function.

Figure 9. Manual Disconnect Lever

WARNINGALL AC ELECTRICAL CONNECTIONS TO THE POWERSOURCE AND THE OPERATOR MUST BE MADE BY ALICENSED ELECTRICIAN AND MUST OBSERVE ALLNATIONAL AND LOCAL ELECTRICAL CODES

Figure 9a. Manual Hand Crank

Page 9: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 7 - Revision 1, 102012

Operator Setup cntd.

Limit Nuts Fine AdjustmentAfter fi nishing the rough limit nut adjustments, run the operator to set the fi ne limit adjustment.

1. Turn the power disconnect switch ON.

2. Stand clear of any moving parts and press the OPEN button.

3. After the gate opens, press the CLOSE button.

4. Observe the gate in both directions as it runs through each completecycle. Adjust the open or close limit nuts again if necessary. Finelevels of adjustment can be made by adjusting a few teeth on thenut at a time. If the gate stops during travel, you may need to adjustthe Open or Close Current Setting or the Maximum Run Timer (seePages 13-14).

Setting Speeds using LSO-2 & LSC-2Limit switches LSO-2 and LSC-2 control when the operatoraccelerates to maximum speed and decelerates tominimum speed. It is recommended that LSO-2 and LSC-2are adjusted fi rst so the gate slows to near stop before hitting LSO-1 or LSC-1 as these will apply the brake uponactivation.

Adjust LSO-2 and LSC-2 by slightly loosening the twoscrews which hold them in place and sliding toward or awayfrom the center of the limit box. Care must be taken not toadjust too close to the center as the limit nut may travel pastthe switch and start accelerating at the end of the cycle.

Torque Limiter AdjustmentBefore adjusting the torque limiter, make sure the gate isin good working condition. With the gate operator in thedisconnected position, one person should be able to movethe gate by hand. Be certain the gate moves freely andwithout binding throughout its travel.

Torque limiters are SET LIGHT AT THE FACTORY. Theymust be adjusted during installation, preferably after limitcams have been manually set. With the gate operatorengaged to the gate, adjust the torque limiter tight enoughto keep it from slipping during normal operation. Theinherent entrapment protection (current sensing) featuremust activate prior to any slipping of the torque limiter.

q NOTE: The open and close current sensing may need to beadjusted before performing the following two steps. See Page 13.

To adjust the torque limiter in a Model TYM-VS2:

1. Loosen the set screw on the adjustment nut.

2. Cycle the gate open and closed while observing the torque limiteraction. TURN THE OPERATOR POWER DISCONNECTSWITCH OFF BEFORE MAKINGANYADJUSTMENTS.

To increase the torque, turn the adjustment nut clockwise one fl at, or 1/6 turn, at a time until desired output is obtained.

To reduce the torque, turn the adjustment nut counterclockwise onefl at, or 1/6 turn, at a time until desired output is obtained.

3. When fi nished, tighten the set screw to lock the adjustment nut in place

Figure 12. Setting the Limits

Figure 10. Limit Box Assembly (Right-hand Installation)

Figure 11. Limit Box Assembly (Left-hand Installation)

Figure 13. Torque Limiter Adjustment

LOCATED ON OUTPUT SHAFT

HEX SPACER

Page 10: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 8 - Revision 1, 102012-

Controller Features

Figure 14. Controller Features

Page 11: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 9 - Revision 1, 102012

Indicator Descriptions

INDICATOR DEFINITION INDICATION WHEN LITDURING NORMAL OPERATION

INDICATION WHEN LITDURING PROGRAMMINGOPERATION PROGRAMMING

24 VOLT INPUTPOWER

LOW VOLTAGE AC POWER IS PRESENT

24 VOLT DCACCY POWER

LOW VOLTAGE DC POWER IS PRESENT

OPENOPEN SIGNAL PRESENT FROM THE INTERNALRECEIVER OR AN EXTERNAL DEVICECONNECTED TO THE OPEN INPUT TERMINAL

CLOSECLOSE SIGNAL IS PRESENT FROM A DEVICECONNECTED TO THE CLOSE INPUT TERMINAL

STOPSTOP INPUT TERMINAL IS OPEN ANDNOT CONNECTED TO COMMON

PROGRAM CONTROLLER IS IN PROGRAMMING MODE

REVERSE DELAY SET SIGNAL FROM REVERSING DEVICE IS PRESENT SET REVERSE DELAY TIME

LOCKOUT ALARM SETCONTROLS AND OPERATOR ARE LOCKED OUTBECAUSE OF EXISTING TROUBLE CONDITION

SET RUN ALARM AND PRE-START ALARM

RADIO LEARNBUILT-IN RECEIVER IS DETECTING A RADIOSIGNAL FROM A REMOTE CONTROL

TRANSMITTERS CAN BE ENTERED INTOMEMORY (UP TO 40 TRANSMITTERS)

OPEN CURRENT SETMOTOR CURRENT HAS EXCEEDED THEOPEN CURRENT SETTING WHILE OPENING

SET MAXIMUM OPEN CURRENT

OPEN OBSTR MGT 2 SETOPEN OBSTRUCTION TERMINAL CONNECTEDTO COMMON BY BEAM OR SAFETY EDGE, ORSIGNAL FROM MGT OBSTACLE TRANSMITTER

SET MGT #2 FUNCTION

OPEN RELAY LH/RH SET OPEN RELAY IS ACTIVATED SET LEFT-HAND RIGHT-HAND OPERATION

OPEN LIMIT BRAKE DELAY OPEN LIMIT SWITCH IS ACTIVATED

CLOSE CURRENT SETMOTOR CURRENT HAS EXCEEDED THECLOSE CURRENT SETTING WHILE CLOSING

SET MAXIMUM CLOSE CURRENT

CLOSE OBSTR MGT 1 SETCLOSE OBSTRUCTION TERMINAL CONNECTEDTO COMMON BY BEAM OR SAFETY EDGE, ORSIGNAL FROM MGT OBSTACLE TRANSMITTER

SET MGT #1 FUNCTION

CLOSE RELAY AUTO CLOSE SET CLOSE RELAY IS ACTIVATED SET AUTO-CLOSE TIME

CLOSE LIMIT AC DC SET CLOSE LIMIT SWITCH IS ACTIVATED SET MOTOR TYPE

SINGLE SETSINGLE TERMINAL CONNECTED TO COMMONBY AN EXTERNAL PUSHBUTTON OR RADIO

SET SINGLE BUTTON INPUT FUNCTION

MAX RUN SET MAXIMUM RUN TIMER HAS BEEN EXCEEDED SET MAXIMUM RUN TIME

COMM LINK SETDUAL OPERATOR CONNECTION DETECTED,BLINKS IF CONNECTION HAS FAILED

MAINT ALERT SET MAINTENANCE IS REQUIRED ON OPERATOR SET MAINTENANCE ALERT CYCLE COUNT

Page 12: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 10 - Revision 1, 102012-

Terminal Descriptions

TERMINAL GROUP FUNCTION

AC N24 VOLT INPUT

FACTORY CONNECTED TO 24 VAC FROM TRANSFORMER OR24 VDC FROM CONTINUOUS DUTY DC SUPPLY.AC

DC -ACCESSORY POWER PROVIDES 24 VOLT DC POWER FOR ACCESSORIES. (.5A MAX)

DC +

RESETRESET BUTTON FACTORY CONNECTED TO THE CONTROLLER’S RESET BUTTON.

COMMON

C

COMM LINK FOR 3-WIRE NETWORK CONNECTION TO SECOND OPERATOR IN DUAL GATE INSTALLATIONS.B

A

COMMONSINGLE BUTTON INPUT

CONNECT TO NORMALLY OPEN SWITCH FOR SINGLE BUTTON OPERATION. ALTERNATESBETWEEN OPEN-CLOSE OR OPEN-STOP-CLOSE DEPENDING ON PROGRAMMING.SINGLE

COMMONFIRE BOX INPUT

CONNECT TO NORMALLY OPEN SWITCH IN FIRE BOX FOR FIRE DEPARTMENT ACCESS.REQUIRES STOP OR RESET TO CANCEL, AND ADDITIONAL COMMAND TO MOVE.FIRE DEPT

COMMONOPEN INPUT

CONNECT TO NORMALLY OPEN DEVICES (KEYPAD, CARD READER, KEYSWITCH,TELEPHONE ENTRY SYSTEM) TO OPEN THE GATE. A CONSTANT OPEN INPUT WILLOVERRIDE THE MID-TRAVEL STOP AND HALT THE AUTO CLOSE TIMER UNTIL RELEASED.

OPEN

OPEN

3-BUTTONSTATION INPUT

CONNECT TO 3-BUTTON STATION FOR OPEN-CLOSE-STOP CONTROL. A CONSTANT OPEN INPUTWILL OVERRIDE THE MID-TRAVEL STOP AND HALT THE AUTO CLOSE TIMER UNTIL RELEASED.

CLOSE

COMMON

STOP

COM

OPENOBSTRUCTIONINPUT

CONNECT TO NORMALLY OPEN DEVICES (GATE EDGE, PHOTO BEAM) TO DETECT ANOBSTRUCTION DURING OPENING. WHILE GATE IS MOVING, ANY OPEN OBSTRUCTIONSIGNAL WILL CAUSE THE GATE TO STOP, REVERSE A SHORT DISTANCE, AND THEN STOPAGAIN. AT THIS TIME THE AUTO CLOSE TIMER IS DISABLED, AND A RENEWED INPUTWILL BE REQUIRED TO START THE GATE AGAIN. SHOULD THE GATE BE RESTARTEDAND THE OBSTACLE SIGNAL OCCUR AGAIN PRIOR TO REACHING A LIMIT, THE GATEWILL STOP AGAIN, LOCKOUT, AND SOUND THE CONTINUOUS TONE ALARM.

O-OBS

C-OBS

CLOSEOBSTRUCTIONINPUT

CONNECT TO NORMALLY OPEN DEVICES (GATE EDGE, PHOTO BEAM) TO DETECT ANOBSTRUCTION DURING CLOSING. WHILE GATE IS MOVING, ANY CLOSE OBSTRUCTIONSIGNAL WILL CAUSE THE GATE TO STOP, THEN REVERSE AND TRAVEL TO THE FULLOPEN POSITION. SHOULD A OPEN OBSTRUCTION INPUT OR AN OPEN DIRECTIONINHERENT ENTRAPMENT CONDITION OCCUR PRIOR TO THE GATE REACHING THEOPEN LIMIT, THE OPERATOR WILL LOCKOUT AND SOUND THE CONTINUOUS TONEALARM. IF THE AUTO CLOSE TIMER IS SET, WHEN THE CLOSE OBSTRUCTION INPUTIS CLEARED, THE GATE WILL CLOSE WHEN THE AUTO CLOSE TIMER EXPIRES.

COM

COMREVERSE

CONNECT TO NORMALLY OPEN DEVICES TO CAUSE A REVERSAL WHEN THE GATE ISTRAVELING CLOSED. THE GATE WILL REVERSE TO THE FULL OPEN POSITION.REV

OPEN LOOPOPEN LOOP

CONNECT TO OPEN LOOP/FREE EXIT LOOP. THE GATE WILL OPENWHEN THE LOOP IS TRIGGERED, AND REMAIN OPEN AS LONG ASTHE LOOP IS TRIGGERED. REQUIRES LOOP DETECTOR.

OPEN LOOP

REVERSE LOOPREVERSE LOOP

CONNECT TO REVERSE LOOP. TRIGGERING THE LOOP WILL CAUSE AREVERSAL WHEN THE GATE IS TRAVELING CLOSED. THE GATE WILL REVERSETO THE FULL OPEN POSITION. REQUIRES LOOP DETECTOR.REVERSE LOOP

SHADOW/RESET LOOPSHADOW/RESET LOOP

CONNECT TO SHADOW/RESET LOOP TO KEEP THE GATE IN ITS FULLY OPENPOSITION AS LONG AS THE SIGNAL IS PRESENT. USED TO KEEP GATE OPENWHILE VEHICLE IS PASSING THROUGH. REQUIRES LOOP DETECTOR.

SHADOW/RESET LOOP

-ALARM FACTORY CONNECTED TO THE ALARM BEEPER.

+

N.O.

AUX RELAYFOR CONNECTION TO AUXILIARY DEVICES (MAGNETIC LOCK, SOLENOID LOCK,STROBE LIGHT) FOR ACTIVATION (OR DEACTIVATION) DURING GATE OPERATION.

COM

N.C.

+24 VOLT SOLAR PANEL NOT USED WITH THIS MODEL OPERATOR.

-

+24 VOLT BATTERY NOT USED WITH THIS MODEL OPERATOR.

-

Page 13: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 11 - Revision 1, 102012

Operator Accessory Connections

Figure 15. Operator Accessory Connections

N.O.

N.O.

N.O.

SEE PG. 15

SEE PG. 25

SEE PG. 25

N.C.

Page 14: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 12 - Revision 1, 102012-

Basic Controller Programming

Programming OverviewThe Controller can be programmed with various options for the operator.The programming fi elds are defi ned as “functions” that have “options”. To make setup easier for the installer, the Controller’s programming isdivided into two groups: basic and advanced. The basic programminggroup contains the functions commonly used in most slide gateinstallations. The advanced programming group contains functions lesscommonly used (i.e. dual gate stagger delay, maximum run timer, etc.).

Entering Programming ModeEnter programming mode by pressing the UP and DOWN buttonstogether for one second. While in programming mode the PROGRAMindicator will light.

Exiting Programming ModeExit programming mode at any time by pressing the UP and DOWNbuttons together. The Controller will automatically exit programmingmode after three minutes of inactivity.

Programming Keystrokes(Typical Programming Method)

While in programming mode, press the UP or DOWN buttons toscroll through the programming functions. When the desired function isdisplayed press the ENTER button to display the currently set optionfor the function. When an option is displayed, the decimalpoints are lit.

To change the option, press and hold the ENTER button for 1 second.To indicate that an option is ready to be changed, the display will fl ash. While the display is fl ashing, press the UP or DOWN button to displaythe other options available for that function.

When the desired option is displayed, press the ENTER button tostore it into memory. To select another function, press ENTER, UP,or DOWN.

Left or Right Hand OperationThe factory default is for right hand operation (operator on right side ofthe driveway when viewed from the inside of the gate). For left handinstallations, program the Controller for left hand operation.

Dual Gate EnableThe factory default is for single gate operation. For dual gate operation,wire the two gate controllers together through the COMM LINKterminals (see Page 24) and enable dual gate operation with thisprogramming step.

q NOTE: The Mid-travel Stop feature is disabled when dual gateoperation is enabled for paired units.

Auto Close TimerThe factory default turns off the Auto Close Timer. The timer can be setfrom 1 to 59 seconds and from 1 to 9 minutes. When the Auto CloseTimer is set, after opening, the gate will wait for the length of the AutoClose Timer then close automatically.

Page 15: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 13 - Revision 1, 102012

Basic Controller Programming(Cont.)

Run Alarm and Pre-start AlarmThe factory default is Run Alarm on and a 3-second Pre-start Alarm. Theoperator’s beeper will sound 3 seconds before the operator starts. Theoptions are:

• Run Alarm Off and Pre-start Alarm Off• Run Alarm On and Pre-start Alarm Off• Run Alarm On and Pre-start Alarm On for 1-9

Seconds

Maximum Open Direction Current SettingTo detect obstacles or mechanical problems with the gate, theoperator monitors its motor current. If the open current load exceedsthe programmed maximum load range number, the operator will stop,reverse a short distance, then stop again. The Auto Close Timer will bedisabled, and another open request will be required to start the operatoragain. If after restart, the overload or an open obstacle happens againbefore the open limit is reached, the operator will lockout and sound thealarm.

To measure the motor load used during opening, while this functionis being displayed, push and hold the OPEN button to fully openthe gate. During movement, the motor current will be displayed as a loadnumber from 0 to 99. This number is useful for troubleshooting but not forsetting the motor current. At the end of travel, a different number will fl ash. This number indicates the range above and below the average motorcurrent during the run. Using the + and - buttons, set the programmedrange number so that a minimal force (50-75 lbs.) will activate a reversalshould an obstruction occur, but high enough to keep the gate movingunder normal conditions without interruption.

Maximum Close Direction Current SettingTo detect obstacles or mechanical problems with the gate, theoperator monitors its motor current. If the close current load exceedsthe programmed maximum load range number, the operator will stop,reverse, and travel to the full open position. Should a open obstructioninput or an open direction inherent entrapment condition occur prior tothe gate reaching the open limit, the operator will lockout and sound thecontinuous tone alarm. Another close request will be required to start theoperator again. If after restart, the overload or a close obstacle happensagain before the close limit is reached, the operator will lockout andsound the alarm. If the auto close timer is set, when the close obstructioninput is cleared, the gate will close when the auto close timer expires.

To measure the motor load used during closing, while this functionis being displayed, push and hold the CLOSE button to closethe gate. During movement, the motor current will be displayed as aload number from 0 to 99. This number is useful for troubleshooting butnot used for setting the motor current. At the end of travel, a differentnumber will fl ash. This number indicates the range above and below the average motor current during the run. Using the + and - buttons, setthe programmed range number so that a minimal force (50-75 lbs.) willactivate a reversal should an obstruction occur, but high enough to keepthe gate moving under normal conditions without interruption.

.

.

Page 16: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 14 - Revision 1, 102012-

Advanced Controller Programming

Entering Advanced Programming ModeTo access and program the Advanced Programming functions, for eachprogramming session, Advanced Programming must be enabled.

After exiting programming, the Advanced Programmingfunctions will be available on the programming displayduring the next programming session unless theoperator has run 50 or more cycles.After that,AdvancedProgramming must be enabled again.

Maximum Run TimeThe factory default for the Maximum Run Time (MRT) is 99 seconds.When the operator starts, a timer will begin counting. If a open or closelimit is not reached or an obstacle or reversing input is not receivedbefore the timer expires, the operator will stop, the unit locks out and thealarm sounds. The timer can be set for 10 to 99 seconds, but should beleft at 99 in most applications. Setting it too close to the actual run timemay cause the time to expire with changing ambient temperature, gateconditions, etc…

If AC is present and an open or close limit is not reached or an obstacleor reversing input is not received before this timer exceeds MRT, theoperator will stop, the unit locks out and the alarm sounds.

Single Button Input SetupThis function is used for selecting the operation for single button controlsand radio receivers.

The factory default sets the SINGLE input terminal so successiveinputs will cycle the operator in OPEN-STOP-CLOSE-STOP order.

Alternately, the SINGLE input can be set to cause the gate to OPENunless the gate is fully open. If the gate is fully open, the input will causethe gate to CLOSE.

Stagger ModeThis function is used in dual gate installations only. Thefactory default sets the Stagger Mode to OFF. In dual gate installationsthe two operators communicate through the 3-wire COMM LINKinterface. When using the Stagger Mode, set one operator for delayedopening and the other operator for delayed closing. The Stagger Timeprogramming function (see below) sets the length of the delay.

q NOTE: This function will only be displayed if dual gate operation isselected.

Stagger Delay TimeThis function is used in dual gate installations only. Thefactory default sets the Stagger Time to 0 seconds (OFF). The StaggerTime sets the delay for the Stagger Mode. The Stagger Delay Time canbe set from 1-99 seconds.

q NOTE: This function will only be displayed if dual gate operation isselected.

Page 17: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 15 - Revision 1, 102012

Advanced Controller Programming (Cont.)

Auxiliary Relay ModeThe Auxiliary Relay has normally open and normally closed contacts.The factory setting disables the Auxiliary Relay. The relay can be set for:

• For solenoid locks with in-rush current less than 5a, the APeX AUXRelay will engage during any pending or actual gate motion (opendirection only) to activate a solenoid lock.

• For solenoid locks with in-rush current between 5a and 13a,a separate interface relay is required. The APeX AUX Relay willenergize during any pending or actual gate motion (open directiononly) to activate the interface relay to activate the solenoid lock.When the solenoid lock is supplied by Tymetal as part of the gateoperator order, the interface relay is added at manufacture and thecontroller is properly programmed to function as above.

• Maglock: The relay will energize during any pending or actualgate motion (open only) to deactivate a magnetic gate lock

• Ticket Dispenser: The relay will be energized at all times(enabling a ticket dispenser) unless the operator is fully open or inan entrapment position.

• Strobe: The relay will energize during any pending or actual gatemotion (either open or close) to activate a warning strobe light.

• Alarm: The relay will energize if the gate is manually forced openfrom the full closed position.

Reverse Delay TimeThe factory default sets the Reverse Delay to 1 second. The operatorwill wait the length of the delay before reversing direction. This featurewill not change the reversal time when the operator is responding to anentrapment condition from an obstruction input or inherent entrapmentprotection sensor. The Reverse Delay can be set from 1 to 9 seconds.Heaver gates require a longer delay to allow time for the gate to stop.

Brake Delay TimeThe factory default sets the Brake Delay to no delay (0 seconds). Heavygates may require delayed braking to allow the gate to slow down beforestopping it. The operator can be set to wait the length of the delay afterrunning before applying the brake. The Brake Delay can be set from0 to 3 seconds.

Constant Pressure ModeThe factory default allows momentary pressure on a control station’sOPEN or CLOSE button to cycle the operator. The controller canbe set to require constant pressure on the OPEN, CLOSE, or bothbuttons to run the operator.

q NOTE: If a button is set for constant pressure, and it is releasedbefore the operator reaches the open or close limit, the operator willstop the gate at its current position.

Shadow Loop Open PreventionIf the shadow loop is triggered, it always prevents the gate from closing ifthe Auto Close Timer activates or a CLOSE command is given while thegate is at the full open position.

The controller can also be set to prevent the gate from opening if theshadow loop is triggered while the gate is at the close limit position. Thisprevents a swing gate from opening into a vehicle if it’s parked near thegate on the inside.

Page 18: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 16 - Revision 1, 102012-

Advanced Controller Programming (Cont.)

Reset Cycle CountThe Controller counts of the number of times the operator has beencycled full open and close. The cycle count can be displayed. The displaywill scroll the cycle count number, fl ashing two digits at a time from left to right.

To reset the Cycle Count, press and hold the ENTER button for 2seconds while the Cycle Count is displayed.

If the Maintenance Alert has been triggered, resetting the Cycle Countwill also reset the Maintenance Alert indicator.

Maintenance Alert TriggerThe Controller has a MAINT ALERT indicator that can be programmedto light when the number of activations exceeds a set number of cycles.

The factory default sets the Maintenance Alert Trigger to 10,000 cycles.The Maintenance Alert Trigger can be programmed for 5, 10, 15, or 25thousand cycles.

The Maintenance Cycle Count can be reset independently from theoperator’s absolute Cycle Count.

Mid-travel Stop PositionThe Controller can be programmed so the gate will stop at a mid-travelpoint instead of fully opening. This can be useful in installations where alarge gate, that takes a long time to open and close fully, only needs tobe opened partway to allow traffi c to pass.

The factory default sets the Controller for full open operation. Alternately,the Controller can be programmed to open for 1 to 99 seconds then stop,before reaching the open limit.

When a Mid-travel Stop Position time has been programmed, the gatewill still fully open if the Fire Department input is triggered, if theOPEN button is held down beyond the Mid-travel Stop Position, or aclose obstruction or reverse loop input is triggered.

q NOTE: The Mid-travel Stop feature is disabled when dual gateoperation is enabled for paired units.

Anti-tailgate EnableThe factory default sets the Anti-tailgate Enable to OFF. With this setting,during a gate cycle, after the shadow loop has been triggered by thevehicle and then has cleared after the vehicle passes, the Auto CloseTimer or a CLOSE command is required to begin closing the gate.

If the Anti-tailgate Enable is set to ON, the gate will close immediatelyas soon as the shadow loop has cleared. Any subsequent shadow looptriggers while the gate is closing will stop the gate. When the shadowloop clears, the gate will continue closing.

Radio EnableThe Controller contains a built-in MegaCode® radio receiver to allowactivation from up to 40 access control transmitters and two Model MGT(gate edge) transmitters. The factory default enables the internal radioreceiver. Alternately, the internal receiver can be disabled.

Antenna InstallationThe Controller is supplied with a local whip antenna installed. If using aremote antenna, remove the whip antenna and connect coax cable fromthe antenna to the ANTENNA connector.

Page 19: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 17 - Revision 1, 102012

Advanced Controller Programming (Cont.)

Radio Transmitter LearnThe Controller’s built-in MegaCode® radio receiver can store the IDs of up to40 transmitters. Refer to the fi gure for the steps required to learn transmitters.

q NOTE: This function will NOT be displayed if the transmittermemory is full, or if the radio receiver is disabled.

Radio Transmitter DeleteTransmitters can be deleted from the Controller’s memory eitherindividually, or all at the same time. Refer to the fi gure for the steps required to delete transmitters.

q NOTE: This function will NOT be displayed if no transmitters arestored in memory, or if the radio receiver is disabled.

MGT Obstacle Transmitter LearnThe Controller supports one or two Model MGT Obstacle Transmitters.The transmitters can be programmed to function as Open Obstruction,Close Obstruction, Reverse, or Stop. Refer to the fi gure for the steps required to learn MGT transmitters.

q NOTE: This function will NOT be displayed if two MGT transmittersare already stored in memory, or if the radio receiver is disabled.

MGT Obstacle Transmitter DeleteMGT transmitters can be deleted from the Controller’s memory eitherindividually, or all at the same time. Refer to the fi gure for the steps required to delete MGT transmitters.

q NOTE: This function will NOT be displayed if no MGT transmittersare stored in memory, or if the radio receiver is disabled.

Motor Type SelectionThe factory sets the default for the Controller to match the type of motor inthe operator. If required, change the motor selection option to a differenttype of motor used in the operator. The options available are:

• AC Motor Only• DC Motor Only with Mechanical Braking• DC Motor with Electronic Soft Start/Stop• 3 Phase AC Motor• AC Motor with DC Motor Backup with Mechanical Braking• AC Motor with DC Motor Backup with Electronic Soft Start/Stop

Reset Controller to Factory DefaultsThe Controller can be reset with this function. ALL PROGRAMMEDDATA WILL BE LOST, and the factory defaults will be loaded. Thisfunction will not erase radio transmitters, current sense values, or motortype. Transmitters must be deleted with the two functions above.

Page 20: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 18 - Revision 1, 102012-

Page 21: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 19 - Revision 1, 102012

Page 22: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 20 - Revision 1, 102012-

Loop Layout Illustration

Page 23: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 21 - Revision 1, 102012

Safety Edge Layout Illustration

Page 24: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 22 - Revision 1, 102012-

Photoeye Installation Illustration

Page 25: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 23 - Revision 1, 102012

Picket Gate Installation

Page 26: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 24 - Revision 1, 102012-

Dual Gate Installations

Two operators can be used in dual gate installations. The operatorscommunicate with each other through the 3-wire COMM LINK terminals.

When one operator activates, the COMM LINK connection signalsthe other operator to activate. Each operator functions independently,controlling its gate and monitoring its inputs and accessories.

A three-wire shielded conductor cable is required to connect twooperators together for dual operation. Use Belden 8760 Twisted PairShielded Cable (or equivalent) only – P/N 2500-1982, per foot).

q NOTE: The shield wire should be connected COMM LINK terminal“C” in both operators.

Three of the programming functions available are only used for dual gateinstallations:

• Dual Gate EnableDual Gate Enable must be set for all dual gate installations.

• Stagger ModeThe Stagger Mode function determines if the operator has a delayedopen or a delayed close. In dual swing gate installations, typically oneoperator is programmed for delayed open, and the other operator isprogrammed for delayed close.

• Stagger Delay TimeThe Stagger Time sets the length of the delay for the Stagger Mode.

See Pages 12 & 14 for details on these three dual gate programmingfunctions.

Set the following parameters in each gate operator individually in a singlegate mode before connecting the network cable and operating in dual gatemode.

1. Open and Close Limit settings

2. Open and Closed direction inherententrapment protection (OC & CC)

After these parameters have been set, and each operator has beentested independently and is functioning correctly in single gate mode,then set BOTH operators to dual gate (dg) in the Paired Mode setup stepunder Basic Programming steps.

Optional In-Cabinet Heater

The operator can be ordered with an optional cold weatherpackage that includes an in-cabinet heater to keep the drivetrain and electronics warm in cold environments.

In-cabinet heaters can also be ordered separately andshould be wired to the operator as shown in Figure 17.Contact Technical Support for heater wiring information fora specifi c voltage and phase of operator.

Figure 16. COMM LINK Wiring

Figure 17. In-cabinet Heater Wiring

Page 27: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 25 - Revision 1, 102012

Gate Operation

Open ButtonOpens the gate. If the Controller is programmed to stopopening the gate at mid-travel, a constant press of the OPENbutton will override the Mid-travel Stop and completely openthe gate. If the Auto Close Timer is set, it will be suspendeduntil the OPEN button is released.

Close ButtonCloses the gate if the gate is open. Also closes the gate ifthe gate is in the process of opening.

Stop ButtonStops the gate from opening or closing at any time. CancelsFire Dept. Hold Open command (requires additionalmovement command to re-start operator).

Reset ButtonResets overload relay. Cancels Fire Dept. Hold Opencommand (requires additional movement command to re-start operator).

Single Input

Opens the gate if it’s closed and closes the gate if it’s open(open-close programming option). Activating the input whilethe gate is moving will reverse the gate.

Can be programmed to stop the gate while the gate ismoving (open-stop-close programming option).

Fire Department InputFully opens the gate when the input is activated. Overridesthe Mid-travel Stop and Auto Close Timer (if either isprogrammed for the gate). The gate will lockout in the openposition without sounding the alarm. Press the STOP buttonto release the lockout. Press open or close to restart gateoperator.

Open InputFunctions the same as the OPEN button.

Open ObstructionWhile the gate is opening, any open obstruction signal willcause the gate to stop, reverse a short distance, and thenstop again. The Auto Close Timer will be disabled, and arenewed input will be required to start the gate again. Shouldthe gate be restarted and the obstacle signal occur againprior to reaching a limit, the gate will stop again, lockout,and sound the emergency alarm.

Close ObstructionWhile the gate is closing, any close obstruction signalwill cause the gate to stop, reverse, and travel to the fullopen position. Should a open obstruction input or an opendirection inherent entrapment condition occur prior to thegate reaching the open limit, the operator will lockout andsound the continuous tone alarm. Another close requestwill be required to start the operator again. If after restart,the overload or a close obstacle happens again before theclose limit is reached, the operator will lockout and soundthe alarm. If the auto close timer is set, when the closeobstruction input is cleared, the gate will close when theauto close timer expires.

Reverse InputIf the reverse input is triggered while the gate is closing, thegate will reverse to the full open position. If the Auto CloseTimer is set, when the reverse input is cleared, the gate willclose when the Auto Close Timer expires.

Open LoopFunctions the same as the OPEN button.

Reverse LoopFunctions the same as the reverse input.

Shadow/Reset LoopHolds the gate fully open or fully closed while triggered.If open, the gate closes immediately when cleared ifAnti-tailgate is enabled.

Operation Indications

During normal operation, the Controller’s displays willindicate current operating conditions and status.

Power-up DisplayWhen the Controller powers up, dashes will show on thedisplay, then the fi rmware version number, then the gate type (SL for slide and swing gates).

Exiting programming restarts the Controller. The power-updisplay will show upon the restart.

Idle ConditionWhile the Controller is idling, waiting for a command, thedisplay will show circulating dashes.

Last Gate Position/ConditionWhen the gate moves or stops, the display will show thestatus for up to one minute.

• Stop is displayed as

• Full Close is displayed as

• Full Open is displayed as

• Entrapment is displayed as

Pre-start DelayDuring the pre-start delay, the display will countdown thenumber of seconds remaining before the operator starts.

Reverse DelayIf the gate travel direction is reversed from a user activationor reversing device, and a reverse delay is set, the displaywill count down the delay time in seconds before theoperator restarts.

Run TimerWhile the gate is opening or closing, the number of secondsrunning time is displayed.

Page 28: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 26 - Revision 1, 102012-

Error Indications

During abnormal operation, the Controller’s displays andbeeper will indicate the error condition that has occurred.

Entrapment or ObstructionIf an entrapment condition occurs detected by two repeatedopen or close obstruction triggers, the Controller will lockthe operator out. The beeper will sound constantly and thegate will not operate. To reset the Controller press the STOPbutton or press the RESET button on the operator’s cover.

COMM LINK Connection FailureIn dual gate installations, if there is a connection failurebetween the two operators, the COMM LINK indicator willblink once a second. During this condition the gate will notoperate, except if triggered by the FIRE DEPT input, whichfunctions normally.

MGT Obstacle Transmitter TroubleIf any MGT transmitters are used with the operator, theirsupervision feature will alert the Controller if there is anytrouble with the transmitter. MGT transmitters send hourlystatus reports and will send low battery reports when thetransmitter has a low battery. The MGT transmitters alsohave a tamper detection switch that will trigger when theircase is opened.

When the Controller detects a low transmitter battery, atamper signal, or missing transmitter status reports, thegate will still operate normally, but the beeper will changeas follows:

• The Pre-start Alarm will beep twice as fast.• The Run Alarm will beep twice as fast and continue for fi ve minutes

after the gate stops.• The sounder will “chirp” every fi ve seconds when the gate is idle.

Correct the trouble (close case, replace battery, or replacetransmitter) to clear the obstacle transmitter troubleindications.

Maximum Run Time ExceededIf the Maximum Run Time is exceeded, the Controllerstops the operator the same as if a double obstacle hasoccurred in an entrapment condition. The entrapment alarmsounds constantly, and is cleared by pressing the STOPbutton or the RESET button on the cover. After the STOPor RESET button is pressed, because the Maximum RunTime has been exceeded, the sounder will beep twice everyfi ve seconds. The next operation of the gate will clear the indication.

CONTROLLER ERROR CAUSES AND INDICATIONS

ERROR CAUSE ERROR INDICATION HOW TO CLEAR

TWO SAFETY REVERSALS (ONSINGLE GATE OR ON EITHERDUAL GATE)

En 00, CONTINUOUS ALARMBEEPER, GATE DISABLED

PRESS STOP BUTTON

MAXIMUM RUN TIMEREXCEEDED ON OPENING

En 01, AND MAX RUN LED,CONTINUOUS ALARM BEEPER,GATE DISABLED

PRESS STOP BUTTON,CLEARS CONTINUOUS ALARM,THEN DOUBLE BEEP EVERY5 SECONDS UNTIL NEXTOPERATION

MAXIMUM RUN TIMEREXCEEDED ON CLOSING

En 02, AND MAX RUN LED,CONTINUOUS ALARM BEEPER,GATE DISABLED

PRESS STOP BUTTON,CLEARS CONTINUOUS ALARM,THEN DOUBLE BEEP EVERY5 SECONDS UNTIL NEXTOPERATION

COMM LINK FAILURE

En 03, AND COMM LINK LED,CONTINUOUS ALARM BEEPERFOR 1 MINUTE, GATE DISABLED(EXCEPT FOR FIRE DEPT INPUT)

PRESS STOP BUTTON, CLEARSCONTINUOUS ALARM

GATE FULL OPEN RESULTINGFROM FIRE DEPT INPUT

En 04, GATE DISABLED PRESS STOP BUTTON

FAIL SAFE OR FAIL SECUREBECAUSE OF BATTERYVOLTAGE DROP BELOW 21.6VDC DUE TO AC POWER LOSS

En 05, GATE DISABLEDBATTERY VOLTAGE MUST RISEABOVE 24 VDC

OTHER CONTROLLER INENTRAPMENT (DUAL GATE)

En 06, GATE DISABLEDCLEAR ENTRAPMENT ONOTHER CONTROLLER (PRESSSTOP)

LOW AC VOLTAGE ATCONTROLLER

En 07, GATE DISABLEDRESTORE AC POWER TONORMAL LEVEL

INPUT TRIGGERED DURINGENTRAPMENT LOCKOUT

En 08, GATE DISABLED PRESS STOP BUTTON

COMPATIBILITY PROBLEM En 09, GATE DISABLEDUPDATE FIRMWARE AND RESETBOTH PAIRED CONTROLLERS

EEPROM PROBLEM En 10, GATE DISABLED TRY RESET, CALLTECH. SUPPORT

DC MOTOR MISMATCH En 11, GATE DISABLED

REPROGRAM MOTOR TYPE ORCHANGE DC MOTOR BOARD,NEXT GATE MOVEMENT WILLRETRY DC MOTOR CHECK

MOTOR FAILURE En 12, GATE DISABLED CALL TECH. SUPPORTAC POWER LOSS IN OPEN ORCLOSE IMMEDIATE POWERFAIL MODE

En 13 REAPPLY AC POWER

MAXIMUM RUN TIMEREXCEEDED AFTER AC POWERLOSS

En 14BATTERY VOLTAGE MUST RISEABOVE 24 VOLTS

MGT SUPERVISORY CONDITION(TAMPER, LOW BATTERY,MISSING HOURLY STATUS)

FAST BEEPS DURING PRESTART,FAST BEEP RUN ALARM, CHIRPEVERY 5 SECONDS AT IDLE

CLEARS WHEN MGT CONDITIONCLEARS

WARNINGThe Stop and/or Reset button must be located in theline-of-sight of the gate. Activation of the reset controlshall not cause the operator to start.

Page 29: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 27 - Revision 1, 102012

Troubleshooting

Contacting Technical SupportFor technical questions regarding Tymetal gate operators, contact theTechnical Support Department at:

1-800-328-4283 from 7 AM to 4:30 PM Eastern time

Operator fails to startA. If the operator has been running a large number of

cycles, the motor may have become too hot andtripped its thermal overload breaker. Allow the motor tocool down and the thermal overload breaker will resetautomatically.

B. Make sure you have power at the master distributionpanel and that the power has not been turned off.

Motor operates, but gate does not moveA. In operators with torque limiters and friction pad clutches,

check for signs of slipping. You can mark the sprocketand clutch with a yellow or white grease pen and watchfor the lines to move apart if slipping is taking place.Adjust the torque limiter tighter if this is the problem.

B. Check for broken chain or worn belts.

C. Check all setscrews on pulleys and sprockets andtighten them if necessary, and check for keys which mayhave fallen loose from keyways.

Motor sounds like it is working harder thannormalA. Make sure the gate is moving freely and without binding

throughout its entire travel.

B. Check the drive chain for obstructions (if the operatorhas one).

C. If the operator has an internal brake mechanism, makesure it is releasing.

Limit switch getting out of timeA. Check for proper tension on all limit chains to be sure

there is no jumping taking place. Mark one tooth and itscorresponding link and run the gate. If the marks havemoved, the chain is skipping.

B. Check the setscrews in limit sprockets for tightness. Inrotary limit boxes, check the rotary limit nut for sloppinessor stripped threads. Replace if necessary.

Gate stopping part way open or closed(but no visible obstruction)A. The Controller may have received a false obstruction

input triggered by current sensing set too low. Make surethe gate moves freely through its entire travel beforeadjusting the current sensing.

B. The Maximum Run Timer may have counted down andexpired. This can be caused by having the timer set toolow, if a chain or belt is broken, or if a sprocket or pulleyis slipping. When the timer expires, the gate stops andthe beeper will sound.

C. An obstruction signal from an accessory wired to theobstruction input may have triggered falsely. Check thecontrol board for lit indicators for any of the followinginputs: safety, shadow/reset, open obstruction, closeobstruction, stop, etc. If any are lit when the operatorshould be running, remove all devices hooked to thatfunction and hook them up one at a time and try to runthe operator until the problem device is found. Refer toPage 9 for details on the control board indicators.

Gate staying open with automatic systemA. If there are vehicle detectors used with the operator, one

of the loops or loop detectors may be sending a falsesignal or needs to be reset. Observe the indicators onthe loop detector. Unplug the detector and try runningthe operator.

B. An opening or reversing device may be stuck ormalfunctioning. Try disconnecting these devices andhook them back up one at a time and try running theoperator until the malfunctioning device is found.

C. Make sure the close limit switch isn’t activated. If it is, theoperator will think the gate is already closed.

Low Control Voltage

If you experience inadequate voltage for your accessoriesdue to low supply voltage, the control power source canbe moved to the 208V transformer tap to boost the controlvoltage. The transformer is located behind the APeX controlboard.

How to Order Replacement PartsUse the part numbers listed on the following pages.

Contact Tymetal Corp. to order parts.

1. Supply the model number and serial number of your operator.

2. Specify the quantity of pieces needed and order by part number and name of part.

3. State whether to ship by freight, truck, parcel post, UPS or air express.

4. State whether transportation charges are to be prepaid or collect.

5. Specify name and address of person or company to whom parts are to be shipped.

6. Specify name and address of person or company to whom invoice is to be sent.

Page 30: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 28 - Revision 1, 102012-

Model TYM-VS2 Exploded View

Page 31: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 29 - Revision 1, 102012

MODEL TYM-VS2 MECHANICAL PARTS LIST

REF.#

PART # DESCRIPTION

2120-508 Complete Enclosure with Door Assembly1 2110-846 Enclosure without Door

2110-847 Complete Door and Lock Assembly2100-848 Door Only

2500-2192 C-Face Brake, 115V2500-2397 C-Face Brake, 208/230/460V

5 2110-265 Rail Assembly15 2100-573 Spacer Plate

2100-661 Back Brace2110-852 Output Shaft Assembly

12 2100-1738 Drive Shaft, 1”48 2400-501 Retaining Ring

9 2200-274 Bearing, 1”43 2100-1737 Pillow Block Retaining Plate40 2200-042 Sprocket, 48 B 15, 1” bore

2200-015 Shaft Collar, 1”

7 2120-509 Torque Limiter Assembly, 5-1/2”7A 2100-1650 Plate with Solid Pin Groove7B 2100-1661 Keyed Plate7C 2300-390 Friction Disc (pair)7D 2200-817 Belleville Washer7E 2100-2156 Belleville Washer Retaining Disc (Hex Disc)7F 2100-1622 Adjustment Nut7G 2400-407 Brass Tipped Set Screw7H 2400-416 Dowel Pin7I 2100-529 Woodruff Key

8 2210-004 Sprocket, 40-A-48, with Bearing

42 2200-886 Drive Sprocket, 50-B-20, 1” Bore

2110-850Gear Reducer/Disconnect Assembly 115V w/Screw-in Heater

2110-851Gear Reducer/Disconnect Assembly 230V w/Screw-in Heater

2 2200-551 Gear Reducer, 10:119 2120-132 Shifter Lever Assembly18 2110-362 Shifter Lever Fulcrum Assembly37 2100-551 Shifter Lever Rod38 2400-169 Pal Nut20 2100-1133 Locking Lever Plate28 2100-910 Locking Lever41 2200-291 Shifter and Locking Lever Spring14 2200-014 Shaft Collar, 1”11 2110-364 Sprocket, 40 A 24, with Bearing30 2200-549 Disconnect Collar, 1” (keyed)31 2110-131 Shifter Block

2400-133 Key, 1/4” x 1/4” x 2-1/4”32 2200-115 Disconnect Spring33 2400-308 Fender Washer, 3/8”34 2400-017 Flat Washer, 3/8”35 2400-016 Lock Washer, 3/8”36 2400-207 HHCS, 3/8”-16 x 2-1/2”

16 2110-700 Idler Assembly2300-697 UHMW Idler Wheel2100-1731 Idler Shaft

6 2520-551 Rotary Limit Box Assembly with Harness2500-764 Limit Switch 4 (Big)2100-057 Standard Limit Shaft2200-030 Limit Nut2100-261 Detent Plate2110-162 Limit Box Enclosure with Cover2100-756-PLT Limit Box Cover only2200-029 Flange Bearing, 1/2” ID2400-029 Push-On Nut2500-2347 Limit Switch 2 (Small)190-112705 Tinnerman Speed Nut (4)2100-1825 Auxiliary Limit Bracket2510-525 Limit Harness Complete

REF.#

PART # DESCRIPTION

2200-042 Limit Drive Sprocket, 48-B-15, 1” boreFor drives up to 34 feet wide:

39 2200-008 Limit Box Sprocket, 48-B-10, 1/2” bore2200-922 #48 Chain, 25 LinksFor drives from 35 to 49 feet wide:2200-041 Limit Box Sprocket, 48-B-15, 1/2” bore2200-200 #48 Chain, per foot, 27 LinksFor drives 50 to 65 feet wide:2200-276 Limit Box Sprocket, 48-B-20, 1/2” bore2200-654 #48 Chain, per foot, 29 Links requiredFor drives over 65 feet wide:2200-432 Limit Box Sprocket, 48-B-30, 1/2” bore2200-654 #48 Chain, per foot, 32 links required

2200-010 #48 Master Link

2200-605 #40 Chain, 37 Links2200-006 #40 Master Link

17 2100-657 Rain Cover2500-2435 Alarm, 24VAC

C-FACE MOTORS

42500-2313 1/2 HP, 208/230/460 VAC, 3 Phase2500-2315 1 HP, 208/230/460 VAC, 3 Phase2500-372 2 HP, 208/230/460 VAC, 3 Phase

49 2100-2169 Stop/Reset Switch Bracket50 2500-1495 Stop/Reset Switch51 2500-2580 Electrical Disconnect Switch52 2100-2167 Support Bracket for Handle53 2200-1012 Handle for Manual Operation54 2500-2581 Contact Key for Switch

55 2510-523 115V Gear Reducer Heater Assembly2510-524 230V Gear Reducer Heater Assembly190-111059 Thermostat for Above Heaters2500-2481 115V Gear Reducer Heater Only2500-2482 230V Gear Reducer Heater Only

56 2510-262 115V Cage Heater Assembly2510-273 230V Cage Heater Assembly2520-354 460V Cage Heater Assembly2500-783 Thermostat for Above Heaters2500-174 115V Strip Heater Only2500-175 230V Strip Heater Only

Page 32: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 30 - Revision 1, 102012-

Controller Parts List

TYM-VS2 CONTROLLER MECHANICAL PARTS LIST

REF.#

PART # DESCRIPTION

Variable Speed Control Box Assemblies

2520-537 1 HP, 208/230V, 1-Phase Controller

2520-538 1 HP, 208/230V, 3-Phase Controller

2520-539 1 HP, 460V, 3-Phase Controller

2520-540 2 HP, 208/230V, 1-Phase Controller

2520-541 2 HP, 208/230V, 3-Phase Controller

2520-542 2 HP, 460V, 3-Phase Controller

1 2120-447 Enclosure with Cover

Transformers

2

2500-212 115V to 24V, 40VA

2500-791 208/230V to 24V, 40VA

2500-214 460V to 24V, 40VA

9 2500-2284460/230V Primary - 115V Secondary. 50VA for115V Gear Reducer. Heater on 460V MachinesOnly.

REF.#

PART # DESCRIPTION

Hitachi Controllers

2500-2247 1 HP, 208/230V, 1-Phase or 3-Phase

2500-2250 1 HP, 460V, 3-Phase

2500-2248 2 HP, 208/230V, 1-Phase or 3-Phase

2500-2251 2 HP, 460V, 3-Phase

APeX Parts

4 2500-1980 3-Phase Motor Board

5 2100-2149 APeX Mounting Straps

6 2500-2393 APeX Module

7 2500-2084-HALF Brake Contactor (1/2)

8 2500-2291 Power On/Off Switch, 30 Amp, 600VAC

Wiring Harnesses

102510-500 Control Box Motor Harness, 115/230V

2510-501 Control Box Motor Harness, 460V

Page 33: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 31 - Revision 1, 102012

Preventative Maintenance

GeneralTymetal gate operators are designed for many years oftrouble-free operation and, under recommended operatingconditions, will require only minimal maintenance. To ensurethat a unit is ready for operation at all times, and to precludeserious damage or failure, inspect the unit systematically.Proper adjustments and lubrication should be made asrecommended.

Lubricationq Bearings — For models which have pillow block style

bearings with grease fi ttings, lubricate at least twice a year with a lithium complex based, petroleum oil NLGI 2rated grease. Oilite and precision sealed bearings do notrequire additional lubrication.

q Motor — Motors have sealed ball bearings and do notrequire further lubrication. If bearing noise developsafter several years of operation, bearings should bereplaced by a motor repair company, or the motor shouldbe replaced if necessary.

q Drive Chain and Sprocket — The main drive chain andsprockets should be inspected for wear, cleaned, andwiped down with a lightly oiled rag every six months.

6-Month Preventative Maintenance1. For operators which utilize torque limiting clutches,

check for proper tightness. If there appears to be dustfrom wear on the pads, inspect the pads and replaceif necessary. If the clutch cannot be adjusted tightlyenough to move the gate without slipping, the pads mustbe replaced.

2. For operators with V-belts, inspect for wear and replaceas necessary. Check for proper tension and adjust ifrequired. Check all pulley setscrews for tightness andtighten if necessary.

3. For operators with internal chain drives, inspect chainand sprockets for wear and replace if necessary. Checkfor proper tension and alignment, and adjust if required.Check all hub sprocket setscrews and tighten if required.

4. Check limit switches and limit actuators (cams, limitnuts, etc.) for wear and replace as required. In rotarylimit switch assemblies, wipe the limit shaft clean andapply a light coating of dry lubricant.

5. For operators with magnetic brakes, check for properadjustment. Brake disc must run free when the brakeis engaged. For brake assemblies other than C-facestyle, the brake should be adjusted so that the solenoidplunger throw is between 3/8” to 1/2”. Too much throwwill damage the solenoid. If the solenoid emits a loudbuzzing sound when the motor is run, the brakemust be adjusted.

6. In operators which have a disconnect handle, inspectdisconnect handle for proper function and lubricate ifnecessary. Use a lithium based grease on all movingparts.

7. Inspect all nuts and bolts for proper tightness and tightenas necessary.

8. Check all reversing devices for proper function. Inspectall contact edges for wear and replace if required. Checkphotoeyes for proper alignment and function.

9. Check current sensing for proper adjustment whenfi nished with inspection and maintenance.

10.Inspect the installation area. Are all the warning signsintact and visible? If they are missing or need replaced,contact Tymetal. Be sure there are no control stationsmounted within reach of the gate. Review safetyliterature with the customer and advise them to removeany such stations found.

FCC Notice

This device complies with FCC Rules Part 15 and IndustryCanada Rules & Regulations. Operation is subject to thefollowing two conditions: (1) This device may not causeharmful interference and (2) this device must accept anyinterference received, including interference that may causeundesired operation.

WARNINGAlways disconnect power from operator beforeservicing. Keep clear of gate during operation.

For all gate operators, you mustinspect the gate forproper operation.The gate should move easily withoutbinding through its entire travel. Ifthe gate does bind, adjust or fi x as required. Failure to keep the gate ingood working condition will haveadverse effects on the operator.

Page 34: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 32 - Revision 1, 102012-

Variable Speed Drive Programming

Programming the Hitachi Inverter1. Apply power

2. Press FUNC

3. Use ▲▼ arrows to advance to F_ _ (F002 for X200)

4. Press FUNC, arrows to change to 3.0 (3.00 for X200),STR

5. Up arrow to advance to next parameter, (F03), FUNCto view, arrows to change, STR to store and continue,advance through listed parameters and store newvalues.

6. To switch from one letter prefi x to another, press FUNC3 times, advance to desired letter prefi x, press FUNC,advance to desired parameter.

7. When all parameters have been changed, advance toD01, press FUNC, then press STR. This will display theoperating speed in Hz. (0-95)

CAUTIONThis unit has been programmed at the factory. Nochanges should be necessary for normal operation.PLEASE CONSULT THE FACTORY BEFORE MAKINGANY CHANGES!

MODEL X200

FUNCTION DESCRIPTIONRECOMMENDED

SETTING

F002 ACCEL TIME 3.00

F003 DECEL TIME 3.00

A001 SPEED SOURCE 00 (POT)

A002 RUN COMMAND SOURCE 01

A004 MAX SPEED 95 (Hz)

A020 TARGET SPEED 95.0 (Hz)

A021 SECOND SPEED 20.0 (Hz)

A042 AUTO TORQUE BOOST 0

A044 BOOST PERCENT 00

A081 AUTO VOLTAGEREGULATION

01

A062 MIN SPEED 20.0 (Hz)

B001 AUTO RESET 01

B130 INHIBIT DECELOVERVOLTAGE

01

C003 TERM 3 FUNC 03

C004 TERM 4 FUNC 11

C005 RESET 18

C036 NORM. OPEN 00

C148 DELAY OUTPUT 3.0

C014 TERM 4 STATE 01

Figure 18. Hitachi X200 Inverter

NOTE: X200 modelmust have this switch in

the UP (SR) position.

NOTE: X200 model musthave these two switchesin the DOWN position.

Page 35: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 33 - Revision 1, 102012

This page left blank intentionally.

Page 36: TYM-VS2 - Tymetal · 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and

TYM-VS2 Slide Gate Operator Installation Guide - 34 - Revision 1, 102012-

Gate Operator Installation Checklist

q q 1. The gate has been checked to make sure it is level and moves freely in both directions.

q q 2. Potential pinch areas have been guarded so as to be inaccessible OR havecontact and/or non-contact obstruction sensing devices installed.

q q 3. The installer has installed one or more contact or non-contact obstruction sensingdevices, in compliance with UL325 requirements for this installation.

q q 4. If pedestrian traffi c is expected, a separate pedestrian gate has been installed, a minimum of seven feet from the gate. The customer has beeninformed that all pedestrian traffi c must use the pedestrian gate.

q q 5. Warning signs have been installed on each side of the gate in highly visible locations.The customer has been informed that these signs must remain at all times.

q q 6. There are no controls installed on the gate operator, or within seven feet of the gate.

q q 7. The installer has properly adjusted the obstruction sensing feature and has tested the gateto make sure that the gate stops and reverses a short distance with minimal resistanceapplied (40 lbs. on a swing gate at the end of the gate, 75 lbs. on a slide gate)

q q 8. The installer has instructed the customer in the proper use of the gate operator and reviewedall of the operational functions, obstruction sensing devices, warning beeper and reset, etc.

q q 9. The installer has instructed the customer in the proper use of the operator’smanual disconnect feature. The manual disconnect must never be usedwhile the gate is in motion. The power switch must be turned off beforeusing the manual disconnect and disengaging the operator.

q q 10. The installer has reviewed all safety instructions with the customer, and has leftthe safety instructions and owner’s information sheets for their reference.

q q 11. The installer has answered any questions the customer has regarding theoperation of the gate operator and gate operator safety precautions.

q q 12. The installer has explained to the customer that a regular maintenanceschedule for both the gate and the gate operator is recommended.

By signing this installation checklist, I/we hereby certify that each item listed and checked above has been covered by theinstaller and is clearly understood by the customer.

INSTALLER CUSTOMER

Customer’s Signature

Installer’s Signature

Date

Date