Conference on ‘Advances & Innovations in Sub- station' 25-26 July 2019 at Delhi By: A. H. Bhardwaj Two Decades Experience on Nitrogen Injection based Explosion Prevention and Fire Extinguishing System

Two Decades Experience on Nitrogen Injection based

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Two Decades Experience on Nitrogen Injection based

Conference on

‘Advances &

Innovations in Sub-

station' 25-26 July

2019 at Delhi

By:

A. H. Bhardwaj

Two Decades Experience on Nitrogen Injection

based Explosion Prevention and Fire Extinguishing

System

Page 2: Two Decades Experience on Nitrogen Injection based

Two Decades Experience on Nitrogen Injection based

Explosion Prevention and Fire Extinguishing System

23

• CIGRE 537, GUIDE FOR TRANSFORMER FIRE SAFETY PRACTICES

A2.33 PUBLISHED IN JUNE 2013.

• NFPA 70/ NFPA 850/ NFPA 851

• POWER TRANSFORMER STANDARDIZATION MANUAL OF IEEMA

(INDIAN ELECTRICAL AND ELECRONICS MANUFACTURERS

ASSOCIATION)\.

• MANUAL OF TRANSFORMER BY CBIP (CENTRAL BOARD OF

IRRIGATION AND POWER)

Page 3: Two Decades Experience on Nitrogen Injection based

Two Decades Experience on Nitrogen Injection based

Explosion Prevention and Fire Extinguishing System

Explosion Or Explosive Failure Is A Technical Term Often

Used In Connection With Transformer Failure, Resulting

From A Pressure Build Up From Short Circuit /Arcing

Causing Rupture Of Bushing Porcelain, A Cable Box , A

Tapchanger Or The Transformer Tank.

Page 4: Two Decades Experience on Nitrogen Injection based

Two Decades Experience on Nitrogen Injection based

Explosion Prevention and Fire Extinguishing System

23

Page 5: Two Decades Experience on Nitrogen Injection based

Two Decades Experience on Nitrogen Injection based

Explosion Prevention and Fire Extinguishing System

Technologies Available world wide:

Rupture Disc Technology

Differential Based Technology

ARC Sensor based Technology

High velocity water spray system Technology

Page 6: Two Decades Experience on Nitrogen Injection based

Two Decades Experience on Nitrogen Injection based

Explosion Prevention and Fire Extinguishing System

23

Page 7: Two Decades Experience on Nitrogen Injection based

Two Decades Experience on Nitrogen Injection based

Explosion Prevention and Fire Extinguishing System

23

IF WE SUMMARISED THE CONCEPT USING MULTIPLE RUPTURE DISCS,

IT IS OBSERVED THAT 8 RUPTURE DISCS ARE REQUIRED TO

REDUCED 30% OF THE PEAK PRESSURE:

Page 8: Two Decades Experience on Nitrogen Injection based

Two Decades Experience on Nitrogen Injection based

Explosion Prevention and Fire Extinguishing System

23

Page 9: Two Decades Experience on Nitrogen Injection based

Two Decades Experience on Nitrogen Injection based

Explosion Prevention and Fire Extinguishing System

23

NFPA 850 2015 Edition:

Page 10: Two Decades Experience on Nitrogen Injection based

23

Transformer is the origin of the fire : Where a transformer may

catch fire, i. e. causing the fire.

Transformer as a Fire Victim : The transformer can become a

victim to a fire started elsewhere. If an external fire is given sufficient

time to heat up the transformer liquid so much that the liquid is

spilled over via the conservator, then the external fire will be

strengthened if the transformer is oil filled or contains other

combustible liquid.

SOURCE : CIGRE 537 GUIDE FOR TRANSFORMER FIRE SAFETY PRACTICES

Two Decades Experience on Nitrogen Injection based

Explosion Prevention and Fire Extinguishing System

Page 11: Two Decades Experience on Nitrogen Injection based

NFPA 850-2015 EDITION GUIDELINES REGARDING OUTDOOR

OIL INSULATED TRANSFORMER:

Guideline and recommended practices to be followed to avoid:

Page 12: Two Decades Experience on Nitrogen Injection based

SYSTEM LAYOUT

Page 13: Two Decades Experience on Nitrogen Injection based

TRANSFORMER TANK AND OLTC

Page 14: Two Decades Experience on Nitrogen Injection based

SYSTEM FOR TRANSFORMER TANK AND OIL FILLED

CABLE BOXES

Page 17: Two Decades Experience on Nitrogen Injection based

Cubicle

Control

Box

Transformer

Conservator

Isolation Valve

SYSTEM COMPRISES OF

Fire Detectors Signal box

Control Box

Page 18: Two Decades Experience on Nitrogen Injection based

Inner view of

Fire

Extinguishing

Cubicle (FEC)

Page 19: Two Decades Experience on Nitrogen Injection based

CONTROL BOXES

Page 20: Two Decades Experience on Nitrogen Injection based

TRANSFORMER CONSERVATOR ISOLATION

VALVE

Page 21: Two Decades Experience on Nitrogen Injection based

FIRE DETECTOR

Page 22: Two Decades Experience on Nitrogen Injection based
Page 23: Two Decades Experience on Nitrogen Injection based

60MVA INDONESIA

Page 24: Two Decades Experience on Nitrogen Injection based

INSTALLATION IN MALAYSIA

Page 25: Two Decades Experience on Nitrogen Injection based

INSTALLATION IN MALAYSIA

Page 26: Two Decades Experience on Nitrogen Injection based

INSTALLATION IN MALAYSIA

Page 27: Two Decades Experience on Nitrogen Injection based

INSTALLATION IN MALAYSIA

Page 28: Two Decades Experience on Nitrogen Injection based

INSTALLATION IN PERU

Page 29: Two Decades Experience on Nitrogen Injection based

INSTALLATION IN SYRIA

Page 30: Two Decades Experience on Nitrogen Injection based

INSTALLATION ON GT IN

VENEZUELA

Page 31: Two Decades Experience on Nitrogen Injection based

INSTALLATION IN SYRIA

Page 32: Two Decades Experience on Nitrogen Injection based

INSTALLATION IN ECUADOR

Page 33: Two Decades Experience on Nitrogen Injection based

SOME MAJOR CUSTOMERS

Page 34: Two Decades Experience on Nitrogen Injection based

Thank you Ashish Bhardwaj