50
TVR LX A leap in efficiency and innovation

TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

TVR™ LXA leap in efficiency and innovation

Page 2: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

2

TVR™ LX Systems, a new leap in technology and innovation 3

Why TVR LX? 4

Simultaneous Heating and Cooling 5

System Features 7

Outdoor Units 12

Indoor Units 14

Intelligent Management Control System 40

New Service Software 46

Other Accessories 46

TVR LX Outside Air Solutions 47

Page 3: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

33

TVR™ LX Systems, a new leap in technology and innovation

A proven solution from a trusted advisor

Trane is proud to present their new line of variable refrigerant systems, TVR LX.

The new TVR LX expanded portfolio of outdoor units comprises the largest capacity range for variable refrigerant systems in the industry. The maximum capacity of the largest modular system is 840MBH, a new mark in this category.

TVR LX represents a leap in efficiency and innovation.This is accomplished through the use of an optimized fan design with a DC fan motor, an improved high performance heat exchanger, Brushless Reluctance DC inverter scroll compressors and intelligent defrost capability.

TVR LX can be applied as the main HVAC system in a building or as a supplemental system that coordinates with an existing HVAC installation to meet different application requirements.

The TVR LX is ideal for buildings that have different requirements for future tenants, for buildings requiring tenant by tenant installation, operation and billing. The compact size of the indoor units, the small footprint and modularity of outdoor units and the use of small refrigerant pipes to transport energy between outdoor and indoor units make this product the ideal solution for existing buildings.

Individual control

The use of individual LCD zone controllers, allows users to meet their individual comfort needs as the TVR LX system will control the refrigerant flow to each individual zone in order to meet the cooling or heating requirements.

TVR LX controls are factory integrated, and when combined with available remote temperature sensors, programmable controllers, centralized controller or integrated into a Building Management System (BMS) you will ensure the most efficient and reliable operation of an air conditioning system.

TVR LX is designed to maximize the comfort of the user by matching the cooling or heating load required in each zone with no overheating or under cooling, keeping the ambient temperature within 0.5°C from the established setpoint.

Indoor air quality

While cooling or heating, the TVR LX system also dehumidifies the indoor air and independently filters the air in each zone with no possibility of cross contamination between independent zones.

All functions necessary for filtration, cooling and heating, ventilation and dehumidification are fully integrated within the TVR LX system.

The indoor air quality can be improved when pretreated outside air is introduced into the building either through direct connection to the indoor units (4-way cassette units) or through our 100% fresh air concealed units.

The TVR LX system can handle the integration with external fresh air through different solutions.

TVR LX’s individual independent control per zone

Page 4: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

4

Why TVR™ LX?Energy Efficient System

The TVR LX system’s automatic power consumption adjustment matches the cooling load perfectly to the changing needs of all the individual zones thus realizing energy savings. The capacity is controlled intelligently and distributed evenly over the different zones without wasting energy.

Energy Efficiency (EER) increases at partial load when fewer indoor units require cooling/heating thus reducing the total power consumption. A TVR LX system does not run at full speed all the time and during a typical daily operation a TVR LX system will work for a majority of its time in the unloading zone with higher energy efficiency. During partial load the inverter compressor runs at reduced speed matching the required building load.

Flexible Design

The TVR LX System can be customized to the highest degree. The ability to use heat pump or heat recovery modular outdoor units and connect them together in series, offers the greatest design flexibility possible.

A total of 41 different outdoor unit combinations are available that can be matched with a total of 72 different indoor units to meet any type of requirement. The largest 840 MBH modules allow the connection of up to 64 indoor units thus delivering comfort as far as 175 m. away from the outdoor units.

The optional high static pressure outdoor fan motor allows floor to floor installation of the outdoor units when this could be the optimal solution for a particular application.

The TVR LX system allows customization towards the future where zones can be easily added, replaced or removed depending on the changing needs of the end user.

Energy Management

The optional centralized control system of the TVR LX system already has all the power management data or information points of each individual zone. Adding the power measurement software to the system allows the user to calculate the individual power consumption per zone, per floor or per building. The control software will require a digital ammeter per outdoor unit and the Web Gateway centralized controller.

DC INVERTER

Page 5: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

5

DC Inverter Advantage

Energy Saving

The introduction of a high efficiency DC inverter scroll compressor driven by the most advanced control technology is designed to provide more precise operation and improved system efficiency.

The compressor speed is adapted to match the fluctuating cooling/heating load of the complete building while ensuring the appropriate individual variable supply of cooling/heating for each independent zone.

The control system uses PWM (Pulse Width Modulation) control that optimizes the efficiency once the setpoint temperature is reached, avoiding temperature fluctuation and thus reducing power consumption.

Graph 1

DC INVERTER

Graph 2

DC INVERTER

Accurate temperature control leading to Ideal comfort

Graph 1: Traditional air conditioners maintain the temperature by continually starting and stopping the compressor after reaching the temperature setpoints.

Traditional compressors require minimum time between starts and stops which leads to a wide fluctuation of indoor temperature.

Graph 2: With advanced digital variable refrigerant flow control technology, TVR™ LX system can accurately control the room temperature within a narrow temperature band thus avoiding wasting energy and creating the most comfortable environment. The setpoint will be stable at +/- 0.5° C.

Page 6: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

6

Longevity

DC Inverter scroll compressors do not start and stop all the time and thus will have a longer lifetime compared to standard compressors used in traditional systems.

The electronic control can adjust/optimize the compressor’s operating conditions under extreme weather by changing the compressor speed during freezing winter or high summer outdoor temperatures. This greatly extends the lifetime operation of the compressor. The TVR™ LX system’s auto diagnostic continually monitors the complete system and allows fast troubleshooting with the display of alarm codes on controllers or through the BMS interfaces.

DC Inverter scroll compressor technology advantages

• New structure-enhanced mid-frequency performance

• Especially designed scroll profile for R410A

• Advanced permanent magnet DC motor improves the low frequency band performance

The high efficiency R410A high pressure dome scroll compressor has a revolutionary asynchronous motor design using integrated permanent Neodymium magnets creating a magnetic field with extra reluctance torque which greatly increases the efficiencies in low and medium speeds.

Due to the magnetic field, the motor will place itself in the perfect position that will allow the compressor a soft start with the lowest amperage draw.

Environment - R410A refrigerantThe TVR LX system operates with the highly efficient R410A refrigerant with zero ozone layer depleting potential. R410A provides increased heat transfer and system performance; as a result it reduces the required amount of refrigerant, the size of required piping, and hence of general installation costs.

TVR LX Energy Efficiency

EER

COP

4TVH0086 4TVH0096 4TVH0115 4TVH0140 4TVH0155 4TVH0170 4TVH0192 4TVH0210

6.5

6.0

5.5

5.0

4.5

4.0

3.5

3.0

4.7

4.5

4.3

4.3

4.1

3.9

3.86 4.

12

3.74 4.

03

5.6

5.3

4.9

4.8

4.6

4.25

Page 7: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

7

Automatically Identify

DC INVERTER

System FeaturesSelf-Addressing of indoor units

• The outdoor unit will automatically distribute the addresses

to indoor units without any manual settings (this function

applies to vertical discharge heat pump units only).

• Wireless controller TCONTRM05B and new TCONTKJR29B

can modify every indoor units address.

• Max. 64 indoor units can be connected to one system and

identified automatically.

Outdoor unit static pressure

Optional adjustable high static outdoor fan motor is available for different applications. All units can be customized to reach 60Pa of external static pressure. The standard static pressure is 0-20Pa.

DC fan motor

The DC fan motor offers substantial improvements in operating efficiency compared to conventional AC motors, especially during low speed rotation.

To achieve the minimum energy consumption and best performance, it controls the speed of DC fan according to the running load and system pressure.

This new DC fan motor also reduces noise level when working under certain part-load conditions

Auto-rotation of outdoor units

When more than one outdoor unit is installed within a modular system, the TVR™ LX system rotates the master unit automatically to ensure a longer life cycle of the complete system. This rotation takes place when the unit re-starts operation after it has reached a setpoint, after the oil return process, and after the defrost process (in heating operation).

Page 8: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

8

Priority Mode Selection

In order to reduce the potential for mode conflict and to satisfy priority needs, several types of mode selection are available.

Heating Priority(default)

Cooling Only Heating Only

Cooling PriorityVote or VIP Priority

High Performance Heat Exchanger

The new TVR LX units have a high performance heat exchanger that allows better air flow and longer time of operation between defrost cycles.

Fan blade with special profile

A blade with sharp edge and reduced curve increases the airflow rate and lowers vibration and airflow resistance.

Installation Flexibility

The knock-out holes for refrigerant piping, as well as for power and communication cables, have been located in a variety of directions. The refrigerant piping and cables can be installed on the front, left, or right side of the unit. This flexible design allows for a more convenient installation.

8

Page 9: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

Improved Serviceability

A new rotating control panel design allows for easier servicing of the outdoor unit. The control panel rotates up to 150° facilitating access for inspection and maintenance of the piping system. The previous models of TVR required dismounting of the control panel in order to access the unit internally. Today, this new design greatly reduces the service time. In addition, a small window has been incorporated into the panel, allowing a quick view of the system status.

Quiet Operation

The highly efficient all DC inverter compressors produce low sound levels especially when working at part load conditions. Together with a new fan grille design, a new fan blade shape, a thicker-wall cabinet (from 1mm to 1,2mm) and multiple noise reduction features, permits the TVR LX to achieve ultra low sound levels.

• New fan grille design

• DC fan motor

• Anti-vibration design of fan motor

• Soundproofing design of compressor

• High performance-Low noise compressor

• Anti-tremor type axial flow fan

• Three-dimensional simulation anti-vibration pipe design

• Resonance Avoidance Technology

• Anti-vibration design of the cabinet

9

Page 10: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

10

Flexibility & Reliability of TVR™ LX System

A

B

C

D

Maximum Actual piping length (A+B+C) 175m

Maximum height between indoor units (D) 30m

Maximum height between indoor units and outdoor units (B) 90m / 110m*

Total Actual pipe length 1000m

* when outdoor unit is below indoor units

Piping Length Flexibilities

The unique concept of a pre-engineered system that arrives on the jobsite with a predefined piping layout per system and the necessary piping kits allows for fast and correct installation of the system.

The actual piping length from the condensing unit to the indoor unit furthest away is 175m (200m equivalent) up to a total piping length of 1000m.

The height difference can be 90m equivalent for outdoor units being installed on the roof and 110m lift for outdoor units installed below or at ground level.

Modular Design

Through the compact modular design the TVR LX outdoor units can be installed in rows and manifolded in series together to maximum 840 MBH, with 64 indoor units connected, providing a clean accessible installation. The 840 MBH outdoor unit is however capable to control down to a 16.8 MBH capacity with only one inverter compressor running.

The load demand for the all inverter compressor units, is better matched through a smooth linear operation that allows them to perform with maximum precision. The establishment of an operating frequency range between 60-140Hz, guarantees the highest efficiency attainable. The compact shape allows transport by elevator.

Back Up function

When a module fails, whether it is a slave unit or a master unit, the other modules can continue to work together as one system provided the gas/liquid valves of the broken down unit are closed.

As the load increases the different condensing modules will work as a master slave system optimizing the performance and energy efficiency.

All inverter compressors

The TVR LX outdoor units utilize all inverter compressors which adds more flexibility and reliability to the system as compared to the combination of fixed and inverter compressor technology. The ability to perform at higher compressor speeds allows the system to reach longer piping distances (up to 175m) and more comfort zones (up to 1000m of total piping length). The automatic rotation function balances the running hours of all outdoor units’ inverter compressors. This feature increases the overall lifespan of the inverter compressors, further increasing the system’s reliability.

Page 11: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

21dB (A) 20dB (A) 30dB (A) 40dB (A) 50dB (A)

Speak in a low voice at 1/5m away

Quiet languagelaboratory

Quiet reading room Quiet office

Noise decibel

DC INVERTER

* applicable for low air volume operation of 4TVL0007 units.

11

Operation Range

• The TVR™ LX can operate in a wide range of outdoor conditions. It can function from -5°C to 48°C in cooling mode and from -20°C to 24°C in heating mode.

[°C]

TVR LX

48°C -5°C-5°C 48°C

24°C24°C-20°C-20°C

-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

Indoor comfort level

• The integration of DC inverter technology used in the condensing unit results in an industry leading low noise level, i.e., 57 dB(A) at 1m for a 86 MBH outdoor unit.

• The noise level of the indoor units is low due to the especially designed fans and heat exchanger designs.

• The variety of ducted indoor units allow for flexible design to meet any sound requirements per zone.

Page 12: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

4TVH0086-115

12

TVR™ LX Modular Heat Pump Outdoor Units - 60 and 50 Hz

• Choice of 3 ~ power supplies: 50/60 Hz 380V-415 V 60 Hz 220V

• 8 different modules can work individually or in a master-slave configuration up to 4 outdoor units

• Any outdoor unit module in a group can be the designated master or slave

• All TVR LX outdoor units have the same height and depth allowing for row installation

• Improved Linear Capacity Control with all inverter compressors

• Continuous cooling down to -5°C and heating down to -20°C

• No mechanical rooms needed, fits in elevator

• Outdoor units allow more indoor units to be connected at same capacities compared to fixed+inverter compressor models

Comfort • Auto restart function no need for re-programming

• Low noise design

• Back up function

4TVH00140-210

Combined ODU

Cooling Capacity kWkW 95 100 106.5 111.5 117.5 123 128.5 134.5 139.5 145.5 151 156.5 161.5 168 173 179 184.5 190 196 201 207 212.5 218 223 229.5 234.5 240.5 246

MBH 324 341 363 380 401 420 438 459 476 496 515 534 551 573 590 611 629 648 669 686 706 725 744 761 783 800 821 84086

96 X X X X X X X X

115 X XX X XX X140155 X X X X X

170 XX X X X X XX X

192 X X XX X X X

210 X X X X XX X X X X XX XX X XX XX XX XXX XX XX XX XX XXX XXX XX XXX XXX XXX XXXX

Max No. Indoor 56 59 63 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64

Table of Outdoor Unit Connections

Combined ODU

Cooling Capacity kWkW 25.2 28 33.5 40 45 50 56 61.5 67 73 78 84 89.5

MBH 86 96 115 140 155 170 192 210 229 249 266 287 30586 X

96 X X X X X

115 X XX140 X155 X X

170 X X

192 X X

210 X X

Max No. Indoor 13 16 20 23 26 29 33 36 39 43 46 50 53

* Factory recommended combinations achieve maximum capacity using the least number of outdoor units possible. Nevertheless, all outdoor units combinations are possible up to four (4) outdoor units per module.

Service • Easy maintenance with the self diagnostic function and test switch

• Flexible start up procedure and automated piping / wiring checks

• Self-addressing of indoor units

• Optional service software

Outdoor Units

Sound Pressure at 1mdB (A)

61

60

59.5

59

58.5

58

57.5

57

56.5

56

55.5

4TVH0086 4TVH0096 4TVH0115 4TVH0140 4TVH0155 4TVH0170 4TVH0192 4TVH0210

57 57

58

60 60

61 61 61

Page 13: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

13

Optional Accessories• TVR™ LX Outdoor unit centralized controller TCONTCCM02A

• Digital Ampere Meter

TCONTCCM02A

Model Numbers<E> 4TVH0086DE0 4TVH0096DE0 4TVH0115DE0 4TVH0140DE0 4TVH0155DE0 4TVH0170DE0 4TVH0192DE0 4TVH0210DE0

<6> 4TVH0086D60 4TVH0096D60 4TVH0115D60 4TVH0140D60 4TVH0155D60 4TVH0170D60 4TVH0192D60 4TVH0210D60

Cooling

CapacitykW 25.2 28 33.5 40 45 50 56 61.5

Btu/h 86,000 95,500 114,300 136,500 153,500 170,500 191,100 210,000

Power Input kW 5.79 7.02 8.71 10.81 12.83 14.47 16.67 18.77

Capacity Range (50% - 130%) Mbh 43-112 48-124 58-150 69-177 78-202 85-222 96-248 105-273

EER W/W 4.7 4.5 4.3 4.3 4.1 3.9 3.86 3.74

Heating

CapacitykW 27 31.5 37.5 45 50 56 63 69

Btu/h 92,100 107,500 128,000 153,500 170,600 191,100 214,900 235,400

Power Input kW 5.79 7.19 8.82 10.98 12.47 14.15 15.98 17.86

Capacity Range (50% - 130%) Mbh 46-120 54-139 64-166 77-200 85-222 96-248 107-279 118-306

COP W/W 5.6 5.3 4.9 4.8 4.6 4.25 4.12 4.03

Cooling Operation Range C -5C ~ 48C

Heating Operating Range C -20C ~ 24C

Air Flow m3/h 12,000 14,000 16,000

Sound Pressure dB(A) 57 58 60 61

Fin Type Hydrophilic Aluminium

Dimensions (W/H/D) mm 990×1635×790 1340×1635×790

Net Weight kg 219 237 297 305 340

Refrigerant R410A

Refrigerant Charge kg 9 11 13 16

Refrigerant Type FVC68D / 500 ml

Refrigerant Oil ml 500 500x2

Refrigerant

Piping

Liquid Side mm Ø9.53 Ø12.7 Ø15.9

Gas Side mm Ø22.2 Ø25.4 Ø28.6

Oil Balance Pipe mm Ø6

Max. Equivalent Pipe Length m 200

Max. Height difference between IUs m 30

Max. Height difference for OU above IU m 90

Max. Height difference for OU below IU m 110

Max. Amount of IUs connected to OU 13 16 20 23 26 29 33 36

<E> = 380-415 V, 3 Ph, 50/60 Hz <6> = 220 V, 3 Ph, 60 Hz * Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1m in front of the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations.* Nominal efficiency rated with high pressure DC ducted indoor units

Note: Specifications subject to change without notice.

Heat Pump Outdoor Units All Inverter Compressors

840MBH unit

Page 14: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

14

4-way Cassette - 4TVC

• Integrated drain pump with 750mm lift.

• EXV kit is factory mounted on the unit.

• Efficient air distribution

• Fresh Air connection possible

• Digital tube displaying on the display board. LED can display the error code so it’s easier to check malfunction

• Ultra thin machine body for an easy installation and maintenance. (9-27 MBH à 230mm , 30-48 MBH à 300mm)

• Reserved knock out spaces for ducting up to 50% of the air flow, hence supplying air to 2 adjacent rooms

Indoor Units

3-dimensional screw fan Four-way Airflow

• The adoption of the most advanced 3-dimensional screw fan:

- Reduces the air resistance

- Smooths the air flow and noise level

- Provides uniform air speed distribution over the heat exchanger

• Different optional color panels to integrate into a design: White (standard), Gray, Blue and Black

• Optional wireless controller or wired controller

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 15: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

15

4-Way Cassette - 60 HzModel Numbers 4TVC0009B10 4TVC0012B10 4TVC0015B10 4TVC0018B10 4TVC0024B10 4TVC0027B10 4TVC0030B10 4TVC0034B10 4TVC0038B10 4TVC0048B10

Power Supply V/Ph/Hz 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60

Capacity

CoolingkW 2.8 3.2 4.5 5.6 7.1 8 9 10 11.2 14

Btu/h 9,600 12,300 6 19,100 24,200 27,300 30,700 34,100 38,200 47,800

HeatingkW 3.2 4 5 6.3 8 9 10 11 12.5 15

Btu/h 10,900 13,600 17,100 21,500 27,300 30,700 34,100 37,500 42,700 51,200

Power Input W 60 71 94 173 186

Rated Current A 0.4 0.5 0.7 0.8

Air Flow (H/M/L) m3/h 847/766/640 864/755/658 1157/955/749 1236/973/729 1590/1300/10901678/1358

/1115

Sound Pressure (H/M/L) dB(A) 42/38/35 45/42/39 48/45/43 50/47/44

Unit Dimensions (W/H/D) mm 840/230/840 840/300/840

Net Weight kg 24 26 32

Front Panel

Dimensions (W/H/D) mm 950/46/950

Model Number RAYPANELWHT001

Net Weight kg 6

Refrigerant Piping

Liquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 32

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Model Numbers 4TVC0009BB0 4TVC0012BB0 4TVC0015BB0 4TVC0018BB0 4TVC0024BB0 4TVC0027BB0 4TVC0030BB0 4TVC0034BB0 4TVC0038BB0 4TVC0048BB0

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 2.8 3.2 4.5 5.6 7.1 8 9 10 11.2 14

Btu/h 9,600 12,300 6 19,100 24,200 27,300 30,700 34,100 38,200 47,800

HeatingkW 3.2 4 5 6.3 8 9 10 11 12.5 15

Btu/h 10,900 13,600 17,100 21,500 27,300 30,700 34,100 37,500 42,700 51,200

Power Input W 80 90 75 82 97 160 170

Rated Current A 0.4 0.5 0.7 0.8

Air Flow (H/M/L) m3/h 847/766/640 864/755/658 1157/955/749 1236/973/729 1540/1300/11201800/1500

/1280

Sound Pressure (H/M/L) dB(A) 42/38/35 45/42/39 48/45/43 50/47/44

Unit Dimensions (W/H/D) mm 840/230/840 840/300/840

Net Weight kg 24 26 32

Front Panel

Dimensions (W/H/D) mm 950/46/950

Model Number RAYPANELWHT001

Net Weight kg 6

Refrigerant Piping

Liquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 32

4-Way Cassette - 50 Hz

Page 16: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

16

Compact 4-way Cassette - 4TVB

Comfort• 360° efficient air distribution

• Three level fan speed that meets different air supply requirements

• Optimum air flow thanks to the 3-Dimensional Screw fan

- Reduced Air resistance

- Smooths the air flow and noise level

- Provides uniform air speed distribution over the entire coil

• Built in Auto Restart

• Fresh Air connection possible

Quick installation• Ultra thin body of 265mm for installation in tight ceilings

• Light weight units are easy to mount

• Integrated drain pump that lifts up to 500mm

Flexibility • 1 panel size 647mm x 647mm that fits in standard ceiling grids for all 4 different sizes

630 mm

570 mm

265 mm

3-Dimensional Screw Fan

Four-way Airflow

Compact Cassette Panel

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 17: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

17

Compact 4-Way Cassette – 60 Hz

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Model Numbers 4TVB0007B10 4TVB0009B10 4TVB0012B10 4TVB0015B10

Power Supply V/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60

Capacity

CoolingkW 2.2 2.8 3.6 4.5

Btu/h 7,500 9,600 12,300 15,400

HeatingkW 2.4 3.2 4 5

Btu/h 8,200 10,900 13,600 17,100

Power Input W 51 52 58

Rated Current A 0.175 0.21

Air Flow (H/M/L) m3/h 532/397/292 539/408/310 632/496/359

Sound Pressure dB(A) 38.1/33.4/23.4 41.5/35.6/28.8

UnitDimensions (W/H/D) mm 630/265/570 630/265/570

Net Weight kg 17.5 19

Front Panel

Dimensions (W/H/D) mm 647/50/647 647/50/647

Model Number RAYCMPCTPNL002

Net Weight kg 3

Refrigerant PipingLiquid Side mm 6.35

Gas Side mm 12.7

Drainage Water Pipe (OD) mm 25

Compact 4-Way Cassette – 50 HzModel Numbers 4TVB0007B10 4TVB0009B10 4TVB0012B10 4TVB0015B10

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 2.2 2.8 3.6 4.5

Btu/h 7,500 9,600 12,300 15,400

HeatingkW 2.4 3.2 4 5

Btu/h 8,200 10,900 13,600 17,100

Power Input W 51 52 58

Rated Current A 0.175 0.21

Air Flow (H/M/L) m3/h 532/397/292 539/408/310 632/496/359

Sound Pressure dB(A) 38.1/33.4/23.4 41.5/35.6/28.8

UnitDimensions (W/H/D) mm 630/265/570 630/265/570

Net Weight kg 17.5 19

Front Panel

Dimensions (W/H/D) mm 647/50/647 647/50/647

Model Number RAYCMPCTPNL002

Net Weight kg 3

Refrigerant PipingLiquid Side mm 6.35

Gas Side mm 12.7

Drainage Water Pipe (OD) mm 25

Page 18: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

18

2-Way Cassette - 4TVG

Flexibility• Compact design

• Standard built-in drain pump (750 mm)

• One panel size for all models (from 7 to 24 MBH)

• Front panel RAYTWOWAYPNL01

Comfort• Low sound level (24 dB (A) on 7 MBH unit)

• Efficient air distribution

• Built-in Auto-restart

• Standard filter

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 19: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

19

2-Way Cassette – 60 HzModel Numbers 4TVG0007B10 4TVG0009B10 4TVG0012B10 4TVG0015B10 4TVG0018B10 4TVG0024B10

Power Supply V/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60

Capacity

CoolingkW 2.2 2.8 3.6 4.5 5.6 7.1

Btu/h 7,500 9,600 12,300 15,400 19,100 24,200

HeatingkW 2.6 3.2 4 5 6.3 8

Btu/h 8,900 10,900 13,600 17,100 21,500 27,300

Power Input W 57 60 92 108 154

Rated Current A 0.35 0.45 0.55 0.75

Air Flow (H/M/L) m3/h 674/509/381 740/577/435 878/689/561 941/776/654 1236/1110/864

Sound Pressure dB(A) 33/29/24 39/35/30 44/40/34

UnitDimensions (W/H/D) mm 1172/300/592

Net Weight kg 34 36.5

Front Panel

Dimensions (W/H/D) mm 1430/53/680

Model Number RAYTWOWAYPNL01

Net Weight kg 10.5

Refrigerant PipingLiquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 32

2-Way Cassette – 50 HzModel Numbers 4TVG0007BB0 4TVG0009BB0 4TVG0012BB0 4TVG0015BB0 4TVG0018BB0 4TVG0024BB0

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 2.2 2.8 3.6 4.5 5.6 7.1

Btu/h 7,500 9,600 12,300 15,400 19,100 24,200

HeatingkW 2.6 3.2 4 5 6.3 8

Btu/h 8,900 10,900 13,600 17,100 21,500 27,300

Power Input W 57 60 92 108 154

Rated Current A 0.35 0.45 0.55 0.75

Air Flow (H/M/L) m3/h 654/530/410 725/591/458 850/670/550 980/800/670 1200/1000/770

Sound Pressure dB(A) 33/29/24 36/32/29 39/35/30 44/40/34

UnitDimensions (W/H/D) mm 1172/300/592

Net weight kg 34 36.5

Front Panel

Dimensions (W/H/D) mm 1430/53/680

Model Number RAYTWOWAYPNL01

Net Weight kg 10.5

Refrigerant PipingLiquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 32

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Page 20: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

20

1-Way Cassette - 4TVE

Flexibility• Compact design

• Standard built-in drain pump (750 mm)

• Two front panels

– RAYONEWAYPNL01B (9 to 12 MBH)

– RAYONEWAYPNL02B (15 to 24 MBH)

Comfort• Low sound level (34 dB (A) on 7 MBH unit)

• Efficient air distribution

• Built-in Auto-restart

• Standard filter

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 21: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

21

1-Way Cassette – 60 HzModel Numbers 4TVE0009B10 4TVE0012B10 4TVE0015B10 4TVE0018B10 4TVE0024B10

Power Supply V/Ph/Hz 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60

Capacity

CoolingkW 2.8 3.6 4.5 5.6 7.1

Btu/h 9,600 12,300 15,400 19,100 24,200

HeatingkW 3.2 4 5 6.3 8

Btu/h 10,900 13,600 17,100 21,500 27,300

Power Input W 41 54 60 75

Rated Current A 0.25 0.27 0.32 0.36

Air Flow (H/M/L) m3/h 573/456/315 693/600/476 792/688/549 933/749/592

Sound Pressure dB(A) 39/37/34 40/38/34 41/39/35 42/40/36 44/41/37

UnitDimensions (W/H/D) mm 1054/153/425 1204/189/443

Net Weight kg 13 18.5 18.8 19.5

Front Panel

Dimensions (W/H/D) mm 1180/25/465 1350/25/505

Model Number RAYONEWAYPNL01B RAYONEWAYPNL02B

Net Weight kg 3.5 4

Refrigerant PipingLiquid Side mm 6.35 12.7

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 25

1-Way Cassette – 50 Hz

Model Numbers 4TVE0009BB0 4TVE0012BB0 4TVE0015BB0 4TVE0018BB0 4TVE0024BB0

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 2.8 3.6 4.5 5.6 7.1

Btu/h 9,600 12,300 15,400 19,100 24,200

HeatingkW 3.2 4 5 6.3 8

Btu/h 10,900 13,600 17,100 21,500 27,300

Power Input W 41 48 60

Rated Current A 0.25 0.27 0.32 0.36

Air Flow (H/M/L) m3/h 573/456/315 693/600/476 792/688/549 933/749/592

Sound Pressure dB(A) 39/37/34 40/38/34 41/39/35 42/40/36 44/41/37

UnitDimensions (W/H/D) mm 1054/153/425 1204/189/443

Net Weight kg 13 18.5 18.8 19.5

Front Panel

Dimensions (W/H/D) mm 1180/25/465 1350/25/505

Model Number RAYONEWAYPNL01B RAYONEWAYPNL02B

Net weight kg 3.5 4

Refrigerant PipingLiquid Side mm 6.35 12.7

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 25

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Page 22: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

22

Low ESP Ducted Indoor Unit - 4TVL

Comfort• Efficient air distribution

• Three level fan speed that meets different air supply requirements

• Very low noise level - 21 dB (A) for 7 MBH unit

• Built-in Auto Restart

Quick installation• Ultra thin body of 190mm for both 50 & 60 Hz models for installation in small false ceilings

• Light weight units are easy to mount

Flexibility • Standard EXV mounted at the factory horizontally

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 23: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

23

Model Numbers 4TVL0007B10 4TVL0009B10 4TVL0012B10 4TVL0015B10 4TVL0018B10

Power Supply V/Ph/Hz 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60

Capacity

CoolingkW 2.2 2.8 3.6 4.5 5.6

Btu/h 7,500 9,600 12,300 15,400 19,100

HeatingkW 2.6 3.2 4 5 6.3

Btu/h 8,900 10,900 13,600 17,100 21,500

Power Input W 32 35 43 43

Rated Current A 0.17 0.24

Air Flow (H/M/L) m3/h 452/409/310 521/460/372 831/712/591

Indoor External Static Pressure (H) Pa 5

Sound Pressure (H/M/L) dB(A) 34/29/21 36/34/30 37/35/31

Dimensions (W/H/D) mm 850/190/405 1030/190/430

Net Weight kg 11.5 14

Refrigerant PipingLiquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 20

Low Pressure Duct – 60 Hz

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Model Numbers 4TVL0007BB0 4TVL0009BB0 4TVL0012BB0 4TVL0015BB0 4TVL0018BB0

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 2.2 2.8 3.6 4.5 5.6

Btu/h 7,500 9,600 12,300 15,400 19,100

HeatingkW 2.6 3.2 4 5 6.3

Btu/h 8,900 10,900 13,600 17,100 21,500

Power Input W 40 56

Rated Current A 0.17 0.24

Air Flow (H/M/L) m3/h 446/323/250 527/359/267 767/634/512

Indoor external static pressure (H) Pa 5

Sound Pressure (H/M/L) dB(A) 34/29/21 36/34/30 37/35/31

Dimensions (W/H/D) mm 850/190/405 1030/190/430

Net weight kg 11.5 14

Refrigerant PipingLiquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage water pipe (OD) mm 20

Low Pressure Duct – 50 Hz

Page 24: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

24

Low ESP Ducted Indoor Unit - 4TVL DC Motor

E�ciency• Ultra high efficiency levels due to the new DC fan motor. Power consumption can be reduced up to 30%.

• Heat exchanger efficiency improved by 22% with the new “V” shape evaporator

Comfort• Efficient air distribution

• Three level fan speed that meets different air supply requirements

• Very low noise level - 24 db(A) for 6, 7 and 9 MBH unit

• Built-in Auto Restart

Quick installation• Thin body of 210 mm for all models for installation where the false ceiling is limited

• Light weight units are easy to mount

Flexibility • Standard EXV mounted at the factory horizontally

• Dual frequency DC Motor that works in 50 or 60Hz

Low ESP Ducted Indoor Unit - 4TVL DC Motor

E�ciency

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 25: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

25

Model Numbers 4TVL0006DF0 4TVL0007DF0 4TVL0009DF0 4TVL0012DF0 4TVL0015DF0 4TVL0018DF0 4TVL0024DF0

Power Supply V/Ph/Hz 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60

Capacity

CoolingkW 1.8 2.2 2.8 3.6 4.5 5.6 7.1

Btu/h 6,100 7,500 9,600 12,300 15,400 19,100 24,200

HeatingkW 2.2 2.6 3.2 4 5 6.3 8

Btu/h 7,500 8,900 10,900 13,600 17,100 21,500 27,300

Power Input W 23 30 46 53

Rated Current A 31 0.36 0.4 0.5

Air Flow (H/M/L) m3/h 590/520/415 655/560/465 856/740/600 905/740/580 970/800/660

Indoor External Static Pressure (H)

Pa 10(10-30)

Sound Pressure (H/M/L) dB(A) 34/26/24 37/31/28 38/31/28 40/32/29

Dimensions (W/H/D) mm 740/210/470 960/210/470 1180/210/470

Net Weight kg 13.5 17.5 21

Refrigerant Piping

Liquid Side

mm 6.35 9.53

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 25

Low Pressure Duct DC Motor – 50-60 Hz

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Page 26: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

26

Medium ESP Ducted Indoor - 4TVD

Comfort• Three level fan speed that meets different air supply requirements

• Low noise level thanks to the fan blade design

• Built in Auto Restart

• Standard long life filter

Quick installation• Ultra thin body of 210mm height for installation in small ceiling pocket

• Light weight units are easy to mount

Flexibility • Different installations patterns possible with bottom return or ducted return

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 27: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

27

Model Numbers 4TVD0007B10 4TVD0009B10 4TVD0012B10 4TVD0015B10 4TVD0018B10 4TVD0024B10 4TVD0027B10 4TVD0030B10 4TVD0038B10 4TVD0048B10

Power Supply V/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60

Capacity

CoolingkW 2.2 2.8 3.2 4.5 5.6 7.1 8 9 11.2 14

Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 27,300 30,700 38,200 47,800

HeatingkW 2.6 3.2 4 5 6.3 8 9 10 12.5 15.5

Btu/h 8,900 10,900 13,600 17,100 21,500 27,300 30,700 34,100 42,650 52,900

Power Input W 66 72 77 101 100 125 133 134 378 352

Rated Current A 0.28 0.5 0.7 1.16 1.65 1.8

Air Flow (H/M/L) m3/h 476/399/335 476/399/335 534/452/391 746/558/470 750/563/470 998/820/607 1226/1018/861 1230/1019/859 1750/1552/1389 1789/1539/1250

Indoor External Static Pressure (H) Pa 10(10~30) 20(10~50) 40(10~80) 40(10~100)

Sound Pressure

(H/M/L)dB(A) 38/35/32 40/38/36 41/38.9/36 42/40/35 45.4/39.8/37 48.0 /41.9/38 47.7/43.2/39.0

Dimensions (W/H/D) mm 700/210/635 920/210/635 1140/210/635 1200/300/865

Net weight kg 21.5 22 27 31.8 38 40 49

Refrigerant Piping

Liquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage Water Pipe

(OD)mm 32

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Mid Pressure Duct – 60 Hz

Mid Pressure Duct – 50 HzModel Numbers 4TVD0007BB0 4TVD0009BB0 4TVD0012BB0 4TVD0015BB0 4TVD0018BB0 4TVD0024BB0 4TVD0027BB0 4TVD0030BB0 4TVD0038BB0 4TVD0048BB0Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 2.2 2.8 3.2 4.5 5.6 7.1 8 9 11.2 14

Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 27,300 30,700 38,200 47,800

HeatingkW 2.6 3.2 4 5 6.3 8 9 10 12.5 15.5

Btu/h 8,900 10,900 13,600 17,100 21,500 27,300 30,700 34,100 42,650 52,900

Power Input W 57 61 92 125 198 200 313 274

Rated Current A 0.28 0.5 0.7 1.16 1.65 1.8

Air Flow (H/M/L) m3/h 530/410/320 850/667/583 998/820/607 1226/1018/861 1752/1552/1389 1918/1539/1250

Indoor External Static Pressure (H) Pa 10(10~30) 20(10~50) 40(10~80) 40(10~80)

Sound Pressure

(H/M/L)dB(A) 38/35/32 40/38/36 41/38.9/36 42/40/35 45.4/39.8/37 48.0 /41.9/38 47.7/43.2/39.0

Dimensions (W/H/D) mm 700/210/635 920/210/635 1140/210/635 1140/270/775 1200/300/865

Net weight kg 21.5 22 27 31.8 38 40 49

Refrigerant Piping

Liquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage Water Pipe

(OD)mm 32

Page 28: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

28

Mid ESP Ducted Indoor Unit - 4TVL DC Motor

E�ciency• Ultra high efficiency levels due to the new DC fan motor. Power consumption can be reduced up to 30%.

Comfort• Three level fan speed that meets different air supply requirements

• Low noise level thanks to the fan blade design

• Built in Auto Restart

• Standard long life filter

Quick installation• Ultra thin body of 210mm height for installation in small ceiling pocket

• Light weight units are easy to mount

Flexibility • Different installations patterns possible with bottom return or ducted return

• Dual frequency DC Motor that works in 50 or 60Hz

• Built-in drain pump as standard

E�ciency

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 29: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

29

Model Numbers 4TVD0005DF0 4TVD0007DF0 4TVD0009DF0 4TVD0012DF0 4TVD0015DF0 4TVD0018DF0 4TVD0024DF0

Power Supply V/Ph/Hz 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60

Capacity

CoolingkW 1.5 2.2 2.8 3.6 4.5 5.6 7.1

Btu/h 5,100 7,500 9,600 12,300 15,400 19,100 24,200

HeatingkW 1.7 2.6 3.2 4 5 6.3 8

Btu/h 5,800 8,900 10,900 13,600 17,100 21,500 27,300

Power Input W 23 24 29 40 47

Rated Current A 0.31 0.33 0.36 0.47

Air Flow (H/M/L) m3/h 509/420/370 521/450/380 592/541/426 748/640/550 821/640/566 1021/940/778

Indoor External Static Pressure (H) Pa 10(10~30)

Sound Pressure

(H/M/L)dB(A) 35/33/31 35/34/31 37/36/33 38/37/33 40/38/34

Dimensions (W/H/D) mm 740/210/500 960/210/500 1180x210x500

Net weight kg 17.5 22.5 28

Refrigerant Piping

Liquid Side mm 6.35 9.53

Gas Side mm 12.7 15.9

Drainage Water Pipe

(OD)mm 25

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Mid Pressure Duct DC Motor - 50-60 Hz

Model Numbers 4TVD0027DF0 4TVD0030DF0 4TVD0038DF0 4TVD0048DF0Power Supply V/Ph/Hz 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60

Capacity

CoolingkW 8 9 11.2 14

Btu/h 27300 30700 38200 47800

HeatingkW 9 10 12.5 15.5

Btu/h 30700 34100 42700 13300

Power Input W 67 68 200 160

Rated Current A 1 1.8 1.55

Air Flow (H/M/L) m3/h 1290/1090/940 1780/1550/1352 1950/1600/1400

Indoor External Static Pressure (H) Pa 20(10~50) 40(10~80) 40(10~100)

Sound Pressure

(H/M/L)dB(A) 44/38/37 47/41/37 47/42/38

Dimensions (W/H/D) mm 1180×270×775 1240x300x865

Net weight kg 38 40 49

Refrigerant Piping

Liquid Side mm 9.53

Gas Side mm 15.9

Drainage Water Pipe

(OD)mm 25

Page 30: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

30

High ESP Ducted Indoor - 4TVA

Comfort• Three level fan speed that meets different air supply requirements

• Built in Auto Restart

• Air filter to be fitted inside return duct system

Flexibility • Broad range of models up to 95 MBH

• External Static Pressure up to 250 Pa

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 31: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

31

High Pressure Duct – 60Hz

High Pressure Duct – 50Hz

Model Numbers 4TVA0024B10 4TVA0027B10 4TVA0030B10 4TVA0038B10 4TVA0048B10 4TVA0055B10 4TVA0068B10 4TVA0085B10 4TVA0095B10

Power Supply V/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60

Capacity

CoolingkW 7.1 8 9 11.2 14 16 20 25 28

Btu/h 24,200 27,300 30,700 38,200 47,800 54,600 68,250 85,300 95,600

HeatingkW 8 9 10 12.5 16 18 22.5 26 31.5

Btu/h 27,300 30,700 34,100 42,650 54,600 61,400 76,800 88,700 107,500

Power Input W 414 402 409 524 627 832 1516

Rated Current A 1.1 1.8 2.3 2.7 3.6 6.6

Air Flow (H/M/L) m3/h 1758/1568/1342 1602/1494/1302 2250/2020/1595 3030/2711/2490 4487/3432/2325

Indoor External Static

Pressure (H)Pa 40(30~ 196) 50(30~ 196) 196(50~250)

Sound Pressure (H/M/L) dB(A) 48/46/44.5 52/49/47 53/50/48 54/52/50 59/55/52

Dimensions (W/H/D) mm 952/420/690 1200/400/600 1356/470/763

Net Weight kg 46.5 50 50.6 70 115

Refrigerant

Piping

Liquid

Sidemm 9.52

Gas Side mm 15.9

Drainage Water Pipe (OD) mm 32

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Model Numbers 4TVA0024BB0 4TVA0027BB0 4TVA0030BB0 4TVA0038BB0 4TVA0048BB0 4TVA0055BB0 4TVA0068BB0 4TVA0085BB0 4TVA0095BB0

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 7.1 8 9 11.2 14 16 20 25 28

Btu/h 24,200 27,300 30,700 38,200 47,800 54,600 68,250 85,300 95,600

HeatingkW 8 9 10 12.5 16 18 22.5 26 31.5

Btu/h 27,300 30,700 34,100 42,650 54,600 61,400 76,800 88,700 107,500

Power Input W 263 423 524 627 832 1516

Rated Current A 1.1 1.8 2.3 2.7 3.6 6.6

Air Flow (H/M/L) m3/h 1510/1399/1236

1500/1396/1221

1936/1721/1511

2117/1950/1644

2988/2670/2229

3890/3200/2700

4268/3780/3200

4280/3820/3200

4400/3708/3200

Indoor External Static Pressure (H) Pa 40(30~ 196) 50(30~ 196) 140(50~250)

Sound Pressure (H/M/L) dB(A) 48/46/44 48/46/44.5 52/49/47 53/50/48 54/52/50 59/55/52

Dimensions (W/H/D) mm 952/420/690 1200/400/600 1425/500/928

Net Weight kg 45 46.5 50.6 68 70 115

Refrigerant Piping

Liquid Side mm 9.52

Gas Side mm 15.9 15.9 *2

Drainage Water Pipe (OD) mm 32

Page 32: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

32

High ESP Ducted Indoor Unit - 4TVA DC Motor

E�ciency• Ultra high efficiency levels due to the new DC fan motor. Power consumption can be reduced up to 30%.

Comfort• Three level fan speed that meets different air supply requirements

• Built in Auto Restart

• Air filter is standard and it can be removed from the bottom of the unit

Flexibility • Broad range of models up to 95 MBH

• External Static Pressure up to 200 Pa

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 33: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

33

High Pressure Duct DC Motor - 50-60 HzModel Numbers 4TVA0024DF0 4TVA0027DF0 4TVA0030DF0 4TVA0038DF0 4TVA0048DF0 4TVA0051DF0 4TVA0068DF0 4TVA0085DF0 4TVA0095DF0

Power Supply V/Ph/Hz 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60 220-240/1/50-60

Capacity

CoolingkW 7.1 8 9 11.2 14 16 20 25 28

Btu/h 24,200 27,300 30,700 38,200 47,800 51,200 68,200 85,300 95,500

HeatingkW 8 9 10 12.5 16 17 22.5 26 31.5

Btu/h 27,300 30,700 34,100 42,700 54,600 58,000 76,800 88,700 107,500

Power Input W 180 220 380 420 700 800

Rated Current A 1.4 1.9 2.9 4.5 6

Air Flow (H/M/L) m3/h 1500/1390/1250 1450/1340/1190 1780/1650/1530 2080/1930/1710 2860/2440/2010 3400/2660/2400 4820/4660/4620 4870/4760/4690

Indoor External Static

Pressure (H)Pa 25(0~ 196) 37(0~ 196) 50(0~ 196) 62(40~200)

Sound Pressure (H/M/L) dB(A) 46/44/42 50/47/45 53/50/48 54/52/50 57/53/50

Dimensions (W/H/D) mm 952/420/690 1436/450/768 1509/550/990

Net Weight kg 41 47 68 70 108

Refrigerant

Piping

Liquid

Sidemm 9.53

Gas Side mm 15.9 15.9x2

Drainage Water Pipe (OD) mm 25 32

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Page 34: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

34

Convertible - 4 TVX

Comfort• Efficient air distribution with two directional airflow and wide angle air flow

• Three level fan speed that meets different air supply requirements

• Low noise level

• Built in Auto Restart

Quick installation• Ultra thin body of 206mm and 660mm height for installation under windows or ceilings

• Light weight units are easy to mount

• Drain pipe connection left or right

Flexibility • Modern and elegant appearance

• Can be installed vertically and horizontally

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 35: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

35

Model Numbers 4TVX0012B10 4TVX0015B10 4TVX0018B10 4TVX0024B10 4TVX0027B10 4TVX0030B10 4TVX0038B10 4TVX0048B10 4TVX0055B10

Power Supply V/Ph/Hz 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60

Capacity

CoolingkW 3.6 4.5 5.6 7.1 8 9 11.2 14 16

Btu/h 12,300 15,400 19,100 24,200 27,300 30,700 38,200 47,800 54,600

HeatingkW 4 5 6.3 8 9 10 12.5 15.5 18

Btu/h 13,600 17,100 21,500 27,300 30,700 34,100 42,650 52,900 61,400

Power Input W 49 147 185 241 405

Rated Current A 0.55 0.57 0.6 0.83 2

Air Flow (H/M/L) m3/h 600/ 480/ 400 750/650/550 1200/900/700 1980/1860/1730 2300/2100/1800

Sound Pressure (H/M/L) dB(A) 40/38/36 43/41/38 45/43/40 47/45/42

Dimensions (W/H/D) mm 990/660/206 1280/660/206 1670/680/244 1670/285/680

Net Weight kg 26 28 34.5 54 57.5

Refrigerant Piping

Liquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD)

mm 15.9 16

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located at a distance of 1m (horizontal) and 1m (vertical) from the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

Convertible – 60 Hz

Convertible – 50 Hz

Model Numbers 4TVX0012BB0 4TVX0015BB0 4TVX0018BB0 4TVX0024BB0 4TVX0027BB0 4TVX0030BB0 4TVX0038BB0 4TVX0048BB0 4TVX0055B10

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 3.6 4.5 5.6 7.1 8 9 11.2 14 16

Btu/h 12,300 15,400 19,100 24,200 27,300 30,700 38,200 47,800 54,600

HeatingkW 4 5 6.3 8 9 10 12.5 15.5 18

Btu/h 13,600 17,100 21,500 27,300 30,700 34,100 42,650 52,900 61,400

Power Input W 49 120 122 125 130 182 300

Rated Current A 0.55 0.57 0.6 0.83 1.41

Air Flow (H/M/L) m3/h 650/570/500 800/600/500 1200/900/700 1980/1860/1730

Sound Pressure (H/M/L) dB(A) 40/38/36 43/41/38 45/43/40 47/45/42

Dimensions (W/H/D) mm 990/660/206 1280/660/206 1670/680/244 1670/285/680

Net Weight kg 26 28 34.5 54 57.5

Refrigerant Piping

Liquid Side mm 6.35 9.52

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD)

mm 15.9 16

Page 36: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

36

Wall Mounted Indoor Unit - 4TVW

7 to 18 MBH

24 MBH

7 to 18 MBH

24 MBH

7 to 18 MBH

Comfort• Double air guides for optimum air distribution

• Three level fan speed that meets different air supply requirements (7 -18 MBH)

• Built in Auto Restart

• Low noise 29dB(A) for 3.6kW model

Quick Installation• LED display integrated, allows trouble shooting

• Multi position piping possibilities

Flexibility • Slim design with an easy to clean mirror (7 to 18 MBH)

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 37: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

37

High Wall – 60 Hz

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located at a distance of 1m (horizontal) and 1m (vertical) from the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations. Note: Specifications subject to change without notice.

High Wall – 50 Hz

Model Numbers 4TVW0007B10 4TVW0009B10 4TVW0012B10 4TVW0015B10 4TVW0018B10 4TVW0024B10

Power Supply V/Ph/Hz 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60

Capacity

CoolingkW 2.2 2.8 3.6 4.5 5.6 7.1

Btu/h 7,500 9,600 12,300 15,400 19,100 24,232

HeatingkW 2.6 3.2 4 5 6.3 8

Btu/h 8,900 10,900 13,600 17,100 21,500 27,304

Power Input W 28 45 79

Rated Current A 0.14 0.2 0.33

Air Flow (H/M/L) m3/h 557/520/467 842/722/597 1190/880/680

Sound Pressure (H/M/L) dB(A) 35/32/29 40/38/34 47

Dimensions (W/H/D) mm 915/290/210 1070/315/210 1250/325/230

Net Weight kg 12 16 19.9

Refrigerant PipingLiquid Side mm 6.35 9.52 9.5

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 16.5

Model Numbers 4TVW0007BB0 4TVW0009BB0 4TVW0012BB0 4TVW0015BB0 4TVW0018BB0 4TVW0024BB0

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 2.2 2.8 3.6 4.5 5.6 7.1

Btu/h 7,500 9,600 12,300 15,400 19,100 24,232

HeatingkW 2.6 3.2 4 5 6.3 8

Btu/h 8,900 10,900 13,600 17,100 21,500 27,304

Power Input W 28 45 79

Rated Current A 0.14 0.2 0.33

Air Flow (H/M/L) m3/h 520/480/430 860/755/630 925/860/755 1190/880/680

Sound Pressure (H/M/L) dB(A) 35/32/29 40/38/34 47

Dimensions (W/H/D) mm 915/290/210 1070/315/210 1250/325/230

Net Weight kg 12 16 19.9

Refrigerant PipingLiquid Side mm 6.35 9.52 9.5

Gas Side mm 12.7 15.9

Drainage Water Pipe (OD) mm 16.5

Page 38: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

38

Console Type - 4TVJ

COOLING MODE

quick cooling to maintain temp anti-cold air normal operation

HEATING MODECOOLING MODE

quick cooling to maintain temp anti-cold air normal operation

HEATING MODE

Flexibility• Compact design

• It can be installed on the floor and mounted on the wall.

• Built-in EXV

Comfort• Low sound level

• Vertical auto swing and wide angle louvers

• Built-in Auto-restart

• Standard filter

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 39: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

39

Console – 60 Hz

Model Numbers 4TVJ0007B10 4TVJ0009B10 4TVJ0012B10 4TVJ0015B10

Power Supply V/Ph/Hz 220-240/1/60 220-240/1/60 220-240/1/60 220-240/1/60

Capacity

CoolingkW 2.2 2.8 3.6 4.5

Btu/h 7,500 9,600 12,300 15,400

HeatingkW 2.6 3.2 4 5

Btu/h 8,900 10,900 13,600 17,100

Power Input W 20 25 45

Rated Current A 0.09 0.11 0.2

Air Flow (H/M/L) m3/h 430/345/229 510/430/229

Sound Pressure (H/M/L) dB(A) 38/32/26 39/33/27 42/39/36

UnitDimensions (W/H/D) mm 700/600/210

Net Weight kg 14 15

Refrigerant PipingLiquid Side mm 6.35

Gas Side mm 12.7

Drainage Water Pipe (OD) mm 16

Console – 50 Hz

Model Numbers 4TVJ0007BB0 4TVJ0009BB0 4TVJ0012BB0 4TVJ0015BB0

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 2.2 2.8 3.6 4.5

Btu/h 7,500 9,600 12,300 15,400

HeatingkW 2.6 3.2 4 5

Btu/h 8,900 10,900 13,600 17,100

Power Input W 20 25 45

Rated Current A 0.09 0.11 0.2

Air Flow (H/M/L) m3/h 430/345/229 510/430/229

Sound Pressure (H/M/L) dB(A) 38/32/26 39/33/27 42/39/36

UnitDimensions (W/H/D) mm 700/600/210

Net Weight kg 14 15

Refrigerant PipingLiquid Side mm 6.35

Gas Side mm 12.7

Drainage Water Pipe (OD) mm 16

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations.

Note: Specifications subject to change without notice.

Page 40: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

40

The TVR™ LX system can be controlled on different user levels, from the individual user level with the zone controllers to a

more centralized tenant by tenant control or a fully integrated building control PC system with a third party BMS control system.

Intelligent Management Control System

Individual Controllers

Wireless controller TCONTRM01WA (for HP systems) • New Stylish design

• Functions: LCD display, Clock, ON/ OFF, Temp. setting, Mode setting, Fan speed setting, Timer, Horizontal Swing, Vertical Swing, Air Direction

• Mode: Auto/Dry/Cool/Heat & Fan only

• Timer: 0 - 24 hrs timer setting

• Addressing function

• Follow me: allows precise room temperature control using the

Temperature sensor in the controller

Wireless Controller TCONTRM05B (for HP systems) • Functions: LCD display, Clock, ON/ OFF, Temp. setting, Mode setting, Fan speed setting, Timer, Horizontal Swing, Vertical Swing, Air Direction

• Mode: Auto/Dry/Cool/Heat & Fan only

• Timer: 0 – 24 hrs timer setting

• Addressing function

Wired controller TCONTKJR29B (for HP systems)• New Stylish design

• Functions: LCD display, Clock, ON/ OFF, Temp. setting, Mode setting, Fan speed setting, Timer, Swing setting, Air Direction

• Mode: Silent/Auto/Dry/Cool/Heat & Fan only

• Timer: 0 - 24 hrs timer setting

• Addressing function

• Controller locking function

• Remote controller receiver function: controls the indoor unit using a wireless controller

• Air filter cleaning reminder: when the running time reaches the pre-set value the air filter icon will light up

• Follow me: allows precise room temperature control using the Temperature sensor in the controller

Note: Do not use HR controllers in HP systems in order to avoid mode conflict.

Wired Controller TCONTKJR90A (for HP systems)• New Stylish Design

• Functions: LCD display, Clock, ON/ OFF, Temp. setting, Mode setting, Fan speed setting, Timer

• Mode: Auto/Dry/Cool/Heat & Fan only

• Timer: 0 – 24 hrs timer setting

TCONTRM05B

TCONTKJR90A

TCONTRM01WA

TCONTKJR29B

Page 41: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

41

TCONTKJR12B

TCONTRM02B

TCONTKJR120B

Wired Controller TCONTKJR12B (for HP systems) • Functions: LCD display, ON/OFF, Temp. setting, Mode setting, Fan speed setting, Timer, Swing setting, Lock

• Mode: Auto/Dry/Cool/Heat & Fan only

• Timer: 0 – 24 hrs timer setting

• Follow me: allows precise room temperature control using the Temperature sensor in the controller

Wireless Controller TCONTRM02B (for HR systems)• Auto-changeover mode for HR systems

• Functions: LCD display, Clock, ON/OFF, Temp. setting, Mode setting, Fan speed setting, Timer

• Addressing function

Wired Controller TCONTKJR120B (for HR systems)• Auto-changeover mode for HR systems

• Functions: LCD display, Clock, ON/OFF, Temp. setting, Mode setting, Fan speed setting, Timer

TCONTCCM03HP

TCONTCCM09A

Centralized Controllers

Indoor unit Centralized Controllers• TCONTCCM09A (for HP systems)

• TCONTCCM03HP (for HP systems)

• TCONTCCM03HR (for HR systems)

Functions:

• Group control

– TCONTCCM09 and 03 can control 64 indoor units

• Centralized ON/OFF

• Mode setting, Temp. setting, Fan setting, Mode lock function

• Weekly timer setting (only for TCONTCCM09)

• Blue lit background LCD

• Lock mode

Outdoor Unit Centralized Controller TCONTCCM02A• Controls 32 outdoor units and a PC can control 16 OU centralized controllers

• This controller cannot be connected directly to Mini TVR™ LX units.

• Centralized ON/OFF, Mode query, Temp. query, Fan query, Mode lock function

• Blue lit background LCD

• Emergency stop contact or forced cooling start signal

• Maximum wiring length 1,000m

TCONTCCM02A

Page 42: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

42

TVR™ LX Cloud Server Controller The new TVR LX Cloud Server Controller allows you to control the TVR LX system at your fingertips, literally! It has been designed to manage remotely the TVR LX System, allowing extensive control of the indoor units via Web, HTTP, TCP or IP access either through a LAN or WAN configuration. The cloud control software can be accessed using a computer, iPhone, iPad or any other intelligent terminal anywhere and at any time. It is also compatible with previous TVR systems as TVR-II and TVR Select. Controlling an HVAC system has never been easier before!

• Up to 1,000m of wiring from the controller to the TVR LX system

• Manages up to 64 indoor units

• Multiple Cloud Server Controllers can be accessed from the same internet access point

• Versatile control through multiple intelligent terminals as iPhone, iPad and Android using a dedicated application available for download at the App Store and Google Play.

• Internet control compatible with most web browsers as Internet Explorer, Chrome, Safari, UC an others.

• Compatible with Windows, Linux, UNIX, IOS, Mac OS.

Picture cloud server

Page 43: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

43

Web browser and IPad control features

• Individual indoor unit and group control.

• Set point configuration, fan speed, operation mode, lock/unlock indoor units.

• Edit names of individual indoor units and multiple zones.

• Assign indoor units to specific zones.

• Add, delete or modify indoor units and zones.

• Weekly schedule.

• Monitor and review error codes, alarms and operational records (logs).

Landing Page

Weekly Schedule

IPhone and Android control features

• Individual indoor unit and group control.

• Set point configuration, fan speed, operation mode.

• Unit swing and error warning.

• Edit names of individual indoor units and multiple zones.

• Assign indoor units to specific zones.

• Add, delete or modify indoor units and zones.

Page 44: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

44

TVR™ LX Web Gateway and PC Network Control So¢ware TVR LX Web Gateway allows basic control of indoor and outdoor units through integrated software especially designed for

the TVR LX. The communication is done through a LAN connection that can be accessed either locally or remotely (VPN).

For advanced control functionality, the TVR LX PC Network Control Software increases the available functions including data

trending, custom reports and power consumption capabilities among others.

• TVR LX centralized controllers are not required

• Energy consumption report (requires additional Digital Ampmeter TCONTDTS)

• TVR LX Web Gate way is required

Digital Ampmeter TCONTDTS• One Ampmeter per Master Outdoor Unit or condensing system

• Needs to be connected to specific wiring terminals on outdoor unit

• Available for models 380-415/50/3, 380-415/60/3 and 220/60/3

• TVR LX Web Gateway and TVR LX PC Network Control Software are required.

TVR LX Web Gateway • Up to 1,200m of wiring can be extended to 3,000m with a signal booster relay

• Manages up to 256 indoor units and 16 outdoor units

• Monitors the system online, records operational data, reports errors

• Compatible with Windows XP and Windows 7

• Remote online service access possible via internet

• TVR LX centralized controllers are not required

TVR LX PC Network Control So¢ware• Manages up to 1,024 indoor units and 64 outdoor units

• Monitors the system online, records operational data, reports errors

• Setpoint limit configuration, weekly timer, custom reports, as-built drawings integration

• Compatible with Windows XP and Windows 7

• Remote online service access possible via internet

TVR™ LX WEB GATEWAY

Page 45: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

45

Building Management Control

The TVR™ LX control network can combine several centralized controllers with a PC or external BMS systems such as Tracer SC

through BACnet™ or MODBUS interfaces to meet customers’ needs in different applications.

BACnet® Interface TCONTCCM08A

• This gateway connects through BACnet® to

the TVR LX entire installation and other external

components through an existing BMS

• Connects through Ethernet to BACnet®/IP

• 4 RS485 connections for connecting to 4 TVR LX

centralized controllers

BACnet® is a registered trademark of ASHRAE.

TCONTCCM08A

BMS System

BACnet/IP protocol

TCONTCCM03HP

TCONTCCM03HP

Outdoor Units

Indoor Units

Indoor Units

Outdoor Units

TCONTCCM02AMAX 4TCONTCCM02A or TCONTCCM03

TCONTCCM08AMAX 4TCONTCCM02A or TCONTCCM03

F1,F2,E K1,K2,E

X,Y,E

P,Q,E

TCONTMODBUSTCONTMODBUS

MODBUS Interface TCONTMODBUS

• Integrates TVR LX systems to BMS systems through

MODBUS.

• Controls up to 1024 indoor units and 64 outdoor units

• Transfers the information via the RTU mode

• Wide voltage 12-48VDC

Page 46: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

46

New Service SoftwareAs part of our new TVR™ LX portfolio, we

introduce a new service tool that allows you to

diagnose and troubleshoot the system.

• Model number: TCONTSERVS.

• Real time display of outdoor unit operating parameters

• Description of error codes.

485A-l K1,K2,E

Other AccessoriesTrane also offers other accessories to maximize customers’ comfort in different applications.

TCONTNAM05A

Air Handler Connection Kit

TCONTAHUKIT1 TCONTNAM09A

This kit allows you to integrate other

indoor units to the TVR LX system. The

kits includes the control boards, EXV,

sensors, and wired controller. The new

air handler connection kits can work in

parallel (up to 4 kits) allowing control of

air handling units up to 765,000 Btu-hr

(80HP).

Stand-alone air handler connection kit:

TCONTAHUKIT1 (14 kW – one circuit)

TCONTAHUKIT2 (28 kW – one circuit)

TCONTAHUKIT3 (56 kW – one circuit)

Combinable air handler connection kit:

TCONTAHUKIT1B (14 kW – one circuit)

TCONTAHUKIT2B (28 kW – one circuit)

TCONTAHUKIT3B (56 kW – one circuit)

Motion Sensor • Turns off the system when it doesn’t sense movement in the room.

Hotel Inserting Card

• Model number: TCONTNAM05A

• ON-OFF control

• Auto-restart function

Page 47: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

47

Indoor air quality depends on many design factors and local codes.

The local ventilation regulations or ASHRAE62.1 will define what ventilation ratio is required per zone and per type of application.

The TVR LX system offers a great level of flexibility to adapt to any ventilation standard and several design strategies can be followed.

1. Direct intake of indoor unit of pre-treated fresh air

2. Direct control connection with TVR LX Energy Recovery Ventilators

3. 100% Fresh air duct units.

4. Separate dedicated outside air system CDQ + rooftop.

TVR LX ERV available in 50 and 60 HzThe energy recovery ventilator can be integrated into the building to provide the necessary ventilation volume with the added benefit of energy recovery, thus reducing the installed capacity of the TVR LX system in each zone equipped with Energy Recovery Ventilator.

TVR™ LX Outside Air Solutions

Features

• Outside air passes trough a heat exchanger and is pre cooled or preheated by the extracted inside air, thus reducing the energy needed to cool/heat up a room and providing a higher quality of indoor air comfort.

• High efficiency Sensible and Latent heat exchanger

• Modular concept with zone by zone indoor air treatment

• Controlled by individual wired controller TCONTKJR27B or by the TVR LX Centralized controller

• Connects easily to ductwork, dual centrifugal fan, single or three phase

• Low vibration and noise level

Model Numbers TERV0120A TERV0175A TERV0235A TERV0300A TERV0470A TERV0600A TERV0900A TERV1200A

Power Supply V/Hz/Ph 220/50/1 220/50/1 220/50/1 220/50/1 220/50/1 220/50/1 380/50/3 380/50/3

V/Hz/Ph - - 220/60/1 220/60/1 220/60/1 220/60/1 220/60/3 220/60/3

Air Flow m3/h 200 300 400 500 800 1000 1500 2000

cfm 120 175 235 300 470 600 900 1200

Temp. Exchange Efficiency % 65 65 65 65 65 65 65 65

Enthalpy Exchange Eff. (Hi Speed)

Cooling % 50 50 50 50 50 50 50 50

Heating % 55 55 60 60 60 60 60 60

"Sound Level (Hi Speed)"

Heat Ex-change Mode

dB(A) 27 30 32 35 39 40 51 53

Bypass Mode dB(A) 28 31 33 36 40 41 52 54

Dimensions (W/H/D) mm 866/655/264 944/722/270 944/927/270 1038/1026/270 1286/1006/388 1286/1256/388 1600/1270/540 1650/1470/540

Weight kg 23 26 31 41 62 79 163 182

Notes: • TERV0120 to TERV0600 have three speeds, while models TERV0900 to TERV1200 have one speed • Sound level measured at 1.4m in an anechoic room • Temp. Exchange Efficiency is the average of cooling and heating values

Energy Recovery Ventilators

Page 48: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

48

100% Fresh Air - 4TVF

Flexibility• External static pressure up to 260 Pa

Comfort• Both fresh air filtration and heating or cooling achieved with the same unit.

• Improved Indoor Air Quality.

• Efficient air distribution

• Standard filter

Layout Example:

Indoor Unit Indoor Unit

Outdoor Units

Outdoor Air processing unit

Air-conditioning Outside air supply

TCONTRM02BHeat Recovery

Wireless

TCONTKJR90AHeat Pump

Wired Controller

TCONTKJR12BHeat Pump

Wired Controller

TCONTKJR120BHeat Recovery

Wired ControllerWired Controller

TCONTKJR29BHeat Pump

Wireless Controller

TCONTRM01WAHeat Pump

*Optional Controllers

Page 49: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

49

* Nominal cooling capacities are based on the following conditions: return air temperature: 27 CDB, 19 CWB, outdoor temperature: 35 CDB, equivalent ref. piping: 8 m (horizontal) * Nominal heating capacities are based on the following conditions: return air temperature: 20 CDB, outdoor temperature: 7 CDB, 6 CWB, equivalent ref. piping: 8 m (horizontal) * Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat * The operating sound has been measured in a semi anechoic chamber. The microphone was located 1.4 m below the unit. With actual installation, the indication value normally differs widely according to the surrounding noise and reverberations.

Note: Specifications subject to change without notice.

Fresh Air Units – 60 Hz

Model Numbers 4TVF0042B10 4TVF0048B10 4TVF0068B10 4TVF0085B10 4TVF0095B10

Power Supply V/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60

Capacity

CoolingkW 12.5 14 20 25 28

Btu/h 42,650 47,800 68,250 85,300 95,600

HeatingkW 10.5 12 18 20 22

Btu/h 35,800 40,950 61,400 68,250 75,000

Power Input W 461 1063

Rated Current A 2.3 5.3

Air Flow (H/M/L) m3/h 1568/1452/1352 1568/1452/1352 4429/3884/3332 4560/4083/3563 4939/4405/3859

Indoor External Static Pressure (H) 50(30~ 196) 140(50~260) 160(50~260)

Sound Pressure (H/M/L) dB(A) 54/52/50 54/53/51 55/54/52

Dimensions (W/H/D) mm 1368/420/691 1443/470/810

Net Weight kg 69.5 115

Refrigerant PipingLiquid Side mm 9.52

Gas Side mm 15.9

Drainage Water Pipe (OD) mm 25 32

Fresh Air Units – 50 Hz

Model Numbers 4TVF0042BB0 4TVF0048BB0 4TVF0068BB0 4TVF0085BB0 4TVF0095BB0

Power Supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50

Capacity

CoolingkW 12.5 14 20 25 28

Btu/h 42,650 47,800 68,250 85,300 95,600

HeatingkW 10.5 12 18 20 22

Btu/h 35,800 40,950 61,400 68,250 75,000

Power Input W 461 1063

Rated Current A 2.3 5.3

Air Flow (H/M/L) m3/h 1700/1350/1050 3150/2650/2300 3300/2850/2500

Indoor External Static Pressure (H) 30~220 50~260

Sound Pressure (H/M/L) dB(A) 54/52/50 54/53/51 55/54/52

Dimensions (W/H/D) mm 1368/420/691 1443/470/810

Net Weight kg 69.5 115

Refrigerant PipingLiquid Side mm 9.52

Gas Side mm 15.9

Drainage Water Pipe (OD) mm 25 32

Page 50: TVR LX - Trane Climatizacion · 2019-05-30 · heat exchanger, Brushless Reluctance DC inverter scroll ... and reliable operation of an air conditioning system. ... The new TVR LX

Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands—

including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport

and protect food and perishables; and increase industrial productivity and efficiency. We are a $12 billion global business committed to a world of sustainable

progress and enduring results. For more information, visit www.ingersollrand.com.

We are committed to using environmentally conscious print practices. ©2015 Ingersoll Rand VRF-SLB013-EN August 5, 2015