20
 ©20 12DobleEng ineering Com pany.  All Righ ts Reser ved PMU App licatio n and Testi ng Do bl e Engineering Company Jay Gosalia Nestor Casilla Presentation Topic s What is S ynchroPha sor Syn chroPhasor Purp ose PMU Applications Testing PMU Conclusion 10th India Doble Power Forum Conference 39

Tutorial 2 PMU Application and Testing

Embed Size (px)

DESCRIPTION

PMU application and testing using Doble kit

Citation preview

  • 2012 Doble Engineering Company. All Rights Reserved

    PMU Application and Testing

    Doble Engineering Company

    Jay GosaliaNestor Casilla

    Presentation Topics

    What is SynchroPhasor

    SynchroPhasor Purpose

    PMU Applications

    Testing PMU

    Conclusion

    10th India Doble Power Forum Conference 39

    Doble E

    ngineering

    Company

  • Phasor Measurement Unit

    Definition : Phasor Phasor is a vector which has magnitude and angle Corresponds to a sinusoidal waveform

    Waveforms + Filter = Phasor

    4

    Fourier filter to waveforms provides Phasor

    10th India Doble Power Forum Conference 40

    Doble E

    ngineering

    Company

  • Definition of Synchro Phasor

    IEEE C37.118 definition : A Phasor calculated from data samples using

    standard time signal as a reference for the measurement

    Common timing reference can be local or global May be Broadcast or direct connection Referenced to Coordinated Universal Time : UTC

    Global Positioning System (GPS) satellite signal is very commonly used

    Phasor and Synchro Phasor

    Time aligned Phasor : Synchro Phasor GPS satellites provides time stamp Time aligning helps to analyze system events

    G GZs

    21 21

    10th India Doble Power Forum Conference 41

    Doble E

    ngineering

    Company

  • IEEE C37.118 and 118-1, 118-2

    IEEE PSRC working group H7 worked on Synchro Phasor standard paper in 1994

    1995 : IEEE 1344 Synchro Phasor standard introduced

    2005 : IEEE C37.118 replaced IEEE 1344 2011 : IEEE C37.118 split in to two standards

    IEEE C37.118-1 : Measurements requirements Frequency response and dynamic response

    IEEE C37.188-2 : Communication requirements New configuration messages and minor changes

    Total Vector Error

    Actual Phasor

    Expected Phasor

    Error

    Ref

    1% TVE .573 degrees (.01 * 360 / 2) 26.5 s (at 60 Hz)

    10th India Doble Power Forum Conference 42

    Doble E

    ngineering

    Company

  • Protection Applications : PMU

    Promising Technology for Protection PMU provides power frequency Phasors

    Basis for all protections No standard : Accuracy limit for wave forms with

    fault transients Different response for different PMUs Fast protection functions with 100 mSec response time

    9

    Back up applications

    Power system stability Two ended fault location algorithm System diagnostics Distributed Busbar protection Load shedding Line reclosing selectivity Wide area frequency monitoring

    10th India Doble Power Forum Conference 43

    Doble E

    ngineering

    Company

  • Power Swing Detection

    Protections settings done with known max and/or min operating conditions of power system events

    Actual operation of power system events may not be optimal for the setting of the protection

    PMU provides Phasors in real time Better decision can be made on load shedding

    and system stability Real time Phasor value helps to fine tune State

    estimation

    11

    PMU : Power Swing

    Calculate the angle difference due to disturbance Apply equal area criteria Make stability decision

    12

    G GZs

    21 21

    10th India Doble Power Forum Conference 44

    Doble E

    ngineering

    Company

  • PMU : Power Swing

    Angle between will vary due to disturbance Algorithm determines if diverging or settling Blocking or tripping decision to be made

    13

    G GZs

    21 21

    Load Shedding scheme

    Special Integrity Protection Schemes (SIPS), Remedial Action Schemes (RAS), Special Protection Scheme (SPS)

    Load rejection, generation control, system reconfiguration

    Based on pre determined sequence of actions Wide Area Stability and Voltage Control (WACS)

    uses PMU data through out the system to make decisions based on power system disturbance based on algorithm

    14

    10th India Doble Power Forum Conference 45

    Doble E

    ngineering

    Company

  • Distance to Fault

    Single ended fault location algorithm inaccuracy Fault resistance, load flow & non homogenous system

    PMU enables double ended fault location PMU data from both end of the line provides very

    accurate fault location Reclose decision can be made for mixed overhead and

    cable transmission line Improved line patrolling :Better productivity & Reliability Fault location algorithm is based on positive sequence

    system parameters

    15

    System Analysis : NZ System

    G1 thermal power station with 400 MW generation G2 small hydro generation station 2x220 kV double circuit line PMU installed at both end Removed 200 MW power to see the response

    16

    G1 G2

    SP SP

    10th India Doble Power Forum Conference 46

    Doble E

    ngineering

    Company

  • System Analysis : NZ System

    Identical frequency response at both stations Generator control compensated frequency back to

    normal Good and quick understanding of system behavior

    PMU provides Time aligned data No data manipulation required : quick response

    17

    G1 G2

    SP SP

    CFE Network

    18

    10th India Doble Power Forum Conference 47

    Doble E

    ngineering

    Company

  • Automatic Generation Shedding

    CFE implemented AGSS scheme CFE has generation in southeast part of the

    country while the large load is in the center If the angle between generation & load bus

    exceeds certain value, generation can be tripped Loss of 400kV transmission capacity can cause

    system out of step condition One line out of service : 70 Phase shift Both line out of service : 140 Phase shift

    CFE chose 100 to be setting for load shedding

    19

    CFE Network

    20

    Local Phasor

    Remote Phasor

    Threshold

    +-

    PU Cyc

    0

    Trip SelectedGenerators

    10th India Doble Power Forum Conference 48

    Doble E

    ngineering

    Company

  • Communication Channel Analysis

    21

    Comm. Channel Analysis

    Both ends Current diff. with PMU measurements Initial charging current higher then expected

    Almost reached tripping threshold Load current will retract away from tripping threshold

    Load increased but diff current increased towards tripping threshold

    Angle difference was almost 60 Degrees Communication asymmetry higher then expected Or Phasing error

    22

    10th India Doble Power Forum Conference 49

    Doble E

    ngineering

    Company

  • Comm. Channel Analysis

    Meter command at both end of the protection Shows same measured values Meter command uses VA source as reference

    VA = 345kV 00

    VB = 345kV -1200

    Vc = 345kV 1200

    Meter command is not sufficient If VA is connected to VB& VB is connected Vc & Vc is

    connected to VA results will be same PMU solves the problem

    23

    PMU Measurements

    24

    10th India Doble Power Forum Conference 50

    Doble E

    ngineering

    Company

  • PMU Measurements

    PMU measurements eliminated rolled Phasor Communication asymmetry the cause for high diff Subsequent tests on comm channel indicated

    high degree of asymmetry

    25

    PMU Testing

    PMU Testing Concepts Setting up a test Running a test Understanding the results

    10th India Doble Power Forum Conference 51

    Doble E

    ngineering

    Company

  • PMU Concepts

    What does a PMU report (see IEEE C37.118.2)?A stream of data messages at a given sample rate(in the range 10-60 per second)

    Each message includes: One or more Phasor vectors (magnitude and angle) Frequency Deviation from nominal (Hz)

    ROCOF (Hz/sec)

    Phasor vectors

    PMUs can report vectors for: Currents and voltages Individual phases (A, B, C) Positive sequence

    All of the above Vectors can be reported as polar or Cartesian,

    and as floating point or scaled integer.

    10th India Doble Power Forum Conference 52

    Doble E

    ngineering

    Company

  • PMU Testing Concepts

    Goal: under various conditions, make sure that the reported each PMU data message matches the expected values for each Phasor Vector, Frequency Deviation and ROCOF.

    PMU Testing Standard

    Defined in IEEE C37.118.1 Specifies quantities to vary, ranges to vary over,

    and required accuracies under different conditions.

    Includes steady state tests, dynamic tests, and transient tests

    10th India Doble Power Forum Conference 53

    Doble E

    ngineering

    Company

  • IEEE C37.118.1 Requirements Steady state tests

    Frequency Voltage Current Phase (discrete or continuous) Harmonic Distortion Out of band interference

    Dynamic tests Phase and Amplitude Modulation Phase Modulation Linear Frequency Ramp

    Transient tests (NYI in Protection Suite) Magnitude step Phase step

    Setting up a test - Hardware

    (PC, F6150 and PMU each have IP addresses)

    Protection Suite F6150 : Waveform definitions, start timeProtection Suite PMU : Request config, start transmissionF6150 PMU : Generated waveformsPMU Protection Suite : Config response, phasor data stream

    10th India Doble Power Forum Conference 54

    Doble E

    ngineering

    Company

  • Setting up a test - Software

    Select PMU capability in Device Parameters Enter nominal voltage, current and frequency Enter VT and CT ratios Enter response time Add all IEEE C37.118 tests to the Test Plan Adjust test parameters as desired

    Definitions

    Pretest Time: period of time at the beginning of each test during which nominal amplitude, phase and frequency are generated

    Test Time: length of each test point in the generated waveform

    Response Time: initial period during each test point during which Phasor results are discarded before analysis

    10th India Doble Power Forum Conference 55

    Doble E

    ngineering

    Company

  • Running a test

    Ensure connectivity from Protection Suite to both F6150 and PMU

    Test clock synchronization by calibrating Adjust Phasor order if necessary Autorun!

    Understanding the Results

    For each test point, maximum error over all PMU samples, excluding Response Time: TVE (Maximum error over all Phasors) Frequency error ROCOF

    Pass/Fail indicator relative to tolerance Export of raw details is available

    10th India Doble Power Forum Conference 56

    Doble E

    ngineering

    Company

  • Detailed Results

    Results for individual Phasors (rather than the maximum error over all Phasors)

    Average and RMS TVE% (in addition to the maximum)

    Angle error (useful for troubleshooting clock issues)

    Complete trace of all PMU data messages

    Detailed Results Complete Trace

    10th India Doble Power Forum Conference 57

    Doble E

    ngineering

    Company

  • Summary

    With Protection Suite 2, all IEEE C37.118 tests can be set up in minutes and autorun in less than half an hour.

    The final two transient tests are scheduled for implementation in release 2.1, within a few months.

    10th India Doble Power Forum Conference 58

    Doble E

    ngineering

    Company