Upload
dhanasekaran19731945
View
6
Download
0
Embed Size (px)
DESCRIPTION
PMU application and testing using Doble kit
Citation preview
2012 Doble Engineering Company. All Rights Reserved
PMU Application and Testing
Doble Engineering Company
Jay GosaliaNestor Casilla
Presentation Topics
What is SynchroPhasor
SynchroPhasor Purpose
PMU Applications
Testing PMU
Conclusion
10th India Doble Power Forum Conference 39
Doble E
ngineering
Company
Phasor Measurement Unit
Definition : Phasor Phasor is a vector which has magnitude and angle Corresponds to a sinusoidal waveform
Waveforms + Filter = Phasor
4
Fourier filter to waveforms provides Phasor
10th India Doble Power Forum Conference 40
Doble E
ngineering
Company
Definition of Synchro Phasor
IEEE C37.118 definition : A Phasor calculated from data samples using
standard time signal as a reference for the measurement
Common timing reference can be local or global May be Broadcast or direct connection Referenced to Coordinated Universal Time : UTC
Global Positioning System (GPS) satellite signal is very commonly used
Phasor and Synchro Phasor
Time aligned Phasor : Synchro Phasor GPS satellites provides time stamp Time aligning helps to analyze system events
G GZs
21 21
10th India Doble Power Forum Conference 41
Doble E
ngineering
Company
IEEE C37.118 and 118-1, 118-2
IEEE PSRC working group H7 worked on Synchro Phasor standard paper in 1994
1995 : IEEE 1344 Synchro Phasor standard introduced
2005 : IEEE C37.118 replaced IEEE 1344 2011 : IEEE C37.118 split in to two standards
IEEE C37.118-1 : Measurements requirements Frequency response and dynamic response
IEEE C37.188-2 : Communication requirements New configuration messages and minor changes
Total Vector Error
Actual Phasor
Expected Phasor
Error
Ref
1% TVE .573 degrees (.01 * 360 / 2) 26.5 s (at 60 Hz)
10th India Doble Power Forum Conference 42
Doble E
ngineering
Company
Protection Applications : PMU
Promising Technology for Protection PMU provides power frequency Phasors
Basis for all protections No standard : Accuracy limit for wave forms with
fault transients Different response for different PMUs Fast protection functions with 100 mSec response time
9
Back up applications
Power system stability Two ended fault location algorithm System diagnostics Distributed Busbar protection Load shedding Line reclosing selectivity Wide area frequency monitoring
10th India Doble Power Forum Conference 43
Doble E
ngineering
Company
Power Swing Detection
Protections settings done with known max and/or min operating conditions of power system events
Actual operation of power system events may not be optimal for the setting of the protection
PMU provides Phasors in real time Better decision can be made on load shedding
and system stability Real time Phasor value helps to fine tune State
estimation
11
PMU : Power Swing
Calculate the angle difference due to disturbance Apply equal area criteria Make stability decision
12
G GZs
21 21
10th India Doble Power Forum Conference 44
Doble E
ngineering
Company
PMU : Power Swing
Angle between will vary due to disturbance Algorithm determines if diverging or settling Blocking or tripping decision to be made
13
G GZs
21 21
Load Shedding scheme
Special Integrity Protection Schemes (SIPS), Remedial Action Schemes (RAS), Special Protection Scheme (SPS)
Load rejection, generation control, system reconfiguration
Based on pre determined sequence of actions Wide Area Stability and Voltage Control (WACS)
uses PMU data through out the system to make decisions based on power system disturbance based on algorithm
14
10th India Doble Power Forum Conference 45
Doble E
ngineering
Company
Distance to Fault
Single ended fault location algorithm inaccuracy Fault resistance, load flow & non homogenous system
PMU enables double ended fault location PMU data from both end of the line provides very
accurate fault location Reclose decision can be made for mixed overhead and
cable transmission line Improved line patrolling :Better productivity & Reliability Fault location algorithm is based on positive sequence
system parameters
15
System Analysis : NZ System
G1 thermal power station with 400 MW generation G2 small hydro generation station 2x220 kV double circuit line PMU installed at both end Removed 200 MW power to see the response
16
G1 G2
SP SP
10th India Doble Power Forum Conference 46
Doble E
ngineering
Company
System Analysis : NZ System
Identical frequency response at both stations Generator control compensated frequency back to
normal Good and quick understanding of system behavior
PMU provides Time aligned data No data manipulation required : quick response
17
G1 G2
SP SP
CFE Network
18
10th India Doble Power Forum Conference 47
Doble E
ngineering
Company
Automatic Generation Shedding
CFE implemented AGSS scheme CFE has generation in southeast part of the
country while the large load is in the center If the angle between generation & load bus
exceeds certain value, generation can be tripped Loss of 400kV transmission capacity can cause
system out of step condition One line out of service : 70 Phase shift Both line out of service : 140 Phase shift
CFE chose 100 to be setting for load shedding
19
CFE Network
20
Local Phasor
Remote Phasor
Threshold
+-
PU Cyc
0
Trip SelectedGenerators
10th India Doble Power Forum Conference 48
Doble E
ngineering
Company
Communication Channel Analysis
21
Comm. Channel Analysis
Both ends Current diff. with PMU measurements Initial charging current higher then expected
Almost reached tripping threshold Load current will retract away from tripping threshold
Load increased but diff current increased towards tripping threshold
Angle difference was almost 60 Degrees Communication asymmetry higher then expected Or Phasing error
22
10th India Doble Power Forum Conference 49
Doble E
ngineering
Company
Comm. Channel Analysis
Meter command at both end of the protection Shows same measured values Meter command uses VA source as reference
VA = 345kV 00
VB = 345kV -1200
Vc = 345kV 1200
Meter command is not sufficient If VA is connected to VB& VB is connected Vc & Vc is
connected to VA results will be same PMU solves the problem
23
PMU Measurements
24
10th India Doble Power Forum Conference 50
Doble E
ngineering
Company
PMU Measurements
PMU measurements eliminated rolled Phasor Communication asymmetry the cause for high diff Subsequent tests on comm channel indicated
high degree of asymmetry
25
PMU Testing
PMU Testing Concepts Setting up a test Running a test Understanding the results
10th India Doble Power Forum Conference 51
Doble E
ngineering
Company
PMU Concepts
What does a PMU report (see IEEE C37.118.2)?A stream of data messages at a given sample rate(in the range 10-60 per second)
Each message includes: One or more Phasor vectors (magnitude and angle) Frequency Deviation from nominal (Hz)
ROCOF (Hz/sec)
Phasor vectors
PMUs can report vectors for: Currents and voltages Individual phases (A, B, C) Positive sequence
All of the above Vectors can be reported as polar or Cartesian,
and as floating point or scaled integer.
10th India Doble Power Forum Conference 52
Doble E
ngineering
Company
PMU Testing Concepts
Goal: under various conditions, make sure that the reported each PMU data message matches the expected values for each Phasor Vector, Frequency Deviation and ROCOF.
PMU Testing Standard
Defined in IEEE C37.118.1 Specifies quantities to vary, ranges to vary over,
and required accuracies under different conditions.
Includes steady state tests, dynamic tests, and transient tests
10th India Doble Power Forum Conference 53
Doble E
ngineering
Company
IEEE C37.118.1 Requirements Steady state tests
Frequency Voltage Current Phase (discrete or continuous) Harmonic Distortion Out of band interference
Dynamic tests Phase and Amplitude Modulation Phase Modulation Linear Frequency Ramp
Transient tests (NYI in Protection Suite) Magnitude step Phase step
Setting up a test - Hardware
(PC, F6150 and PMU each have IP addresses)
Protection Suite F6150 : Waveform definitions, start timeProtection Suite PMU : Request config, start transmissionF6150 PMU : Generated waveformsPMU Protection Suite : Config response, phasor data stream
10th India Doble Power Forum Conference 54
Doble E
ngineering
Company
Setting up a test - Software
Select PMU capability in Device Parameters Enter nominal voltage, current and frequency Enter VT and CT ratios Enter response time Add all IEEE C37.118 tests to the Test Plan Adjust test parameters as desired
Definitions
Pretest Time: period of time at the beginning of each test during which nominal amplitude, phase and frequency are generated
Test Time: length of each test point in the generated waveform
Response Time: initial period during each test point during which Phasor results are discarded before analysis
10th India Doble Power Forum Conference 55
Doble E
ngineering
Company
Running a test
Ensure connectivity from Protection Suite to both F6150 and PMU
Test clock synchronization by calibrating Adjust Phasor order if necessary Autorun!
Understanding the Results
For each test point, maximum error over all PMU samples, excluding Response Time: TVE (Maximum error over all Phasors) Frequency error ROCOF
Pass/Fail indicator relative to tolerance Export of raw details is available
10th India Doble Power Forum Conference 56
Doble E
ngineering
Company
Detailed Results
Results for individual Phasors (rather than the maximum error over all Phasors)
Average and RMS TVE% (in addition to the maximum)
Angle error (useful for troubleshooting clock issues)
Complete trace of all PMU data messages
Detailed Results Complete Trace
10th India Doble Power Forum Conference 57
Doble E
ngineering
Company
Summary
With Protection Suite 2, all IEEE C37.118 tests can be set up in minutes and autorun in less than half an hour.
The final two transient tests are scheduled for implementation in release 2.1, within a few months.
10th India Doble Power Forum Conference 58
Doble E
ngineering
Company