TURBINE GLAND STEAM CONDENSER

Embed Size (px)

Citation preview

  • 7/26/2019 TURBINE GLAND STEAM CONDENSER

    1/4

    Function of the Gland Steam Pressure Control System:

    This system ensures the sealing of glands in HP, IP and LP turbine under various

    Load conditions.

    The Turbine glands are self seal type. Upto approximately 40% load steam from auxiliary

    source (CRH/Aux.steam header) through gland steam valve is taken to seal all the HP, IP

    and LP glands. During this period the steam leakage valve connecting this header to

    condenser is kept closed. After approx. 40% of load, gland steam valve is closed and

    steam leakage valve is opened. Pipings are so sized that the leak-off steam from Front

    and Rear end of HP turbine goes to the condenser through steam leakage valve while

    leak-off steam from the IP front and rear glands is utilised for sealing the LP glands,thus

    ensuring proper temperature of sealing steam. The leak-off steam and air from the last

    chambers of each rotor is sucked into a gland cooler.

    Building up of vacuum in the condenser is the first step during start-up. For building up

    vacuum it is necessary to seal the turbine gland by supplying steam to the shaft through

    gland steam valve. The control system opens the gland steam supply valve until the

    pressure in the header acquires a preset value. Subsequently when the set picks up Load,

    the pressure of steam inside HP and IP turbine builds up resulting in the leakage of steam

    from the Turbine into gland steam supply header which in turn would result in increase of

    pressure. The controller gradually closes the gland steam supply valve and opens gland

    leak-off valve, if required.

    Electro-Hydraulic valve actuators:

    The actuators of the two control valves are continuously under the control commands

    from the electric controller through 2 Electro hydraulic converters.

    The +ve voltage output opens the gland steam supply valve while the -ve voltage output

    opens the gland leak-off valve.

    Each hydraulic actuator has its own motor driven oil pump supplied from station AC syste

    In the event of pump failure, the valve remains in stayput position. Subsequent operation

    of the valve can be carried out locally though hand pump.

    Pressure measurement:

    The pressure in the header is measured by means of a pressure transducer. This

    measurement is used for control as well as display purposes. The measurement range is -1

    to +300mmWC

    Control system equipment:

    The control system is comprised of solid-state control system. The modules, including

    power supply, operating and monitoring modules are arranged in a 3 tier group frame and

    housed in a cubicle.

    The pressure controller has PI characteristics. Its output is fed to electro-hydraulic

    actuators via a PID position controller. The function of this controller is to set the

    position of the valve as determined by the pressure controller as quickly and accurately

    as possible.

  • 7/26/2019 TURBINE GLAND STEAM CONDENSER

    2/4

    The actuators incorporate magneto-resistor potentiometer to give contactless

    non-wearing position indication. The output voltage of the potentiometer varies

    proportionally with the valve position. The voltage is used to give an actual value

    signal to the position controller as well as for valve position indication in the control

    room. In order to ensure stable control characteristics during the transition period of

    Gland steam supply valve closure to Leakage steam supply valve opening or vice-versa,the valve travel of both the valves have got slight overlap.

    The reference value for the steam pressure in the header can be set between 0-220mmW

    by means of potentiometer on the controller.

    The pressure reference value is compared with the actual value supplied by the

    transducer at the input to control of the deviation amplifier. The press controller is

    given the progressive static characteristics so that its action is increased in the event

    of large disturbance to the press control system eg., Load Trip. For small deviation

    uptp +10mmWC, the characteristics is chosen to ensure stable control under all

    operating conditions. The controller action is increased for larger deviations.

    Progressive characteristics of the press controller indicates that it is possible to

    adjust the amplifications between the press controller and position controller

    independently for each valve. This feature enables to take care of any inaccuracies in

    the sizing of the supply and leakage valves and the pipe lines.