Please check www.trespa.info for the latest version of this document
1
This system offers a cost effective solution for installing Trespa® Meteon® panels in a large variety of panel dimensions.
Trespa® Meteon® panels with a minimum thickness of 6 mm may be fixed on a timber sub-frame, using powder
coated screws (available in a wide range of Trespa® colours through third parties).
TS150 ViSible (exPoSed) fixing wiTh ScrewS on a Timber Sub-frame
> Birches Head School, Great Britain> Arch. Aedas
This document is intended to provide general recommendations only. Trespa provides these guidelines and all testing,
code and design data for informational purposes only and strongly advises that the customer, project owner and architect
seek independent advice from a certified construction professional and/or engineer regarding application and installation
as well as compliance with design requirements, applicable codes, laws and regulations, and test standards. Please check
your local codes and applicable design requirements for proper use.
Please check www.trespa.info for the latest version of this document
2
oVerView of aVailable cerTificaTeS
The following overview provides you with a general and non-binding indication of certificates in relation to fixing
system TS150: visible (exposed) fixing with screws on a timber sub-frame commonly used by Trespa customers in
specific countries. To consult full details of available certificates please visit www.trespa.info/meteon/certificates
country country code commonly used certificate
Netherlands NL 防KOMO attest-met-productcertificaat, Gevelbekleding systeem met Trespa Meteon en Trespa Meteon/ FR panelen GB-001/7
Germany DE 防Allgemeine bauaufsichtliche Zulassungen:Z-33.2-10 Trespa Meteon/FR-KR Fassadensystem Z-33.2-17 Trespa Meteon/FR Fassadensystem
Belgium BE 防
Technische goedkeuring met certificaat voor Trespa Meteon en Trespa Meteon FR ATG 05/2021 Agrément technique avec certification de Trespa Meteon et Trespa Meteon FR ATG 05/2021
France FR 防 Avis Technique 2/10-1396: Trespa Meteon TS150 fixation par vis sur ossature bois.
United Kingdom UK 防Agrément certificate Trespa Meteon wall cladding panels and fixings BBA Agrément Certificate 99/3629
Spain ES 防 Sistema de revestimiento de fachadas ventiladas con placas Trespa Meteon FR
Italy IT 防 No certificate available.
China CN No certificate available.
Chili CL No certificate available.
Trespa Export Countries
Other Not applicable, local certificates may apply.
code
U30
50 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Please check www.trespa.info for the latest version of this document
3
general inSTallaTion deTailS
cavity depth and ventilationFor a continuous ventilation behind the panel, Trespa
recommends the free air cavity depth between the
rainscreen cladding and the insulation or wall
construction to be between 20 and 50 mm, in order to
allow for ambient air to flow through from the ventilation
inlets and outlets. Ventilation inlets and outlets must be
the equivalent of minimum 50 square cm per linear meter
over the whole façade. Cavity depth as well as ventilation
inlets and outlets must be in accordance with applicable
building standards, regulations and certificates.
Sub-frameTrespa® Meteon® panels must be installed on a sub-frame
of sufficient strength and permanent durability. Quality
and/or treatment of the sub-frame must be in accordance
with applicable building standards, regulations and
certificates. Trespa further recommends the use of a flat
EPDM gasket to the full width of vertical battens of the
sub-frame.
fixing detailTrespa® Meteon® panels with a thickness of 6, 8 and 10 mm
can be fixed on the sub-frame with fast fixing screws (available
in a wide range of Trespa® colours through third parties).
To retain panel position, each panel must have one fixed
point in the centre of the panel.
Fixed point – hole diameter:
防 5 mm for fast fixing screw
防 equal to shank diameter for other screws
Sliding point – hole diameter:
防 8 mm for fast fixing screw
防 shank diameter + 3 mm for other screws
Screws must always be centered in the holes and must not
be over tightened.
b
c
c
c
c
b
b a a b
10 mm 20 mm
MIN. 105 mm
MIN. 34 mm
20 mm MINIMUM
Fixed point Sliding point
Please check www.trespa.info for the latest version of this document
oVerView of Technical inSTallaTion deTailSThe following table gives a general overview of some of
the most significant technical installation details in
those countries where this fixing system is commonly
used. For details of certification see: Overview of
available certificates.
In certain countries specific certification requirements
may apply. For countries in which a certificate for this
fixing system is available, the following table presents a
summary of the certificate. For countries in which no
certificate for this fixing system may be available, the
information given in the following table only contains an
advise as to the installation commonly used by Trespa
customers, as based on Trespa’s experience. For all
countries Trespa strongly advises that the customer,
project owner and architect seek independent advice from
a construction professional regarding the accordance to
national and/or local building regulations of fixing systems.
The information below does not contain all requirements
with regard to the certificates. For design and installation, the
complete certificate(s) must be considered. To consult these
certificates, please visit www.trespa.info/meteon/certificates
Panel thicknessa (mm) country with certificate country without certificate
6, 8, 10 NL, DE, BE, FR, UK, ES IT
max. panel dimension (mm) country with certificate country without certificate
3050 x 1530 or 2550 x 1860 NL, DE, BE, FRB, UK, ES IT
Joint width (mm) country with certificate country without certificate
10 NL, DE, BE, FRC, UK, ES IT
A 13 mm may be applied in certain circumstances, please contact your local Trespa representative.
B For other panel dimensions, please consult the certificate.
C For other joint width, please consult the certificate.
Based on applicable building standards, regulations or certificates, wider joints may be permissible.
Panel thickness
maximum panel dimension
Joint width
minimum dimensions sub-frame
minimum dimension timber battens (mm)
country with certificate country without certificate
Intermediate / End battens 45 x 34 Jointing battens 95 x 34
NL, UK, ES IT
Intermediate / End battens 46 x 35 Jointing battens 95 x 35
BE
Intermediate / End battens 50 x 34 Jointing battens 105 x 34
DE
Intermediate / End battens 40 x 45 Jointing battens 80 x 45
FR
4
code
U30
50 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Please check www.trespa.info for the latest version of this document
5
edge clearance
recommended maximum fixing distances
edge clearance (mm) country with certificate country without certificate
Min. 20 mm and max. 10 x panel thickness
NL, DE, BE, UK, FR, ES IT
maximum fixing distancesd,e (mm)
Panel thickness (mm) for Satin / rock
Panel thickness (mm) for glossf
country with certificate
country without certificate
6 8 10 10
2 fixings in one direction
450 600 750 550 NL, DE, BE, FR, UK, ES IT
3 or more fixings in one direction
550 750 900 700 NL, BE, FR, UK, ES IT
3 or more fixings in one direction
550 700 800 700 DE
D Fixing distances for soffit application must be multiplied by 0.75.
E The maximum permitted fixing distances shown have been designed with a maximum (wind) load of 600 N/ m² and maximum deflection of L/200.
F Based on the surface properties of Gloss panels, fixing distances are reduced.
Fixing distances must be calculated in accordance with applicable local standards, regulations and certificates and should be
verified by a structural engineer.
For more information about deflection and wind loads, please visit www.trespa.info/meteon/fixingsystems
a
b
b
b
b
c c ac ca
c
c
b
b
b
b
c
c
a = horizontal fixing distance
b = vertical fixing distance
c = edge clearance
= fixed point in panel centre
= sliding point
Please check www.trespa.info for the latest version of this document
6
14
3
5
6
7
8
2
horizontal cross-section
1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel
6. EPDM gasket
7. Vertical timber batten
8. Fast fixing screw
code
U30
50 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Please check www.trespa.info for the latest version of this document
7
Vertical cross-section
1
4
3
5
6
7
8
2
1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity and vertical timber batten
5. Trespa® Meteon® panel
6. Vertical timber batten
7. Fast fixing screw
8. Ventilation profile
Please check www.trespa.info for the latest version of this document
8
code
U30
50 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Disclaimer
This is a print generated by you from www.trespa.info (“Website”). By accessing the Website and printing this document you have accepted the
Terms of Use of the Website. Please refer to the Website for all conditions that apply to this document. Not all the systems shown in this document
may be suitable for all applications and jurisdictions. We provide you with testing, code and design data for informational purposes only and
strongly recommend that you or any other user of this document obtains independent advice regarding compliance with design requirements,
applicable codes, laws and regulations, and test standards. Please check your local codes and design requirements for proper use. Trespa will not
accept any liability in relation to your use of this document.
All intellectual property rights, including copyrights and other rights regarding the content of the Website and this print generated from the
Website (including logos, trademarks, service marks, software, databases, audio, video, text and photographs) are owned by Trespa and/or its
licensors. Trespa®, Meteon®, Athlon®, TopLab®, TopLabPLUS ®, TopLabECO-FIBRE ®, Virtuon®, Volkern®, Trespa Essentials® and Mystic Metallics®
are registered trademarks of Trespa.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related activities of Trespa are governed by
the Trespa General Terms and Conditions of Sale (Algemene verkoopvoorwaarden Trespa International B.V.) filed with the Chamber of Commerce
and Industry for Noord- en Midden- Limburg in Venlo (NL) on 11 April 2007 under number 24270677,which can be found on and downloaded
from the Trespa website, www.trespa.com.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related work of Trespa North America, Ltd.
are governed by the Trespa General Terms and Conditions of Sale, which can be found on and downloaded from the Trespa North America Ltd.
website, www.trespa.com/na. A copy of these general conditions of sale will be provided free of charge on request.
Please check www.trespa.info for the latest version of this document
1
This system offers large flexibility for installing Trespa® Meteon® panels, the use of adjustable brackets allow for
precise joints and an optimal façade grid.
Trespa® Meteon® panels with a minimum thickness of 10 mm may be fixed invisibly on an aluminium sub-frame
comprising horizontal rails and hanging brackets fixed with inserts or screws to the back of the panel.
TS200 inviSible (concealed) fixingwiTh brackeTS on railS
> Ecole de musique, France> SIZ-IX Architectes
This document is intended to provide general recommendations only. Trespa provides these guidelines and all testing,
code and design data for informational purposes only and strongly advises that the customer, project owner and architect
seek independent advice from a certified construction professional and/or engineer regarding application and installation
as well as compliance with design requirements, applicable codes, laws and regulations, and test standards. Please check
your local codes and applicable design requirements for proper use.
2
Please check www.trespa.info for the latest version of this document
overview of available cerTificaTeS
The following overview provides you with a general and non-binding indication of certificates in relation to fixing
system TS200: invisible (concealed) fixing with brackets on rails commonly used by Trespa customers in specific
countries. To consult full details of available certificates please visit www.trespa.info/meteon/certificates
country country code commonly used certificate
Netherlands NL 防KOMO attest-met-productcertificaat, Gevelbekleding systeem met Trespa Meteon en Trespa Meteon/ FR panelen GB-001/7
Germany DE 防Allgemeine bauaufsichtliche Zulassung: Rückseitige Befestigung mittels Hinterschnittanker Z-21.9-1544
Belgium BE 防
Technische goedkeuring met certificaat voor Trespa Meteon en Trespa Meteon FR ATG 05/2021 Agrément technique avec certification de Trespa Meteon et Trespa Meteon FR ATG 05/2021
France FR 防 Avis Technique 2/07-1245: Trespa Meteon système invisible TS200.
United Kingdom UK 防 BBA certificate Trespa Meteon wall cladding panels and fixings. 99/3629
Spain ES 防 Sistema de revestimiento de fachadas ventiladas con placas Trespa Meteon FR. DIT 473.
Italy IT 防 No certificate available.
China CN 防 No certificate available.
Chile CL 防 No certificate available.
Trespa Export Countries
Other Not applicable, local certificates may apply.
code
U30
53 v
ersi
on 2
.0 d
ate
14-0
6-20
11
3
Please check www.trespa.info for the latest version of this document
general inSTallaTion deTailS
cavity depth and ventilationFor a continuous ventilation behind the panel, Trespa
recommends the free air cavity depth between the
rainscreen cladding and the insulation or wall
construction to be between 20 and 50 mm, in order to
allow for ambient air to flow through from the ventilation
inlets and outlets. Ventilation inlets and outlets must be
the equivalent of minimum 50 square cm per linear meter
over the whole façade. Cavity depth as well as ventilation
inlets and outlets must be in accordance with applicable
building standards, regulations and certificates.
Sub-frameThe horizontal aluminium rails can be fixed on a vertical
timber or aluminium sub-frame.
Trespa® Meteon® panels must be installed on a sub-frame
of sufficient strength and permanent durability. Quality
and/or treatment of the sub-frame must be in accordance
with applicable building standards, regulations and
certificates.
Some countries may allow the use of a stainless/galvanized
steel sub-frame. Please consult the certificate or contact
your local Trespa representative.
fixing detailPanel brackets are attached to the Trespa® Meteon® panels
using two stainless steel inserts or screws per bracket.
Each panel has two adjusting points. To retain panel position,
the panel must have one fixed point at the top by inserting
a self-drilling screw (or similar) through the hanging
bracket and into the rail. Alternatively, where access is
impossible, each panel must have one glued fixed point
(with proprietary adhesive system e.g. polyurethane).
Fixing method:
防 straight insert
防 thread cutting screw
防 conical insert
防 TU-S fastener (rivet screw)
a
b
b
b
b
c c ac ca
c
c
b
b
b
b
c
c
x x x x
Remaining panel thickness: at least 2.5 mm.
Anchoring depth: total panel thickness minus 3 mm.
Due to aesthetics, the use of gloss panels is not recommended
for this system.
Conical Insert
Straight insert
TU-S fastener (rivet screw)
Threat cutting screw
Please check www.trespa.info for the latest version of this document
overview of Technical inSTallaTion deTailSThe following table gives a general overview of some of
the most significant technical installation details in
those countries where this fixing system is commonly
used. For details of certification see: Overview of
available certificates.
In certain countries specific certification requirements
may apply. For countries in which a certificate for this
fixing system is available, the following table presents a
summary of the certificate. For countries in which no
certificate for this fixing system may be available, the
information given in the following table only contains an
advise as to the installation commonly used by Trespa
customers, as based on Trespa’s experience. For all countries
Trespa strongly advises that the customer, project owner
and architect seek independent advice from a construction
professional regarding the accordance to national and/or
local building regulations of fixing systems.
The information below does not contain all requirements
with regard to the certificates. For design and installation, the
complete certificate(s) must be considered. To consult these
certificates, please visit www.trespa.info/meteon/certificates
Panel thickness (mm) country with certificate country without certificate
10, 13 NL, DE, BE, FR, UK, ES IT, CN, CL
Max. panel dimensions (mm) country with certificate country without certificate
3050 x 1530 or 2550 x 1860 DE
Max. height 3050Max. length 3650
NL, BE, FRA, UK, ES IT, CN, CL
Joint width (mm) country with certificate country without certificate
10 NL, DE, BE, UK, FRB, ES IT, CN, CL
A For other panel lengths, please consult the certificate.
B For other joint width, please consult the certificate.
Based on applicable building standards, regulations or certificates, wider joints may be permissible.
Panel thickness
Maximum panel dimension
Joint width
Minimum dimensions sub-frameAny vertical timber, aluminium or stainless/galvanized steel sub-frame must be designed in accordance with applicable
local standards, regulations and certificates.
4
edge clearance
edge clearance (mm) country with certificate country without certificate
Please consult the certificate for the edge clearances
NL, BE, DE, FR, ES
Vertical and horizontal edge distance minimum 65 mm and maximum 10 x panel thickness, counted from the center of the first fixing
UK, IT, CN, CL
code
U30
53 v
ersi
on 2
.0 d
ate
14-0
6-20
11
5
Please check www.trespa.info for the latest version of this document
recommended maximum fixing distances
C Fixing distances for soffit application must be multiplied by 0.75.
D The maximum permitted fixing distances shown have been designed with a maximum (wind) load of 600 N/ m² and maximum deflection of L/200.
Fixing distances must be calculated in accordance with applicable local standards, regulations and certificates and should be
verified by a structural engineer.
For more information about deflection and wind loads, please visit www.trespa.info/meteon/fixingsystems
a
b
b
b
b
c c ac ca
c
c
b
b
b
b
c
c
x x x xFixing and edge clearances
a = horizontal fixing distance
b = vertical fixing distance
c = edge clearance
= fixed point
= adjusting point
= sliding point:
Lower brackets fixed higher at such a level as to facilitate
downward panel movement (2.5 mm/m1)
Maximum fixing distances (mm)c,d
Panel thickness (mm) for Satin / rock
country with certificate
country without certificate
10 13
2 fixings in one direction Please consult the certificate for the fixing distances
NL, DE, BE, FR
3 or more fixings in one direction
Please consult the certificate for the fixing distances
NL, DE, BE, FR
2 fixings in one direction 750 950 UK, ES IT, CN, CL
3 or more fixings in one direction
900 1200 UK, ES IT, CN, CL
6
Please check www.trespa.info for the latest version of this document
13
4
5
6
7
8
9
2
horizontal cross-section1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel
6. Wall bracket
7. Vertical aluminium rail
8. Horizontal aluminium rail
9. Aluminium hanging bracket
code
U30
53 v
ersi
on 2
.0 d
ate
14-0
6-20
11
7
Please check www.trespa.info for the latest version of this document
vertical cross-section
1
4
3
5
6
7
2
1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel
6. Horizontal aluminium rail
7. Ventilation profile
8
Please check www.trespa.info for the latest version of this documentPlease check www.trespa.info for the latest version of this document
code
U30
53 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Disclaimer
This is a print generated by you from www.trespa.info (“Website”). By accessing the Website and printing this document you have accepted the
Terms of Use of the Website. Please refer to the Website for all conditions that apply to this document. Not all the systems shown in this document
may be suitable for all applications and jurisdictions. We provide you with testing, code and design data for informational purposes only and
strongly recommend that you or any other user of this document obtains independent advice regarding compliance with design requirements,
applicable codes, laws and regulations, and test standards. Please check your local codes and design requirements for proper use. Trespa will not
accept any liability in relation to your use of this document.
All intellectual property rights, including copyrights and other rights regarding the content of the Website and this print generated from the
Website (including logos, trademarks, service marks, software, databases, audio, video, text and photographs) are owned by Trespa and/or its
licensors. Trespa®, Meteon®, Athlon®, TopLab®, TopLabPLUS ®, TopLabECO-FIBRE ®, Virtuon®, Volkern®, Trespa Essentials® and Mystic Metallics®
are registered trademarks of Trespa.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related activities of Trespa are governed by
the Trespa General Terms and Conditions of Sale (Algemene verkoopvoorwaarden Trespa International B.V.) filed with the Chamber of Commerce
and Industry for Noord- en Midden- Limburg in Venlo (NL) on 11 April 2007 under number 24270677,which can be found on and downloaded
from the Trespa website, www.trespa.com.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related work of Trespa North America, Ltd.
are governed by the Trespa General Terms and Conditions of Sale, which can be found on and downloaded from the Trespa North America Ltd.
website, www.trespa.com/na. A copy of these general conditions of sale will be provided free of charge on request.
Please check www.trespa.info for the latest version of this document
1
This system is ideally suited to quickly install large uninterrupted façade surfaces offering a grid with horizontal lines.
Trespa® Meteon® panels with a minimum thickness of 8 mm may be installed by fitting their profiled horizontal edges
into continuous aluminium TS300 rails. Panel edges are designed to mask the aluminum profiles used to install the
Trespa® Meteon® panels.
TS300 InvISIble (concealed) fIxIng uSIng profIled edgeS
> Kantoor van de Meerakker, The Netherlands> Anomalie Architects
This document is intended to provide general recommendations only. Trespa provides these guidelines and all testing,
code and design data for informational purposes only and strongly advises that the customer, project owner and architect
seek independent advice from a certified construction professional and/or engineer regarding application and installation
as well as compliance with design requirements, applicable codes, laws and regulations, and test standards. Please check
your local codes and applicable design requirements for proper use.
Please check www.trespa.info for the latest version of this document
2
overvIew of avaIlable cerTIfIcaTeS
The following overview provides you with a general and non-binding indication of certificates in relation to fixing
system TS300: invisible (concealed) fixing using profiled edges commonly used by Trespa customers in specific
countries. To consult full details of available certificates please visit www.trespa.info/meteon/certificates
country country code commonly used certificate
Netherlands NL 防KOMO attest-met-productcertificaat, Gevelbekleding systeem met Trespa Meteon en Trespa Meteon/ FR panelen GB-001/7
Germany DE 防 Allgemeine bauaufsichtliche Zulassung:Z-33.2- 456 Trespa System 300
Belgium BE 防
Technische goedkeuring met certificaat voor Trespa Meteon en Trespa Meteon FR ATG 12/2021 Agrément technique avec certification de Trespa Meteon et Trespa Meteon FR ATG 12/2021
France FR 防 Avis Technique 2/06-1223: Trespa Meteon Système Modulaire TS300
United Kingdom UK 防 No certificate available.
Spain ES 防 Sistema de revestimiento de fachadas ventiladas con placas Trespa Meteon FR. DIT 473.
Italy IT 防 No certificate available.
China CN 防 No certificate available.
Chile CL 防 No certificate available.
Trespa Export Countries
Other Not applicable, local certificates may apply.
code
U30
54 v
ersi
on 2
.0 d
ate
17-1
2-20
12
Please check www.trespa.info for the latest version of this document
3
general InSTallaTIon deTaIlS
cavity depth and ventilationFor a continuous ventilation behind the panel, Trespa
recommends the free air cavity depth between the
rainscreen cladding and the insulation or wall
construction to be between 20 and 50 mm, in order to
allow for ambient air to flow through from the ventilation
inlets and outlets. Ventilation inlets and outlets must be
the equivalent of minimum 50 square cm per linear meter
over the whole façade. Cavity depth as well as ventilation
inlets and outlets must be in accordance with applicable
building standards, regulations and certificates.
Sub-frameThe horizontal aluminium rails can be fixed on a vertical
timber or aluminium sub-frame.
Trespa® Meteon® panels must be installed on a sub-frame
of sufficient strength and permanent durability. Quality
and/or treatment of the sub-frame must be in accordance
with applicable building standards, regulations and
certificates.
Some countries may allow the use of a stainless/galvanized
steel sub-frame. Please consult the certificate or contact
your local Trespa representative.
fixing detail防 TS300 can only be used for horizontal single-field spans.
As a result, the maximum panel height is limited.
防 Not all joint solutions are possible with 8 mm thick
Trespa® Meteon® panels.
防 To retain position each panel must have one glued fixed
point (with proprietary adhesive system e.g. polyurethane)
on the bottom rail central in the panel length.
Please check www.trespa.info for the latest version of this document
overvIew of TechnIcal InSTallaTIon deTaIlSThe following table gives a general overview of some of
the most significant technical installation details in
those countries where this fixing system is commonly
used. For details of certification see: Overview of
available certificates.
In certain countries specific certification requirements may
apply. For countries in which a certificate for this fixing
system is available, the following table presents a summary
of the certificate. For countries in which no certificate for
this fixing system may be available, the information given
in the following table only contains an advise as to the
installation commonly used by Trespa customers, as based
on Trespa’s experience. For all countries Trespa strongly
advises that the customer, project owner and architect
seek independent advice from a construction professional
regarding the accordance to national and/or local building
regulations of fixing systems.
The information below does not contain all requirements
with regard to the certificates. For design and installation, the
complete certificate(s) must be considered. To consult these
certificates, please visit www.trespa.info/meteon/certificates
panel thickness (mm) country with certificate country without certificate
8, 10, 13 NL, DE, BE, FR, ES UK, IT, CN, CL
Max. panel dimensions (mm) country with certificate country without certificate
max. panel length 3650 NL, BE, ES UK, IT, CN, CL
max. panel length 3050 FR
max. panel length 3000 DE
Joint width (mm) country with certificate country without certificate
10 NL, DE, BE, FRA, ES UK, IT, CN, CL
A For other joint width, please consult the certificate.
Based on applicable building standards, regulations or certificates, wider joints may be permissible.
panel thickness
Maximum panel length
Joint width
Minimum dimensions sub-frame
4
Minimum dimension timber battens (mm)
country with certificate country without certificate
45 x 75 NL, DE, BE, ES UK, IT, CN, CL
45 x 60 FR
code
U30
54 v
ersi
on 2
.0 d
ate
17-1
2-20
12
Please check www.trespa.info for the latest version of this document
5
recommended maximum panel height
B The maximum permitted fixing distances shown have been designed with a maximum (wind) load of 600 N/ m² and maximum deflection of L/200.
C Based on the surface properties of Gloss panels, the fixing distances are reduced.
Fixing distances must be calculated in accordance with applicable local standards, regulations and certificates and should be
verified by a structural engineer.
For more information about deflection and wind loads, please visit www.trespa.info/meteon/fixingsystems
panel thickness (mm) for Satin / rockb
panel thickness (mm) for glossc country with certificate
country without certificate
8 10 13 10 13
605 759 759 550 750 DE
600 750 900 550 750 NL, BE, FR, ES UK, IT, CN, CL
Please check www.trespa.info for the latest version of this document
6
1
4
3
5
6
7
8
2
horizontal cross-section
1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel
6. Vertical aluminium rail
7. Wall bracket
8. Horizontal TS300 profile
code
U30
54 v
ersi
on 2
.0 d
ate
17-1
2-20
12
Please check www.trespa.info for the latest version of this document
7
vertical cross-section
1
4
3
5
6
7
2
1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel
6. Horizontal TS300 profile
7. Ventilation profile
Please check www.trespa.info for the latest version of this document
8
code
U30
54 v
ersi
on 2
.0 d
ate
17-1
2-20
12
Disclaimer
Not all certification required for your project may be available through Trespa or additional certification may have to be obtained by the customer.
Therefore, also in relation to the above overview, Trespa strongly advises that the customer, project owner and architect seek independent advice
from a construction professional regarding the accordance to national and/or local building regulations of a chosen fixing system.
This is a print generated by you from www.trespa.info (“Website”). By accessing the Website and printing this document you have accepted the
Terms of Use of the Website. Please refer to the Website for all conditions that apply to this document. Not all the systems shown in this
document may be suitable for all applications and jurisdictions. We provide you with testing, code and design data for informational purposes
only and strongly recommend that you or any other user of this document obtains independent advice regarding compliance with design
requirements, applicable codes, laws and regulations, and test standards. Please check your local codes and design requirements for proper use.
Trespa will not accept any liability in relation to your use of this document.
All intellectual property rights, including copyrights and other rights regarding the content of the Website and this print generated from the
Website (including logos, trademarks, service marks, software, databases, audio, video, text and photographs) are owned by Trespa and/or its
licensors. Trespa®, Meteon®, Athlon®, TopLab®, TopLabPLUS ®, TopLabECO-FIBRE ®, Virtuon®, Volkern®, Trespa Essentials® and Mystic Metallics®
are registered trademarks of Trespa.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related activities of Trespa are governed
by the Trespa General Terms and Conditions of Sale (Algemene verkoopvoorwaarden Trespa International B.V.) filed with the Chamber of
Commerce and Industry for Noord- en Midden- Limburg in Venlo (NL) on 11 April 2007 under number 24270677,which can be found on and
downloaded from the Trespa website, www.trespa.com/documentation.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related work of Trespa North America, Ltd.
are governed by the Trespa North America General Terms and Conditions of Sale, which can be found on and downloaded from the Trespa website,
www.trespa.com/documentation. A copy of these general conditions of sale will be provided free of charge on request.
1
Although the majority of past Trespa installations have been mechanically fixed, the use of adhesive fixing systems is
possible under certain conditions, including careful attention to various installation details, installation by a qualified
party in accordance with all guidelines and recommendations of a qualified adhesive manufacturer, and in compliance
with all applicable codes. Trespa is not responsible for the selection or use of adhesives in fixing systems.
Trespa® Meteon® panels of various thicknesses may be fixed to a vertical aluminium or timber sub-frame using a
permanently flexible adhesive system.
InvIsIble (concealed) fIxIng wIth adhesIve on an alumInIum or tImber sub-frame
This document is intended to provide general recommendations only. Trespa provides these guidelines and all testing,
code and design data for informational purposes only and strongly advises that the customer, project owner and architect
seek independent advice from a certified construction professional and/or engineer regarding application and installation
as well as compliance with design requirements, applicable codes, laws and regulations, and test standards. Please check
your local codes and applicable design requirements for proper use.
Please check www.trespa.info for the latest version of this document
2
general InstallatIon guIdelInes
cavity depth and ventilationFor a continuous ventilation behind the panel, Trespa
recommends the free air cavity depth between the
rainscreen cladding and the insulation or wall
construction to be between 20 and 50 mm, in order to
allow for ambient air to flow through from the ventilation
inlets and outlets. Ventilation inlets and outlets must be
the equivalent of minimum 50 square cm per linear meter
over the whole façade. Cavity depth as well as ventilation
inlets and outlets must be in accordance with applicable
building standards, regulations and certificates.
sub-frameTrespa® Meteon® panels must be installed on a sub-frame
of sufficient strength and permanent durability. Quality
and/or treatment of the sub-frame must be in accordance
with certificate holders’ recommendations as well as
applicable building standards and regulations.
fixing detailThe effectiveness of an adhesive fixed panel is determined
mainly by weather conditions at the time of fixing. Damp,
cold and / or dusty conditions may have a negative effect
on the strength of the adhesive bond. For this reason
Trespa cannot take any responsibility for the load bearing
performance of the adhesive fixed construction.
The installation guidelines of the manufacturer of the
adhesive system must be followed at all times.
Please check www.trespa.info for the latest version of this document
code
U30
55 v
ersi
on 2
.0 d
ate
29-0
8-20
12
General principle of adhesive fixing on an aluminium sub-frame
1. Trespa® Meteon® panel
2. double sided adhesive tape
3. adhesive
4. aluminium profile
General principle of adhesive fixing on a timber sub-frame
1. Trespa® Meteon® panel
2. double sided adhesive tape
3. adhesive
4. timber subframe
y
a
x
a
d
1
23
4
y
a
x
a
d
1
23
4
3
best PractIces
The design and installation guidelines of the adhesive
supplier are imperative. The following best practices are
a result of many years of experiences with adhesive fixed
facade cladding in countries where such fixing methods
are allowed and certified.
For all countries Trespa strongly advises that the customer,
project owner and architect seek independent advice from
a construction professional regarding compliance to
national and/or local building regulations of fixing systems.
The information below does not contain all requirements
with regard to the certificates. For design and installation,
the complete certificate(s) must be considered.
A please consult the adhesive system certificate
topic best practice
Panel thicknessA 6, 8, 10 mm
Maximum panel dimensionsA Portrait position: maximum height 3050 mm, maximum diagonal 3315 mmLandscape position: maximum width 2550 mm, maximum diagonal 2818 mm
Joint width 10 mm
Minimum dimensions aluminium sub-frameA Intermediate and end rails: width 40 mmJointing rails: width 100 mm
Minimum dimensions timber sub-frameA Intermediate and end battens: 45 x 28 mmJointing battens: 95 x 28 mm
recommended maximum fixing distances based on trespa® meteon® panel characteristics
maximum fixing distances (mm)b
Panel thickness (mm) for satin / rock Panel thickness (mm) for glossc
6 8 10 10
2 fixings in one direction
450 600 750 550
3 ore more fixings in one direction
550 750 900 700
B The maximum permitted fixing distances shown have been designed with with a maximum (wind)load of 600 N/m2 and maximum deflection of L/200.
C Based on the surface properties of Gloss panels, the fixing distances are reduced.
Please check www.trespa.info for the latest version of this document
4
Fixing distances must be calculated in accordance with applicable local standards, regulations and certificates and should be
verified by a structural engineer.
For more information about deflection and wind loads, please visit www.trespa.info/meteon/fixingsystems
a = horizontal fixing distance
Please check www.trespa.info for the latest version of this document
a a
code
U30
55 v
ersi
on 2
.0 d
ate
29-0
8-20
12
Disclaimer
Not all certification required for your project may be available through Trespa or additional certification may have to be obtained by the customer.
Therefore, also in relation to the above overview, Trespa strongly advises that the customer, project owner and architect seek independent advice
from a construction professional regarding the accordance to national and/or local building regulations of a chosen fixing system.
This is a print generated by you from www.trespa.info (“Website”). By accessing the Website and printing this document you have accepted the
Terms of Use of the Website. Please refer to the Website for all conditions that apply to this document. Not all the systems shown in this
document may be suitable for all applications and jurisdictions. We provide you with testing, code and design data for informational purposes
only and strongly recommend that you or any other user of this document obtains independent advice regarding compliance with design
requirements, applicable codes, laws and regulations, and test standards. Please check your local codes and design requirements for proper use.
Trespa will not accept any liability in relation to your use of this document.
All intellectual property rights, including copyrights and other rights regarding the content of the Website and this print generated from the
Website (including logos, trademarks, service marks, software, databases, audio, video, text and photographs) are owned by Trespa and/or its
licensors. Trespa®, Meteon®, Athlon®, TopLab®, TopLabPLUS ®, TopLabECO-FIBRE ®, Virtuon®, Volkern®, Trespa Essentials® and Mystic Metallics®
are registered trademarks of Trespa.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related activities of Trespa are governed
by the Trespa General Terms and Conditions of Sale (Algemene verkoopvoorwaarden Trespa International B.V.) filed with the Chamber of
Commerce and Industry for Noord- en Midden- Limburg in Venlo (NL) on 11 April 2007 under number 24270677,which can be found on and
downloaded from the Trespa website, www.trespa.com/documentation.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related work of Trespa North America, Ltd.
are governed by the Trespa North America General Terms and Conditions of Sale, which can be found on and downloaded from the Trespa website,
www.trespa.com/documentation. A copy of these general conditions of sale will be provided free of charge on request.
Please check www.trespa.info for the latest version of this document
1
This system offers overlapping Trespa® Meteon® panels generating a façade with deep shadow lines.
Trespa® Meteon® panels with a thickness of 8 mm have a groove in their bottom edge enabling them to be attached
using special stainless steel fixing clamps.
TS600 / TS650 InvISIble (concealed) fIxIng of SIdIngS
> Rozengaard, The Netherlands> K3 Architectuur
This document is intended to provide general recommendations only. Trespa provides these guidelines and all testing,
code and design data for informational purposes only and strongly advises that the customer, project owner and architect
seek independent advice from a certified construction professional and/or engineer regarding application and installation
as well as compliance with design requirements, applicable codes, laws and regulations, and test standards. Please check
your local codes and applicable design requirements for proper use.
Please check www.trespa.info for the latest version of this document
2
overvIew of avaIlable cerTIfIcaTeS
The following overview provides you with a general and non-binding indication of certificates in relation to fixing
system TS600/TS650 – invisible (concealed) fixing of sidings commonly used by Trespa customers in specific countries.
To consult full details of available certificates please visit www.trespa.info/meteon/certificates
country country code commonly used certificate
Netherlands NL 防KOMO attest-met-productcertificaat, Gevelbekleding systeem met Trespa Meteon en Trespa Meteon/ FR panelen GB-001/7
Germany DE 防 No certificate available, however local standards allow installation under certain circumstances.
Belgium BE 防
Technische goedkeuring met certificaat voor Trespa Meteon en Trespa Meteon FR ATG 05/2021Agrément technique avec certification de Trespa Meteon et Trespa Meteon FR ATG 05/2021
France FR 防 Avis Technique 2/07-1268: Trespa Meteon TS650/Pose à Clin
United Kingdom UK 防 No certificate available.
Spain ES 防 Sistema de revestimiento de fachadas ventiladas con placas Trespa Meteon FR. DIT 473.
Italy IT 防 No certificate available.
China CN 防 No certificate available.
Chile CL 防 No certificate available.
Trespa Export countries
Other Not applicable, local certificates may apply.
code
U30
57 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Please check www.trespa.info for the latest version of this document
3
general InSTallaTIon deTaIlS
cavity depth and ventilationFor a continuous ventilation behind the panel, Trespa
recommends the free air cavity depth between the
rainscreen cladding and the insulation or wall
construction to be between 20 and 50 mm, in order to
allow for ambient air to flow through from the ventilation
inlets and outlets. Ventilation inlets and outlets must be
the equivalent of minimum 50 square cm per linear meter
over the whole façade. Cavity depth as well as ventilation
inlets and outlets must be in accordance with applicable
building standards, regulations and certificates.
Sub-frameTrespa® Meteon® panels must be installed on a sub-frame
(timber or aluminium) of sufficient strength and
permanent durability. Quality and/or treatment of
the sub-frame must be in accordance with applicable
building standards, regulations and certificates.
Some countries may allow the use of a stainless/galvanized
steel sub-frame. Please consult the certificate or contact
your local Trespa representative.
fixing detail防 The Trespa® Meteon® panels must be installed from the
bottom upwards, with the first line of clamps being fixed
to adjusting blocks or to an 8 mm thick adjusting batten.
防 The panel overlap is approx. 25 mm.
防 To retain panel position, each panel must have one fixed
point (rivet/screw with an edge clearance of 10 mm)
central in the panel length.
防 The top row of Trespa® Meteon® panels is riveted/screwed
at their top edge.
1. Stainless steel clamp screwed onto timber
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel 8 mm
6. Adjustment block thickness 8 mm
7. Ventilation profile
7
6
4 2
3
1
5
Please check www.trespa.info for the latest version of this document
overvIew of TechnIcal InSTallaTIon deTaIlSThe following table gives a general overview of some of
the most significant technical installation details in those
countries where this fixing system is commonly used.
For details of certification see: Overview of available
certificates.
In certain countries specific certification requirements
may apply. For countries in which a certificate for this
fixing system is available, the following table presents
a summary of the certificate. For countries in which
no certificate for this fixing system may be available,
the information given in the following table only contains
an advise as to the installation commonly used by Trespa
customers, as based on Trespa’s experience. For all
countries Trespa strongly advises that the customer,
project owner and architect seek independent advice from
a construction professional regarding the accordance to
national and/or local building regulations of fixing systems.
The information below does not contain all requirements
with regard to the certificates. For design and installation, the
complete certificate(s) must be considered. To consult these
certificates, please visit www.trespa.info/meteon/certificates
Panel thickness (mm) country with certificate country without certificate
8 NL, BE, FR, ES DE, UK, IT, CN, CL
Max. panel dimensions (mm) country with certificate country without certificate
Panel height 200 – 350Panel length 3650
NL, BE, FR, ES UK, IT, CN, CL
Panel height 200 – 300Panel length 3650
DE
Joint width (mm) country with certificate country without certificate
10 NL, BE, FRA, ES DE, UK, IT, CN, CL
A For other joint width, please consult the certificate.
Based on applicable building standards, regulations or certificates, wider joints may be permissible.
Panel thickness
Maximum panel dimension
Joint width
Minimum dimensions sub-frame
4
Minimum width timber battens (mm)
country with certificate country without certificate
Inner / End battens 45 x 34Intermediate jointing battens 95 x 34
NL, ES DE, UK, IT, CN, CL
Inner / End battens 46 x 35Intermediate jointing battens 95 x 35
BE
Inner / End battens 50 x 50Intermediate jointing battens 80 x 50
FR
code
U30
57 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Please check www.trespa.info for the latest version of this document
5
recommended maximum fixing distances
Fixing distances must be calculated in accordance with applicable local standards, regulations and certificates and should be
verified by a structural engineer.
For more information about deflection and wind loads, please visit www.trespa.info/meteon/fixingsystems
Maximum fixing distances (mm)
Panel thickness (mm) for Satin / rock
country with certificate
country without certificate
8
fixings in horizontal direction 600 NL, BE, FR, ES DE, UK, IT, CN, CL
Please check www.trespa.info for the latest version of this document
6
13
4
5
6
7
2
horizontal cross-section
1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel
6. Vertical timber batten
7. Stainless steel fixing clamp
code
U30
57 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Please check www.trespa.info for the latest version of this document
7
1
4
3
5
7
6
8
2
vertical cross-section
1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel
6. Vertical timber batten
7. Stainless steel fixing clamp
8. Ventilation profile
Please check www.trespa.info for the latest version of this document
8
code
U30
57 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Disclaimer
This is a print generated by you from www.trespa.info (“Website”). By accessing the Website and printing this document you have accepted the
Terms of Use of the Website. Please refer to the Website for all conditions that apply to this document. Not all the systems shown in this document
may be suitable for all applications and jurisdictions. We provide you with testing, code and design data for informational purposes only and
strongly recommend that you or any other user of this document obtains independent advice regarding compliance with design requirements,
applicable codes, laws and regulations, and test standards. Please check your local codes and design requirements for proper use. Trespa will not
accept any liability in relation to your use of this document.
All intellectual property rights, including copyrights and other rights regarding the content of the Website and this print generated from the
Website (including logos, trademarks, service marks, software, databases, audio, video, text and photographs) are owned by Trespa and/or its
licensors. Trespa®, Meteon®, Athlon®, TopLab®, TopLabPLUS ®, TopLabECO-FIBRE ®, Virtuon®, Volkern®, Trespa Essentials® and Mystic Metallics®
are registered trademarks of Trespa.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related activities of Trespa are governed by
the Trespa General Terms and Conditions of Sale (Algemene verkoopvoorwaarden Trespa International B.V.) filed with the Chamber of Commerce
and Industry for Noord- en Midden- Limburg in Venlo (NL) on 11 April 2007 under number 24270677,which can be found on and downloaded
from the Trespa website, www.trespa.com.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related work of Trespa North America, Ltd.
are governed by the Trespa General Terms and Conditions of Sale, which can be found on and downloaded from the Trespa North America Ltd.
website, www.trespa.com/na. A copy of these general conditions of sale will be provided free of charge on request.
Please check www.trespa.info for the latest version of this document
1
This system offers a cost effective solution for installing Trespa® Meteon® panels in a large variety of panel dimensions.
Trespa® Meteon® panels with a minimum thickness of 6 mm may be fixed on a metal sub-frame, using powder coated
rivets (available in a wide range of Trespa® colours through third parties). The sub-frame should preferably consist
of vertical profiles which are fixed to the structure with special wall brackets.
TS700 ViSible (exPoSed) fixing wiTh riVeTS on a meTal Sub-frame
This document is intended to provide general recommendations only. Trespa provides these guidelines and all testing,
code and design data for informational purposes only and strongly advises that the customer, project owner and architect
seek independent advice from a certified construction professional and/or engineer regarding application and installation
as well as compliance with design requirements, applicable codes, laws and regulations, and test standards. Please check
your local codes and applicable design requirements for proper use.
> Kindergarten Gabersdorf, Austria> Zinterl Architekten ZT GmbH
Please check www.trespa.info for the latest version of this document
2
oVerView of aVailable cerTificaTeS
The following overview provides you with a general and non-binding indication of certificates in relation to fixing system
TS700: visible (exposed) fixing with rivets on a metal sub-frame commonly used by Trespa customers in specific countries.
To consult full details of available certificates please visit www.trespa.info/meteon/certificates
country country code commonly used certificate
Netherlands NL 防KOMO attest-met-productcertificaat, Gevelbekleding systeem met Trespa Meteon en Trespa Meteon/ FR panelen GB-001/7
Germany DE 防Allgemeine bauaufsichtliche Zulassungen:Z-33.2-10 Trespa Meteon/FR-KR FassadensystemZ-33.2-17 Trespa Meteon/FR Fassadensystem
Belgium BE 防
Technische goedkeuring met certificaat voor Trespa Meteon en Trespa Meteon FR ATG 05/2021Agrément technique avec certification de Trespa Meteon et Trespa Meteon FR ATG 05/2021
France FR 防 Avis Technique 2/10-1397: Trespa Meteon TS700 fixation sur ossature métallique.
United Kingdom UK 防 Agrément certificate Trespa Meteon wall cladding panels and fixings BBA Agrément Certificate 99/3629
Spain ES 防 Sistema de revestimiento de fachadas ventiladas con placas Trespa Meteon FR. DIT 473.
Italy IT 防 No certificate available.
China CN 防 No certificate available.
Chile CL 防 No certificate available.
Trespa Export Countries
Other Not applicable, local certificates may apply.
code
U30
58 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Please check www.trespa.info for the latest version of this document
3
general inSTallaTion deTailS
cavity depth and ventilationFor a continuous ventilation behind the panel, Trespa
recommends the free air cavity depth between the
rainscreen cladding and the insulation or wall
construction to be between 20 and 50 mm, in order to
allow for ambient air to flow through from the ventilation
inlets and outlets. Ventilation inlets and outlets must be
the equivalent of minimum 50 square cm per linear meter
over the whole façade. Cavity depth as well as ventilation
inlets and outlets must be in accordance with applicable
building standards, regulations and certificates.
Sub-frameTrespa® Meteon® panels must be installed on a sub-frame
of sufficient strength and permanent durability. Quality
and/or treatment of the sub-frame must be in accordance
with applicable building standards, regulations and
certificates.
fixing detail防 Shank diameter of the rivet is 5 mm.
防 Head diameter of the rivet is 16 mm.
防 Hole diameter for fixed point is 5.1 mm.
防 Hole diameter for sliding points in the panel is 10 mm.
防 The rivet head should be 0.3 mm free from the panel
surface by using a special tool (spacer nosepiece).
防 Rivets must always be centered in the holes.
防 To retain the panel position, each panel must have one
fixed point in the centre of the panel. All other fixing
points are sliding points.
a
b
b
b
b
c c ac ca
c
c
b
b
b
b
c
c
Fixed point Sliding point
Please check www.trespa.info for the latest version of this document
oVerView of Technical inSTallaTion deTailSThe following table gives a general overview of some of
the most significant technical installation details in those
countries where this fixing system is commonly used.
For details of certification see: Overview of available
certificates.
In certain countries specific certification requirements
may apply. For countries in which a certificate for this
fixing system is available, the following table presents a
summary of the certificate. For countries in which no
certificate for this fixing system may be available, the
information given in the following table only contains
an advise as to the installation commonly used by Trespa
customers, as based on Trespa’s experience. For all countries
Trespa strongly advises that the customer, project owner
and architect seek independent advice from a construction
professional regarding the accordance to national and/or
local building regulations of fixing systems.
The information below does not contain all requirements
with regard to the certificates. For design and installation, the
complete certificate(s) must be considered. To consult these
certificates, please visit www.trespa.info/meteon/certificates
Panel thicknessa (mm) country with certificate country without certificate
6, 8, 10 NL, DE, BE, FR, UK, ES IT, CN, CL
max. panel dimensions (mm) country with certificate country without certificate
3050 x 1530 or 2550 x 1860 NL, DE, BE, FRB, UK, ES IT, CN, CL
Joint width (mm) country with certificate country without certificate
10 NL, DE, BE, FRC, UK, ES IT, CN, CL
A 13 mm may be applied in certain circumstances, please contact your local Trespa representative.
B For other panel dimensions, please consult the certificate.
C For other joint width, please consult the certificate.
Based on applicable building standards, regulations or certificates, wider joints may be permissible.
Panel thickness
maximum panel dimension
Joint width
minimum dimensions sub-frame
minimum dimension aluminium rail 2 (mm) country with certificate country without certificate
Intermediate / End rails width 40Jointing rails width 100
NL, DE, BE, FR, UK, ES IT, CN, CL
4
edge clearance
edge clearance (mm) country with certificate country without certificate
Min. 20 mm and max. 10 x panel thickness
NL, DE, BE, FR, UK, ES IT, CN, CL
code
U30
58 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Please check www.trespa.info for the latest version of this document
5
recommended maximum fixing distances
maximum fixing distancesd,e (mm)
Panel thickness (mm) for Satin / rock
Panel thickness (mm) for glossf
country with certificate
country without certificate
6 8 10 10
2 fixings in one direction
450 600 750 550 NL, DE, BE, FR, UK, ES IT, CN, CL
3 or more fixings in one direction
550 750 900 700 NL, BE, FR, UK, ES IT, CN, CL
3 or more fixings in one direction
550 700 800 700 DE
D Fixing distances for soffit application must be multiplied by 0.75.
E The maximum permitted fixing distances shown have been designed with a maximum (wind) load of 600 N/ m² and maximum deflection of L/200.
F Based on the surface properties of Gloss panels, fixing distances are reduced.
Fixing distances must be calculated in accordance with applicable local standards, regulations and certificates and should be
verified by a structural engineer.
For more information about deflection and wind loads, please visit www.trespa.info/meteon/fixingsystems
a
b
b
b
b
c c ac ca
c
c
b
b
b
b
c
c
a = horizontal fixing distance
b = vertical fixing distance
c = edge clearance
= fixed point in panel centre
= sliding point
Please check www.trespa.info for the latest version of this document
6
13
4
5
6
7
8
2
horizontal cross-section
1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel
6. Wall bracket
7. Vertical rail
8. Rivet
code
U30
58 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Please check www.trespa.info for the latest version of this document
7
Vertical cross-section
13
4
5
6
7
8
2
9
1. Load bearing wall (concrete, masonry)
2. Thermal insulation
3. Weather barrier (vapour permeable)
4. Ventilated cavity
5. Trespa® Meteon® panel
6. Vertical rail
7. Wall bracket
8. Rivet
9. Ventilation profile
Please check www.trespa.info for the latest version of this document
8
code
U30
58 v
ersi
on 2
.0 d
ate
14-0
6-20
11
Disclaimer
This is a print generated by you from www.trespa.info (“Website”). By accessing the Website and printing this document you have accepted the
Terms of Use of the Website. Please refer to the Website for all conditions that apply to this document. Not all the systems shown in this document
may be suitable for all applications and jurisdictions. We provide you with testing, code and design data for informational purposes only and
strongly recommend that you or any other user of this document obtains independent advice regarding compliance with design requirements,
applicable codes, laws and regulations, and test standards. Please check your local codes and design requirements for proper use. Trespa will not
accept any liability in relation to your use of this document.
All intellectual property rights, including copyrights and other rights regarding the content of the Website and this print generated from the
Website (including logos, trademarks, service marks, software, databases, audio, video, text and photographs) are owned by Trespa and/or its
licensors. Trespa®, Meteon®, Athlon®, TopLab®, TopLabPLUS ®, TopLabECO-FIBRE ®, Virtuon®, Volkern®, Trespa Essentials® and Mystic Metallics®
are registered trademarks of Trespa.
All oral and written statements, offers, quotations, sales, supplies, deliveries and/or agreements and all related activities of Trespa are governed by
the Trespa General Terms and Conditions of Sale (Algemene verkoopvoorwaarden Trespa International B.V.) filed with the Chamber of Commerce
and Industry for Noord- en Midden- Limburg in Venlo (NL) on 11 April 2007 under number 24270677,which can be found on and downloaded