Troubleshooting Your Way Through Electrical Problems

  • Upload
    denramr

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

  • 8/13/2019 Troubleshooting Your Way Through Electrical Problems

    1/7

    Troubleshooting Your Way Through Electrical Problems

    Today's troubleshooters use many tools, from simple handheld meters that measure

    resistance and voltage to sophisticated recording oscilloscopes that capture fast

    transients.

    Ever watch veteran electrical troubleshooters in action? If not, you should: It'ssomething to

    see. Years of experience coupled with intelligent "hunches" seem to guide their

    investigation. To help you in your troubleshooting efforts, we've compiled the following tips

    to solving motor control, power distribution, and adjustable speed drive problems.

    Testing contact quality on energized motor starters.Typically, you must get a

    "failed" motor to run again as soon as possible. Obviously, you're under pressure and must

    use all the troubleshooting techniques you've acquired over the years. One tried-and-true

    technique involves testing contact quality on energized starters.

    To understand this method, consider a typical manual or magnetic motor starter having

    three sets of power contacts and three overload (OL) relays. When a starter energizes a

    motor, equal currents (theoretically) flow through each contact and OL relay. So, you can

    measure the voltage drops across the contact or OL relay poles and compare them with one

    another. How do you do it? First, connect your multimeter's lead set to the correct input

    terminals and set it to read AC millivolts (mV). With the starter energized, begin with the

    lefthand pole and place one probe's tip on the line-side terminal. Then, carefully position

    the other tip on the corresponding load-side terminal, but electrically upstream of the OL

    relay. Then, note the reading. Repeat this process for the other terminals and compare the

    results. For each reading, try to place the test lead probes in the same relative position at

    each contact and OL relay.

    You can apply this online millivolt-drop test to contactors serving other loads too. With a

    little experience, you can measure the voltage drop on a cable termination. Where there's a

    small amount of exposed bare conductor on the cable, place one probe on a strand and the

    other on the corresponding lug or bus bar. You shouldn't use this procedure to establish a

    precise benchmark, substitute as a preventive maintenance program, or replace current-

    injection OL relay testing or thermographic surveying. It only provides a basic check for use

    in breakdown troubleshooting situations.

  • 8/13/2019 Troubleshooting Your Way Through Electrical Problems

    2/7

    Suppose you do the testing as indicated above on a magnetic starter and get the readings

    shown in the Table (in the original article). Reviewing these readings, you would see those

    of the OL relays are nearly the same. However, the starter contact reading for Phase C is

    significantly higher than the others. This may be the result of an internal problem such as

    excessive wear, loose hardware, or poor contact pressure.

    By taking phase current readings and using Ohm's Law, you can calculate and compare the

    respective contact resistance values (technically, impedance). With the resultant high-

    resistance value for Phase C, this condition (if left as is) can cause high heating and eventual

    starter failure. The result will be unannounced downtime. Remember, even though you're

    making a fraction-of-a-volt measurement, you're connecting your meter to points energized

    by line voltage. Therefore, follow these safety guidelines:

    Use only a test instrument having internal protection circuitry that prevents damage,should you inadvertently apply input terminals to line voltages while set at lower voltages.

    Use the utmost caution and exercise all required safety practices.

    Wear appropriate protective equipment such as safety glasses, rubber gloves, etc.

    Make sure you have good work-area lighting.

    Be well aware of the circuit voltage, available short-circuit current, immediate

    surroundings, working clearances, and the capabilities and limitations of your testinstrument. Special thanks to Scott Falke, former High-Voltage Electrician at the Lawrence

    Livermore National Laboratory, for this troubleshooting tip.

    Troubleshooting control power transformers.Getting a process line back into

    operation can be stressful, considering the electrical components tied into the control

    system. Sometimes it's not the exotic sensor or mysterious black box (known as the PLC)

    that's the problem. The source can be as mundane as the ubiquitous control power

    transformer (CPT) in a motor control center.

    Typical CPT problems include open circuits, partial shorts, complete shorts, and grounded

    windings. First, you should check the primary of the CPT to verify you have power.

    Partial shorts.Sometimes, a partial short occurs in the CPT's secondary, causing a voltage

    drop. Overheating of the CPT is the usual symptom because large circulating currents are

    flowing through the shorted windings.

  • 8/13/2019 Troubleshooting Your Way Through Electrical Problems

    3/7

    Troubleshooting here involves a sequence of steps. First, verify line power is available by

    taking a voltage reading at the CPT's primary. Then take a reading at the secondary. If the

    readings are somewhat lower than normal, suspect a partial short.

    Another method is to use a sensitive ohmmeter with the CPT's leads disconnected and thesystem de-energized. Here, a lower-than-normal resistance reading indicates a partial short.

    However, the difference in resistance from normal will be very slight.

    Complete shorts.Sometimes a CPT's winding shorts out, activating a circuit breaker or fuse

    to protect the circuit by de-energizing it. However, there may be instances where the CPT

    continues to operate, resulting in excessive overheating (due to very large circulating

    current) and melting of CPT winding insulation. The most apparent symptom is a strong

    odor. Another is no voltage output across the shorted winding. But be careful: The short

    may be in the external secondary circuit and not the CPT's winding.

    The best way to find the location is to disconnect the external secondary circuit from the

    CPT and take a voltage reading at the CPT's secondary. If the voltage is normal, the problem

    is in the external secondary circuit. If the voltage is zero across the secondary leads, the CPT

    is shorted and needs replaced.

    Grounded windings.In older transformers, especially overloaded units, insulation

    breakdown is common. Here, the insulation physically breaks down or deteriorates to the

    point where the winding's bare wire exposes. If the exposed wire comes in contact with a

    grounded surface (such as the CPT housing), the CPT shorts to ground.

    Should the above condition develop, and a point in the external secondary circuit also

    becomes grounded, part of the CPT winding will be shorted out. Here, the symptoms are

    overheating, which you can detect by touch or smell. You can also detect this by a low-

    voltage reading at the CPT's secondary. The only alternative here is to replace the damaged

    CPT.

    The best method for detecting this condition is to use a megohmmeter. First, disconnect the

    leads from the CPT's primary and secondary windings. Then, connect the megohmmeter's

    negative test lead to an associated ground and its positive test lead to the winding you're

    testing. Record the reading. Finally, take an insulation resistance reading between the

    windings by connecting one test lead to the primary and the other to the secondary.

  • 8/13/2019 Troubleshooting Your Way Through Electrical Problems

    4/7

    Diagnosing ASD "trip" problems.Repeated "tripping out" (shutdown) of an installed

    adjustable speed drive (ASD) is not only an annoying and elusive problem, but an expensive

    one when manufacturing or production processes stop.

    While altering the trip levels of the ASD is tempting (and in some cases economicallyjustifiable), it's not a long-term solution. Repetitive tripping of a drive may be a warning

    sign complete failure is not far off.

    Most modern ASDs monitor many different fault conditions that can trip the drive. Use

    these parameters as a guide: DC bus overvoltage; DC bus undervoltage; current overload;

    and ground fault protection relay tripping.

    DC bus overvoltage faults.Line transients from the AC source are a common cause of an

    overvoltage fault. (See Fig. 1, in the original article) The best way to discover the cause of

    this is to connect a voltage recorder to the AC line inputs and time-stamp the transient

    event. If the transient events are greater than 2 p.u. (per unit) and less than 0.5 cycle

    duration, it's likely they're caused by lightning, utility switching (transformer taps, kVAR

    capacitors), load switching within the building, or some power line fault clearing event.

    If you can correlate the transients to a regular utility switching event, contact the utility. It's

    possible the utility is unaware of the effect it's having on customers. It may even be willing

    to modify practices or install equipment to minimize such effects. If you can't determine the

    source of the transient event, then you should install a surge protection device at the service

    entrance to the building.

    For shorter magnitude, longer duration transients, which are classified as swells (1.3 p.u. to

    2.0 p.u. and 0.5 cycles to 30 cycles), it's possible an isolation transformer or series line

    reactor will take care of the instantaneous overvoltage. An isolation transformer will also

    reduce common mode noise from the ASD. Swells longer than one or two cycles may require

    some additional voltage regulation like an uninterruptable power supply (UPS). Be careful

    though: Not all UPS systems can regulate overvoltages.

    A longer duration overvoltage lasting greater than 30 cycles is a less common fault affecting

    ASDs. It occurs when the local utility is slow to respond and compensate for large loads

    from industrial and commercial customers being switched off, such as at the end of a work

    shift. The problem is fairly easy to detect with a recording power line monitor. If you can't

    resolve the problem with the local utility, then a UPS designed to compensate for

    overvoltages may be the answer.

  • 8/13/2019 Troubleshooting Your Way Through Electrical Problems

    5/7

    If line voltage monitoring doesn't record a transient or swell associated with the overvoltage

    fault, it's possible the increased energy at the DC bus is coming from the load side of the

    inverter, not the line side. We call this motor regeneration. One problem with elevators and

    large centrifugal loads, regeneration occurs when the motor is "coasting" and changes from

    being a motor to a generator.

    You can detect regeneration by looking at a change in direction of the DC current level, as

    measured at the output side of the DC bus. A simultaneous measurement of the DC voltage

    will confirm current flowing back into the DC bus is causing the overvoltage. Installing a

    dynamic brake is the most common way to solve this problem. If you've already done this,

    check the resistance measurements according to the manufacturer's specifications. If it's a

    solid-state type, check the transistors for proper conduction, using the diode test function

    on your multimeter. It's also possible the dynamic braking is too excessive, stopping the

    motor too suddenly. If your drive permits, lengthen the deceleration time to minimize the

    regenerative effect.

    One final word about overvoltage transients: Inadequate building grounds can cause

    transients to propagate through a distribution system at magnitudes greater than normal.

    This might explain why one building is having more problems than adjacent ones.

    DC bus undervoltage faults.Your best bet in detecting ASD undervoltage faults is to use a

    recording line voltage monitor. Because most ASDs have enough "ride through" to handle

    short duration (less than 0.5 cycle) sags or dropouts, you don't need to detect fastundervoltage events. While this makes the problem easier to detect, fixing it is more difficult

    due to large current surges caused by large loads either inside or outside your building. (See

    Fig. 2, in the original article.) In either case, you'll probably need voltage regulation like that

    from a UPS.

    Another possible cause for undervoltage is when the line voltage supply has "flat-topped"

    peaks. (See Fig. 3, in the original article.) This happens when you have other large electronic

    loads in the building. Because all electronic loads convert from AC to DC, the AC-to-DC

    conversion is responsible for almost all nonlinear (harmonic generating) currents that causeflat-topping. Basically, all electronic loads draw a short burst of current at the voltage peaks.

    (See Figs. 4 and 5, in the original article.) If the AC source is weak (either the transformer

    kVA is too low, or the conductors are too small or too long), then the peak currents flatten

    the peak of the voltage waveform. This reduces the charge on the DC bus capacitor, which

    presents a problem when someone switches another large load on in the building. As a

  • 8/13/2019 Troubleshooting Your Way Through Electrical Problems

    6/7

    result, the voltage peak drops further, the capacitor charge becomes even lower than it was

    due to flat-topping, and the DC bus voltage drops below the trip point. About the only way

    to recognize this problem is with an oscilloscope or power monitor that can display the

    voltage waveform.

    Current overload faults.While there are several different causes of overload tripping with

    ASDs, some are easier to find than others. First, make sure there's a proper match between

    the motor and drive. While this may seem obvious, the actual motor is sometimes different

    than the original specification due to cost and/or size concerns. Also, make sure the motor is

    sized properly for the load. Measure the motor current on all three phases and check against

    the nameplate rating to be sure.

    Another overload consideration is whether the load has changed. Sometimes an equipment

    operator increases the demand of a load without knowing the consequences. What's more,the ASD may not be programmed properly. If the acceleration time decreases, or trip points

    change, this could account for overload tripping.

    You should also make sure the ambient air temperature at the ASD installation is within

    specified operating temperatures. An increase in environmental temperatures can cause

    component failure and/or higher-than-normal conduction of components.

    An open phase connection can also cause an overload condition known as single phasing.

    Basically, the other two phase windings in the motor have significantly increased current,

    and the motor keeps running. If this is the case, the drive will probably trip when you restart

    it. Open circuits are sometimes difficult to find because wiring is not always easily

    accessible. The best way to check for single phasing is to measure the in-rush (acceleration)

    current on all three phases. The one with no in-rush current is the culprit.

    Voltage imbalance between phases at the motor terminals can cause excessive current to

    flow in one or two motor windings. This, in turn, can cause the overload to trip. It could be

    due to a problem with one of the output transistors in the drive not conducting properly, or

    a bad connection between the drive and motor, resulting in a voltage drop on one of the

    phases.

    Shorted windings can also cause an overload condition. However, because the ASD may trip

    and shutdown before you can take a visual reading, you should use a DMM or oscilloscope

    capable of measuring and recording the peak in-rush (acceleration) current. Make this

    measurement on all three phases to see if a shorted winding in one of the phases is causing

  • 8/13/2019 Troubleshooting Your Way Through Electrical Problems

    7/7

    more current to flow in it than the others. Be careful though: A voltage imbalance may be

    the cause of any current variations between phases. This means you may have to disconnect

    the drive and motor and test them separately.

    If you exceed the overload current on each phase, and it's beyond the nameplate rating ofthe motor, you may need to investigate whether you're exceeding the mechanical load

    connected to the motor for the application.

    Ground fault protection relay tripping.The fast edged pulses of a pulse width

    modulation (PWM) drive may cause leakage currents to flow between the motor windings

    and the grounded motor frame through the capacitor created by the metal windings,

    winding insulation, and metal frame. With normal 60 Hz sine wave operational, this isn't a

    problem. However, the high switching frequency of the PWM signal reduces the motor's

    internal capacitive reactance, causing greater amounts of leakage currents to flow. This cancause nuisance tripping of the drive, as many GFP relays trip at 300mA or less.

    Measuring this phenomenon can be difficult, as it may require isolating the motor frame

    from ground and then reestablishing a connection to ground via a cable that allows you to

    take ground current measurements.

    To reduce leakage currents, use a common-mode choke and dampening resistor or special

    cabling that employs either EMI suppression, low-pass filtering, or ferrite granule coating

    that absorbs the radio frequency (RF) energy and turns it into heat. Isolation transformers

    also minimize common-mode leakage currents, but may not be a cost-effective solution

    unless you're using them to solve other problems