CE470 Lab 8
Column splices
Live load reduction
Tributary and Influence Area
ASCE 7-10
Lab 8 – Column Design
Column Splices
Forney Hall Addition (Chemical Engineering)
Column Splices
Splices every 2 stories; typically
located a few feet
above the floor
Column Splices
Forney Hall Addition (Chemical Engineering)
Hole in web for lifting column into place Splices may also have web splice plates
Tributary Area, AT
Interior Column Tributary Area, AT
Interior Column Influence Area, AI
AI = AT*KLL
AI = AT*4
Interior Beam Tributary Area, AT
Interior Beam Influence Area, AI
AI = AT*KLL
AI = AT*2
ASCE 7-10 Live Load Reduction
ASCE 7-10 Live Load Reduction
Interior Column, Beam KLL Factor
From ASCE7-10 Commentary
Corner Column KLL Factor From ASCE7-10 Commentary
ASCE 7-10 Live Load Reduction
Note: see Section 4.8 for reduction in roof live loads
Lab #8 Column B-2
Lab #8 Column Design
Lab #8 Column Design
0.5Lo limit only for design of column section immediately below penthouse
Lab #7 Column Design
Try for the lightest W-shapes; note that it is not necessary that BOTH Ag and lower r value satisfy required values based on KL/r assumption.