28
Trend EnergyEYE Installation and Configuration Instructions Issue 1

Trend EnergyEYE Installation and Configuration Instructions

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Trend EnergyEYE Installation and Configuration Instructions

Trend EnergyEYE Installation and Configuration Instructions

Issue 1

Page 2: Trend EnergyEYE Installation and Configuration Instructions

Author: Technical Publications

Issue: 1

Date: 16/06/2009

Part Number: TG201069

Copyright: © 2009 Honeywell Technologies Sàrl, ECC Division. All rights reserved.

This manual contains proprietary information that is protected by copyright. No part of this manual may be reproduced, transcribed, stored in a retrieval system, translated into any language or computer language, or transmitted in any form whatsoever without the prior consent of the publisher.

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, ZA, La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

For information contact:

Trend Control Systems Limited

P.O. Box 34

Horsham

W. Sussex

RH12 2YF

NOTICE: Trend Control Systems Limited makes no representations or warranties of any kind whatsoever with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for any particular purpose. Trend Control Systems Limited shall not be liable for any errors contained herein or for incidental or consequential damages in connection with the furnishing, performance or use of this material. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes in the content hereof without obligation to notify any person of such revisions or changes.

Windows, Windows XP Professional, Windows XP Home, Windows 2003, and Windows Vista are trademarks of Microsoft Corporation.

Please send any comments on this or any other Trend technical publication to [email protected]

Page 3: Trend EnergyEYE Installation and Configuration Instructions

Table of Contents

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 3

TABLE OF CONTENTS

1 ABOUT THIS MANUAL................................................................................................................................. 5 1.1 Contacting Trend.......................................................................................................................................... 5

2 ABOUT TREND ENERGYEYE ..................................................................................................................... 7

3 INSTALLATION.............................................................................................................................................. 9 3.1 System Requirements................................................................................................................................... 9 3.2 Install Trend EnergyEYE........................................................................................................................... 10

3.2.1 Install the software.......................................................................................................................... 10 3.2.2 Setup a Mapped Network Drive...................................................................................................... 10 3.2.3 Update the 963 Functionality.......................................................................................................... 11 3.2.4 Configure 963 ................................................................................................................................. 11

4 CONFIGURE TREND ENERGYEYE......................................................................................................... 13 4.1 Configure the 963 Element ........................................................................................................................ 13

4.1.1 Configure TrendGraphValues.txt.................................................................................................... 13 4.1.2 Configure SpotGraphValues.txt...................................................................................................... 15

4.2 Configure the Trend EnergyEYE Element................................................................................................. 16 4.3 License Trend EnergyEYE......................................................................................................................... 22

5 RUN TREND ENERGYEYE......................................................................................................................... 25

Page 4: Trend EnergyEYE Installation and Configuration Instructions

Table of Contents

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 4

This page is intentionally left blank.

Page 5: Trend EnergyEYE Installation and Configuration Instructions

About This Manual

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 5

1 ABOUT THIS MANUAL

These instructions apply to Trend EnergyEYE version 1.0. They provide information about installing, upgrading, and licensing Trend EnergyEYE.

Other relevant documentation is:

Trend EnergyEYE Data Sheet (TA201068)

1.1 Contacting Trend

Head Office Trend Control Systems Ltd PO Box 34 Horsham Sussex RH12 2YF England

Tel: +44 (0) 1403 211888 Fax: +44 (0) 1403 241608

Details of regional offices can be found on our Web site.

Internet Our company web site (www.trend-controls.com) provides information about our products and us, or our support web site (http://pnet.trend-controls.com).

Technical Support Our support department provides technical support during normal office hours. Before contacting them ensure that you have your Technical Support PIN number available, without this we will be unable to provide you with any support.

Trend Control Systems Ltd. Technical Support Department PO Box 34 Horsham Sussex RH12 2YF England

Tel: +44 (0) 1403 226600 Email: [email protected] Fax: +44 (0) 1403 226310

Technical Publications Please send any comments on this or any other Trend technical publication to [email protected].

Page 6: Trend EnergyEYE Installation and Configuration Instructions

About This Manual

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 6

This page is intentionally left blank.

Page 7: Trend EnergyEYE Installation and Configuration Instructions

About Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 7

2 ABOUT TREND ENERGYEYE

The Trend EnergyEYE is a display that utilises existing Trend utility data stored within the Trend 963 Supervisor and displays energy consumption figures on a display screen. It is divided into 3 areas that can be configured to show scrolling text, movie files and utility data i.e. electricity and gas in the form of spot values and graphs.

Page 8: Trend EnergyEYE Installation and Configuration Instructions

About Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 8

This page is intentionally left blank.

Page 9: Trend EnergyEYE Installation and Configuration Instructions

Installation

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 9

3 INSTALLATION

This section describes how Trend EnergyEYE should be installed to ensure that it operates correctly.

3.1 System Requirements

The specifications below are those recommended to run 963. They refer to a standard PC with mouse, keyboard, hard drive, floppy disk drive, DVD drive, monitor, and sound capabilities (optional).

Recommended Hardware Processor 2 GHz. RAM 1 GB Disk space 40 GB hard disk with 1 GB for installation + space for site data. Graphics card 128 MB, 1280x1024 resolution. Network card Ethernet Network Card (required to connect to 963 over Ethernet).

Software Operating system Windows XP SP2 Professional or Windows Vista™ Business SP1

Minimum Hardware Processor 1 GHz. RAM 512 MB Disk space 20 GB hard disk with 1 GB for installation + space for site data. Graphics card 64 MB, 1280x1024 resolution. Network card Ethernet Network Card (required to connect to 963 over Ethernet).

Software Operating system Windows XP SP2 Professional or Windows Vista™ Business SP1

Trend EnergyEYE also requires:

963 v2.2 or higher A desktop PC with network connectivity to the 963 PC Some kind of display screen connected to the desktop machine Utility data recorded by 963 software

Page 10: Trend EnergyEYE Installation and Configuration Instructions

Installation

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 10

3.2 Install Trend EnergyEYE

To install Trend EnergyEYE follow the procedure described below: 1. Install the software as described in the ‘Install the Software’ section of these instructions. 2. Set up a mapped network drive as described in the ‘Setup a Mapped Network Drive’ section of these

instructions. (only if Trend EnergyEYE is run from a remote PC to the 963). 3. Update 963 functionality as described in the ‘Update 963 Functionality’ section of these instructions. 4. Configure 963 as described in the ‘Configure 963’ section of these instructions. 5. Configure Trend EnergyEYE as described in the ‘Configure Trend EnergyEYE’ section of these

instructions. 6. Licence Trend Energy Eye as described in the ‘Licence Trend EnergyEYE’ section of these instructions.

3.2.1 Install the software

To install the software: 1. On the PC that is to run Trend EnergyEYE close all programs (including virus protection applications), and

insert the CD into the CD-ROM drive. A window is opened that displays the contents of the CD. 2. Run SETUP.exe. The installation screen is displayed. 3. Follow the instructions on the screen.

3.2.2 Setup a Mapped Network Drive

If the Trend EnergyEYE is run from a remote PC to the 963 it requires a mapped network drive to be set up. This is the location in which Trend Energy Eye will look for the XML files generated by 963 containing the data that is displayed.

To set up a mapped network drive: 1. On the PC that is to run Trend EnergyEYE on the Start menu point to Programs then point to Accessories

and click Windows Explorer. 2. On the Tools menu, click Map Network Drive. The Map Network Drive dialogue box is displayed.

3. In the Drive box select an available drive letter. Any drives already mapped will have a shared folder name displayed inside the dropdown list, next to the drive letter.

4. Click the Browse…. The Browse For Folder dialogue box is displayed.

5. Click on the required location. 6. Click OK. 7. Select the Reconnect at login checkbox.

Page 11: Trend EnergyEYE Installation and Configuration Instructions

Installation

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 11

3.2.2 Setup a Mapped Network Drive (continued)

8. If the remote computer requires a different username and password to log in specify the required user name and password.

Click different user name. The Connect As dialogue box is displayed.

In the User name box enter the required user name. In the Password box enter the matching password. Click OK.

9. Click Finish.

3.2.3 Update the 963 Functionality

The 963’s functionality must be updated to enable it to provide the necessary information required by Trend EnergyEYE.

To update the 963’s functionality: 1. Install and licence 963 as described in the 963 Installation Instructions (T201026). 2. On the PC running 963 close all programs (including virus protection applications), and insert the CD into

the CD-ROM drive. A window is opened that displays the contents of the CD. 3. Run the 963. 4. Open the ‘Config Files\ SQL Script Files’ folder. 5. Double click Install EnergyEye SQL Script.bat. A batch file will be run. 6. When this is complete go back to the root folder of the CD and open the ‘Config Files\963 Script Files’. 7. Copy the files ‘TrendGraphValues.txt’ and ‘TrendSpotValues.txt’ to the ‘C:\Program Files\Trend Control

Systems\963\Scripts’ directory.

3.2.4 Configure 963

963 must be configured to record the required sensors. This is described in the 963 documentation.

Page 12: Trend EnergyEYE Installation and Configuration Instructions

Installation

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 12

This page is intentionally left blank.

Page 13: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 13

4 CONFIGURE TREND ENERGYEYE

This section describes how to correctly configure Trend EnergyEYE.

To configure Trend EnergyEYE follow the procedure described below: 1. Configure the 963 element as described in the ‘Configure the 963 element’ section of these instructions. 2. Configure the Trend EnergyEYE element as described in the ‘Configure the Trend EnergyEYE Element’

section of these instructions.

4.1 Configure the 963 Element

Configuration of the 963 element requires two files (‘TrendGraphValues.txt’ and ‘SpotGraphValues.txt’) must be configured to define the information displayed by Trend EnergyEYE.

4.1.1 Configure TrendGraphValues.txt

To configure TrendGraphValues.txt: 1. Run notepad, and open the TrendGraphValues.txt file in the scripts directory (normally

c:\programfiles\trend control systems\963\scripts). 2. If Trend EnergyEYE is to display data from more than one site it is necessary to add additional sites.

Search through the file to find the following text ‘--To add a new site please copy from here to </Site>’.

Select the text from‘--To add a new site please copy from here to </Site>’ to ‘</Site>’ copy it to the clipboard.

Past the text below the following text ‘-- Copy to here and paste below this line when adding an additional site’.

Repeat the steps above until all the required sites have been added. Search through the file to find the following text ‘<Param Name="$" Type="2" Value="Site1">’. Leave the first occurrence of ‘<Param Name="$" Type="2" Value="Site1">’ as it is but edit

subsequent occurrence to increment the site number e.g. the second occurrence ‘<Param Name="$" Type="2" Value="Site2">’ etc

Search through the file to find the following text ‘<Param Name="D" Type="2" Value="<Display Name>">’.

Change ‘Display Name’ in each occurrence to name of the site.

3. Specify the label information for the graph 1 site 1.

Search through the file to find the following text ‘--Label of Graph 1’. In the line below replace ‘Monthly Electricity Consumption’ with the label required for graph 1. Search through the file to find the following text ‘--Label of the units for Graph 1’. In the line below replace ‘kwh’ with the units for graph 1. Search through the file to find the following text ‘--Label of the x Axis for Graph 1’. In the line below replace ‘Months’ with the label for the x axis of graph 1. Search through the file to find the following text ‘--Label of the y Axis for Graph 1’. In the line below replace ‘kWh’ with the label for the y axis of graph 1.

4. Repeat step (3) for each site. 5. Specify the label information for the graph 2 site 2.

Search through the file to find the following text ‘--Label of Graph 2’. In the line below replace ‘Monthly Gas Consumption’ with the label required for graph 2. Search through the file to find the following text ‘--Label of the units for Graph 2’. In the line below replace ‘kwh’ with the units for graph 2. Search through the file to find the following text ‘--Label of the x Axis for Graph 2’. In the line below replace ‘Months’ with the label for the x axis of graph 1. Search through the file to find the following text ‘--Label of the y Axis for Graph 2’. In the line below replace ‘kWh’ with the label for the y axis of graph 2.

6. Repeat step (4) for each site.

Page 14: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 14

4.1.1 Configure TrendGraphValues.txt (continued)

7. Specify the values displayed on graph 1 site 1.

Search through the file to find the following text ‘--Start of the individual readings for the month's (1 for each month) for Graph 1’. Below this are 12 lines in the format below one for each month on the graph. Each line specifies a value on graph 1.

Value="<SQLVALUE usp_TrendGraphData '<Connection String>',<LAN>,<Outstation>,'<Sensor Reference>',4,1>" />

Replace <Connection String> with the telephone number, or IP address required to access the controller containing the required value. When entering an IP address it must be prefixed by 'IP' e.g. IP192.186.23.87. If specifying a hostname it must be prefixed by 'IP' and enclosed in double quotes e.g. IP"Albery House". When entering a telephone number it can contain the following characters. The number may be up to 20-characters in length, if the device is on the local site leave this field blank.

Characters Description 0 to 9 Dialling characters. ABCD#* Considered as dialling characters on some systems. J or : Wait for secondary dial tone. K or ; or , 2 second pause (Note on some autodiallers this may be a 1 second pause). < Pulse dialling. M or = Tone dialling.

Replace <LAN> with the Lan number of the controller containing the required value. (0, 1, and 4 to 119 excluding 10).

Replace <Outstation> with the address on the network of the controller containing the required value. (0, 1, and 4 to 119 excluding 10).

Replace <Sensor Reference> with the sensor number of the required value proceeded by a ‘S’ e.g. ‘S1’ for sensor 1

8. Repeat step (7) for each site. 9. Specify the values displayed on graph 2 site 1.

Search through the file to find the following text ‘--Start of the individual readings for the month's (1 for each month) for Graph 2’. Below this are 12 lines in the format below one for each month on the graph. Each line specifies a value on graph 2.

Value="<SQLVALUE usp_TrendGraphData '<Connection String>',<LAN>,<Outstation>,'<Sensor Reference>',4,1>" />

Replace <Connection String> with the telephone number, or IP address required to access the controller containing the required value. When entering an IP address it must be prefixed by 'IP' e.g. IP192.186.23.87. If specifying a hostname it must be prefixed by 'IP' and enclosed in double quotes e.g. IP"Albery House". When entering a telephone number it can contain the following characters. The number may be up to 20-characters in length, if the device is on the local site leave this field blank.

Characters Description 0 to 9 Dialling characters. ABCD#* Considered as dialling characters on some systems. J or : Wait for secondary dial tone. K or ; or , 2 second pause (Note on some autodiallers this may be a 1 second pause). < Pulse dialling. M or = Tone dialling.

Replace <LAN> with the Lan number of the controller containing the required value. (0, 1, and 4 to 119 excluding 10).

Replace <Outstation> with the address on the network of the controller containing the required value. (0, 1, and 4 to 119 excluding 10).

Replace <Sensor Reference> with the sensor number of the required value proceeded by an ‘S’ e.g. ‘S1’ for sensor 1.

10. Repeat step (9) for each site. 11. Using find and replace replace all occurrences of ‘<Data Path>’ with the actual pathname of the location of

the XML files generated by 963. 12. Save and close the file.

Page 15: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 15

4.1.2 Configure SpotGraphValues.txt

To configure SpotGraphValues.txt: 1. Run notepad, and open the TrendSpotValues.txt file in the scripts directory (normally c:\programfiles\trend

control systems\963\scripts). 2. If Trend EnergyEYE is to display data form more than one site it is necessary to add additional sites.

Search through the file to find the following text ‘--To add a new site please copy from here to </Site>’.

Select the text from‘--To add a new site please copy from here to </Site>’ to ‘</Site>’ copy it to the clipboard.

Past the text below the following text ‘-- Copy to here and paste below this line when adding an additional site’.

Repeat the steps above until all the required sites have been added. Search through the file to find the following text ‘<Param Name="$" Type="2" Value="Site1">’. Leave the first occurrence of ‘<Param Name="$" Type="2" Value="Site1">’ as it is but edit

subsequent occurrence to increment the site number e.g. the second occurrence ‘<Param Name="$" Type="2" Value="Site2">’ etc

Search through the file to find the following text ‘<Param Name="D" Type="2" Value="<Site Display Name>">’.

Change ‘Site Display Name’ in each occurrence to name of the site.

3. Specify the spot values for each site.

Search through the file to find the following text ‘<SQLVALUE usp_TrendSpotData <Connection String>',<LAN>,<Outstation>,'<Sensor Reference>’.

Replace <Connection String> with the telephone number, or IP address required to access the controller containing the required value. When entering an IP address it must be prefixed by 'IP' e.g. IP192.186.23.87. If specifying a hostname it must be prefixed by 'IP' and enclosed in double quotes e.g. IP"Albery House". When entering a telephone number it can contain the following characters. The number may be up to 20-characters in length, If the device is on the local site leave this field blank.

Characters Description 0 to 9 Dialling characters. ABCD#* Considered as dialling characters on some systems. J or : Wait for secondary dial tone. K or ; or , 2 second pause (Note on some autodiallers this may be a 1 second pause). < Pulse dialling. M or = Tone dialling.

Replace <LAN> with the Lan number of the controller containing the required value. (0, 1, and 4 to 119 excluding 10).

Replace <Outstation> with the address on the network of the controller containing the required value. (0, 1, and 4 to 119 excluding 10).

Replace <Sensor Reference> with the sensor number of the required value proceeded by a ‘S’ e.g. ‘S1’ for sensor 1.

Repeat the steps above for each occurrence of ‘<SQLVALUE usp_TrendSpotData <Connection String>',<LAN>,<Outstation>,'<Sensor Reference>’.

4. Using find and replace replace all occurrences of ‘<Data Path>’ with the actual pathname of the location of the XML files generated by 963.

5. Save and close the file.

Page 16: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 16

4.2 Configure the Trend EnergyEYE Element

Configuration of the Trend EnergyEYE element is carried out using a configuration wizard that helps you set up the graphical elements of the application.

To configure the Trend EnergyEYE element: 1. On the Start menu of the PC that is to run the Trend EnergyEYE, point to Programs, Trend Control

Systems, Trend EnergyEYE and then click Configuration Tool. . The Trend EnergyEYE Configuration Tool is displayed.

2. Click Live Data XML Setup. The screen shown below is displayed.

3. In the Spot Data XML Relative URL area click Browse for new file browse to the required location and select the XML file generated by 963 that defines the spot data that is to be displayed.

4. In the Graph Data XML Relative URL area click Browse for new file browse to the required location and select elect the XML file generated by 963 that defines the graph data that is to be displayed.

5. Click Save these changes. The screen shown below is displayed.

Page 17: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 17

4.2 Configure the Trend EnergyEYE Element (continued)

6. Click Next. The screen shown below is displayed.

7. Specify the sites for which information is to be displayed. The left hand box displays the available sites and the right hand box displays the sites that are to be displayed by Trend EnergyEYE.

To specify a site to be displayed: In the left hand box click the required site and click COPY Selected. To add all sites click Copy

ALL.

To specify a site not to be displayed: In the right hand box click the required site and click Remove Selected. To remove all sites click

Clear List.

8. Click Save these changes. The screen shown below is displayed.

9. Click Next. The screen shown below is displayed.

Page 18: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 18

4.2 Configure the Trend EnergyEYE Element (continued)

10. Select the layout you want to use by selecting the radio button next to the required layout. To see an enlarged view of the layout click the graphic.

11. Click Save these changes. The screen shown below is displayed.

12. Click Next. The screen shown below is displayed.

13. In the Spot Data Loop Delay in Seconds box specify the length of time spot data is to be display before it changes to the next set of spot data.

14. In the Graph Data Loop Delay in Seconds box specify the length of time each graph is displayed for. 15. In the CO2 Electricity Factor box enter the CO2 conversion factor for electricity required for this site. 16. In the CO2 Gas Factor box enter the CO2 conversion factor for gas required for this site. 17. In the Separator for thousands box select the thousands separator from the drop down list. 18. In the High Threshold box in the Gas Daily CO2 Threshold Values area specify the maximum threshold

value for daily gas values. Values above this will be displayed in red. 19. In the Low Threshold box in the Gas Daily CO2 Threshold Values area specify the minimum threshold

value for daily gas values. Values above this will be displayed in green. 20. In the High Threshold box in the Electricity Daily CO2 Threshold Values area specify the maximum

threshold value for daily electricity values. Values above this will be displayed in red. 21. In the Low Threshold box in the Gas Daily CO2 Threshold Values area specify the minimum threshold

value for daily electricity values. Values above this will be displayed in green.

Note that monthly and yearly values are calculated automatically.

22. Click Save these changes. The screen shown below is displayed.

Page 19: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 19

4.2 Configure the Trend EnergyEYE Element (continued)

23. Click Next. The screen shown below is displayed.

24. In the Logo Loop Delay in Seconds box enter the amount of time each logo is displayed for before the next one.

Note that this only applies of more than one logo has been added.

25. Specify the logos that are displayed. Logo’s need to be in .jpg format:

To specify a different logo: Click Browse for new file. Browse to the location of the required file. Select the required file. Click Select.

To add another logo: Click + add another image. Browse to the location of the required file. Select the required file. Click Select.

To remove a logo: Click - remove image. Browse to the location of the required file. Select the required file. Click Select.

26. Click Save these changes. The screen shown below is displayed.

Page 20: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 20

4.2 Configure the Trend EnergyEYE Element (continued)

27. Click Next. The screen shown below is displayed.

28. Select either the Text ON or Text OFF option to specify whether the scrolling text is displayed. 29. Click Browse for new file and browse to the file that contains the text that is to scroll. The file is a

standard text file and can be edited using a text editor such as Notepad. 30. Click the box under ‘Text Scroll Colour’ and click the required colour from the displayed choices to

specify the colour of the scrolling text. 31. Click the box under ‘Text Scroll Background Colour’ and click the required colour from the displayed

choices to specify the background colour for the scrolling text. 32. In the Text Scroll Background opacity box enter the value of the opacity of the background colour for the

scrolling text. Range 0 to 100. 0 = clear 100 = solid. 33. Click Save these changes. The screen shown below is displayed.

34. Click Next. The screen shown below is displayed.

Page 21: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 21

4.2 Configure the Trend EnergyEYE Element (continued)

35. Select either the Movie ON or Movie OFF option to specify whether the Trend EnergyEYE displays a video.

36. Specify the movies that are displayed. The movie must be in .FLV format this is a standard internet movie format that easily be converted to:

To specify a different movie: Click Browse for new file. Browse to the location of the required file. Select the required file. Click Select.

To add another movie: Click + add another movie. Browse to the location of the required file. Select the required file. Click Select.

To remove a movie: Click - remove movie. Browse to the location of the required file. Select the required file. Click Select.

37. Click Save these changes. The screen shown below is displayed.

38. Click Next. The screen shown below is displayed.

39. Specify the labels and colours used on the main display. To edit any text simply click in the text box and enter the required text. To edit a colour click it and selecting the colour required for the displayed dialogue box.

40. Click Save these changes. The screen shown below is displayed.

41. Click Return Home.

42. Click to close the wizard.

Page 22: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 22

4.3 License Trend EnergyEYE

Trend EnergyEYE will run for 30 days as a trial after which it must be licensed.

To license Trend EnergyEYE: 1. Obtain an Unlock Code as described in the 'Obtain an Unlock Code' section of this manual. 2. Enter the Unlock Code as described in the 'Enter the Unlock Code' section of this manual.

4.3.1.1 Obtain an Unlock Code

To obtain an unlock code: 1. Run Windows®. 2. On the Start menu, point to Programs, Trend Control Systems, Trend EnergyEYE and then click

Licensing Configuration. The Trend Energy Screen Config dialogue box is displayed.

3. Click Licence. The Trend EnergyEYE - Licencing dialogue box is displayed.

4. In the Serial no box enter the serial number. The serial number can be found on the sticker on the back of the CD case.

5. Click Request. The Licence Details dialogue box is displayed.

6. In the Contact Name box enter your name. 7. In the Company Name box enter your company name. 8. In the Your Fax No box enter the fax number to which the unlock code should be sent. 9. In the Contact Number box enter a telephone number at which you can be contacted. 10. In the Email box enter your email address. 11. In the Site Name box enter the name of the site on which the OPC server is installed. 12. In the Site Address box enter the address of the site. 13. Click OK. Notepad will now be run with the file OPCLicence.txt. 14. On notepad’s File menu click Print to print out the file. 15. Return to Licence Details dialogue box and click Close. The Trend Energy Screen Config dialogue box

is displayed. 16. Click Close. 17. Email the ‘faxform.txt’ file to [email protected], fax the printout to our Customer Services

Department on +44 (0) 1403 226310 or phone customer services on +44 (0)1403 226600.

Your request will be processed, and the unlock code faxed back to the specified fax number as soon as possible.

Page 23: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 23

4.3.1.2 Enter the Unlock Code

To enter the unlock code: 1. Run Windows®. 2. On the Start menu, point to Programs, Trend Control Systems, Trend EnergyEYE and then click

Licensing Configuration. The Trend Energy Screen Config dialogue box is displayed.

3. Click Licence. The Trend EnergyEYE - Licencing dialogue box is displayed.

4. In the Unlock code boxes enter the unlock code. 6. Click Unlock. 7. Click Close. The Trend Energy Screen Config dialogue box is displayed. 8. Click Close.

Page 24: Trend EnergyEYE Installation and Configuration Instructions

Configure Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 24

This page is intentionally left blank.

Page 25: Trend EnergyEYE Installation and Configuration Instructions

Run Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 25

5 RUN TREND ENERGYEYE

Trend EnergyEYE is run in the same way as any other Windows based application. Trend EnergyEYE will run for 30 days as a trial after which it must be licensed as described in the ‘License Trend EnergyEYE’ section of this manual.

To run Trend EnergyEYE: 1. Run Windows®. 2. On the Start menu, point to Programs, Trend Control Systems, Trend EnergyEYE and then click

Trend EnergyEYE.

Page 26: Trend EnergyEYE Installation and Configuration Instructions

Run Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 26

This page is intentionally left blank.

Page 27: Trend EnergyEYE Installation and Configuration Instructions

Run Trend EnergyEYE

Trend EnergyEYE Installation and Configuration Instructions TG201069 Issue 1, 16/06/2009 27

This page is intentionally left blank.

Page 28: Trend EnergyEYE Installation and Configuration Instructions

Trend Control Systems Limited P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

Trend Control Systems USA 6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trendcontrols.com