Upload
others
View
14
Download
0
Embed Size (px)
Citation preview
Silicon Valley Rapid Transit Program VTA 's BART Silicon Valley Berryessa Extension
1436 California Circle, 2nd Floor Milpitas, CA 95035
Transmittal No. 07722 P0728
Contract No.: C700
Contract: VT A Berryessa Extension Project
Date: 11/17/16
To:
Phone:
Skanska Shimmick Herzog 1436 California Circle Milpitas, CA 95035
951-368-6465
Attn: Brad Nystrom
Additional Distribution: V. Desai@
Submitted For: D Approval
IZI Your Use D As Requested D Review and Comment
Sent Via: ~ Attached D Separate Cover Via: Item Copies Date Description
Response to Submittal: HV AC Ducts & Casings Draft
0 &MManual
PDCC#: P0728-C700-233100-1.06E.RO
From: John V. Engstrom, P.E.
Phone:
Valley Transportation Authority
San Jose, CA 95035 408-942-6198
Action Taken: D Approved As Submitted
D No Exceptions Taken
~ Make Corrections Noted
D Amend and Resubmit
D No Action Taken
D Approved As Noted
D D
Status 1 10/14/2016 HV AC Ducts & Casings Draft 0 & M Manual MCN
Remarks:
Please provide written response to attached comments.
Lead Reviewer: S. Beaver #ti'
Attachment: HV AC Ducts & Casings Draft 0 & M Manual Comment Disposition Form
Prepared By: Christine Siordia (
Signed:
Page 1of1
Stoia Om Valley Transportation Authorily
XO EXCEPTIOXS TAKLV ~"El) ./ MAKECORRECl10XSXOTED01GI) _ A;\IL\ll Ai'\ll RESL"B~DT (Affi)
Any aclion shown above is subject to the terms of the contract aod does not reliere the Contractor of any of its obligations
under the contract, iocludiog design and detailing.
Contract No.: C700
By: //!2-f Date:
I/ · t l · I /rJ (Date:
Source of Comments - Agency or Group Name Page 1
16-Nov-16
(Enter Comment Resolution Date)
Stephanie Buquis
Item No. Agency Reviewer Name
Dra
win
g
Spec
. Se
ctio
n
Page
Line Review Comment
Redline markup Attached
(Y/N)
Comment Level
Designer Responder In
itial
CR
M
Fina
l
Designer Response (or Disposition Explanation)
1 BART S.Buquis 01 78 231.13
Front and inside cover: BART and VTA show Oct/16, this should read October 2016
- template is "Month Year" therfore it read "October 2016" rather than "Oct/16"
N 1
2 BART R. Ona 1.15
` Configuration Control Record has "VTA" in title, but ultimate owner of manual is BART, so please remove VTA prior to Configuration. Center "Record of Revisions" to align with header.
N 2
Disposition Codes: A - Agree and will comply/take action; B - Will investigate and comment; C - Disagree for reasons noted in response; D - Will Address at Next Submittal; E - Multiple response Codes, See Response
Comments Due Date:
Sort Numbers Disposition
T
Comment Level Codes: 1 = Mandatory (Design Discrepancy Identified - Correction and Documentation Required) 2 = Best Practice - (Please Check) 3 = Editorial - (Minor Correction/Consider)
Review Item:
Design Development Stage Review:
HVAC Ducts and Casings O&M Manual per BFS Spec. No. 23 31 00 Submittal - 233100-1.06E.R0
Check One:
Review Item Document Date:
Comments Resolved:
Actions Completed:
Interim Design
Definitive Readiness for Construction
Final
Other
Draft
Skanska Shimmick Herzog
Phone: 213 785 0132Milpitas, CA 95035
1436 California Circle
PROJECT:
JOB NO:CONTRACT NO:
98005
VTA Berryessa Extension ProjectC700
08 71 00 - 1.05.010
TO:
FROM:
TITLE: Pump Station Door Frames SPD
Brad NystromSkanska Shimmick Herzog RECOMMENDED CONTACT:
DESCRIPTION/REMARKS STATUSRECEIVED SENT RETURNEDREVISION
NO.
SUBMITTAL
SUBMITTAL NO:
John Engstrom
08 71 00 - Pump Station Frames andHardware - SPD
OPN10/13/201610/3/20160
REMARKS:***Please expedite review with Bill O'Hair
f_sb_01_usac_01_ws_098005
23 31 00 - 1.06E
John Engstrom
HVAC Ducts & Casings Draft O&M Manual
0 HVAC Ducts & Casings Draft O&MManual
10/06/2016 10/14/2016 10/03/2016 OPN
We have enclosed 6 copies for your use.
Please forward to Paul Plecnik.
SVBX - Berryessa Extension
SUBMITTAL REVIEW
Submittal Title: Document Control
Spec Section & P a r a g r a p h # (i.e, 01 31 01-1.04B): Sub No.:
Discipline: Rev No.:
□ For EOR Approval □ For VTA Approval □ For VTA Information Only □ For Third Party
Description of Item Submitted
(Type size, model #, etc)
Type of Submittal( Shop
dwg, samples, matls)
Spec Parameter & Section #
(General Req, Contract, Performance Spec, Tech Spec)
Drawing Sheet #
Submittal Prepared By: Date Submitted: Requested Response Date:
Subcontractor/Supplier, If Applicable:
Deviation: No( ) Yes( ) See Notes Substitution: No( ) Yes( ) See Attached Information
Deviation/Substitution Notes (attach additional pages if necessary):
YES NO N/A
Submittal Reviewer's Checklist
1. Are specification and contract drawing references correct and included? (If not change or add them) □ □ □
2. Are the submittal date & requested return date included? (ASAP is not acceptable) □ □ □
3. Have you reviewed the specification section which requires this submittal? □ □ □
4. Do all materials submitted meet the applicable specification(s)? □ □ □
5. Are any deviations or substitutions clearly defined in the submittal notes above? □ □ □
6. Have all resubmittal comments been addressed? □ □ □
7. If required, does the submittal have a PE stamp from a Professional Engineer? □ □ □
8. Has the subcontractor/supplier signed and dated the submittal? □ □ □
9. Have you spot checked dimensions, unit weights, quantities, size, etcB with Plans? □ □ □
10. If required, are samples the correct quantity, size, type, and are labeled correctly? □ □ □
11. Is the presentation satisfactory (pages numbered, bound, tabs, spelling/grammar, etc.)? □ □ □
12. Is the correct number of legible copies being submitted? □ □ □
SSH Coordina
(PRINT NAME)
Signature:
Expected Rev
tor:
Date:
iew Hours:
Issue Cost Code:______________________________________
hkganskakS |mm|ceflzog M M
.1111:-| '|'rnI:ur|:r|.fl.:s |.11|un h H l'|'LIn
□ Civil □ Structures □ Utililities □ Stations □ Landscape □ Geotech □ Traffic □ Guideway □ Track□ Systems □ Electrical
Blocka Construction Inc. 4455 Enterprise StreetFremont CA 94538510-657-3686
Submittal Cover Sheet
10/04/2016
To: Skanska-Shimmick-Herzog
License:
Submittal Description:
679326 Submittal Date:
O&M Draft - HVAC Ducts & Casings
Project: BART Berryessa ExtensionMilpitas & Berryessa StationsSanta Clara CountyMilpitas CA
4182
01 78 23
1436 California CircleMilpitas CA 95035
BCI Record No: 6208
Item Status Notes
1.07-E Under Review O&M Manual - Draft: HVAC Ducts & Casings
Notes/Clarifications:
Spec Section/Submittal No.:
Cesar Lopez
Uflfifl
VTA’s BART Silicon Valley Berryessa Extension
HVAC DUCTS AND CASINGS Book No. 540
Operation and Maintenance Manual
Santa Clara Valley Transportation Authority ▪ 3331 North First Street ▪ San Jose, CA 95134 ▪ (408) 321-5680
San Francisco Bay Area Rapid Transit District ▪ 300 Lakeside Drive ▪ Oakland, CA 94612 ▪ (510) 464-6000
VTA’s BART Silicon Valley Berryessa Extension
HVAC DUCTS AND CASINGS
BOOK 540
Oct/16
InLR
Operation and Maintenance Manual
Santa Clara Valley Transportation Authority ▪ 3331 North First Street ▪ San Jose, CA 95134 ▪ (408) 321-5680
San Francisco Bay Area Rapid Transit District ▪ 300 Lakeside Drive ▪ Oakland, CA 94612 ▪ (510) 464-6000
VTA’s BART Silicon Valley Berryessa Extension
HVAC DUCTS AND CASINGS
BOOK 540
VTA CONFIGURATION CONTROL RECORD FOR
BOOK 540
Record of Revisions
Location BECO # Rev. # Publish Date Revision Description
THIS PAGE INTENTIONALLY LEFT BLANK
TABLE OF CONTENTS
CHAPTER 1 – FIRE DAMPERS
INSTALLATION OPERATION & MAINTENANCE MANUAL .................................................... 1-1 Receiving and Handling ..................................................................................... 1-1 Safety Warning ................................................................................................... 1-1 General Information ............................................................................................ 1-2 Pre-Installation Guidelines ................................................................................. 1-2 Preparation of Openings .................................................................................... 1-3 Clearances Required between Damper Sleeves & Wall/Floor Openings .......... 1-4 Installing Multiple Section Assemblies ............................................................... 1-5 Maximum Assembly Tables ............................................................................... 1-5 Sleeve Requirements ......................................................................................... 1-6 Securing the Damper/Sleeve Assembly to Wall/Floor Openings ....................... 1-7 Duct to Sleeve Connection ............................................................................... 1-10 Damper Maintenance ....................................................................................... 1-12 Damper Troubleshooting .................................................................................. 1-12
CHAPTER 2 – FIRE / SMOKE DAMPERS
INSTALLATION, OPERATION & MAINTENANCE MANUAL ................................................... 2-1 Receiving & Handling ......................................................................................... 2-1 Safety Warning ................................................................................................... 2-1 General Information ............................................................................................ 2-2 Electrical Guidelines ........................................................................................... 2-2 Pre-Installation Guidelines ................................................................................. 2-2 Preparation of Openings .................................................................................... 2-3 Clearances Required between Damper Sleeves & Wall/Floor Openings .......... 2-4 Installing Multiple Damper Section Assemblies ................................................. 2-5 Maximum Assembly Tables ............................................................................... 2-5 Inserting Damper into Wall/Floor Openings ....................................................... 2-6 Securing the Damper/Sleeve Assembly to Wall/Floor Openings ....................... 2-7 Duct to Sleeve Connection ................................................................................. 2-9 Actuator & Temperature Response Device Connections ................................ 2-11 Maintenance ..................................................................................................... 2-12 Troubleshooting ................................................................................................ 2-12
CHAPTER 3 – ACTUATORS FOR FIRE / SMOKE DAMPERS
GND SERIES ACTUATOR: INSTALLATION, OPERATION & MAINTENANCE MANUAL ...... 3-1 Instructions ......................................................................................................... 3-1
HONEYWELL FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE .... 3-3
Application .......................................................................................................... 3-3 Fire Code References and Information .............................................................. 3-3 Replacement Guidelines – Actuator Specifications ........................................... 3-3 Replacement Guidelines – Applications ............................................................. 3-3 Replacement Guidelines – Damper Manufacturer’s Guidelines ........................ 3-4 Maintenance Information .................................................................................... 3-4 Product Information ............................................................................................ 3-5 Installation and Wiring ........................................................................................ 3-6
Rev. Oct/16 Book 540
CHAPTER 4 – BACKDRAFT DAMPERS
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS ................................. 4-1
Receiving and Handling ..................................................................................... 4-1 Safety Warning ................................................................................................... 4-1 Instructions ......................................................................................................... 4-1 Damper Maintenance ......................................................................................... 4-2 Counterbalance Adjustment Instructions ........................................................... 4-2 Standard Components ....................................................................................... 4-3
MANUFACTURER’S LETTER: BACKDRAFT DAMPER – NFPA130 ....................................... 4-4
CHAPTER 5 – WARRANTY
WARRANTY .............................................................................................................................. 5-1
LIST OF FIGURES
CHAPTER 1: Figure 1: Frame Wall Openings ......................................................................... 1-3 Figure 2: Frame Wall Openings (Metal Stud Only) ............................................ 1-3 Figure 3: Opening Between Studs (Wooden Construction) ............................... 1-3 Figure 4: Opening Between Studs (Metal Stud Construction) ........................... 1-3 Figure 5: Installing Multiple Section Assemblies ................................................ 1-5 Figure 6: Field Attachment of Fire Dampers to Sleeves .................................... 1-6 Figure 7: Two Sided Angle Installation ............................................................... 1-7 Figure 8: Single Side Angle with Steel Stud Wall – Angle over Wallboard ........ 1-8 Figure 9: Single Side Angle with Wood Stud Wall ............................................. 1-8 Figure 10: Single Side Angle with Steel Stud Wall – Angle over Wallboard ...... 1-8 Figure 11: Single Side Angle with Masonry or Concrete Wall & Floor ............... 1-8 Figure 12: Wood Stud – Grille ............................................................................ 1-8 Figure 13: Metal Stud – Grille............................................................................. 1-8 Figure 14: Damper/Sleeves with Transition ....................................................... 1-9 Figure 15: Transverse Joints ............................................................................ 1-10 Figure 16: Drive Slip Joint ................................................................................ 1-10 Figure 17: Type R and O Transition ................................................................. 1-11 Figure 18: Approved Breakaway Connections Installation Detail .................... 1-11 Figure 19: Typical TDC/TDF Joint .................................................................... 1-11 Figure 20: Clip Spacing .................................................................................... 1-11 Figure 21: Fasten Corner Pieces with Metal Bolts & Nuts ............................... 1-11 Figure 22: Transfer Opening or No Connecting Duct ...................................... 1-12
Book 540 Rev. Oct/16
CHAPTER 2: Figure 1: Frame Wall Openings ......................................................................... 2-3 Figure 2: Frame Wall Openings (Metal Stud Only) ............................................ 2-3 Figure 3: Opening Between Studs (Wooden Stud Construction)....................... 2-3 Figure 4: Opening Between Studs (Metal Stud Construction) ........................... 2-3 Figure 5: Single Sleeve around Outside with Support Mullion ........................... 2-5 Figure 6: Two Individually Sleeved Units with No Mullions ................................ 2-5 Figure 7: Properly Installation Combination Fire Smoke Damper ...................... 2-6 Figure 8: Two Sided Angle Installation Method.................................................. 2-7 Figure 9: Single Side Angle with Steel Stud Wall – Angle over Wallboard ........ 2-8 Figure 10: Single Side Angle with Wood Stud Wall ........................................... 2-8 Figure 11: Single Side Angle with Steel Stud Wall – Angle under Wallboard .... 2-8 Figure 12: Single Side Angle with Masonry or Concrete Wall & Floor ............... 2-8 Figure 13: Wood Stud – Grille ............................................................................ 2-8 Figure 14: Metal Stud – Grille............................................................................. 2-8 Figure 15: Transverse Joints .............................................................................. 2-9 Figure 16: Drive Slip Joint .................................................................................. 2-9 Figure 17: Type R and O Transition ................................................................. 2-10 Figure 18: Approved Breakaway Connections Installation Detail .................... 2-10 Figure 19: Typical TDC/TDF Joint .................................................................... 2-10 Figure 20: Clip Spacing .................................................................................... 2-10 Figure 21: Fasten Corner Pieces with Metal Bolts & Nuts ............................... 2-10 Figure 22: NOT APPLICABLE.......................................................................... 2-11 Figure 23: NOT APPLICABLE.......................................................................... 2-11 Figure 24: NOT APPLICABLE.......................................................................... 2-11 Figure 25: Temperature Response Device Connections: TOR ....................... 2-11
CHAPTER 3: GND SERIES ACTUATOR: INSTALLATION, OPERATION & MAINTENANCE MANUAL
Figure 1: Siemens Series Internal Mount (exploded view) ................................ 3-1 HONEYWELL FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE
Figure 1: Typical Fire and Smoke Damper Assembly ........................................ 3-4 Figure 2: Dimensions for MS4104 Series Actuators .......................................... 3-6 Figure 3: NOT APPLICABLE.............................................................................. 3-6 Figure 4: NOT APPLICABLE.............................................................................. 3-7 Figure 5: Typical 120 Vac wiring ........................................................................ 3-7 Figure 6: NOT APPLICABLE.............................................................................. 3-7 Figure 7: NOT APPLICABLE.............................................................................. 3-7 Figure 8: NOT APPLICABLE.............................................................................. 3-7 Figure 9: NOT APPLICABLE.............................................................................. 3-7
CHAPTER 4:
None CHAPTER 5:
None
Rev. Oct/16 Book 540
LIST OF TABLES
CHAPTER 1: None
CHAPTER 2:
None CHAPTER 3: GND SERIES ACTUATOR: INSTALLATION, OPERATION & MAINTENANCE MANUAL
None HONEYWELL FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE
Table 1: Fire and Smoke Cross Reference ........................................................ 3-5 CHAPTER 4:
None CHAPTER 5:
None
END OF TABLE OF CONTENTS
Book 540 Rev. Oct/16
TABLE OF CONTENTS
CHAPTER 1 – FIRE DAMPERS
INSTALLATION OPERATION & MAINTENANCE MANUAL .................................................... 1-1 Receiving and Handling ..................................................................................... 1-1 Safety Warning ................................................................................................... 1-1 General Information ............................................................................................ 1-2 Pre-Installation Guidelines ................................................................................. 1-2 Preparation of Openings .................................................................................... 1-3 Clearances Required between Damper Sleeves & Wall/Floor Openings .......... 1-4 Installing Multiple Section Assemblies ............................................................... 1-5 Maximum Assembly Tables ............................................................................... 1-5 Sleeve Requirements ......................................................................................... 1-6 Securing the Damper/Sleeve Assembly to Wall/Floor Openings ....................... 1-7 Duct to Sleeve Connection ............................................................................... 1-10 Damper Maintenance ....................................................................................... 1-12 Damper Troubleshooting .................................................................................. 1-12
LIST OF FIGURES
CHAPTER 1: Figure 1: Frame Wall Openings ......................................................................... 1-3 Figure 2: Frame Wall Openings (Metal Stud Only) ............................................ 1-3 Figure 3: Opening Between Studs (Wooden Construction) ............................... 1-3 Figure 4: Opening Between Studs (Metal Stud Construction) ........................... 1-3 Figure 5: Installing Multiple Section Assemblies ................................................ 1-5 Figure 6: Field Attachment of Fire Dampers to Sleeves .................................... 1-6 Figure 7: Two Sided Angle Installation ............................................................... 1-7 Figure 8: Single Side Angle with Steel Stud Wall – Angle over Wallboard ........ 1-8 Figure 9: Single Side Angle with Wood Stud Wall ............................................. 1-8 Figure 10: Single Side Angle with Steel Stud Wall – Angle over Wallboard ...... 1-8 Figure 11: Single Side Angle with Masonry or Concrete Wall & Floor ............... 1-8 Figure 12: Wood Stud – Grille ............................................................................ 1-8 Figure 13: Metal Stud – Grille............................................................................. 1-8 Figure 14: Damper/Sleeves with Transition ....................................................... 1-9 Figure 15: Transverse Joints ............................................................................ 1-10 Figure 16: Drive Slip Joint ................................................................................ 1-10 Figure 17: Type R and O Transition ................................................................. 1-11 Figure 18: Approved Breakaway Connections Installation Detail .................... 1-11 Figure 19: Typical TDC/TDF Joint .................................................................... 1-11 Figure 20: Clip Spacing .................................................................................... 1-11 Figure 21: Fasten Corner Pieces with Metal Bolts & Nuts ............................... 1-11 Figure 22: Transfer Opening or No Connecting Duct ...................................... 1-12
LIST OF TABLES
CHAPTER 1: None
END OF TABLE OF CONTENTS
Rev. Oct/16 Book 540
HVAC DUCTS CASINGS - PRODUCT INFORMATION PAGE
Equipment Description: Fire Dampers
Equipment Identification: None
Equipment Manufacturer:
Greenheck
1100 Greenheck Dr., Schofield, WI 54476
(715) 359-6171
Equipment Make / Model: SSDFD-150 & DFD-150
Location of Equipment: Berryessa & Milpitas Stations
Filter Sizes & Quantity: Not Applicable for this Equipment
Service Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Dealer Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Valve Number: Not Applicable for this Equipment
Valve Type: Not Applicable for this Equipment
Valve Size: Not Applicable for this Equipment
Valve Location: Not Applicable for this Equipment
Valve Function: Not Applicable for this Equipment
Damper Certification & Verification: UL 555
Domestic Water System Cleaning & Disinfection Test
Results & Report:Not Applicable for this Equipment
Air & Water System Balance Report: Not Applicable for this Equipment
Controls Operation & Maintenace Data with Wiring
Diagrams:Not Applicable for this Equipment
Approved Seismic Calculations: Not Applicable for this Equipment
Warranties See Chapter 5
Book 540 Rev. Oct/16
481324 Curtain Fire Dampers®
Document number 481324 CURTAIN FIRE DAMPERS
DFD, DFD-150X, FD, FD-150X, SSDFD, SSFD, AND KFD Series 11⁄2 and 3 Hour Curtain Fire Dampers
Vertical and Horizontal Mount
Installation, Operation and Maintenance ManualPlease read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
These instructions apply to 11⁄2 and 3 hour rated fire dampers mounted (blades must be horizontal) in: 1) masonry, block, or stud walls and 2) concrete floors. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL 555.
Note: Fire dampers are manufactured and labeled for either vertical or horizontal installation. The dampers must be installed in accordance with labeling.
Receiving and HandlingUpon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).
Safety WarningImproper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
This manual is the property of the owner and is required for future maintenance. Please leave it with the owner when the jobs is complete.
®
Rev. Oct/16 Book 5401-1
55"”§€”'J',E9f‘
[ l
J7
481324 Curtain Fire Dampers ®
General Information
Installation SupplementsRefer to the appropriate Greenheck installation supplements for special requirements:
• Closed Indicator Switch • Concrete Floor with Steel Deck • Drive Slip Breakaway Connection • Field Installed Sleeve • Fire Resistant Ventilated Duct Assembly • Firestop Material • Fusible Link Replacement • Grille Installation • Metal Stud in Shaftwall Partition • Non-Concrete Horizontal Mount • Quick Connect Breakaway Connection • Sealant Supplement • Single Side Retaining Angle • Single 3-Sided Retaining Angle Supplement • Sleeve Extension • Support Mullions
Installation supplements available at www.greenheck.com.
“UL CLASSIFIED (see complete marking on product)”“UL CLASSIFIED to Canadian safety standards (see complete marking on product)” Standard 555 (Listing #R13317)
The following items will aid in completing the damper installation in a timely and effective manner.
1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place and has not activated. Never install a fire damper without the proper UL approved fusible link in place. Visually inspect the link to verify its not damaged. Replace link as necessary.
2) Lift or handle damper using sleeve or frame. Do not lift damper using blades.
3) Dampers have a label indicating the required mounting orientation. Care must be taken to ensure that the indicated orientation is adhered to.
4) Damper must be installed into duct or opening square and free of twist or other misalignment.
5) Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to:
a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray
6) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper.
7) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles.
8) ACCESS: Suitable access (such that the fusible link may be removed and the damper's blade stack may be reset, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).
9) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
Pre-Installation Guidelines
Book 5401-2
Rev. Oct/16
481324 Curtain Fire Dampers®
Preparation of Openings
• Frame wall openings as shown below (see Figure 1 & 2).
• Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening.
• Prepare opening between studs and sleeve assembly as shown below (see Figure 3 & 4).
• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes.
Figure 1
12 in.
24 in. o.c.Maximum
Floor Runner
Ceiling Runner24 in. o.c.Maximum
(metal studs)
24 in. o.c.Maximum
(metal studs)
16 in. o.c.Maximum
(wood studs)
16 in. o.c.Maximum
(wood studs)
2 in. (51mm)
2 in. (51mm)
2 Panhead Screws
Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller.
Figure 2
Second set of studs are not required on openings36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
Second set of studs are not required on openings36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,gypsum wallboard must coverall wood stud surfaces.
Gypsum Wallboard
Stud or Runner
RetainingAngle
1 in. Min.
DamperSleeve
In metal stud construction,exposed steel surfaces neednot be covered with gypsumwallboard.
Gypsum Wallboard
Stud or Runner
RetainingAngle
1 in. Min.
DamperSleeve
Figure 3 (2 sided angle installation shown)
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,gypsum wallboard must coverall wood stud surfaces.
Gypsum Wallboard
Stud or Runner
RetainingAngle
1 in. Min.
DamperSleeve
In metal stud construction,exposed steel surfaces neednot be covered with gypsumwallboard.
Gypsum Wallboard
Stud or Runner
RetainingAngle
1 in. Min.
DamperSleeve
Figure 4 (2 sided angle installation shown)
Rev. Oct/16 Book 5401-3
iii” \ H ”\Q Q UH/\¢§
l- -I\ I\ /
__ ()+ A—A
NNNNNed ,Z ‘ ‘Piece / \Bent \
O
//
AA
Ceilingnnnner
nnnnerH H /H\
/\ /
M t I StudF g Sh
Detail
A;W
44
X X
U?/J+ Ii Lil
481324 Curtain Fire Dampers ®
Clearances Required Between Damper Sleeves & Wall/Floor Openings
Two-sided Angle InstallationTwo sided angle installations require clearances for thermal expansion between the damper sleeve and the wall/floor opening. The minimum required clearances are:
• For galvanized steel fire dampers and sleeves: 1⁄8 in. per foot (3mm per .3 m) of damper width and 1⁄8 in. per foot (3mm per .3 m) height with a minimum clearance of 1⁄4 in. (6mm), maximum of 11⁄2 in. (38mm).
• For stainless steel fire/smoke dampers and stainless steel or galvanized sleeves: 3⁄16 in. per foot (5mm per .3 m) of damper width and height with a minimum clearance of 1/4 in. (6mm), maximum of 2 in. (51mm).
These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper.
Although the minimum requirements are listed above, for ease of installation the following are the recommended clearances for galvanized dampers:
• Width/Height of 48 in. (1219 mm) or less - 1⁄2 in. (13mm) clearance
• Width/Height between 48.01 in. (1220 mm) and 96 in. (2438 mm): 1 in. (25mm) clearance
• Width/Height greater than 96 in. (2438 mm): 11⁄2 in. (38 mm) clearance
Example: A 12 in. x 12 in. (305mm x 305mm) will
require a minimum clearance of 1/4 in. (6mm) width and 1/4 in. (6mm) on height
A 48 in. x 12 in. (1219mm x 305mm) damper will required a minimum clearance of 1⁄2 in. (13mm) on width and 1/4 in. (13mm) on height.
Single Side Angle Installation
On vertical mount single side angle installations there are no minimum clearance requirements between the wall opening and the damper sleeve. However, to facilitate installation, clearances between the wall opening and the damper sleeve are recommended.
On horizontal mount single side angle installations a minimum clearance is required between the outside of the damper sleeve and the floor opening of 1⁄8 in. per foot (3mm per .3m) of damper width and 1⁄8 in. per foot (3mm per .3m) height with a minimum clearance of 1/4 in. (6mm).
Book 5401-4
Rev. Oct/16
481324 Curtain Fire Dampers®
Maximum Assembly TablesWhen multiple sections are shipped unassembled, installer shall fasten dampers together. The table shows maximum sizes for multiple section dampers. Dampers that are two or more sections tall must be factory assembled. Note: All dimensions are shown in inches (W x H). * Sizes listed is the damper size, not transition size.
Damper Model MountingMaximum Single
Section Damper Sizes*Maximum Multi-Section
Damper Sizes*
FD-100 , FD-300, FD-310, SSFD-350 Vertical 48 X 48 (1219mm x 1219mm) -
FD-150 Vertical or Horizontal 48 X 48 (1219mm x 1219mm)96 x 48 (2438mm x 1219mm) or120 x 40 (3048mm x 1016mm)
FD-110 Vertical or Horizontal 48 x 48 (1219mm x 1219mm) 96 x 48 (2438mm x 1219mm)
SSFD-150Vertical 48 X 48 (1219mm x 1219mm)
96 X 48 (2438mm x 1219mm) or 120 X 40 (3048mm x 1016mm)
Horizontal 36 x 36 (914mm x 914mm) -
FD-350Vertical 48 x 48 (1219mm x 1219mm) -
Horizontal 40 x 40 (1016mm x 1016mm) 80 x 40 (2032mm x 1016mm)
KFD-150 Vertical or Horizontal 36 x 16 (914mm x 406mm)96 x 48 (2438mm x 1219mm) or120 x 40 (3048mm x 1016mm)
KFD-110 Vertical or Horizontal 36 x 16 (914mm x 406mm) 96 x 48 (2438mm x 1219mm)
SSKFD-150 Vertical 36 x 16 (914mm x 406mm)96 X 48 (2438mm x 1219mm) or 120 X 40 (3048mm x 1016mm)
KFD-350Vertical 36 x 16 (914mm x 406mm) -
Horizontal 36 x 16 (914mm x 406mm) 80 x 40 (2032mm x 1016mm)
SSKFD-350 Vertical 36 x 16 (914mm x 406mm) -
DFD-150, DFD-110
Vertical 36 x 36 (914mm x 914mm)72 x 48 (1828mm x 1219mm) or60 x 60 (1524mm x 1524mm) or
120 x 30 (3048mm x 762mm)
Horizontal24 x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm)
30 x 30 (762mm x 762mm) -
DFD-350
Vertical 36 x 36 (914mm x 914mm) -
Horizontal24 x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm)
30 x 30 (762mm x 762mm)
DFD-310Vertical 36 x 36 (914mm x 914mm) -
Horizontal 30 x 30 (762mm x 762mm) -
SSDFD-110, SSDFD-150. SSDFD-350 Vertical 30 x 30 (762mm x 762mm) -
FD-150X Vertical or Horizontal 48 x 48 (1219mm x 1219mm) -
DFD-150XVertical 36 x 36 (914mm x 914mm) -
Horizontal 30 x 30 (762mm x 762mm) -
Installing Multiple Section Assemblies
A damper assembly is not restricted to a maximum number of sections, but must not exceed the section sizes and overall sizes shown (see chart below).
The damper sections must be attached together with #10 (3/4 in. max. [19mm]) sheet metal screws, 1/4 in. (6mm) diameter nuts and bolts, tack or spot welds, or 3⁄16 in. (48mm) diameter steel pop rivets. Attachments must be spaced a maximum of 6 in. (152mm) on centers and a maximum of 2 in. (51mm) from corners. Attachments must be made on front face and back face (air entering and air exiting side) of damper sections.
Attachments--Do not place attachments between blade channels
Blade Channel
Figure 5
Rev. Oct/16 Book 5401-5
i~ P T J Q K
:’>.
D !|,I D
/ V
481324 Curtain Fire Dampers ®
Sleeve Requirements
Attachments--Do not place attachments between blade channels
Blade Channel
2 in. Max.
6 in. Max.Attachments can be staggered or evenlyspaced.
NOTE: Attachments must not enter blade channel or they may cause interference with blade closure. Narrow Line and Ultra Thin dampers do not have flange for attachments and must be welded to sleeve.
Figure 6: Field attachment of fire dampers to sleeves.
All fire dampers must be installed in a steel sleeve of the required gauge and length. Note that DFD-150X and FD-150X series dampers are provided with an integral sleeve. See Table on page 10 for required minimum sleeve gauges. Maximum sleeve thickness is 10 gauge (3.5mm). Sleeve inside dimensions must equal damper outside dimensions.
Sleeves shall extend a maximum of 6 in. (152mm) beyond the wall or floor opening on each side. When a factory mounted access door is incorporated as a part of the sleeve the sleeve may extend a maximum of 16 in. (406mm) beyond the wall or floor opening on the access door side.
Fire dampers must be attached to sleeves as shown in Figure 6. All four sides of the damper frame must be attached to the sleeve with one row of attachments on each side of the blade channel. Attachments must be spaced a maximum of 6 in. (152mm) on centers and a maximum of 2 in. (51mm) from corners. A minimum of 4 attachments (2 on each side of the blade channel) per side (16 per damper) are required. One of the methods of attachment shown below must be used:
• tack or spot welds • #10 sheet metal screws • 1⁄4 in. (6mm) bolts and nuts • 3⁄16 in. (4.7mm) steel pop rivets
Book 5401-6
Rev. Oct/16
_'|||‘q’|||||‘q_||||q'_||||||‘u_|||||q'_|’’‘I__:‘z‘z‘z_’IIIIIIIIIIIIIIIIIIIIIII-1°’2'_”””
’
+’
__'
‘’
’’’
V+
OW"/7¢ file!VIlllllhll||.|__||||||._d__’/C”
’¢'5'5'5¢
‘MyifI
5
IIIIIIIIIIIIIl:IIIcI‘IIII'
6’Flwll/7lI
IIII.IIIIIIlllllollllllblllllloll
llIf
481324 Curtain Fire Dampers®
All fire dampers may utilize the two sided angle installation method described below. 11⁄2 hour rated fire dampers may use the single sided angle installation method up to the following maximum sizes:
• Vertical mount: 80 in. W x 50. in. H (2032mm W x 1270mm H), 50 in. W x 80 in. H (1270mm W x 2032mm H), or 40 in. W x 100 in. H (1016mm W x 2540mm).
• Horizontal mount: 144 in. W x 96 in. H (3658mm W x 2438mm H)
• Retaining Angle Gauge: Retaining angles for 11⁄2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm).
• Retaining Angle Size: The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm).
• Retaining Angle Attachment to Sleeve: Retaining angles must be attached to the damper using one or more of the following methods of attachment (refer to label on outside of sleeve for ‘No Screw’ area):
- Tack or spot welds - #10 (3⁄4 in. [19mm] max.) sheet metal screws - 1⁄4 in. (6mm) bolts and nuts - 3⁄16 in. (5mm) steel pop rivets
A minimum of two connections per side, top, and bottom, 12 in. (305mm) O.C. maximum for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers greater than 48 in. wide (1219mm) or 36 in. high (914mm) require the connections to be no more than 6 in. (152mm) O.C.
The angles must be attached to all 4 sides of the sleeve. Ensure that fasteners do not interfere with the operation of the damper. The angles need not be attached to each other at the corners.
• Retaining Angle Attachment to Wall/Floor:
Two sided Angle Method: For two sided angle installations the retaining angles shall not be attached to the wall/floor (see Figure 7).
Single Sided Angle Method: For single side installations the retaining angles must be attached to the wall/floor (see Figures 8-11). For metal stud partitions only, the single-side mounting angle may be directly attached to the metal stud prior to the installation of the drywall.
• Retaining angles must be attached to the partition using one of the methods shown below:
- Drywall screws of a length such that the screw engages the steel stud/track by 1⁄2 in. (13mm) (steel framing).
- Drywall screws of a length such that the screw engages the wood stud by 13/4 in. (44mm) (wood framing).
- Steel anchors or self tapping concrete screws penetrating masonry or block 11/4 in. (31mm).
• A minimum of two connections per side are required. Additional connections made at a maximum of 12 in. (305mm) O.C. maximum for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers greater than 48 in. wide (1219mm) or 36 in. high (914mm) require the connections to be no more than 6 in. (152mm) O.C.
Securing the Damper/Sleeve Assembly to Wall/Floor Openings
2 in. Max.
6 in. Max.
Sleeve
RetainingAngle
Damper
Duct
Min. 1 in.Overlap*
Wall orFloor
RetainingAngle
*only applicable for damper sizes above 36 in. x 36 in.
6 in. Max.
2 in. Max.
Figure 7: Two Sided Angle Installation
Rev. Oct/16 Book 5401-7
$
4/
\ l
E
481324 Curtain Fire Dampers ®
Securing the Damper/Sleeve Assembly to Wall/Floor Openings cont.......
Damper Sleeve
Angle Fastener
2 1/2 in. min.Stud or Runner
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Figure 8: Single Side Angle With Steel Stud Wall - Angle Over Wallboard
Damper Sleeve
2 1/2 in. min.Metal Studor Runner
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Figure 10: Single Side Angle With Steel Stud Wall - Angle Under Wallboard
2 1/2 in. Min.Stud or Runner
DamperSleeve
Angle Fastener
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Figure 9: Single Side Angle With Wood Stud Wall
Masonry orConcreteWall
DamperSleeve
Angle Fastener
Masonry orConcrete Floor
DamperSleeve
Angle Fastener
Top Side
Figure 11: Single Side Angle With Masonry or Concrete Wall and Floor
Grille Installations (Dampers up to 36 in. x 36 in. [914mm x 914mm])Retaining angles used in conjunction with grille installations must be a minimum of 5⁄8 in. x 1 in. (15mm x 25mm) 16 gauge (1.5mm) steel. Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side). See Figure 12 and Figure 13.
Note: Screws used to attach grille are allowed to penetrate reversed angle leg.
DamperSleeve
Angle Fastener
Grille (suppliedby others)
#10 sheet metal screwsspaced 6 in. on centerand a maximum of 2 in.from the corners(minimum of 2 screws perside). Screw into studs soas to avoid spaceconflicts with the grille
2 1/2 in. Min.Stud or Runner
Retaining Angle/Flange
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Figure 13: Metal Stud - Grille
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Grille (supplied by others)Retaining Angle
Angle Fastener
Damper Sleeve
#10 sheet metal screws, 2 1/2 inches long, spaced 6 in. on center and amaximum of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conflicts with the grille.
2 1/2 in. minimumStud or Runner
Figure 12: Wood Stud - Grille
Book 5401-8
Rev. Oct/16
fix
4/_
%\
X
/
‘L
XQ” ix\E\\\\\\\\\\
X
—\AW
i\ K1
/ j‘W U
481324 Curtain Fire Dampers®
Securing the Damper/Sleeve Assembly to Wall/Floor Openings cont.......
1/4 in. minimumtotal clearance
Wall or Floor
Maximum 6 in.
Maximum 6 in.
Duct
Duct
Duct
Damper
Damper
Damper
Wall or Floor
Wall or Floor
Retaining Angles
Type A
Type B
On types R, CO & CR factoryfurnished duct collarqualifies as breakaway connection.
Type C, CO, CR, & R
Factory or Field installed Sleeve
1/4 in. minimumtotal clearance
Wall or Floor
Maximum 6 in.
Maximum 6 in.
Duct
Duct
Duct
Damper
Damper
Damper
Wall or Floor
Wall or Floor
Retaining Angles
Type A
Type B
On types R, CO & CR factoryfurnished duct collarqualifies as breakaway connection.
Type C, CO, CR, & R
Factory Sleeve
Type B2
Type B2
Wall or floor
Damper
Sleeve
Wall or floor
Damper
Sleeve
Factory Sleeve
Damper
1/4 in. minimumtotal clearance(See Section 1)
Maximum 6 in.
Maximum 6 in.
Wall or floor
Wall or floor
Wall or floor
Damper
Damper
Duct
Duct
Duct
Retaining Angles(See Section 4)
Sleeve(See Sleeve Requirements)
Sleeve
Sleeve
On types R & CR factoryfurnished duct collarqualifies as breakawayconnection (See Connecting Ducts to Fire Damper Sleeve)
1 in. min. overlapFour sides
Mounting Angles(See Para. 4)
1/4 in. minimum total clearance(See Para. 1)
Retaining angle leg shall not exceed 7 in. (178mm)
Type A
Type B
Type C, CO, CR & R
Field Installed Sleeve
Damper
1/4 in. minimumtotal clearance(See Section 1)
Maximum 6 in.
Maximum 6 in.
Wall or floor
Wall or floor
Wall or floor
Damper
Damper
Duct
Duct
Duct
Retaining Angles(See Section 4)
Sleeve(See Sleeve Requirements)
Sleeve
Sleeve
On types R & CR factoryfurnished duct collarqualifies as breakawayconnection (See Connecting Ducts to Fire Damper Sleeve)
1 in. min. overlapFour sides
Mounting Angles(See Para. 4)
1/4 in. minimum total clearance(See Para. 1)
Retaining angle leg shall not exceed 7 in. (178mm)
Type A
Type B
Type C, CO, CR & RField installed SleeveFactory Sleeve
1/4 in. minimumtotal clearance
Wall or Floor
Maximum 6 in.
Maximum 6 in.
Duct
Duct
Duct
Damper
Damper
Damper
Wall or Floor
Wall or Floor
Retaining Angles
Type A
Type B
On types R, CO & CR factoryfurnished duct collarqualifies as breakaway connection.
Type C, CO, CR, & R
Figure 14: Damper/Sleeves with Transition
Rev. Oct/16 Book 5401-9
wkW gmifig
481324 Curtain Fire Dampers ®
Duct to Sleeve Connection
Sleeve Gauge and Connection Type Requirements
Sleeve Gauge Duct Dimension
Type of Duct to Sleeve
Connection Permitted
14 ga. (0.075 in.) - 10 ga. (0.138
in.)[2mm - 3.5mm]
All duct sizesRigid or
Breakaway
16 ga. (0.060 in.)[1.5mm]
36 in. (914mm) max. width24 in. (610mm) max.
height24 in. (610mm) diameter
Rigid or Breakaway
16 ga. (0.060 in.)[1.5mm]
All duct sizes
Breakaway only
18 ga. (0.048 in.)[1.2mm]
85 in. (2159mm) wide and over
20 ga. (0.036 in.)[0.9mm]
55 in. - 84 in. wide(1397mm - 2134mm)
22 ga. (.030 in.)[0.76mm]
31 in. - 54 in. wide(787mm - 1372mm)
24 ga. (0.024)[0.6mm]
13 in. - 30 in. wide(330mm - 762mm)
26 ga. (0.018 in.)[0.46mm]
12 in. wide and under(305mm)
See Breakaway Connection section for additional information.UL Standard 555 requires all ducts to terminate at fire damper sleeves.
Approved Breakaway ConnectionsAll breakaway connections described below may utilize the following duct sealants: PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie, Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.
Transverse JointsThe transverse joints shown below are approved as breakaway connections.
• A maximum of two #10 (19mm) sheet metal screws on each side and on the bottom may be used. The screws should be located in the center of the slip pocket and penetrate both sides of the slip pocket.
• Dampers up to 20 inches (508mm) high may use transverse joints on the top and bottom and Drive Slip joints (see Figure 16) on the sides.
Plain “S” Slip Hemmed “S” Slip Double “S” Slip
Inside Slip Joint Standing “S” Standing “S” (Alt.)
Standing “S” (Alt.) Standing “S” Standing “S” (Bar Reinforced) (Angle Reinforced)
Figure 15 - Transverse Joints
Drive Slip Joint
Figure 16
The size of the damper/duct determines the required sleeve gauge and the required duct to sleeve connection (see table to the right). The sleeve thickness must also not be less than the gauge of the connecting duct. Any duct connection other than the breakaway connections described below are considered rigid.
Book 5401-10
Rev. Oct/16
%33%in?ii
481324 Curtain Fire Dampers®
Duct to Sleeve Connection cont....
DuctSleeve
6 in.
Std. ClipLength
CLDuct
60 in. Duct4 Req’d.
48 in. Duct3 Req’d.
36 in. Duct3 Req’d.
24 in. Duct2 Req’d.
18 in. Duct &Smaller1 Req’d.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.9 in.
7 in.7 in.
5 in. 5 in.
5 in.5 in.
Figure 20
Duct EndFlange
Corner Piece
3/8 in. bolt (optional)
Figure 21
Proprietary Flange System Breakaway Connections(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF addendum to the SMACNA Duct Construction. Standard 6 in. (152mm) metal clip may be used with spacing as shown in diagram (see Figure 19 & 20). 33⁄8 in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces (see Figure 21).
DuctSleeve
6 in.
Std. ClipLength
CLDuct
60 in. Duct4 Req’d.
48 in. Duct3 Req’d.
36 in. Duct3 Req’d.
24 in. Duct2 Req’d.
18 in. Duct &Smaller1 Req’d.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.9 in.
7 in.7 in.
5 in. 5 in.
5 in.5 in.
Figure 19
Round and Oval Duct Breakaway ConnectionsRound or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19mm) sheet metal screws as follows:
• Ducts up to 22 in. (558mm) wide (or dia.) and less shall have three screws.
• Ducts larger than 22 in. (558mm) wide (or dia.) up to and including 36 in. (914mm) wide (or dia.) shall have five screws.
Factory furnished duct collars, type R and O, are also considered breakaway (see Figure 17).
Fire Damper Sleeve
Neoprene or Butyl gasketbetween all angles
Flanged system angles
(Attach permanufacturer'sinstructions)
Duct
3/8 in. bolts incorners are optional
6 in. long metal cleat or 1/16 in.max. thickness plastic cleat;12 in. c-c (min. 1 per side)
Figure 18
Wall or Floor
Sleeve
Duct Damper
Type B
Wall or Floor
Sleeve
Duct Damper
Type R, O
Type R and Ofactory furnishedduct collars qualifyas breakawayconnections.
Figure 17: Type R and O Transition
Manufactured Flanged System Breakaway ConnectionsFlanged connection systems manufactured by Ductmate, Durodyne, Ward, Nexus, Radiant T-35m, and MEZ are approved as breakaway connections when installed as illustrated (see Figure 18).
Rev. Oct/16 Book 5401-11
Z
7\\
@\flEWJF 1%?\/gm“W/
LAAiAA
X
U
HkjiflW__2__
AILFLL
Ll“
filfiflWa
Damper MaintenanceDampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Damper TroubleshootingThe following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not fully open and/or close
Frame is 'racked' causing blades to bind on jamb seals
Adjust frame such that it is square and plumb
Screws in damper linkage Damper installed too far into wall. Move out to line as designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see Damper Maintenance)
Link separated Heat Replace link
No Connecting Duct or Transfer OpeningOpenings where duct does not attach on either side will not require a breakaway connection. Transfer openings are typical of a non-ducted installation (see Figure 22).
• Sleeve may end flush with the rated wall/floor on both sides
• Refer to Securing the Damper/Sleeve Assembly to Wall/Floor Openings for securing retaining angles to the sleeve.
Figure 22: Transfer opening or no connecting duct
481324 • DFD DFD-X FD FD-X Rev. 1 December 2015 Copyright 2015 © Greenheck Fan Corporation
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.Specific Greenheck product warrantees can be located on greenheck.com within the product area tabs and listed in the Library under Warrantees.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com
Our Commitment
Book 5401-12
Rev. Oct/16
%
I I ~~ ::~=% | I~ :1| I II I |I ll ll IIll |||Ill |||Ill |||Ill |||
III! IIII_/' |Ill |||| L1
i_i\
‘Ii fi::§'§;Ifi {I LFLANGI I=|"l;;:_§§=—ll I I
E
GRILLE
IE1;“',. I3
El..-
@G”§€”'J',E¢,I‘
TABLE OF CONTENTS
CHAPTER 2 – FIRE / SMOKE DAMPERS
INSTALLATION, OPERATION & MAINTENANCE MANUAL ................................................... 2-1 Receiving & Handling ......................................................................................... 2-1 Safety Warning ................................................................................................... 2-1 General Information ............................................................................................ 2-2 Electrical Guidelines ........................................................................................... 2-2 Pre-Installation Guidelines ................................................................................. 2-2 Preparation of Openings .................................................................................... 2-3 Clearances Required between Damper Sleeves & Wall/Floor Openings .......... 2-4 Installing Multiple Damper Section Assemblies ................................................. 2-5 Maximum Assembly Tables ............................................................................... 2-5 Inserting Damper into Wall/Floor Openings ....................................................... 2-6 Securing the Damper/Sleeve Assembly to Wall/Floor Openings ....................... 2-7 Duct to Sleeve Connection ................................................................................. 2-9 Actuator & Temperature Response Device Connections ................................ 2-11 Maintenance ..................................................................................................... 2-12 Troubleshooting ................................................................................................ 2-12
LIST OF FIGURES
CHAPTER 2: Figure 1: Frame Wall Openings ......................................................................... 2-3 Figure 2: Frame Wall Openings (Metal Stud Only) ............................................ 2-3 Figure 3: Opening Between Studs (Wooden Stud Construction)....................... 2-3 Figure 4: Opening Between Studs (Metal Stud Construction) ........................... 2-3 Figure 5: Single Sleeve around Outside with Support Mullion ........................... 2-5 Figure 6: Two Individually Sleeved Units with No Mullions ................................ 2-5 Figure 7: Properly Installation Combination Fire Smoke Damper ...................... 2-6 Figure 8: Two Sided Angle Installation Method.................................................. 2-7 Figure 9: Single Side Angle with Steel Stud Wall – Angle over Wallboard ........ 2-8 Figure 10: Single Side Angle with Wood Stud Wall ........................................... 2-8 Figure 11: Single Side Angle with Steel Stud Wall – Angle under Wallboard .... 2-8 Figure 12: Single Side Angle with Masonry or Concrete Wall & Floor ............... 2-8 Figure 13: Wood Stud – Grille ............................................................................ 2-8 Figure 14: Metal Stud – Grille............................................................................. 2-8 Figure 15: Transverse Joints .............................................................................. 2-9 Figure 16: Drive Slip Joint .................................................................................. 2-9 Figure 17: Type R and O Transition ................................................................. 2-10 Figure 18: Approved Breakaway Connections Installation Detail .................... 2-10 Figure 19: Typical TDC/TDF Joint .................................................................... 2-10 Figure 20: Clip Spacing .................................................................................... 2-10 Figure 21: Fasten Corner Pieces with Metal Bolts & Nuts ............................... 2-10 Figure 22: NOT APPLICABLE.......................................................................... 2-11 Figure 23: NOT APPLICABLE.......................................................................... 2-11 Figure 24: NOT APPLICABLE.......................................................................... 2-11 Figure 25: Temperature Response Device Connections: TOR ....................... 2-11
LIST OF TABLES
CHAPTER 2: None
END OF TABLE OF CONTENTS
Rev. Oct/16 Book 540
HVAC DUCTS CASINGS - PRODUCT INFORMATION PAGE
Equipment Description: Fire / Smoke Dampers
Equipment Identification: None
Equipment Manufacturer:
Greenheck
1100 Greenheck Dr., Schofield, WI 54476
(715) 359-6171
Equipment Make / Model: SEFSD-211 & FSD-212
Location of Equipment: Berryessa & Milpitas Stations
Filter Sizes & Quantity: Not Applicable for this Equipment
Service Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Dealer Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Valve Number: Not Applicable for this Equipment
Valve Type: Not Applicable for this Equipment
Valve Size: Not Applicable for this Equipment
Valve Location: Not Applicable for this Equipment
Valve Function: Not Applicable for this Equipment
Damper Certification & Verification: UL 555 and/or UL 555S
Domestic Water System Cleaning & Disinfection Test
Results & Report:Not Applicable for this Equipment
Air & Water System Balance Report: Not Applicable for this Equipment
Controls Operation & Maintenace Data with Wiring
Diagrams:Not Applicable for this Equipment
Approved Seismic Calculations: Not Applicable for this Equipment
Warranties See Chapter 5
Book 540 Rev. Oct/16
481318 Multi-Blade Fire and Combination Fire Smoke Dampers®
Document 481318 MULTI-BLADE FIRE AND
COMBINATION FIRE SMOKE DAMPERSDFD-XXX, DFDAF-XXX, DFDTF-XXX, FSD-XXX, FSD-XXXV,
IMO-XXX,SEDFD-XXX, SEFSD-XXX, AND SSFSD-XXX 11⁄2 and 3 Hour Fire & Combination Fire Smoke Dampers
(with factory installed sleeve and actuator)Vertical and Horizontal Mount
Installation, Operation and Maintenance ManualPlease read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
These instructions apply to 11⁄2 and 3 hour rated fire and combination fire smoke dampers mounted in: 1) masonry, block, or stud walls and 2) concrete floors. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL 555 and/or UL 555S.Note: Combination fire smoke and fire dampers are manufactured and labeled for either vertical or horizontal installation. The dampers must be installed in accordance with labeling.
Receiving and HandlingUpon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).
This manual is the property of the owner and is required for future maintenance. Please leave it with the owner when the jobs is complete.
Safety WarningImproper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
®
Rev. Oct/16 Book 5402-1
55G”§€”'J',E¢,I‘
I I
E
7
481318 Multi-Blade Fire and Combination Fire Smoke Dampers ®
General Information
Installation SupplementsRefer to the appropriate Greenheck installation supplements for special requirements: • Concrete Floor with Steel Deck • Drive Slip Breakaway Connection • Field Installed Sleeve • Fire Resistant Ventilated Duct Assembly • Firestop Material • Fusible Link Replacement • Greenheck Test Switch • Grille Installation • Metal Stud in Shaftwall Partition • Non-Concrete Horizontal Mount • Open or Close Indicator (OCI) • Quick Connect Breakaway Connection • Resettable Link (RRL) • Resettable Link with Blade Indicator (RRL/OCI) • Sealant Supplement • Single 3-Sided Retaining Angle Supplement • Sleeve Extension • Smoke Detector - Various Types • Temperature Limited Override (TOR) • Tunnel CorridorInstallation supplements available at www.greenheck.com.
The following items will aid in completing the damper installation in a timely and effective manner.1) Check the drawings for proper damper locations
within the building. Visually inspect the damper for damage and verify that the Reusable Resettable Link (RRL) is in place and has not activated if provided. These electric links have a button for resetting. Visually inspect the link to verify its not missing or broken. Replace link as necessary.
2) Lift or handle damper using sleeve or frame. Do not lift damper using blades or actuators.
3) Damper has label on outside of sleeve indicating a ‘No Screw’ area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing.
4) Damper has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturer’s appropriate UL Classification file number.
5) Damper must be installed into duct or opening square and free of twist or other misalignment. Out of square, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design.
6) Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to:
a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray7) Damper should be sufficiently covered as to prevent
overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on the damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles.
9) ACCESS: Suitable access (such that RRL’s and actuators can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
Electrical GuidelinesAll wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications.
Important!Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation.
Electrical Guidelines
Pre-Installation Guidelines“UL CLASSIFIED (see complete marking on product)”“UL CLASSIFIED to Canadian safety standards (see complete marking on product)” Standard 555 & 555S (Listing #R13317)
Book 5402-2
Rev. Oct/16
481318 Multi-Blade Fire and Combination Fire Smoke Dampers®
Preparation of Openings
• Frame wall openings as shown below (see Figure 1 & 2).• Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening.• Prepare opening between studs and sleeve assembly as shown below (see Figure 3 & 4).• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance
Directory) and/or local codes.
Figure 1
12 in.
24 in. o.c.Maximum
Floor Runner
Ceiling Runner24 in. o.c.Maximum
(metal studs)
24 in. o.c.Maximum
(metal studs)
16 in. o.c.Maximum
(wood studs)
16 in. o.c.Maximum
(wood studs)
2 in. (51mm)
2 in. (51mm)
2 Panhead Screws
Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller.
Figure 2
Second set of studs are not required on openings36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
Second set of studs are not required on openings36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,gypsum wallboard must coverall wood stud surfaces.
Gypsum Wallboard
Stud or Runner
RetainingAngle
1 in. Min.
DamperSleeve
In metal stud construction,exposed steel surfaces neednot be covered with gypsumwallboard.
Gypsum Wallboard
Stud or Runner
RetainingAngle
1 in. Min.
DamperSleeve
Figure 3 (2 sided angle installation shown)
Metal Stud Construction
Wooden Stud Construction
In wood stud construction,gypsum wallboard must coverall wood stud surfaces.
Gypsum Wallboard
Stud or Runner
RetainingAngle
1 in. Min.
DamperSleeve
In metal stud construction,exposed steel surfaces neednot be covered with gypsumwallboard.
Gypsum Wallboard
Stud or Runner
RetainingAngle
1 in. Min.
DamperSleeve
Figure 4 (2 sided angle installation shown)
Rev. Oct/16 Book 5402-3
\L ~ \ I /\iiiii r19 I IA
rDetailA—A__ <>_.
FlooIN I /iiii6|’
NNNNNed ,Z ‘ ‘Piece /
\\
Io /
\ /
//
AA
% iy‘ \ /
Metal StudF aming Sh
XiX X
I@I1 Ii U
481318 Multi-Blade Fire and Combination Fire Smoke Dampers ®
Clearances Required Between Damper Sleeves & Wall/Floor Openings
Two-sided Angle InstallationTwo sided angle installations require clearances for thermal expansion between the damper sleeve and the wall/floor opening. The minimum required clearances are: • For galvanized steel fire dampers and sleeves: 1⁄8 in. per foot (3mm per .3 m) of damper width and 1⁄8 in. per
foot (3mm per .3 m) height with a minimum clearance of 1⁄4 in. (6mm), maximum of 11⁄2 in. (38mm). • For stainless steel fire/smoke dampers and stainless steel or galvanized sleeves: 3⁄16 in. per foot (5mm per
.3 m) of damper width and height with a minimum clearance of 1/4 in. (6mm), maximum of 2 in. (51mm).These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper.
Although the minimum requirements are listed above, for ease of installation the following are the recommended clearances for galvanized dampers:
• Width/Height of 48 in. (1219 mm) or less - 1⁄2 in. (13mm) clearance
• Width/Height between 48.01 in. (1220 mm) and 96 in. (2438 mm): 1 in. (25mm) clearance
• Width/Height greater than 96 in. (2438 mm): 11⁄2 in. (38 mm) clearance
Example: A 12 in. x 12 in. (305mm x 305mm) will
require a minimum clearance of 1/4 in. (6mm) width and 1/4 in. (6mm) on height
A 48 in. x 12 in. (1219mm x 305mm) damper will required a minimum clearance of 1⁄2 in. (13mm) on width and 1/4 in. (13mm) on height.
Single Side Angle Installation
On vertical mount single side angle installations there are no minimum clearance requirements between the wall opening and the damper sleeve. However, to facilitate installation, clearances between the wall opening and the damper sleeve are recommended.
On horizontal mount single side angle installations a minimum clearance is required between the outside of the damper sleeve and the floor opening of 1⁄8 in. per foot (3mm per .3m) of damper width and 1⁄8 in. per foot (3mm per .3m) height with a minimum clearance of 1/4 in. (6mm).
Book 5402-4
Rev. Oct/16
481318 Multi-Blade Fire and Combination Fire Smoke Dampers®
Installing Multiple Section Damper Assemblies
A damper assembly is not restricted to a maximum number of sections, but must not exceed the section sizes and overall sizes shown (see chart below).
Some multiple section high damper assemblies require additional structural support between the damper frames. The following multiple section high damper assemblies require the use of either a support mullion between the damper frames as shown in Figure 5 or individual sleeves around each row of dampers as shown in Figure 6:
• All horizontal mount dampers
• All vertical mount dampers over 72 in. (1829mm) high and greater than 2 sections wide
• All vertical mount dampers rated for more than 4 in. wg (1 kPa)
• All vertical mount dampers that use fusible links as a closure device
The damper sections must be attached together with #10 (3/4 in. max. [19mm]) sheet metal screws, 1/4 in. (6mm) diameter nuts and bolts, tack or spot welds, or 3⁄16 in. (48mm) diameter steel pop rivets. Attachments must be spaced a maximum of 6 in. (152mm) on centers and a maximum of 2 in. (51mm) from corners. Attachments must be made on front face and back face (air entering and air exiting side) of damper sections.
Note: Dampers ordered for individual installation may not be installed together. The full assembly size must be specified at the time the dampers are ordered.
Support mullion: 14 ga. 5 in. wide for
vertical mount dampers; 12 ga. 9 in. wide for
horizontal mount dampers
Figure 5: Single sleeve around outside with support mullion
Figure 6: Two individually sleeved units with no mullions
Maximum Assembly Tables
Damper ModelMaximum Single
Section Size(inches)
Maximum Overall Size for Multi-Section
Dampers (inches)
DFD-210 36 x 36 or 32 x 50 128 x 96
DFD-230 36 x 36 or 32 x 48 72 x 48
DFDAF-310 32 x 50 144 x 96
DFDTF-21032 x 36 96 x 72
32 x 48 64 x 48 or 32 x 96
FSD-211, 212, 213 36 x 48 or 32 x 50 144 x 96
FSD-211M, 212M 30 x 36 144 x 72
FSD-231 36 x 36 or 32 x 48 72 x 48
FSD-231M 36 x 36 72 x 48
FSD-311, 312 32 x 50 144 x 96
FSD-311M, 312M 32 x 50 128 x 96
FSD-331, DFDAF-330 30 x 48 144 x 96
IMO-310 32 x 50 NA
IMO-311 32 x 50 NA
SEDFD-210, SEFSD-211
24 x 30 48 x 30
SSFSD-211 24 x 30 48 x 30
Horizontal Mount
Note: FSD model dampers fitted with a fusible link closure device are limited to single section sizes.
Damper ModelMaximum Single
Section Size(inches)
Maximum Overall Size for Multi-section
Dampers(inches)
DFD-210 36 x 36 or 32 x 50 128 x 100
DFD-230 36 x 36 or 32 x 50 72 x 48
DFDAF-310 32 x 50 128 x 100
DFDTF-21032 x 36 96 x 72
32 x 50 64 x 50
FSD-211, 212, 213 36 x 48 or 32 x 50 128 x 100
FSD-231 36 x 36 or 32 x 48 72 x 48
FSD-311, 311M, 312, 312M
32 x 50 128 x 100
FSD-311V 50 X 32 100 x 32
FSD-331, DFDAF-330 32 x 36 or 30 x 48 120 x 96
IMO-31132 x 50 NA
32 x 50 NA
SEDFD-210, SSDFD-210
24 x 30 or 22 x 36 48 x 30
SEFSD-211SSFSD-211
24 x 30 or 22 x 36 88 x 72
Vertical Mount
Rev. Oct/16 Book 5402-5
481318 Multi-Blade Fire and Combination Fire Smoke Dampers ®
Inserting Damper into Wall/Floor Openings
Insert the sleeved damper assembly into the prepared opening. Refer to label on outside of sleeve for the recommended location of the damper in the wall or floor (see Dimension A and Detail 1, Figure 7).Special attention must be paid to ensure the following:
1) The CL (centerline) of the damper frame remains within the plane of the wall or floor
2) Attachments made through the retaining angle do not penetrate the ‘No Screw’ area designated on the damper sleeve.
3) The sleeve does not extend more than 16 in. (406mm) beyond the wall or floor on the actuator side of the damper and 6 in. (152mm) on the side opposite the actuator. The sleeve may also extend up to 16 in. (406mm) beyond the wall or floor if the damper has a factory supplied access door.
Optional blade indicatorand/or electric link.
LINE OF WALL
DO NOT INSTALL SCREW SBETWEEN THESE LINESAROUND ENTIRE DAMPER
Clearance for expansion(1/4 in. min., 1 1/2 in. max.)
Retaining Angles(see Section 4)
LIne of Wall
Airflow
Detail 1
DO NOT INSTALL SCREWSBETWEEN THESE LINESAROUND ENTIRE DAMPER
Access door required onjackshaft side of damper.Refer to the latest editionof NFPA 90A. Jackshaft
Actuator
Damper Sleeve
Sleeve Length (L)
6 in. max.16 in. max.
‘A’ Dim.(Distance from end of sleeve to face of damper)
458549
Tw
CL
Figure 7: Properly Installed Combination fire smoke damper
Most fire and combination fire smoke dampers come with factory supplied sleeves. For field supplied sleeves, see the Field Supplied Sleeves supplement at www.greenheck.com. The following are recommended sleeve lengths for various wall thicknesses:
Wall Thickness Dimension (TW)
Recommended Sleeve LengthDimension (L)
4 - 6 in. (102mm - 152mm)
16 in.(406mm)
7 - 10 in.(178mm - 254mm)
21 in.(533mm)
11 - 13 in.(279mm - 330mm)
24 in.(610mm)
Book 5402-6
Rev. Oct/16
L|'
-E#
'0‘‘$:$fVVM
//“VL\<QO/
Q_
:7J
481318 Multi-Blade Fire and Combination Fire Smoke Dampers®
Securing the Damper/Sleeve Assembly to Wall/Floor Openings
All fire and combination fire smoke dampers may utilize the two sided angle installation method described below. 11⁄2 hour rated fire and combination fire smoke dampers may use the single sided angle installation method up to the following maximum sizes: • Vertical mount: 80 in. W x 50. in. H (2032mm W x 1270mm H), 50 in. W x 80 in. H
(1270mm W x 2032mm H), or 40 in. W x 100 in. H (1016mm W x 2540mm). • Horizontal mount: 144 in. W x 96 in. H (3658mm W x 2438mm H)
• Retaining Angle Gauge: Retaining angles for 11⁄2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm).
• Retaining Angle Size: The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm).
• Retaining Angle Attachment to Sleeve: Retaining angles must be attached to the damper using one or more of the following methods of attachment (refer to label on outside of sleeve for ‘No Screw’ area):
- Tack or spot welds - #10 (3⁄4 in. [19mm] max.) sheet metal screws - 1⁄4 in. (6mm) bolts and nuts - 3⁄16 in. (5mm) steel pop rivetsA minimum of two connections per side, top, and bottom, 12 in. (305mm) O.C. maximum for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers greater than 48 in. wide (1219mm) or 36 in. high (914mm) require the connections to be no more than 6 in. (152mm) O.C.The angles must be attached to all 4 sides of the sleeve. Ensure that fasteners do not interfere with the operation of the damper. The angles need not be attached to each other at the corners.
• Retaining Angle Attachment to Wall/Floor: Two sided Angle Method: For two sided angle installations the
retaining angles shall not be attached to the wall/floor (see Figure 8).
Single Sided Angle Method: For single side installations the retaining angles must be attached to the wall/floor (see Figures 9-12). For metal stud partitions only, the single-side mounting angle may be directly attached to the metal stud prior to the installation of the drywall.
• Retaining angles must be attached to the partition using one of the methods shown below:
- Drywall screws of a length such that the screw engages the steel stud/track by 1⁄2 in. (13mm) (steel framing).
- Drywall screws of a length such that the screw engages the wood stud by 13/4 in. (44mm) (wood framing).
- Steel anchors or self tapping concrete screws penetrating masonry or block 11/4 in. (31mm). • A minimum of two connections per side are required. Additional connections made at a maximum
of 12 in. (305mm) O.C. maximum for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers greater than 48 in. wide (1219mm) or 36 in. high (914mm) require the connections to be no more than 6 in. (152mm) O.C.
2 in. Max.
6 in. Max.
Sleeve
RetainingAngle
Damper
Duct
Min. 1 in.Overlap*
Wall orFloor
RetainingAngle
*only applicable for damper sizes above 36 in. x 36 in.
6 in. Max.
2 in. Max.
Figure 8: 2 sided angle installation method
Rev. Oct/16 Book 5402-7
K
//
\ I
E
481318 Multi-Blade Fire and Combination Fire Smoke Dampers ®
Securing the Damper/Sleeve Assembly to Wall/Floor Openings cont.......
Damper Sleeve
Angle Fastener
2 1/2 in. min.Stud or Runner
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Figure 9: Single Side Angle With Steel Stud Wall - Angle Over Wallboard
Damper Sleeve
2 1/2 in. min.Metal Studor Runner
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Figure 11: Single Side Angle With Steel Stud Wall - Angle Under Wallboard
2 1/2 in. Min.Stud or Runner
DamperSleeve
Angle Fastener
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Figure 10: Single Side Angle With Wood Stud Wall
Masonry orConcreteWall
DamperSleeve
Angle Fastener
Masonry orConcrete Floor
DamperSleeve
Angle Fastener
Top Side
Figure 12: Single Side Angle With Masonry or Concrete Wall and Floor
Grille Installations (Dampers up to 36 in. x 36 in. [914mm x 914mm])Retaining angles used in conjunction with grille installations must be a minimum of 5⁄8 in. x 1 in. (15mm x 25mm) 16 gauge (1.5mm) steel. Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side). See Figure 13 and Figure 14.Note: Screws used to attach grille are allowed to penetrate reversed angle leg.
DamperSleeve
Angle Fastener
Grille (suppliedby others)
#10 sheet metal screwsspaced 6 in. on centerand a maximum of 2 in.from the corners(minimum of 2 screws perside). Screw into studs soas to avoid spaceconflicts with the grille
2 1/2 in. Min.Stud or Runner
Retaining Angle/Flange
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Figure 14: Metal Stud - Grille
Two layers of 1/2 in. UL Classified Gypsum Wallboard for 2 hour rated walls. One layer for 1 hour rated walls (see UL Rated Wall Design for Additional Details).
Grille (supplied by others)Retaining Angle
Angle Fastener
Damper Sleeve
#10 sheet metal screws, 2 1/2 inches long, spaced 6 in. on center and amaximum of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conflicts with the grille.
2 1/2 in. minimumStud or Runner
Figure 13: Wood Stud - Grille
Book 5402-8
Rev. Oct/16
X
4/_
I
X
\ \
_/Y
KX€\ Q/ i/
X
X
\ W Ki
itU \\\\\\\\\\\\\\ U
481318 Multi-Blade Fire and Combination Fire Smoke Dampers®
Duct to Sleeve Connection
Sleeve Gauge and Connection Type Requirements
Sleeve Gauge Duct Dimension
Type of Duct to Sleeve
Connection Permitted
14 ga. (0.075 in.) - 10 ga. (0.138
in.)[2mm - 3.5mm]
All duct sizesRigid or
Breakaway
16 ga. (0.060 in.)[1.5mm]
36 in. (914mm) max. width24 in. (610mm) max.
height24 in. (610mm) diameter
Rigid or Breakaway
16 ga. (0.060 in.)[1.5mm]
All duct sizes
Breakaway only
18 ga. (0.048 in.)[1.2mm]
85 in. (2159mm) wide and over
20 ga. (0.036 in.)[0.9mm]
55 in. - 84 in. wide(1397mm - 2134mm)
22 ga. (.030 in.)[0.76mm]
31 in. - 54 in. wide(787mm - 1372mm)
24 ga. (0.024)[0.6mm]
13 in. - 30 in. wide(330mm - 762mm)
26 ga. (0.018 in.)[0.46mm]
12 in. wide and under(305mm)
See Breakaway Connection section for additional information.UL Standard 555 requires all ducts to terminate at fire damper sleeves.
Approved Breakaway ConnectionsAll breakaway connections described below may utilize the following duct sealants: PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie, Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.
Transverse JointsThe transverse joints shown below are approved as breakaway connections. • A maximum of two #10 (19mm) sheet metal screws on each side and on the bottom may be used. The
screws should be located in the center of the slip pocket and penetrate both sides of the slip pocket. • Dampers up to 20 inches (508mm) high may use transverse joints on the top and bottom and Drive Slip
joints (see Figure 16) on the sides.
Plain “S” Slip Hemmed “S” Slip Double “S” Slip
Inside Slip Joint Standing “S” Standing “S” (Alt.)
Standing “S” (Alt.) Standing “S” Standing “S” (Bar Reinforced) (Angle Reinforced)
Figure 15 - Transverse Joints
Drive Slip Joint
Figure 16
The size of the damper/duct determines the required sleeve gauge and the required duct to sleeve connection (see table to the right). The sleeve thickness must also not be less than the gauge of the connecting duct. Any duct connection other than the breakaway connections described below are considered rigid.
Rev. Oct/16 Book 5402-9
%Ii_
1
7%%flfin_€i;
481318 Multi-Blade Fire and Combination Fire Smoke Dampers ®
Round and Oval Duct Breakaway ConnectionsFactory furnished duct collars, type R and O, are also considered breakaway (see Figure 17).
Round or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19mm) sheet metal screws as follows: • Ducts up to 22 in. (558mm) wide (or dia.) and less
shall have three screws. • Ducts larger than 22 in. (558mm) wide (or dia.) up
to and including 36 in. (914mm) wide (or dia.) shall have five screws.
Fire Damper Sleeve
Neoprene or Butyl gasketbetween all angles
Flanged system angles
(Attach permanufacturer'sinstructions)
Duct
3/8 in. bolts incorners are optional
6 in. long metal cleat or 1/16 in.max. thickness plastic cleat;12 in. c-c (min. 1 per side)
Figure 18
Approved Breakaway Connections....
DuctSleeve
6 in.
Std. ClipLength
CLDuct
60 in. Duct4 Req’d.
48 in. Duct3 Req’d.
36 in. Duct3 Req’d.
24 in. Duct2 Req’d.
18 in. Duct &Smaller1 Req’d.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.9 in.
7 in.7 in.
5 in. 5 in.
5 in.5 in.
Figure 20
Duct EndFlange
Corner Piece
3/8 in. bolt (optional)
Figure 21
Proprietary Flange System Breakaway Connections(TDC by Lockformer, TDF by Engle)TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF addendum to the SMACNA Duct Construction. Standard 6 in. (152mm) metal clip may be used with spacing as shown in diagram (see Figure 19 & 20). 33⁄8 in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces (see Figure 21).
DuctSleeve
6 in.
Std. ClipLength
CLDuct
60 in. Duct4 Req’d.
48 in. Duct3 Req’d.
36 in. Duct3 Req’d.
24 in. Duct2 Req’d.
18 in. Duct &Smaller1 Req’d.
Clip Spacing
Typical TDC/TDF joint
6 in. 6 in.9 in.
7 in.7 in.
5 in. 5 in.
5 in.5 in.
Figure 19
Wall or Floor
Sleeve
Duct Damper
Type B
Wall or Floor
Sleeve
Duct Damper
Type R, O
Type R and Ofactory furnishedduct collars qualifyas breakawayconnections.
Figure 17: Type R and O Transition
Manufactured Flanged System Breakaway ConnectionsFlanged connection systems manufactured by Ductmate, Durodyne, Ward, Nexus, Radiant T-35m, and MEZ are approved as breakaway connections when installed as illustrated (see Figure 18).
Book 5402-10
Rev. Oct/16
flankkEm In
ifi_13\/!J\E__LE>//%__fi_
LFLIfiafiflinWE //5 //W
X}J _/H@ %T/K
_AA_AA
\|
481318 Multi-Blade Fire and Combination Fire Smoke Dampers®
Actuator and Temperature Response Device Connections
Actuator ConnectionsElectrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations (see Electrical Guidelines).
Temperature Response Device ConnectionsRRL - The RRL (resettable link device) incorporates a single thermostat. When the thermostat temperature is reached the sensor interrupts power to the actuator and the actuator's spring return mechanism causes the damper to close. Refer to Figure 22 for wiring of the RRL thermostat.OCI - The OCI (open or closed indicator) option contains two single pole single throw switches used to indicate the damper blade position. The switches provide a positive open and closed signal and can be used in conjunction with remote indicator lights. Refer to Figure 23 for wiring of the OCI option.RRL /OCI - The RRL/OCI performs the function of an RRL and OCI (see description above). Refer to Figure 24 for wiring of the RRL/OCI option.TOR - The TOR (temperature override device) option incorporates two thermostats with fixed settings (usually 165°F [74°C] and 350°F [177°C]). The primary sensor (the sensor with the lower temperature setting) can be bypassed by an external contact closure allowing the damper to reopen until the secondary temperature is reached (the sensor with the higher temperature setting). See Figure 25.
Figure 22: RRL Wiring
Figure 23: OCI
The TOR assembly contains two single pole single throw switches used to indicate damper blade position. The switches provide a positive open and closed signal and can be used in conjunction with remote indicator lights. See Figure 25 for wiring of the TOR thermostats and indicator switches.If either the TOR or the RRL is ordered with a pneumatic actuator, an EP switch is required with an appropriate electric power circuit to allow the electric thermostat to control the pneumatic actuator.
Ratings (Figure 22, 23, 24, & 25)Integral Switch Type: Single Pole, double throwElectrical Capacity: 10 Amps, 1/3 hp, 120 or 240 Vac 1⁄2 Amp, 125 Vdc; 1/4 Amp 250 Vdc 5 Amps, 120 Vac “L” (lamp load) 1.0 Amps, 24 Vac 1.5 Amps, 24 VdcTemperature Limit: 165° F (standard primary sensor) 212° F (optional primary sensor) 250° F (secondary sensor )* 350º F (secondary sensor)* * based on actuator temperature rating
Figure 24: RRL/OCI
Figure 25: TOR
Rev. Oct/16 Book 5402-11
460632
450633
RESE ABLE ABLE LINK
RES ABLE REUSABLE LINK/OPEN-C ED INDICATOR » ~Z*Q97 \<a
)\ Q SW
<°~9r5Wx‘(’ 4’EsE’\Asse‘ ESE‘
OPTIONAL M TARY
@559 L1 f$€?¥2“ CH
/ ELEURIC DAMPER
ORANGE NC B , NC \ BLACK /M\ WHITE\ /
H5 ACTUATOR ORPNEU, SOLENOID
PRIMARY TEMP SENSOR 7 VALVECo ONAL MONENTARV OPTIONAL TOGGLE E
L1 TEE” " '-2 SWITCHES AMP MAX)ORANGE NC BLACK / NC \ BLACK
/WHITE
\L,/,JPRIMARY TEMP SENSOR
ECFRIC DAMPERA TOR anPNE , LENOID
7 VALVE460531
DISCONNECI SWITCH
ow (w/ BLUE TAPE)51 (MAKES WHEN BY OTHERS TDAMPER (10555) O YELLOW (WI BLUE TAPE) /
/, \\ AMPERI ICATOYELLOW (w/0 BLUE TAPE) \\ /, HG
OPTIONAL TOGGLE sz ES WHEN I ’ \DISCONNECF SWITCH \ PER OPENS) N0 YELLOW (W/O BLUE TAPE) I_ _____
e
OPEN — CLOSED I TOR
/\ ~Z*$8 T {XL5 W
OPTIONAL MONENTARL 1 f 2%TcH
BLACK c LACK
OPTIONAL TOGGLEDISCONNECI SWIT
SWIT s (1OAMP MAX)YELLOW (WI BLUE TAPE)
WHITE
ELECTRIC DAMPERAUUATOR ORPNEU, SOLENOID
T VALVE
4447
51 (MAKES W _5%fi4§5_DAMPER c NO \\ I //
EC0 7 7 777/, \\ DAMPER\ I INDICATO
5) YELLOW (WI BLUE TAPE)
YELLOW (W/O BLUE TAPE)
|,_ |\\/ I1?II II II L_I_”__J66/ LIGHTS
S2 (MAKES WHENDAMPER OPENS) NO YELLOW (w/0 BLUE TAPE)
6 8
O 7aw
9
6
6
flEMPERATURE LIMITEDOVERRIDE ANDOPEN-CLOSEDINDICATOR
\z,)(,\'\ I-I/I7!)
7“5\N'\
@556‘*EsE‘
/\ IMA6:9 <61‘ Q? Q},
QEEIEE OPTIONAL MONENTARYT _| CONTACT
I-1 I BROWN /_ TEST SWITCHOrr
ORANGE BROWN BLACK / 9_I_a \ BLACK /X WHITE
SWITCHES (10AMP MAX) °I""°"AL T°°°LEDISCONNECI SWITCHYELLOW (WI BLUE TAPE)
/ I NC NC
I@~ \~»_I ( "C MI | ya ELECTRIC DAMPERLIMEEEPS Q §§EH“l€'L‘EII§ID
PRIMARY TEMP EENQOR HIGH LIMIT SENSOR f VALVE
460630 ‘IIIIIs1 (MAKES WHEN NO BY OTHERSDAMPER CI-9555) YELLOW (W/ BLUE TAPE) \\ I //o — — —
// \YELLOW (W/O BLUE TAPE) \ , II“§§,§§T°
L____J
_O\ DAMPK —\I, x:
sz (MAKES WHEN ’/QR‘\ DAMPER OPENS) NO YELLOW (W/O BLUE TAPE) L_____ /e
Damper MaintenanceDampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with: • The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes. • Actuator manufacturer recommendations.
Damper TroubleshootingThe following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not fully open and/or close
Frame is 'racked' causing blades to bind on jamb seals
Adjust frame such that it is square and plumb
Actuator linkage loose Close damper, disconnect power, adjust and tighten linkage
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out to line as designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see Damper Maintenance)
RRL or TOR sensor tripped
Heat Push reset button located on backside of RRL or TOR
Damper does not operate
No power supplied to the actuator Add power supply
481318 • FSD, DFD, FSD-3xxV Rev. 2 March 2016 Copyright 2016 © Greenheck Fan Corporation
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.Specific Greenheck product warranties can be located on greenheck.com within the product area tabs and listed in the Library under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com
Our Commitment
Book 5402-12
Rev. Oct/16
BEEF‘E’ -El . E“
@G”§€”'iE¢I<
TABLE OF CONTENTS
CHAPTER 3 – ACTUATORS FOR FIRE / SMOKE DAMPERS
GND SERIES ACTUATOR: INSTALLATION, OPERATION & MAINTENANCE MANUAL ...... 3-1 Instructions ......................................................................................................... 3-1
HONEYWELL FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE .... 3-3
Application .......................................................................................................... 3-3 Fire Code References and Information .............................................................. 3-3 Replacement Guidelines – Actuator Specifications ........................................... 3-3 Replacement Guidelines – Applications ............................................................. 3-3 Replacement Guidelines – Damper Manufacturer’s Guidelines ........................ 3-4 Maintenance Information .................................................................................... 3-4 Product Information ............................................................................................ 3-5 Installation and Wiring ........................................................................................ 3-6
LIST OF FIGURES
CHAPTER 3: GND SERIES ACTUATOR: INSTALLATION, OPERATION & MAINTENANCE MANUAL
Figure 1: Siemens Series Internal Mount (exploded view) ................................ 3-1 HONEYWELL FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE
Figure 1: Typical Fire and Smoke Damper Assembly ........................................ 3-4 Figure 2: Dimensions for MS4104 Series Actuators .......................................... 3-6 Figure 3: NOT APPLICABLE.............................................................................. 3-6 Figure 4: NOT APPLICABLE.............................................................................. 3-7 Figure 5: Typical 120 Vac wiring ........................................................................ 3-7 Figure 6: NOT APPLICABLE.............................................................................. 3-7 Figure 7: NOT APPLICABLE.............................................................................. 3-7 Figure 8: NOT APPLICABLE.............................................................................. 3-7 Figure 9: NOT APPLICABLE.............................................................................. 3-7
LIST OF TABLES
CHAPTER 3: GND SERIES ACTUATOR: INSTALLATION, OPERATION & MAINTENANCE MANUAL
None HONEYWELL FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE
Table 1: Fire and Smoke Cross Reference ........................................................ 3-5
END OF TABLE OF CONTENTS
Rev. Oct/16 Book 540
HVAC DUCTS CASINGS - PRODUCT INFORMATION PAGE
Equipment Description: Actuators for Fire / Smoke Dampers
Equipment Identification: None
Equipment Manufacturer:
Honeywell
1985 Douglas Dr. North, Golden Valley, MN 55422
(877) 841-2840
Equipment Make / Model: MS4104F1010
Location of Equipment: Berryessa & Milpitas Stations
Filter Sizes & Quantity: Not Applicable for this Equipment
Service Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Dealer Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Valve Number: Not Applicable for this Equipment
Valve Type: Not Applicable for this Equipment
Valve Size: Not Applicable for this Equipment
Valve Location: Not Applicable for this Equipment
Valve Function: Not Applicable for this Equipment
Damper Certification & Verification: Not Applicable for this Equipment
Domestic Water System Cleaning & Disinfection Test
Results & Report:Not Applicable for this Equipment
Air & Water System Balance Report: Not Applicable for this Equipment
Controls Operation & Maintenace Data with Wiring
Diagrams:
HVAC Controls Information, including Wiring
Diagrams can be found in O&M Book 538
Approved Seismic Calculations: Not Applicable for this Equipment
Warranties See Chapter 5
Book 540 Rev. Oct/16
HVAC DUCTS CASINGS - PRODUCT INFORMATION PAGE
Equipment Description: Actuators for Fire / Smoke Dampers
Equipment Identification: None
Equipment Manufacturer:
Siemens
3650 Industrial Blvd., #100, W. Sacramento, CA 95691
(800) 743-6367
Equipment Make / Model: GND221.1
Location of Equipment: Berryessa & Milpitas Stations
Filter Sizes & Quantity: Not Applicable for this Equipment
Service Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Dealer Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Valve Number: Not Applicable for this Equipment
Valve Type: Not Applicable for this Equipment
Valve Size: Not Applicable for this Equipment
Valve Location: Not Applicable for this Equipment
Valve Function: Not Applicable for this Equipment
Damper Certification & Verification: Not Applicable for this Equipment
Domestic Water System Cleaning & Disinfection
Test Results & Report:Not Applicable for this Equipment
Air & Water System Balance Report: Not Applicable for this Equipment
Controls Operation & Maintenace Data with
Wiring Diagrams:
HVAC Controls Information, including Wiring Diagrams
can be found in O&M Book 538
Approved Seismic Calculations: Not Applicable for this Equipment
Warranties See Chapter 5
Rev. Oct/16 Book 540
THIS PAGE INTENTIONALLY LEFT BLANK
Book 540 Rev. Oct/16
Figure 1: Siemens Series internal mount (exploded view).
1.563 in. (39mm)
.203 in. (5.2mm) Diameter.(2)
Blade Axle Bracket
Damper Blade
1.75 in. (44mm)Blade Lever Hole Location
Detail A
ACTUATOR PART #GND121.1U 24V 383774GND126.1U 120V 383775GND221.1U 120V 383776GND226.1U 120V 383777GND321.1U 230V 383778GND362.1U 120V 383779
ITEM # QTY PART # DESCRIPTION1 1 723981 INTERNAL ACTUATOR BRKT2 1 839475 DRIVE LINK ASSEMBLY3 1 829206 1/2" CRANKARM ASSEMBLY4 1 451588 1/4" E-RING5 1 593831 6.5" JACKSHAFT, 1/2" DIA.6 1 415385 10-32 KEPS NUT7 1 846591 1/2" ANTI-ROTATION BRKT. ASM8 1 416122 THREADED MOUNTING STUD9 2 415264 1/4-20x1/2 TCS10 1 SEE CHART ACTUATOR11 1 370159 1/2" SNAP IN BEARING12 1 416179 RETAINING RING 1/2"
Tools Required:
Wrenches: (1) 1⁄2 in., (1) 7⁄16 in.,
(1) 3⁄8 in., (1) 10 mm
Document Number 473707GND Series Actuator
Models GND-121, GND-221, and GND-321
Mounted Internally
Installation, Operation and Maintenance ManualNote: For dampers installed in ducts or sleeves.
These instructions apply to the internal field replacement of the Siemens GND series actuators on Greenheck Control dampers.
Rev. Oct/16 Book 5403-1
E
[K
\\
W/Ly/XL@
J1%AI®
__\Eh6/\fi_\/9 6\
eN_‘\\
E&
Copyright © 2016 Greenheck Fan Corporation473707 GND Series Rev. 2 August 2016
Instructions Siemens GND SeriesThese installation instructions assume a damper is already mounted in a duct or sleeve. Have damper blades in the fail position.
1. Drill (2) .203 inch holes in the third blade from bottom, at location shown in Detail A.
2. Attach blade drive lever to blades using (2) 1⁄4 in. 20 x 1⁄2 in. thread cutting screws, self drilling screws or 1⁄4 in. - 20 x 11⁄4 in. bolts.
3. Fasten internal actuator bracket (item 1) to the left jamb of damper frame using (2) thread cutting screws. Snap bearing (item 11) into the internal actuator bracket (item 1).
4. Snap bearing (item 11) into the anti-rotation bracket (item 7) and attach to the internal mount bracket (item 1) using [2] thread cutting screws (item 9).
5. Slide 1⁄2 in. diameter rod (item 5) slightly through the anti rotation bracket (item 7). Install crankarm (item 3) and drive link (item 2) onto the 1⁄2 in. diameter rod and (item 5) and install retaining ring (item 12) to lock drive link onto the internal actuator bracket (item 1).
6. Install threaded mounted stud (item 8) to the anti rotation bracket (item 7) using #10-32 Keps nut (item 6).
7. Attach actuator (item 10) to the anti-rotation bracket assembly (item 7). Tighten actuator onto shaft.
8. Connect drive link to blade drive lever using e-clip. With blades closed and the actuator in its fail position, position blades in their fail position and tighten the crankarm to the 1⁄2 in. shaft.
9. Connect all electrical leads to the actuator. Apply power to the actuator. The damper blades should power position and return to the fail position when power is disconnected.
Model Volts Running Holding
GND121.124 20VA 8VA
GND126.1
GND221.1120 20VA 9VA
GND226.1
GND321.1230 20VA 9VA
GND326.1
Book 5403-2
Rev. Oct/16
P.O. Box 410 - Schofield, WI 54476-0410 - 715.359.6171 - greenheck.com
REPLACEMENT GUIDE
Fire and Smoke Damper Actuator Field Replacement Guide
APPLICATIONSafety should never be left to chance. Honeywell fire and smoke actuators are designed to meet both UL-555 and UL555S 350F safety requirements for fire and smoke applications. Fast-acting actuators close dampers in 15 seconds, and the integral spring return ensures the consistent, proper level of torque. For the highest level of occupant safety, you can count on Honeywell.
Fire and Smoke actuators and assemblies must function properly during a fire or life-safety emergency. Honeywell Fire and Smoke Actuators provide fast action when timeliness is key in preventing the spread of fire and smoke. Proper installation and periodic performance testing are required to ensure fire and smoke damper assemblies will fully function should an emergency occur. The following guidelines are crucial to keep fire and smoke damper assemblies operating properly, and to stay in adherence to standards and codes.
FIRE CODE REFERENCES AND INFORMATIONHoneywell Fire and Smoke Actuators are designed to meet both UL555 and UL555S safety requirements for combined fire and smoke applications.
The following maintenance guidelines are a summary of the National Fire Protection Association (NFPA) Codes as well as Air Movement and Control Association (AMCA) and Honeywell manuals. We recommend that you become familiar with NFPA 80, 90A, 92A & B, and 105 and AMCA publication 503. Be aware that other codes, such, International Building Code (IBC), regional, state and local codes, may also apply to your area.
REPLACEMENT GUIDELINES
Actuator SpecificationsUL555 and UL555S require fire and smoke actuators to be tested to 20,000 close and reopen cycles and close within 75 seconds. UL555 also requires them to be rated to either 250F or 350F.
Honeywell fire and smoke actuators are rated to 30,000 cycles, operate within 15 seconds, and are rated to 350F.
ApplicationsCombined Fire and smoke dampers are used to maintain fire barrier ratings when walls and floors are penetrated by ductwork.
Smoke dampers are used to prevent the passage of smoke through the HVAC system or from one side of a fire-rated separation to the other. They may be dedicated to this function or also function as HVAC dampers.
Rev. Oct/16 Book 5403-3
Q
W
\i
HOneywG"
FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE
38-00001—01
Damper Manufacturer’s GuidelinesWhen replacing actuators, it is important to follow the guidelines that are provided by the damper manufacturer for the damper assembly. When replacing a fire and smoke actuator the replacement should be either like-for-like with the original, factory-mounted actuator, or a technically superior product where the total assembly has passed UL testing with the damper manufacturer.
Please refer to the damper manufacturer’s guidelines for details.
MAINTENANCE INFORMATIONFire and Smoke damper assemblies must undergo periodic performance testing to be properly maintained and to ensure they are functioning and will function in a fire or life-safety emergency.
The NFPA codes require combined fire and smoke dampers be tested and inspected at the time the system is commissioned, after it has been balanced, and one year after installation. Then they need to be tested and inspected every 4 years, except in hospitals, where they need to be tested and inspected every 6 years. See "Option 1” and “Option 2” in this section for detailed test instructions.
AMCA suggests that smoke dampers be tested at least semi-annually. Smoke dampers should be operated, and the correct outputs should be observed, to verify operation. These tests need to also be conducted under standby power, if used.
Honeywell Fire and Smoke Actuators are found in combination fire and smoke damper assemblies that use a bi-metallic disc type thermostat to interrupt electrical power to the actuator at a specified temperature. Once the specified temperature is reached, power will be interrupted and the spring return of the actuator will close the damper. When these actuators are used in smoke damper applications, they are usually controlled by smoke detectors or fire alarms.
Periodic inspection includes:1. Verify that there is full unobstructed access to the
damper2. Test the damper with normal HVAC airflow and verify
that it opens following either Option 1 or Option 2. There should be no interference due to rust, damaged frame or blades, or other moving parts.
Option 1: Dampers with Position Indication Wired to indication Lights, or Control Panels:
Switches can be wired to local or remote control panels or building automation systems (BAS) to indicate that the damper is in the fully-open position, fully-closed position, or neither.
a. Use the signal from the damper’s position indication device to confirm that the damper is in the fully-open position.
b. Remove electrical power or air pressure from the actuator to allow the actuator’s spring return feature to close the damper.
c. Use the signal from the damper’s position indication device to confirm that the damper reaches its fully-closed position.
d. Re-apply electrical power to re-open the damper.e. Use the signal from the damper’s position indication
device to confirm the damper reaches its fully-open position.
Option 2: Dampers without position indication:a. Visually confirm that the damper is fully-open posi-
tion.b. Ensure that all obstructions, including hands, are
out of the path of the damper blades.c. Remove electrical power or air pressure from the
actuator to allow the actuator’s spring return feature to close the damper.
d. Visually confirm that the damper closes completely.e. Re-apply electrical power to re-open the damper.f. Visually confirm that the damper is in the fully open
position.
3. If the damper is not operable, it must be repaired as soon as possible. If the actuator has failed, replace it with a UL approved actuator. See Table 1. See Figs. 2-3 for mounting and installation information and Figs. 4-9 for wiring. After these repairs, the damper should be tested again.
4. If there is a latch, verify that it is operable.5. Perform any other damper manufacture recommended
maintenance such as lubrication.6. Following the test and any repairs, document the loca-
tion of the damper, the date, the inspector, and deficien-cies or repairs. Keep the record for the life of the damper, and have it available as you may need to show it to an inspector.
Fig. 1. Typical Fire and Smoke Damper Assembly.
Source: AMCA International: Guide for Commissioning and Periodic Performance Testing of Fire, Smoke, and other Life Safety Related Dampers, 2012.
Book 5403-4
Rev. Oct/16
JR
_L"H)L1
'_-4‘L
_‘_‘_
r‘__I
n
FT_l|'____‘_ _N’'_Hv_'\.__k
FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE
38-00001—01
PRODUCT INFORMATION
Table 1. Fire and Smoke Cross Reference.
TorqueModel
Number VoltageSPST
Aux SwitchLegacy
HoneywellBelimoCross
Siemens Cross
30 lb-in (3.4 Nm)
MS4104F1010
120 Vac 0 ML4115A1009ML4115A1017ML4115B1008ML4115B1016ML4115H1002ML4115J1009ML4202F1000ML4302F1008
FSLF120 US None
MS4104F1210 120 Vac 2 Internal None FSLF120-S US None
MS4604F1010 230 Vac 0 ML4115C1007ML4115C1015ML4115D1006ML4115D1014ML4702F1009ML4802F1007
FSLF230 US None
MS4604F1210 230 Vac 2 Internal None FSLF230-S US None
MS8104F1010 24 Vac 0 ML8115A1005ML8115A1013ML8115B1004ML8115B1012ML8115H1008ML8115J1005ML8202F1006ML8302F1004
FSLF24 US None
MS8104F210 24 Vac 2 Internal None FSLF24-S US None
80 lb-in (9 Nm) MS4109F1010 120 Vac 0 MS4209F1007MS4309F1005
FSNF120 US GND221.1U
MS4109F1210 120 Vac 2 Internal None FSNF120-S US GND226.1U
MS4609F1010 230 Vac 0 MS4709F1014MS4809F1012
FSNF230 US GND321.1U
MS4609F1210 230 Vac 2 Internal None FSNF230-S US GND326.1U
MS8109F1010 24 Vac 0 MS8209F1003MS8309F1001
FSNF24 US GND121.1U
MS8109F1210 24 Vac 2 Internal None FSNF24-S US GND126.1U
175 lb-in (20 Nm) MS4120F1006 120 Vac 0 None FSAF120 US GGD221.1U
MS4120F1204 120 Vac 2 Internal None FSAF120-S US None
MS4620F1005 230 Vac 0 None FSAF230 US GGD321.1U
MS4620F1203 230 Vac 2 Internal None FSAF230-S US None
MS8120F1002 24 Vac 0 None FSAF24 US GGD121.1U
MS8120F1200 24 Vac 2 Internal None FSAF24-S US None
Rev. Oct/16 Book 5403-5
FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE
38-00001—01
INSTALLATION AND WIRING
Fig. 2. Dimensions for MS4104, MS4109, MS4604, MS4609, MS8104, and MS8109 Series actuators.
See the following literature for further details and mounting instructions:• Product Data and Installation Instructions: 63-2740• Specification data: 38-00006
Fig. 3. Dimensions for MSXX20F actuators.
See the following literature for further details and mounting instructions:• Product Data and Installation Instructions: 63-2584• Specification Data: 63-2592
M34622
2 (51)
1 (25)
90° 0°
11/16(17)
6-3/8(161)
8-15/16(227)
4 (102)2 (51) 1/16
(2)3-1/4 (83)
5-1/8 (130)
9/16 (14)
10-11/16(271)
1-9/16(40)
8-5/8(220)
2 (50)
3-15/16 (100)
2-15/16 (75)1/4 (6)M20051A
Book 5403-6
Rev. Oct/16
VML‘I‘M;
Uv_5_E+7I"\L4”‘DI__I+
anE
E_/EIii7MI. lE"
I
AdIQEFL
FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE
38-00001—01
Wiring
For 30 lb-in and 80 lb-in (3.4 Nm, 9 Nm) models:
Fig. 4. Typical 24 Vac wiring.
Fig. 5. Typical 120 Vac wiring.
Fig. 6. Typical 230 Vac wiring.
For 175 lb-in (20 Nm) models:
Fig. 7. Typical 24 Vac wiring
Fig. 8. Typical 120 Vac wiring.
Fig. 9. Typical 230 Vac wiring.
M34624
24 VAC
BLACK
RED
L1 ( )
L2 ( )
YELLOW
YELLOW
BLUE7° AUXILIARY
SWITCH
85° AUXILIARYSWITCH
BLUE
WHITE
BLACK
GREENL1 ( )
L2 ( )
YELLOW
YELLOW
BLUE
BLUE7° AUXILIARY
SWITCH
85° AUXILIARYSWITCH
120 VAC
M34625
M34626
BLUE
BROWN
GREEN
230 VAC
L1 ( )
L2 ( )
YELLOW
YELLOW
BLUE
BLUE7° AUXILIARY
SWITCH
85° AUXILIARYSWITCH
M20053B
24 VAC
BLACK
RED
GREEN
MS8120F
L1 ( )
L2 ( )
YELLOW
YELLOW
BLUE7° AUXILIARY
SWITCH
85° AUXILIARYSWITCH
BLUE
M20056B
WHITE
BLACK
GREEN
MS4120F
L1 ( )
L2 ( )
YELLOW
YELLOW
BLUE
BLUE7° AUXILIARY
SWITCH
85° AUXILIARYSWITCH
120 VAC
M20057B
BLUE
BROWN
GREEN
230 VAC
MS4620F
L1 ( )
L2 ( )
YELLOW
YELLOW
BLUE
BLUE7° AUXILIARY
SWITCH
85° AUXILIARYSWITCH
Rev. Oct/16 Book 5403-7
1- 1-
-l- -1-
\||||
IQ1:‘HQ
"\/
4 ‘<
I II I g
"\¢
I II Q
FIRE AND SMOKE DAMPER ACTUATOR FIELD REPLACEMENT GUIDE
Automation and Control SolutionsHoneywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark© 2016 Honeywell International Inc.38-00001—01 M.S. 01-16Printed in United States
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Book 5403-8
Rev. Oct/16
Honeywell
TABLE OF CONTENTS
CHAPTER 4 – BACKDRAFT DAMPERS
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS ................................. 4-1
Receiving and Handling ..................................................................................... 4-1 Safety Warning ................................................................................................... 4-1 Instructions ......................................................................................................... 4-1 Damper Maintenance ......................................................................................... 4-2 Counterbalance Adjustment Instructions ........................................................... 4-2 Standard Components ....................................................................................... 4-3
MANUFACTURER’S LETTER: BACKDRAFT DAMPER – NFPA130 ....................................... 4-4
LIST OF FIGURES
CHAPTER 4:
None
LIST OF TABLES
CHAPTER 4:
None
END OF TABLE OF CONTENTS
Rev. Oct/16 Book 540
HVAC DUCTS CASINGS - PRODUCT INFORMATION PAGE
Equipment Description: Backdraft Damper
Equipment Identification: None
Equipment Manufacturer:
Greenheck
1100 Greenheck Dr., Schofield, WI 54476
(715) 359-6171
Equipment Make / Model:HB-110 (Emergency Ventilation & Supply Fans)
HB-230 (Emergency Exhaust Fans)
Location of Equipment: Milpitas Station - Emergency Fans
Filter Sizes & Quantity: Not Applicable for this Equipment
Service Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Dealer Contact:
Norman S. Wright
99A South Hill Dr., Brisbane, CA 94005
(415) 476-7600
Valve Number: Not Applicable for this Equipment
Valve Type: Not Applicable for this Equipment
Valve Size: Not Applicable for this Equipment
Valve Location: Not Applicable for this Equipment
Valve Function: Not Applicable for this Equipment
Damper Certification & Verification: NFPA-130 (Emergency Exhaust Fans)
Domestic Water System Cleaning & Disinfection Test
Results & Report:Not Applicable for this Equipment
Air & Water System Balance Report: Not Applicable for this Equipment
Controls Operation & Maintenace Data with Wiring
Diagrams:Not Applicable for this Equipment
Approved Seismic Calculations: Not Applicable for this Equipment
Warranties See Chapter 5
Book 540 Rev. Oct/16
Document number 469620HB series
The following instructions should be followed when trying to adjust counterbalance weights on HB series dampers. This is not intended to be used to modification for use as pressure relief damper.
counterbalance on one (linkage) side of damper. Dampers with two sections will have linkage on both sides of damper assembly. Arms are usually mounted on every other axle, starting at the bottom, until the magnitude of the counterbalance requires arms on every axle. The steel airfoil models HB-230 and HB-330 will require more counterbalance weights than model HB-120 with single thickness blade or models HB-110 and HB-240 with aluminum blades. The longer arms are angled so they will nest when installed on every axle. Greenheck policy is to distribute counterbalance evenly among blades to minimize linkage loading and to improve blade closure.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
Receiving anD HanDling
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F(37ºC).
Safety WaRning:
improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
Heavy Duty/Industrial backdraft damper are adjusted for the specified flow direction at the factory. The external counterbalance is adjusted for “easy operation”. These instructions address adjustment of the blade counterbalance for the following:• Damper mounting orientation and/or flow direction has
changed in the field• Damper requires excessive start-open pressure or does
not close• Blade seal has been removed in the field• Counterbalance settings have been erroneously
“adjusted” in the field
Single section wide dampers will have external blade
instructions
installation, Operation, and Maintenance instructions
®
Rev. Oct/16 Book 5404-1
KMnhymEmWHEMRGE
‘414
\
//\/\/\§\“EU‘’V§_§__\_‘L~_~‘\‘\‘§‘\_
///
\/\/\\/\//
4\/
L\N_N
1. Adjust FULL OPEN blade stop first. On most models, a bolt with a spacer is used through the top linkage clevis arm. Open and close damper to verify there is no interference between axles and the nested counterweight arm.
2. Place damper in the installed mounting position and flow direction.
3. Adjust blade counterbalance at full open position first. Fan (flow) must not be operating. Rotate damper blades open. the crankarms or counterweight arms are generally 180° from the damper blade centerline. On very small dampers with aluminum blades, the crankarm may be inclined towards damper outlet, due to the torque of the linkage. Adjust counterweight plate center distance until blades will start to close from full open position. Moving plate(s) out will increase counterbalance. It may be necessary to add or delete a plate. Counterweight plate quantity per arm should not vary by more than one and the distance outward from the axle centerline should not vary more than 1/2 inch among counterweight arms.
4. Close damper. Blades should close completely (you can feel the blade edge seals make contact) without slamming. NOTE: Counterweight arms are welded to the axles as shipped. Arm adjustment will require weld to be removed and to be rewelded after modification. • If closing too hard, loosen arm fastener to the axle
and rotate top of arm towards upstream of air entering side. Retighten fastener.
• If not closing, loosen the arm fastener to the axle and rotate top of arm towards downstream or discharge. Retighten fastener.
Counterbalance weight assembly(square axle units)
Counterbalance arm assembly(long & short arm)
Damper Maintenance
Greenheck's dampers are designed to be trouble free and hassle free under normal operation. Dampers are to be installed square and straight so as to prevent binding during operation. The following annual damper maintenance suggestions will help to insure proper damper operation and increase the life expectancy of the damper.
foreign Matter Over the course of time, dirt and grime may collect on damper surfaces. The damper surfaces should be cleaned to prevent hindrance to airflow.
Moving Parts Make sure that parts such as linkage, bearings, blades, etc. that are intended to move freely, can do so.
Bearings. Plastic and pressfit ball bearings (without grease fittings) do not require lubrication. Ball bearings with grease fittings should be lubricated as follows:
Maximum Duct Temperature
°F °C Lubricant Minimum Frequency
250 121 NLGI Grade 2 lithium 12-hydrostearate grease
twice a year
closure Remove foreign materials that may be interfering with blade closure or effective sealing of the blades with each other or with the frame. Inspect blade seals yearly and replace as necessary.
Operation While operating the damper through its full cycle, check to see that the blades open and close properly. If there is a problem, check for loose linkage.
counterbalance adjustment instructions
See letter fromManufacturer included withO&M Manual
Book 5404-2
Rev. Oct/16
0
\_/
‘E?
COUNTER WEEHTPLATES
COUNTERWETGHT ARM O
(5 H O RT/ LO N G) @
1 ‘5/4" AXLE ORAXLE ADAPTER
\A/
counterbalance adjustment instructions cont...
5. Open damper and recheck full open operation. Readjust per step 3 if necessary. Recheck full closed position (step 4) as any modification at one position has a slight impact on the other.
6. Tighten all counterweight and arm fasteners securely.
componentapplicable
Modelgalvanized
Part numberStainless
Part numberAxle Adapter, 3/8” to 3/4” square OD
HB-110, HB-120 370120 416343
3/4” Crankarm All 652982 687738
3/8”-16x2 Crankarm Bolt All 415882 415924
3/8”-16 Hex Nut for Crankarm
All 415457 415799
Short Counterweight Arm (81/2 in. )
All 657344 689404
Long Counterweight Arm (121/2 in. )
All 657343 683951
3/8”-16 set screw for short/long arm
All 415050 415763
3/8” -16 Weldnut/Hex nut for short/long arm
All 415127 415799
Counterweight plate, 21/2” x 31/2”
All 653143 687636
Counterweight plate, 31/2” x 31/2”
All 653142 687635
1/4”-20 Serrated Flange Nut All 415455 415575
1/4”-20 x 3/4” Bolt All 415490 415573
1/4”-20 x 11/4” bolt/ 11/2” bolt
All 415973 416103
Standard components
7. Test damper closure by opening damper blades and releasing from 1/4, 1/2, 3/4 and full open position. Damper should close from all positions without assistance.
469620• HB Series Rev. 2, October 2012 Copyright 2012 © Greenheck Fan Corporation
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com
Our Commitment
Rev. Oct/16 Book 5404-3
T T@G”§€”'J',E¢!‘
P.O. Box 410 Schofield, WI 54476
Phone: 715.359.6171
www.greenheck.com
March 18, 2015
Mr. Aaron Avila
Norman S. Wright Mechanical
99A South Hill Dr
Brisbane, CA 94005
Re: Backdraft damper – NFPA130
Dear Aaron,
In response for a backdraft damper at 40” x 40” (12 total) with the following qualifications-
• 2900 FPM Velocity
• 0.1” Opening Pressure
• Rated for a ONE TIME usage of 482 F for maximum of 1 hour in an emergency smoke
evacuation, consider the damper unusable after this event.
Our model HB-230, fitted with stainless steel sleeve bearings will put up with the temperature
requirements of the NFPA-130 specifications.
Should you have further questions, please let us know.
Best regards,
Bill Lampkin
Product Manager
Industrial Damper Group
Book 5404-4
Rev. Oct/16
5§G"§€»"'€',E9!-‘
71¢»/91»?/4
TABLE OF CONTENTS
CHAPTER 5 – WARRANTY
WARRANTY .............................................................................................................................. 5-1
LIST OF FIGURES
CHAPTER 5:
None
LIST OF TABLES
CHAPTER 5:
None
END OF TABLE OF CONTENTS
Rev. Oct/16 Book 540
THIS PAGE INTENTIONALLY LEFT BLANK
Book 540 Rev. Oct/16
VTA’s BART Silicon Valley Berryessa Extension
WARRANTY INFORMATION
Covered Equipment Description Dampers:
• Fire Dampers
• Fire/Smoke Dampers
• Actuators for Fire/Smoke Dampers
• Backdraft Dampers
Equipment Location & Tag Numbers Berryessa & Milpitas Stations:
General Contractor Skanska, Shimmick, Herzog 1436 California Circle Milpitas, CA 95035 (408) 490-1082
Subcontractor Blocka Construction Inc. 4455 Enterprise Street Fremont, CA 94538 (510) 657-3686
Manufacturer’s Representative Norman S. Wright 99A South Hill Drive Brisbane, CA 94005 (415) 467-7600
Manufacturer Greenheck Fan Corporation P.O. Box 410 Schofield, WI 54476 (715) 359-6171
Date of Substantial Completion/Acceptance To Be Determined (TBD)
The Subcontractor, detailed above, warrants that all equipment, materials, and labor furnished or performed to install the covered equipment under the Contract shall be satisfactory for its intended purposes and shall be free of all defects in the materials and workmanship for a period of two (2) years from and after Substantial Completion/Acceptance. This warranty does not cover defects and/or failures resulting from improper maintenance and/or operation.
Warranty Commencement Date TBD
Warranty Expiration Date TBD
Upon written notice from the District of any defect in the materials or labor for the equipment detailed above during the applicable warranty period due to defective equipment, materials, or workmanship, the affected item or part thereof shall be repaired, or replaced within a time period and in a manner acceptable to the District.
Rev. Oct/16 Book 5405-1
THIS PAGE INTENTIONALLY LEFT BLANK
Book 5405-2
Rev. Oct/16