Upload
skylarks
View
240
Download
0
Embed Size (px)
Citation preview
7/27/2019 Transient Threats in RS-485.pdf
1/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
odays process control architectures and closed-loop systems are developed with numerous
serial drops using point-to-point, multi-drop, or multipoint systems. Te distances between serial
drops can range rom several meters to over a thousand meters. Data transer protocols such
as IA/EIA-485, IA/EIA-232, IA/EIA-422, eld buses, CAN, Probus, Interbus, and LVDS,
enable communication with various remote devices such as sensors, actuators, or monitors
connected throughout the system. Te RS-485 dierential interace is useul in long distance
communications where immunity to commonmode noise is prevalent, typically ound in theprocess control actory setting. Process control systems must be designed with robust protection
needed during installation (handling) and commissioning (miswiring), with high expectation
o surviving signicant transients (system transients/lightning). Tis application note describes
circuit protection solutions that can be implemented to meet a variety o transient standards or
RS-485 serial device ports. Bourns circuit protection evaluation boards have been introduced
to assist the system designer in developing solutions utilizing the Bourns BU High-Speed
Protector (HSP), Metal Oxide Varistor (MOV), Gas Discharge ube (GD), and ransient
Voltage Suppression (VS) diode products.
Introduction to RS-485As a standard or industrial communications, RS-485 eatures ast data rates that achieve 35 Mbps
or short distances and 100 kbps over longer distances. It is not unusual to encounter miswiring
and short circuit aults, especially when covering longer distances. ransients and surges also can
be generated by induced energy on the data lines due to environmental conditions or switching o
heavy inductive loads. Any o these issues can degrade the serial ports data transer perormance.
RS-485 commonly is deployed in building automation, security system controls, and other
industrial communication applications. One common application o RS-485 that illustrates its
sensitivity is an elevator control system. With cables in motion, and large motors and inductors in
proximity, rugged communication systems are required.
RS-485 systems are inherently more robust than many other networks because the signal is
delivered dierentially between two wires, relative to a third reerence voltage. Te reerence
voltage is oen, but not always, the local earth potential. Tis provides substantial immunity to
common mode noise such as ground noise and induced noise rom nearby motors, solenoids
and transormers. Te interace uses voltages that are high by communication system standards,
also making it more robust than networks using other protocols. For instance, Ethernet signals
are about 2 V and the popular USB standard communicates at a maximum o 5 V, though much
internal communication in a computer is even lower. RS-485, on the other hand, allows or
common mode voltages rom -7 V to +12 V. Te voltage drop between distant nodes can be
accommodated without adding expensive equipment along the path.
7/27/2019 Transient Threats in RS-485.pdf
2/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
able 1: RS-485 Interace Specifcations
Dierential yes
Max. number of drivers 32
Max. number of receivers 32
Modes of operation half duplex
Network topology multipoint
Max. distance 1200 m
Max. speed at 12 m 32 Mbps
Max. speed at 1200 m 100 kbps
Receiver input sensitivity +/- 200 mV
Receiver input range -7 V to +12 V
Max. driver output voltage -7 V to +12 V
Max. driver output voltage with load +/- 1.5 V
RS-485 Port Interace RequirementsDisplayed in table 1 are the interace specications or RS-485 ports. Key electrical parameterso -7 V to +12 V operating voltage with 32 Mbps data transer at distances o 1200 meters
are included. A ully compliant RS-485 port must meet IEC 61000-4-2 (ESD), IEC 61000-4-4
(EF) and IEC 61000-4-5 (Surge) standards.
Every serial port design ollows the nominal recommended voltage range or the bus pins.
RS-485 denes how much protection the device has beyond the 7 V to +12 V. I the
environment demands that the bus survives up to 24 V, then external protection must be
added or adapted to meet compliance standards. Bourns oers various circuit protection
technologies or overcurrent and overvoltage protection. Te selection o a device or
combination o devices depends on the requirements o the application and the specications
o other devices such as the serial bus driver.
7/27/2019 Transient Threats in RS-485.pdf
3/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
Protection or RS-485 Ports
A general protection scheme or an RS-485 network includes a VS diode array such as the BournsModel CDSO23-SM712 device on each node. Tis single-stage bidirectional device provides
asymmetrical overvoltage protection or the RS-485 transceiver across the entire -7 V to +12 V
common mode voltage range. For RS-485 systems with limited exposure, this VS diode array may
be all that is needed or reliable operation.
Efective Circuit Protection in ActionTe single-stage VS diode solution will provide eective clamping o the transient signal up to
the peak impulse current, IPP, o the VS diode. IPP is the maximum current the VS diode can be
subjected to without ailure. As the VS diode is exposed to higher transient voltages, concern orexceeding this devices current limitation rises as well. Current limiting must be used to keep IPP
within its rated limit. A VS diode with series resistance Rx, shown in gure 1, is eective or low
level transients. As the transient voltage increases, the power rating (and physical size) o the VS
diode and series resistance also must increase to limit the VS diodes current below the devices
IPP (peak pulse current rating). Te transient energy will be a unction o the transient pulse
width, duration, and slew rate (dv/dt). Most VS diode data sheets will provide the PPP rating
or either 8/20 s or 10/1000 s surges. In addition, VS diode data sheets may provide a log-log
graph describing the diode perormance when exposed to longer or shorter transient pulses.
As the transient energy increases, the limitation o the single-stage solution becomes apparent.
For example, i the series resistance Rx is increased to limit the maximum current to the VS
diode, then the voltage drop during normal operation o the communications loop will aect
signal transition levels. Te communication loop distance is shortened as a result o the increased
resistance. Te required size and power dissipation o the Rx resistor increases as the magnitude
o the transient voltage and current increases and a practical solution is no longer achievable. As
we will discuss, the three-stage transient protection scheme oers the capability to handle large
transients with minimal impact on the length o the communication link, occupying a small area
on the printed circuit board (PCB).
Figure 1: VS Diode Plus Resistor
RS485
Transceiver Itransient
Rx
CDSOT23-SM712
TVS Diode
7/27/2019 Transient Threats in RS-485.pdf
4/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
Efective Circuit Protection in Action (Continued)
Te three-stage protection scheme, gure 2, provides an optimal approach when protecting the RS-485 transceiver in applications located in more exposed transient environments with large signal
levels and ast rising, long duration surges. Tis solution uses VS diodes or secondary protection,
Bourns BU HSP devices or coordination, and either MOVs or GDs or primary protection.
Te response characteristics o these circuit protection components are coordinated to provide a
robust level o protection or the RS-485 interace that ar exceeds the transient handling capability
o a single-stage component solution.
Implementing the Three-Stage Protection SolutionFigure 2 shows the topology or three-stage coordinated protection. Components are chosen
to provide coordinated protection beginning where the transient enters the protected port.
An MOV or GD primary device protects the Bourns BU HSP rom exposure to excessive
transient voltage, clamping or crowbarring to a level less than impulse. When the transient
current exceeds the Bourns BU HSP trigger current limit, the sub-microsecond response o
the Bourns BU HSP limits the current let-through to the sensitive transceiver. Te VS diodes
at the RS-485 transceiver provide a tight voltage clamp to keep the RS-485 signals within the
absolute maximum voltage ratings o the transceiver.
EquipmentPrimaryDevice Port
TBU HSP
TBU HSP
TVSDiodes
Figure 2: Tree-Stage Coordinated Protection
7/27/2019 Transient Threats in RS-485.pdf
5/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
Understanding the Operation o the Bourns TBU High-Speed Protector
Te BU-CA Series o Bourns BU HSP products are low capacitance, single, bidirectional, high-speed (sub-microsecond) circuit protection components constructed with MOSFE semiconductor
technology. Tey are designed to protect against aults caused by short circuits, AC power cross,
induction, and lightning surges up to rated limits, and then reset once the ault clears. Te Bourns
BU HSP oers a signicant perormance increase in terms o response time compared to solutions
previously available. Te Bourns BU HSP oers simplied place and route manuacturing
due to the small size o the Bourns BU-CA package, which measures a mere 6.5 mm by 4 mm.
Te Bourns BU HSP is available in a surace mount DFN package meeting industry standard
requirements such as RoHS* and Pb-ree solder refow proles.
Te three-stage topology handles large transient surges through sub-microsecond coordination
o the BU HSP with the primary and secondary elements. During normal circuit operation, the
Bourns BU HSP presents a nite series resistance to the communication loop. As the transient
current increases to the BU HSP trigger current level, the BU HSP switches to a very high
resistance or protected state, eectively disconnecting the transient rom the sensitive RS-485
transceiver. Te Bourns BU HSP enters this protected state in less than 1 microsecond, providing
a fat response over operating temperature, independent o requency o the incident transient
signal. Te linear, high-speed response o the BU HSP helps to minimize transient testing
requirements and time spent preparing or regulatory compliance.
In any transient environment, power cross and high surge current are signicant challenges or
circuit designers especially when working in a nite PCB area. As discussed previously, the VSdiode and resistor single-stage solution is eective in handling small to medium transients but
impractical or power cross and large surge currents. Te Bourns BU HSP oers a signicantly
smaller ootprint that will handle power cross up to 265 Vrms and surge currents above 20 kA when
used in combination with the right primary protector. o demonstrate the response o the three-
stage protection scheme, measurements were made using the schematic in gure 3. Te 100 load
resistor eatured in the schematic is not necessary in an actual application. It is used in this instance
to mimic the load o the application circuit.
Figure 3: Bourns BU HSP ransient esting Circuit
TBU-CA085-300-WH
LoadGenerator
Schaffner 1.2/500.5/50
ECAT 0.5/70010/700
1:2 AC IsolationTransformer
Surge GeneratorCDSOT23-SM712
100
+
-100TBU-CA085-300-WH
7/27/2019 Transient Threats in RS-485.pdf
6/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
Selecting the Primary and Secondary Protector in a Three-Stage Topology
Te purpose o the primary protector is to prevent voltage excursions greater than Vimpulse romreaching the Bourns BU HSP. Tus the clamping or crowbar voltage o the primary protector must
be less than Vimpulse at the surge current, Isurge, where Isurge = Vgenerator/Rgenerator. Isurge is based on
the transient environment with threat levels dened per IEC 61000-4-5.
Te secondary voltage protector is chosen to clamp or crowbar at a voltage less than the absolute
maximum voltage rating o the RS-485 transceiver. Since the BU HSP has a very ast response o
less than 1 s, only a minimal amount o current is let-through to the secondary device, worst-case
leaving a small amount o energy to be handled by the transceiver internal steering diodes.
Capacitance is another key consideration when selecting the primary and secondary protectors. I
the maximal allowable capacitance o the interace is exceeded, then the bandwidth o the nodes is
limited. Te capacitance on this signal is a lumped eect rom the cabling, connector, and circuit
protection components. Estimating the capacitance rom the cabling and connector will indicate the
maximal capacitance budget remaining or the circuit protection components.
Transient Test DataTe ollowing oscillograms are helpul in understanding the perormance o the Bourns BU
HSP-based three-stage protection solution or AC power cross and a variety o transient surges.
Using the schematic rom gure 3, the ollowing waveorms demonstrate the negligible signal
energy seen at the secondary VS diode clamp, i.e. IBU is a raction o Itransient.
Figure 4: 28 Vrms Power Cross
4
2
Ch1
500 mA Ch4
10.0 VCh250.0 V
T
1
T
TrigdT
Vtransient
= 28.2 Vrms
Vtvs
= 15.47 V peak
Itbu
= 478 mA
Line 100 VM A4.00 ms
19.40 %T
7/27/2019 Transient Threats in RS-485.pdf
7/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
Transient and Protection Level Test Data (Continued)
Figure 5: 120 Vrms Power Cross
Figure 6: 220 Vrms Power Cross
2
4
Ch1
500 mA Ch4
10.0 VCh2200 V
T
1
TT
TrigdT
Vtransient
= 123.7 Vrms
Vtvs
= 15.3 V peak
Itbu
= 308 mA
Line 100 VM A4.00 ms
19.20 %T
4
2
Ch1
500 mA Ch4
10.0 VCh2200 V
T
1
TTT
TrigdT
Vtransient
= 220.5 Vrms
Vtvs
= 15.2 V peak
Itbu
= 280 mA
Line 100 VM A4.00 ms
19.40 %T
7/27/2019 Transient Threats in RS-485.pdf
8/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
Transient and Protection Level Test Data (Continued)
Te above power cross and transient surge examples demonstrate the predictable response o
the BU HSP in limiting current to the protected load. Further, the three-stage protection
topology allows the designer to easily select primary and secondary components to provide a
robust transient response with minimal verication testing.
Figure 7: 1.2 s trise/50 s tallSurge
Figure 8: 0.5 s trise/700 s tallSurge
42
Ch1
500 mA Ch4
10.0 VCh2200 V
T
T
1
TT
TrigdT
Vtransient
= 864 Vrms
Vtvs
= 18.2 V peak
Itbu
= 1.78 mA
Line 100 VM A1.00 s
19.40 %T
214
Ch1
500 mA Ch4
10.0 VCh2200 V
T
TTTT
TrigdT
Vtransient
= 856 Vrms
Vtvs
= 18.6 V peak
Itbu
= 2.6 mA
Line 100 VM A1.00 s
19.40 %T
7/27/2019 Transient Threats in RS-485.pdf
9/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
RS-485Transceiver
P40-G240-WH
D5 D6
Output_P
Output_N
TISP4015L1BJ TISP4015L1BJ
1
1 1
3
2 2
4 6
24 VDCTransient
Handling DC Power Faults using the TBU HSP
A DC bus, used or relay control and actuators, is typically ound in the implementation oindustrial communication systems. Tis leaves the potential or DC power being miswired rom
installation mishaps resulting in a DC power connection to the RS-485 dierential signal lines.
Tis hard ault (vs. transient ault) requires special consideration when designing a BU HSP
electronic current limiter-based protection circuit. As the BU HSP is a semiconductor, the
power dissipation with a sustained ault rom direct current is signicant and a design which
ensures the BU HSP is in the protected (high-impedance) state is critical to a repeatable and
robust solution. Te circuit conguration in gure 4 utilizes a P40-G240-WH HSP to handle
the 24 V power ault case:
Figure 9: Handling DC power aults with the BU HSP
7/27/2019 Transient Threats in RS-485.pdf
10/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
Handling DC Power Faults using the TBU HSP (Continued)Te BU HSP operates in the high-impedance (protected) state when the voltage across the
BU HSP is greater than Vreset (typically 7 volts). During the DC power ault, the thyristor
(ISP4015L1BJ) is used to crowbar the power ault to zero volts at the RS-485 transceiver. Te 24
V across the BU HSP exceeds the P40-G240-WH Vreset orcing the BU HSP into the protected
state. Aer the power ault is cleared, the BU HSP resets and normal RS-485 circuit operation
resumes. Te P40-G240-WH solution can handle aults less than or equal to 40 V (Vimpulse).
By combining the transient solution rom gure 3, and the DC power ault solution o gure 4,
high-speed transients and AC and DC power cross are able to be handled in the ollowing
BU HSP-based circuit, gure 5:
In the robust transient solution above, the MOV provides ESD/EF protection while the
GD handles high surge current, protecting the BU-CA085 rom signals greater than 850 V
(BU-CA085 Vimpulse). At the input to the P40, back-to-back VS diodes are used to protect
the P40-G240-WH, clamping signals to less than 40 V. (P40-G240-WH Vimpulse). Te DC
ault is handled by the combination o the thyristor (ISP4015L1BJ) and P40-G240-WH HSP.
As the transient environment varies in each application, the BU HSP congurations
discussed are or the specic conditions outlined within. Please contact Bourns to discuss
your specic application requirements.
Figure 10: Handling AC & DC Power Fault & High-Speed ransients with the BU HSP
SMBJ25A
RS-485Transceiver
TBU-CA085-300-WHInput_P
Input_N
MOV-10D201
MOV-10D201
2027-15
2027-15
TBU-CA085-300-WH
P40-G240-WH
D5 D6
D1
SMBJ25A
SMBJ25A
SMBJ25A
D3
D2 D4
Output_P
Output_N
TISP4015L1BJ TISP4015L1BJ
1
1
1 1
1
3
3
3
2 2
4 6
Transient Levels (minimum):ESD IEC61000-4-2 Level 4, 8 kV contact;
15 kV air dischargeEFT IEC61000-4-4 Level 3, 1 kV, 20 ACurrent surge IEC61000-4-5 Level 4, 4 kV, 95 AAC power cross 120 VrmsDC power cross +/- 24 VDC
Transient
7/27/2019 Transient Threats in RS-485.pdf
11/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 e/CPK1146
Bourns Evaluation Boardswo evaluation board options are available to designers when evaluating the bidirectional
Bourns BU-CA HSP Series. RS-485 Evaluation Board 1 provides a very high current primary
protector solution with a GD. Tis solution will support high bandwidth signals with no
signal degradation because o the GDs extremely low 1 p capacitance loading. RS-485
Evaluation Board 2 will support medium bandwidth signal interaces above 10 MHz using an
MOV primary protector. Tis level o protection provides a low cost solution or most RS-485
interaces and transient currents up to 2.5 kA. o oer maximal fexibility these evaluation
boards support many protection combinations. It is important to review the transient
requirements prior to use to ensure the current surge and power cross levels are capable o the
required perormance. Please contact a local Bourns representative or Bourns customer service
to order evaluation boards.
Figure 11: RS-485 Evaluation Board 1: GD Primary Protector
Figure 12: RS-485 Evaluation Board 2: MOV Primary Protector
7/27/2019 Transient Threats in RS-485.pdf
12/12
Handling Transient Threats in RS-485 Systems
BU-CA085-300-WH
P40-G240-WH
MOV-10D201K
2031-23-SM-RPLF
CDSO23-SM712
ISP4015L1BJ
10/11 /CPK1146
Summary
Te recommended three-stage protection solution eaturing Bourns BU HSP devices oersenhanced perormance over competing solutions. Design engineers can take advantage o this three-
stage solution to increase the surge and transient protection levels on RS-485 ports and have robust
protection against signicant transient events such as AC power cross, ESD, EF, and surge current.
Bourns approach protects the RS-485 transceiver by combining the Bourns BU HSP to limit the
let-through voltage and energy, the VS diode to keep the signal within the maximum limits o the
RS-485 transceiver, and a primary GD or MOV to protect the BU HSP by limiting the maximum
voltage to which it is exposed. Bourns oers developers evaluation boards to allow easy prototyping.
Board conguration options assist in selecting the most suitable part number or this Bourns BU
HSP-based three-stage solution. Te compact size o the BU HSP can reduce the overall board area
compared to what was required previously to meet the protection requirements.
Te use o Bourns BU HSP devices brings a new level o overvoltage and overcurrent protection to
RS-485 drivers.
Why Bourns?Te BU High-Speed Protector technology is unique to Bourns, a company that has been a proven
leader in the circuit protection industry or several decades. Bourns invests in innovative new products
through internal development and strategic acquisition o companies and products lines. Bourns serves
diverse markets rom computers and peripherals to telecommunications. Te companys commitment
to excellence in design and customer service and its established track record in circuit protection or
over hal a century sets Bourns apart rom its competition in terms o quality and integrity.
Reerences:More inormation on the Bourns BU HSP and other Bourns circuit protection solutions can be
ound online:
http://www.bourns.com/data/global/pdfs/bourns_tbu_white_paper.pdf
http://www.bourns.com/data/global/pdfs/TBU-CA_MDS.pdf
http://www.bourns.com/ProductFamily.aspx?name=circuitprotection
http://www.bourns.com/data/global/pdfs/Bourns_FU1106_RS-485_Evalboard_
DesignNote_1.pdf
http://www.bourns.com/data/global/pdfs/Bourns_FU1106_RS-485_Evalboard_
DesignNote_2.pdf
For urther technical support and or complete port solutions,please visit
www.bourns.com
Americas: el+1-951 781-5500 Fax+1-951 781-5700 Europe: el+41-(0)41 768 55 55 Fax+41-(0)41 768 55 10 Asia-Pacifc: el+886-2 256 241 17 Fax+886-2 256 241 16
Bournsand TBU are registered trademarks of Bourns, Inc. in the U.S. and other countries.
COPYRIGHT 2011 BOURNS, INC. 10/11 e/CPK1146
*RoHS Directive 2002/95/EC Jan. 27, 2003 including Annex.