Upload
anadamms
View
234
Download
0
Embed Size (px)
DESCRIPTION
test
Citation preview
TRANSIENT IMPEDANCE OF GROUNDING RODS
I. F. Gonos F. V. Topalis I. A. Stathopulos
National Technical University of AthensDepartment of Electrical and Computer Engineering, High Voltage Laboratory
Abstract: The aim of this paper is thecorrelation of the transient impedance and itsparameters with the stationary resistance ofsimple grounding systems. Impulse current testsof the standard form 8/20 s were performed onseveral types of equilateral triangles and singledriven rods of different lengths. The injectedcurrent in the grounding system and thedeveloped potential were recorded, resulting inthe determination of the time variation of thetransient impedance. Further mathematicalanalysis of the experimental results led to simplelinear relations between the parameter oftransient impedance and the stationaryresistance. The results provide usefulinformation for the design of a grounding systemand the measures for the protection ofinstallations from lightning strokes.
Key words: Grounding system, transientimpedance, stationary resistance.
1. Introduction
The grounding systems serve multiple purposes.Not only they do insure a reference potentialpoint for the electric and electronic devices butalso provide a low resistance path for faultcurrents into the earth. Such fault currents canarise either from internal sources or fromexternal ones e.g. by lightning strokes andindustrially-generated static electricity. Theresistance of grounding systems has an essentialinfluence on the protection of the groundedsystem. Grounding systems can consist of one ormore vertical or horizontal ground rods, three ormore vertical ground rods connected to eachother and two or three-dimensional grids frommetal rods and foundation grounding systems.
The behaviour of the grounding system underlightning determines the degree of protectionprovided. This makes obvious the purpose ofanalysis procedures predicting the transientresponse of grounding systems. If an equivalentcircuit approach is adopted these procedure canbe implemented in a simulation model [1-7].
The specific value of impulse impedance whichis of main interest is the one corresponding tothe beginning of the steep ascent for the wave-front. The results reveal its value to be quitehigher than the stationary value of its groundresistance and reduces to this latter value [3, 5].
The work presented in this paper refers to theproblem of transient analysis of practicalgrounding systems consisting of grounding rodsunder impulse lightning currents.
2. Fundamentals
The driven rod is one of the simplest and mosteconomical form of electrodes. The stationaryresistance R of a driven rod is given by thefollowing formula [7]:
R ln8 l
d1=
2 l
(1)
where: is the resistivity of the ground,l is the length of the rod andd is the radius of the rod.
Fig. 1: Equivalent circuit for a driven rodstressed by an impulse current
When the electrode voltage changes with time,there will be a conductive current in addition toa capacitive current. The equivalent circuit of adriven rod under impulse current is shown inFig. 1. The resistance R of the rod is given bythe Eq. (1) and the inductance L of such a rod isequal to [7, 8]:
L ln4 l
d10 7=
2 l (2)
The capacitance C of the ground rod is [7]:
C
18 ln4 l
d
10 9=
r l (3)
where r is the dielectric constant of the soil.
The impulse impedance of a grounding system isnecessary for determining its performance whiledischarging impulse currents to ground, as in thecase of lightning and transient grounds faults.The impulse impedance is define Z is defined asthe ratio of the impulse voltage to the impulse:
Z tU ti t
( )( )( )
= (4)
U(t)
i(t)
Z(t)
t2t1
Imax
Umax
Fig. 2: Definition of the parameters of impulseimpedance
Four parameters of impulse impedance (Fig. 2)are defined as follows [3]:
Z1 = max(Z(t)) (5)
ZU t
i t21
1
=( )
( )(6)
ZU ti t3
1
2
=( )
( )(7)
ZU t
i t42
2
=( )
( )(8)
where:Z1 is the maximum value of the ratio of impulsevoltage to impulse current, Z2 is the ratio of themaximum value of voltage to the respectivevalue of current when voltage reaches itsmaximum, Z3 is the ratio of maximum value ofvoltage to the maximum value of current and Z4is the ratio of voltage when current reaches itsmaximum to the maximum value of current.
It is obvious:
Z1 > Z2 > Z3 > Z4>R (9)
A lightning discharge affects the resistance of agrounding system in two ways. The current is upto 100 kA or more and has a much higherfrequency spectrum than the stationary case.The transient impedance becomes greater as:
the inductivity of the wire and of theconnection becomes greater
the high value of current can dry the ground,
the high frequency spectrum shortens theelectrical length of long grounding wires
the skin effect rises the resistance and theinductivity of wires due to the value of thefrequency.
The transient impedance becomes smaller as theelectrical field strength on the surface ofgrounding system can reach values wherepredischarges in the ground start; thesedischarges can lead to ground ionisation thatdestroy layers with high resistance [4].
3. Experimental apparatus and testtechniques
The layouts of grounding system (Fig. 3) weretested experimentally under impulse lightningcurrent of waveshape 8/20 s The maximumvalue of the current was varying up to 3 kA. Thefirst grounding layout was a single driven rodand the second one was an equilateral trianglewith three vertical rods. Cooper rods withdiameter 20 mm were used. The measured value
of the earth resistivity was found to be equal to30 m. The waveforms of the impulse currentand of the potential of grounding system wererecorded directly by a data acquisition systemcontrolled by a personal computer, withmeasuring bandwidth of 20 MHz.
Fig. 3: Experimental set-up
4. Test results
The measurements values of peak voltage, peakcurrent and impedance of ten different groundinglayouts are presented in Table 1.
Table 1: Experimental results.
Electrode l[cm]
R[]
Upeak[kV]
Ipeak[A]
Z3[]
A rod 50 68.2 5.14 13.7 375A rod 75 31.0 5.08 16.5 308A rod 100 22.3 5.03 17.7 284A rod 125 14.6 5.00 18.8 266A rod 150 12.1 4.99 19.3 259
Three rods 50 27.0 4.91 16.7 294Three rods 75 15.6 4.87 18.3 266Three rods 100 10.7 4.83 19.3 250Three rods 125 7.6 4.80 20.0 240Three rods 150 6.9 4.79 20.3 236
0 10 20 30 40 50 60 70 80 90 100-5
0
5
10
15
20
t [sec]
I [A
]
Fig. 4: Waveform of the injected current.
In these figures, the test results for thegrounding system of a driven rod with diameter20mm and length 75cm are presented. Thewaveforms of the injected current is shown inFig. 4. The measured potential with reference tothe ideal earth is shown in Fig 5. The transientimpedance of the grounding system under thisstress is the one of Fig. 6.
0 10 20 30 40 50 60 70 80 90 1000
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
t [sec]
U [V
]
Fig. 5: Waveform of the potential.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10
100
200
300
400
500
600
700
800
900
1000
t [sec]
Z [
]
Fig. 6: Variation of the impulse impedance
5 10 15 20 25 30230
240
250
260
270
280
290
300
R []
Z3
[]
Fig. 7: Variation of the impulse impedance vs.stationary resistance for driven rod.
10 20 30 40 50 60 70240
260
280
300
320
340
360
380
R []
Z3
[]
Fig. 8: Variation of the impulse impedance vs.stationary resistance
The variation of the parameter Z3 of impulseimpedance versus the stationary resistance ofsingle driven rod is presented in Fig. 7. Therespective variation of the equilateral triangle ispresented in Fig 8. Further mathematicalanalysis of the experimental results leads to thefollowing relation between Z3 and R of thesingle driven
Z R3 2 053 237 5= +. . (10)
A similar relation for the equilateral triangle,was found to be:
Z R3 2 847 2187= +. . (11)
5. Conclusions
The performed measurements show that thetransient impedance reaches its maximum valuevery fast (fraction of microsecond) andconsecutively is reduced to the value of thestationary resistance. the one corresponding tothe beginning of the steep ascent for the wave-front. The results reveal the value of thetransient impedance to be quite higher than thestationary resistance. The determined analyticalrelations between the parameters of the transientimpedance and the stationary resistance allowthe limitation or even elimination of time andmoney consuming experiments. It will alsofacilitate the optimisation of any plannedgrounding system. The computer aidedoptimisation of grounding systems is veryuseful, since the improvement of them after theirinstallation is a difficult task and sometimes notpossible.
References.[1] Suflis, S.A., Gonos, I.F., Topalis, F.V. and
Stathopulos I.A.: Transient behaviour of ahorizontal grounding rod under impulsecurrent, Recent Advances in Circuits andSystems, Word Scientific PublishingCompany, Singapore, 1998, pp. 61-64,
[2] Suflis, S.A., Gonos, I. F., Topalis, F. V. andStathopulos I. A.: Transient behaviour of ahorizontal grounding rod under impulsecurrent, 2nd International Conference onCircuits, Systems and Computers (IMACS-CSC98), October 1998, Piraeus, Greece,pp. 289-292.
[3] Gonos, I.F., Antoniou, M.K., Topalis, F.V.and Stathopulos I. A.: Behaviour of agrounding system under impulse lightningcurrent, 6th International Conference andExhibition on Optimisation of Electrical andElectronic Equipment (OPTIM 98), May1998, Brasov, Romania, pp. 171-174.
[4] Bogensperger, H.J., Frei, J. and Pack, S.:Resistance of grounding systems, stationaryand transient behaviour, 9th InternationalSymposium on High Voltage Engineering,August 1995, Graz, Austria, pp. 6715-1-4.
[5] Verma, R. and Mukhedkar D.: Impulseimpedance of buried ground wire, IEEETrans. on Power Apparatus and Systems,1980, PAS-99 (5) pp. 2003-2007.
[6] Meliopoulos, P.A. and Moharam, G.M.Transient Analysis of Grounding Systems,IEEE Trans. on Power Apparatus andSystems, 1983, PAS-102 (2) pp. 389-397.
[7] Kalifa, M.: High Voltage Engineering,Theory and Practice, Dekker, USA, 1990,pp. 331-356.
[8] Gupta, R.B., and Thapar, B. ImpulseImpedance of Grounding Grids, IEEETrans. on Power Apparatus and Systems,1980, PAS-99 (6) pp. 2357-2362.
Address of AuthorsNational Technical University of AthensDept. of Electrical and Computer Engineering42, Patission Str., GR-10682 Athens, GreeceTel.: +30-1- 7723539, 7723627, 7723582Fax.: +30-1- 7723628, 7723504Email.: [email protected]