Transformer Substations
Prefabricated TransformersSubstationsUp to 36 kV
Index Transformer Substations
3PFU House-Type Monoblock Transformer Substations
PF House-Type Modular Transformer Substations 10
MINIBLOK Outdoor Packaged Substation 15
ORMABAT End-of-line Packaged Substation 21
MB Frame-mounted Packaged Substation 23
PF-15 Switching Substation 22
MINISUB Underground Packaged Substation 18
ORMASET Half-buried Packaged Substations 14
PFS Underground Monoblock Transformer Substations 8
2
As a result of the constant development of standards and newdesigns, the characteristics of the items shown in this cataloguemay be changed without prior notice.
Characteristics and availability of materials must be confirmedby our Technical-Commercial department.
The quality of the products designed, manufactured andinstalled by Ormazabal is guaranteed by the implementationand certification of a quality assurance system that conformsto the ISO 9001 international standard.
Our company’s commitment to the environment protection isasserted by the implementation and certification of anenvironmental management system that conforms to the ISO14001 international standard.
The PFU Transformer Substations consist of a concrete monoblock-structure enclosure that houses all electrical switchgear fromMV switchgear to LV switchboards, including transformers,control devices and interconnecting equipment for the variouselements.
The main advantage of these Transformer Substations is thefact that both the construction, assembly and built-in equipmentcan be entirely factory-built, thus ensuring uniform quality andsignificantly minimising any on-site construction and assemblywork. In addition, the careful design of the substations allowsthe substations to be installed in both industrial and urbanenvironments.
OVERVIEW
PFU Transformer Substations allow typical power supplyarrangements consisting of up to 2 transformers with a maximumunit power of 1000 kVA(1) to be installed.
FIELD OF APPLICATION INSTALLATION
PFU-5 with 2 transformers,1000 kVA each
The installation of PFU substations is simple, since “on-site”operations can be reduced to positioning on the trench andconnecting the supply service cables, which are threaded intothe substation through knockout holes located on the bottom.
3
Transformer SubstationsPFU House-Type Monoblock TransformerSubstations
(1) For further conditions, please contact our Technical/Commercial department.
PFU-3 with 1 transformer
Access to the Transformer Substation is possible through a frontdoor, which enables access to the equipment compartment thataccomodates MV panels, LV panels and control devices of thesubstation. If operating conditions so require, a second accessdoor for personnel can be added and a physical separationbetween the utility company and customer panels can be created.
Each transformer is provided with its own door so it can beremoved from the substation or accessed for maintenancepurposses.
TECHNICALREGULATIONS/STANDARDS
IEC 61330, RU 1303AIEC 60298, RU 6407B
UNE 21428-1, HD 428, RU 5201DUNE 21538, HD 538IEC 60439-1, RU 6302B
OPERATION
PFU-5 with 1 transformer and PFU-4 substation
The substations have a reinforced vibrated concrete enclosureconsisting of two sections: one that comprises the bottom platesand side walls which include doors and natural ventilationgrilles and another one that forms the ceiling.
All concrete steel reinforcements are connected to each otheras well as to the earth bus, as specified in RU 1303. In addition,the doors and grilles feature a 10 kΩ resistance to the earthingconnection of the enclosure.
The standard finish of the substation is a rough acrylic paint(white for walls and brown for ceilings, doors and grilles).
CONSTRUCTION CHARACTERISTICS
4
CGM switchgear panels inside a PFU substation
PFU House-Type Monoblock Transformer Substations
SUBSTATIONS UP TO 36 kVPFU-3 PFU-4 PFU-5
Lenght [mm]Width [mm]Height [mm]Area [m2]Visible Height [mm]
Lenght [mm]Width [mm]Height [mm]Area [m2]
Lenght [mm]Width [mm]Depth [mm]
Weight [kg]
328023803240
7,82780
310022002550
6,8
40803180560
11000
44602380324010,7
2780
428022002550
9,4
52603180
560
12500
60802380324014,5
2780
59002200255013,0
68803180
560
18000
Outsidedimensions
Insidedimensions
Diggingdimensions
NOTE: Access door dimensions: 900/1100 x 2100 mmTransformer door dimensions: 1260 x 2100/2400
5
Transformer Substations
SUBSTATIONS UP TO 24 kVPFU-3 PFU-4 PFU-5
Lenght [mm]Width [mm]Height [mm]Area [m2]Visible Height [mm]
Lenght [mm]Width [mm]Height [mm]Area [m2]
Lenght [mm]Width [mm]Depth [mm]
Weight [kg]
328023803045
7,82585
310022002355
6,8
40803180
560
10500
44602380304510,7
2585
428022002355
9,4
52603180
560
12000
60802380304514,52585
59002200235513,0
68803180560
17000
Outsidedimensions
Insidedimensions
Trenchdimensions
For transformers rated above630 kVA, additional ventilationgrilles are mounted on the sidewall.
6
PFU-31 transformer
PFU-4without transformer
PFU-3without a transformer
3280
100
460
Visi
ble
Hei
ght
2380
Rear View
Levelling Sand
3100
MV Panels
2200
32802380
Rear View
Levelling Sand
3100
MV Panels
2200Transfo.
LV switchboards
100
460
Visi
ble
Hei
ght
Rear View
Levelling Sand
4480
4280
MV Panels
2200
2380
100
460
Visi
ble
Hei
ght
PFU House-Type Monoblock Transformer Substations
PFU-41 transformer
PFU-51 transformer2 access doors
For transformersrated above 630kVA, additionalventilation grillesare mounted onthe side wall.
For transformersrated above 630kVA, additionalventilation grillesare mounted onthe side wall.
7
Transformer Substations
PFU-52 transformers
For transformersrated above 630kVA, additionalventilation grillesare mounted onthe side wall.
4480 100
460
Visi
ble
Hei
ght
2380
Rear View
Levelling Sand
4280
MV Panels
2200Transfo.
LV switchboards
Rear View
Levelling Sand
6080
5900
MV Panels
2200
100
460
Visi
ble
Hei
ght
2380
Tranfo. Transfo.
LV switchboards
6080
100
460
Visi
ble
Hei
ght
2380
Rear View
Levelling Sand
5900
MV Panels
2200Transfo.
LV switchboards
8
PFS Transformer Substations feature a monoblock structure andhave been designed for underground installation and can housedifferent electrical power distribution arrangements, makingthem suitable for public distribution and private installationload-centre substations.
The underground installation and the easy adaptation of thesubstation area minimise any environmental impact.
Depending on the ventilation system, two different versions areavailable: PFS-V (vertical grille ventilation, protruding) andPFS-H (horizontal grille ventilation, non-protruding)
PFS Underground Monoblock Transformers Substations up to 2 Transformers
OVERVIEW
PFS Transformer Substations can be used for electrical powerdistribution up to 36 kV, including a transformer with amaximum power of 1000 kVA or 2 transformers of maximunpower of 630 kVA(1).
FIELD OF APPLICATIONINSTALLATION
PFS-V exterior view of 1 Transformer.
TECHNICALREGULATIONS/STANDARDS
IEC 61330, RU 1303AIEC 60298, RU 6407BUNE 21428-1, HD 428, RU 5201DUNE 21538, HD 538IEC 60439-1, RU 6302B
PFS-H exterior view
Installation consists mainly in bringing the packaged substationto the trench, positioning it on a compacted sand layer andconcrete slab, and then connecting the supply service andearth conductors, since switchgear assembly can be performedat the factory. All this reduces “on-site” operations to oneworking day, thus minimising costs and ensuring uniformquality for all substations.
PFS Substations have been designed for installation in gardensand on the sideways (even for those not protected fromoccasional access by vehicles, in accordance with the Instructionrelated to actions to be considered for road bridge projects)and substation finishing can be performed at the factory oron-site by means of gravel, floor tiles, etc.
On-site handing
PFS
29003700
Concrete Slaband Sand Layer
Earth Conductor
5580 - 70006380 - 7800 AA
200+
50 3040
PFS-2T
AA
(1) For further conditions, please contact our Technical/Commercial department.
Personnel can access the substation through an opening of1300 x 700 mm located on the ceiling. This entrance is coveredby a balanced cover plate such that it can be opened by asingle operator. It also deploys a metal peripheral protectionaround the access opening. The operator can descend into theload-centre substation using a step ladder, with a tilting angleunder 68°. The switching gangway is far from the access area,thus avoiding rainfall on the corridor.
The transformers access covers plates feature an opening of2100 x 1270 mm, and are equipped with four tapped insertson the outside for handling. The transformers inside the substationare separated by means of a plate and placed over the oilcollecting pit.
Materials and tools can be entered through specific cover thathas also four inserts on the outside for handling.
9
Transformer Substations
OPERATION
The substation features an extra-sturdy monoblock structureand is made of vibrated concrete and electrically welded steelreinforcements joined to the earth bus of the Transformer Substation.
Due to an impermeable concrete surface which is resistant to thepresence of sulphate on the ground, as well as the existence ofwatertight joints on the cable side entries as well as on the uppercover plates, the substation can be installed on grounds with ahigh ground-water level, even in areas with a high flood risk.
CONSTRUCTION DATA
TECHNICAL DATAPFS-H PFS-V
Lenght [mm]Width [mm]Height (depth) [mm]Visible height [mm]Maximum weight [kg]
6.1802.4602.790
025.000
5.1402.4602.790
610/82024.000
View of a PFS-V substation withthe personnel access cover opened
CGM 36 kV panels inside a PFS
PFS-H PFS-V
7.6003.0002.790
029.000
6.5602.4602.790
61026.400
1 Transformer 2 Transformers
PF Transformer Substations consist of different prefabricatedconcrete elements that are assembled on-site to create a buildingthat houses all electric switchgear: from the MV switchgear tothe low-voltage switchboards, including transformers, controldevices and interconnecting means for the different elements.
The modular structure allows Transformer Substations to beeasily transported for installation in hard-to-access areas andpermit any arrangement of the Transformer Substation to be
implemented, including the number of access doors andtransformers required for each application.Prefabrication of all elements used for building the substationsand Ormazabal’s Quality System ensures uniform quality inall Transformer Substations.
UTILIZACIÓN
OVERVIEW
PF Transformer Substations allow any electrical power supplyarrangement, with a maximum transformer unit power of1000 kV(1).
FIELD OF APPLICATION INSTALLATION
PF-204 with 2 transformers
TECHNICALREGULATIONS/STANDARDS
IEC 61330, RU 1303AIEC 60298, RU 6407BUNE 21428-1, HD 428, RU 5201DUNE 21538, HD 538IEC 60439-1, RU 6302B
PF-203 with 2 transformers and PF-201 for metering
(1) For higher power values, please contact our Technical/Commercial department.
PF Substation installation is limited to on-site assembly of allprefabricated elements as well as inclusion of electricalcomponents, and finally connection of the supply service cablesthat enter the substations through knockout holes located onthe bottom of the side wall.
10
OPERATION
Access to the Transformer Substation is possible through a frontdoor that allows direct access to the equipment compartmentthat houses the medium-voltage panels, the low-voltageswitchboards and the control elements of the substations. Ifoperation conditions so require, a second access door forpersonnel can be added and a physical separation betweenthe utility company and customer panels can be created.
Each transformer has its own door so the transformer can beremoved from the substation or accessed for maintenancepurposses.
PF House Type Modular
11
The enclosure panels are made of vibrated reinforced concrete,with the concrete steel reinforcements joined to each other andto the earth bus as specified in RU 1303. In addition, the doorsand grilles feature a 10 kΩ resistance to the earthing connectionof the enclosure.
A standard polyurethane finish has been used for the substation(white for walls and brown for ceiling, doors and grilles).
CONSTRUCTION DATA
PF-200 SUBSTATIONS UP TO 24 kV
PF-201 PF-202 PF-203
Lenght [mm]Width [mm]Height [mm]Area [m2]Visible Height [mm]
Lenght [mm]Width [mm]Height [mm]Area [m2]
Lenght [mm]Width [mm]Depth [mm]
Weight [kg]
262025203195
6,62595
246023602285
5,8
34203420700
10200
48802620319512,82595
47202460228511,6
56803420700
17100
72402620319519,0
2595
70802460228517,4
80403420700
24200
Outsidedimensions
Insidedimensions
Trenchdimensions
PF-204
96002620319525,22595
94402460228523,2
104003420700
30850
PF-300 SUBSTATIONS UP TO 36 kV
Lenght [mm]Width [mm]Height [mm]Area [m2]Visible Height [mm]
Lenght [mm]Width [mm]Height [mm]Area [m2]
Lenght [mm]Width [mm]Depth [mm]
Weight [kg]
Outsidedimensions
Insidedimensions
Trenchdimensions
262025203600
6,63000
246023602700
5,8
34203420700
11000
48802620360012,8
3000
47202460270011,6
56803420700
18500
72402620360019,03000
70802460270017,4
80403420700
25800
96002620360025,23000
94402460270023,2
104003420700
32900
PF-304PF-303PF-302PF-301
NOTES: Access door dimensions: 900 x 2100 (24 kV) / 900 x 2400 (36 kV). Transformer door dimensions: 1260 x 2100 (24 kV) / 1260 x 2400 (36 kV).
Transformer Substations
12
PF House-Type Modular Transformer Substations
For transformers rated above630 kVA, additionalventilation grilles are mountedon the side wall.
For transformers rated above630 kVA, additional ventilationgrilles are mounted on the sidewall.
Rear view
Levelling sand
4880
MV panels
2460
4720
100
600
Visi
ble
heig
ht
2620Transfo.
LV switchboards
2460
2620
MV panels
2360Transfo.
LV switchboards100
600 25
20
100
600
Visi
ble
Hei
ght Rear view
Levelling Sand
2620
2360
2460
2520
PF-201 / 301without a transformer
PF-202/3021 transformer
PF-201/3011 transformer
Visi
ble
Hei
ght Rear view
Levelling Sand
MV panels
LV switchboardsTransfo.Transfo.
MV panels
LV switchboardsTransfo.
PF-203/3031 transformer
PF-203/3032 transformers
PF-204/3042 transformers
For transformers rated above630 kVA, additional ventilationgrilles are mounted on the sidewall.
For transformers rated above630 kVA, additional ventilationgrilles are mounted on the sidewall.
For transformers rated above630 kVA, additional ventilationgrilles are mounted on the sidewall.
13
100
600
Visi
ble
heig
ht
7080
Rear view
Levelling sand
7240
MV panels
2460Transfo.
LV switchboards 2620
100
600
70807240
2620
2460
94409600
2460
100
600
2620
Visi
ble
heig
ht Rear view
Levelling sand
Transfo.
Visi
ble
heig
ht Rear view
Levelling sand
Transformer Substations
3475 2070
1660
1500
850
100
1660
2350
MV
pan
els
LV switchboards
Transfo.
Weight: 7.200 kg (without a transformer)
ORMASET Half-buried Packaged Transformer Substations
OVERVIEW
The ORMASET is a packaged Transformer Substation that hasbeen designed for half-buried installation, incorporating MVswitchgear with SF6 as insulation and interrupting medium(CGM/CGC), a transformer, a LV switchboard as well asinterconnecting and auxiliary devices.
Its careful outdoor design, compact size and half-buriedinstallation (visible height 1.5 m) reduces the substation visualimpact, making it suitable for both industrial and residentialareas.
ORMASET (view of LV switchboard access doors)
View of the CGM paneland the LV switchboardaccess doors in aORMASET
FIELD OF APPLICATION
IEC 61330, RU 1303AIEC 60298, RU 6407BUNE 21428-1, HD 428, RU 5201D
TECHNICALREGULATIONS/STANDARDS
Prefabrication of the Substitions allows full equipment assemblyat the factory, such that “on-site” operations can be limited tofinal positioning of the building on the trench, as shown in thefigures, and connection of electrical service supply cables.
INSTALLATION
The MV switchgear and the LV switchboard can be accessedfrom outside through independent doors, thus making operationseasy.
OPERATION
14
The ORMASET Transformer Substation allows electrical powersupply arrangements with a transformer up to 1000 kVA(1), at24 and 36 kV, to be implemented, where the maximumconfigurations are:
24 kV 3L + 1P (3 feeder protection panels and one fusedprotection panel).36 kV 2L + 1P (2 feeder protection panels and one fusedprotection panel).
Level “0”
(1) at the transformer, pluggable terminals are used.
MINIBLOK Outdoor PackagedTransformer Substation
The MINIBLOK is a compartmentalised packaged TransformerSubstation, with operation from the outside that has beendesigned by Ormazabal for use in public MV distributionnetworks.
Basically it consists of a compact prefabricated concrete enclosurethat houses the CGC system MV compact switchgear, atransformer, a LV switchboard and the respective interconnectingand auxiliary devices. The substation is shipped fully factory-assembled to ensure a uniform, high-quality finish.
The conceptual design of these substations, which keeps allcomponents separate from each another, limits the use ofcombustible insulating liquids and makes replacement of anycomponent easy.
Additionally, the use of SF6 total-insulation MV voltage switchgearreduces maintenance needs and gives excellent characteristicsin terms of resistance to pollution and other environmentalfactors, including resistance to possible flooding of the TransformerSubstation.
Finally, the optimised ventilation provided in this building reducestransformer overheating, and allows maximum use and optimaloperating conditions to be achieved.
OVERVIEW
The MINIBLOK can be integrated in distribution networks up to24 kV, where a 250, 400 or 630 kVA(1) transformer is required.
The electrical diagram that is available in medium voltage hastwo feeder protection panels (incoming and outgoing feeder)and a fuse-switch panel for operation and protection of thetransformer as well as a LV switchboard with fused outgoingcables.
Its compact size makes the substation an appropriate solutionwhen limited space is available. Also, its low visible heightenables a reduction of visual impact.
FIELD OF APPLICATION
Outside view of a MINIBLOK
(1) For higher power output values, please contact our Technical-Commercial department.
15
THERMOSTAT
TRIPPINGLIGHTING
Transformer Substations
MINIBLOK Outdoor Packaged Transformer Substation
OPERATION
MV or LV switching operations as well as replacing MV or LVfuses are performed by opening the packaged substation doors,with access inside the substation not being necessary.
There are two safe opening positions: at 90° and 180°.
16
Maximum weight: 7.500 kg (630 kVA)
2240 15
40
21002100
800
100
4300
Leveling sand
Surroundingsideway area
4300
Installation of a MINIBLOK requires digging a trench of thedimensions shown in the figure. The trench foundation shouldbe levelled by a compacted sand layer on which the packagedsubstation will be placed.
Installation operations consist of positioning the packagedsubstation on the dug trench and connecting the MV and LVcables and the outside earthing network. The knockout holesprovided on the enclosure should be drilled so this can be done.
After bringing these cables in, the cable service entrancesshould be sealed to prevent water from entering the substation,before the trench is covered.
INSTALLATION
MV and LV switchgear in a MINIBLOK
17
CONSTRUCTION CHARACTERISTICS AND TECHNICAL SPECIFICATIONS
24kV
50kV125 [kV]peak
IP 23DIK 1010K
400 A200 A16/20 kA20 kA
250, 400 or 630 kA420 VDyn114%
440 V630 or 1000 A160, 400 or 630 A
IEC 61330, RU 1303A
IEC 60298, IEC 60298, RU 6407B
UNE 21428-1, IEC 60076, HD 428, RU 5201D
IEC 60439
GeneralRated voltageInsulation level
At power frequencyAt lightning impulse
Prefabricated enclosureRated protectionImpact resistanceClass
MV panelsRated busbar currentRated transformer-off currentRated short-time current (3 s)Switch-fuse combination breaking capacity
TransformerPowerNo-load secondary voltageVector groupShort-circuit voltage
LV SwitchboardRated voltageRated currentRated current at outputs
Transformer Substations
MINISUB is a compact packaged Transformer Substation thathas been designed by Ormazabal to be used for public MVdistribution networks. The substation has been designed forunderground installation.
Inside the compact concrete enclosure, the CGC system MVpanels, the transformer and the LV switchboard, as well as theinterconnecting elements between these elements and the restof accessories, are installed at the factory.
Two versions are available: MINISUB-H, in which the ventilationgrilles are located on a horizontal plane, where stepping ispossible without any restrictions, and the MINISUB-V, whichhas ventilation grilles located in appropriate small ventilationtowers that have been designed to be integrated with all othertypical elements of sideways or parks and gardens.
The construction of the foundation and walls that form a singleconcrete part prevents water from filtering from the underground.
This feature, together with the use of gaskets on the upper coverplate and the access door, prevents water from entering theTransformer Substation. The design of the ventilation grilles inthe MINISUB-V model prevents rainfall and even surface waterfrom entering the enclosure until it reaches an approximateheight of 200 mm. In the MINISUB-H model, manholes areavailable that can be coupled to the general rain water sewerto remove water that enters through the grilles, thus preventingit from entering the Transformer Substation.
In addition, the use of SF6 total insulation MV switchgear in theCGC system reduces maintenance needs and provides the unitwith excellent characteristics in terms of resistance to pollutionand other environmental factors, including possible flooding ofthe Transformer Substation.
The compartmentalization of these MINISUB Substations keepsall components separate from each other, making componentreplacement easy.
OVERVIEW
MINISUB is applicable to electrical power distribution networksof up to 24 kV, where one transformer of 250, 400 or 630 kVAis required. The available MV electrical diagram has two feeder(incoming and outgoing) protection panels and a fuse-switchpanel for operation and protection of the transformer as wellas a LV switchboard with fused outgoing cables.
Its underground installation makes it the ideal solution whenone of the installation goals is the use of floor space as a transitarea or the minimisation of visual impact.
FIELD OF APPLICATION
18
MINISUB Underground Packaged Transformer Substation
Outside view of a MINISUB-V
THERMOSTAT
TRIPPING LIGHTNING
UTILIZACIÓN
Installation of the MINISUB requires previous digging of atrench with the dimensions shown in the figure with concretefoundation. Levelling is performed by means of a compactedsand layer on which the packaged substation is placed.
Installation is limited to simply positioning the TransformerSubstation in the trench and connecting outside earthing linksand MV and LV cables. This operation is performed throughknockout holes provided on the concrete enclosure. Thoseknockout holes are provided with gaskets that seal the inletonce cables have been connected (also connection to the rainwater sewer must be performed, if that option has been chosen).
INSTALLATION
19
OPERATIONMV or LV switching operations as well asMV or LV fuse replacement and transformerregulator operation is done after accessingthe space provided for the operator (afterdescending the step ladder available forthat purpose). When the the operator coverplate is opened, a peripheral protectionthat fully surrounds the opening and allowsaccess to the inside of the MINISUB isautomatically deployed.
2270
2470
1000
3460
3800
400
1740
2000
2460
150+
50
Con
cret
e sla
b +
leve
lling
san
d
540
1920
2700
680 2100 680
Operatoraccesscover plate
Maximum weight:13.500 kg (630 kVA)
2270
2470
1000
4500
3800
1740
2000
2460
150+
50
Con
cret
e sla
b +
leve
lling
san
d 2700
Operatoraccesscover plate
Maximum weight:16.500 kg (630 kVA)
MINISUB-V
Transformer Substations
MINISUB-H
20
CONSTRUCTION CHARACTERISTICS AND TECHNICAL SPECIFICATIONS
24kV
50kV125 [kV]peak
IP 23DIK 1010K
400 A200 A16/20 kA20 kA
250, 400 or 630 kA420 VDyn114%
440 V630 or 1000 A160, 400 or 630 A
IEC 61330, RU 1303A
IEC 60298, RU 6407B
UNE 21428-1, IEC 60076, HD 428, RU 5201D
IEC 60439-1
GeneralRated voltageInsulation level
At power frequencyAt lightning impulse
Prefabricated enclosureRated protectionImpact resistanceClass
MV panelsRated busbar currentRated transformer-off currentRated short-time current (3 s)Switch-fuse combination breaking capacity
TransformerPowerNo-load secondary voltageVector groupShort-circuit voltage
LV SwitchboardRated voltageRated currentRated current at outputs
MINISUB Underground Packaged Transformer Substation
21
The ORMABAT is a packaged, monoblock-structure TransformerSubstation that has been designed for ground installation. Thesubstation can be equipped with MV switchgear, with SF6 asinsulation and interrupting medium (CGM), the transformerand interconnecting and auxiliary devices.
The basic model contains a fuse-switch panel(1) for transformerprotection that is operated from outside.
The Substation features easy installation, compact dimensionsand low-weight and recyclable components,allowing it to beused for both permanent and temporary applications.
OVERVIEW
The ORMABAT Transformer Substation can be used witha transformer up to 160 kVA(1) at 24 kV.
FIELD OF APPLICATION
Prefabrication of these substations allows fullequipment assembly at the factory such thatinstallation operations are limited to positioning thesubstation in the trench and connecting the supplyservice cables.
INSTALLATION
IEC 60298, RU 6407BUNE 21428-1, HD 428, RU 5201D
TECHNICALREGULATIONS/STANDARDS
Opening the Transformer Substation doors enablesaccessing the switchgear and the transformer fromoutside in order to perform switching andmaintenance operations.
OPERATION
Weight: 2.800 kg
(1) For further conditions, please contact our Technical/Commercial department.
2100 1450
2045
235
ORMABAT
Transformer SubstationsORMABAT End-of-line PackagedTransformer Substation
OVERVIEWThe PF-15 is an MV Switching Substation, featuring a monoblockstructure and designed for ground installation.
The PF-15 standard configuration contains three load interrupterswitches(1) for 24 kV, with SF6 as insulation and interruptingmedium (CGM), that are operated from outside.
The substation features easy installation, compact dimensions,low-weight and recyclable components which allow its use bothfor permanent and temporary applications.
PF-15 Switching Substation
The PF-15 switching station can be used up to 24 kV(1).
FIELD OF APPLICATION
IEC 60298, RU 6407B
TECHNICALREGULATIONS/STANDARDS
Prefabrication of the substation allows full equipment assemblyat the factory such that “on-site” operations are limited topositioning the substation and connecting the supply servicecables.
INSTALLATION
Opening the two-leaf door of the switching substation allowsaccess of the switchgear from the outside to perform switchingand maintenance operations.
OPERATION
Weight: 2.400 kg
(1) For further conditions or configurations, please contact our Technical/Commercial department.
22
1460
1360
1215
1070
550
1500
100
PF-15 with access from public roads
The MB (Basic Module) is a compact, compartmentalisedTransformer Substation that has been designed to be installedfor public MV electrical power distribution networks inTransformer Substation rooms that are inside buildings usedfor other purposes.
It basically consists of compact MV switchgear from the CGCsystem, one transformer, one LV switchboard and the respectiveinterconnecting and auxiliary elements. All elements are factory-built and supplied with a standalone frame equipped withwheels for transportation to ensure a uniform, high-qualityfinish.
MB Frame-mounted PackagedTransformer Substation
OVERVIEW
FIELD OF APPLICATION
23
1650 1540
1830
1220
1400
1500
Approximate weight: 2.100 kg (630 kVA)
The MB can be integrated in electrical power distributionnetworks of up to 24 kV, where a 250, 400 or 630 kVAtransformer is required.
The MV electrical diagram includes two (incoming and outgoing)feeder panels and a fuse-switch panel for transformer switchingand protection as well as one LV switchboard with fusedoutgoing circuits.
The compact size and easy installation of the substations makethem ideal when available space is limited or when an oldTransformer Substation is to be replaced and upgrading effortsshould be minimised.
Transformer Substations
The installation of an MB consists basically of installing theassembly in the room, an operation that is made easy by thewheels available and the rear connection of MV and LV andearthing network connections.
The building that houses the assembly should have adequateventilation for the transformer power output and constructioncharacteristics of the site.
INSTALLATION
CONSTRUCTION CHARACTERISTICS AND TECHNICAL SPECIFICATIONS
24kV
50kV125 [kV]peak
400 A200 A16/20 kA20 kA
250, 400 or 630 kA420 VDyn114%
440 V630 or 1000 A160, 400 or 630 A
IEC 60298, RU 6407B
UNE 21428-1, IEC 60076, HD 428, RU 5201D
IEC 60439-1
GeneralRated voltageInsulation level
At power frequencyAt lightning impulse
MV panelsRated busbar currentRated transformer-off currentRated short-time current (3 s)Switch-fuse combination breaking capacity
TransformerPowerNo-load secondary voltageVector groupShort-circuit voltage
LV SwitchboardRated voltageRated currentRated current at outputs
MB Frame-mounted Packaged Transformer Substation
24
THERMOSTAT
TRIPPINGLIGHTNING
TECHNICAL/COMMERCIAL DEPARTMENT (INTERNATIONAL)Tel: +34 94 630 51 03Fax +34 94 630 51 04e-mail: [email protected]
www.ormazabal.com
CA·101·GB·0209
Transformer Substations
Prefabricated Transformer Substations up to 36 kVTransformer Substations for Wind Farms up to 36 kV (CA·105)
Medium Voltage Switchgear for Secondary Distribution Networks
CGM System (CA·102)
CGMCOSMOS System (CA·100)
Medium Voltage Switchgear for Primary Distribution Networks
Power Switchgear Panels (CA·104)
Protection, Control, Automation and Telecommand
Protection and Control (CA·103)
Automation and Telecommand (CA·106)
MV/LV Power Transformers
Low Voltage Switchgears