Transformer monitoring system catalog
Transformer monitoring system Catalog CA024009EN
Effective May 2021 Supersedes November 2020
Table of contents
www.eaton.com/cooperpowerseries2
System architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Main enclosure diagram � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3
Major features and benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Standard systems include � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4
Transformer ruggedized telemetry link (TRTL) . . . . . . . . . . . . . . . . . . . . . . . . . . 5Device overview � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5Features include � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5Benefits � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5Flexible inputs � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6
Communications enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Device overview � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7Package includes � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8
VaultGard interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Device overview � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9Features � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9Functions � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9Benefits � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9Security � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9Architecture diagram � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
NPServe communications module features . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Device overview � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 11Product design � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 11Analog and digital input control module � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
HMi terminal features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Device overview � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13Product design � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13Key features: � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
Transformer gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Interconnection cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Bulkhead ethernet adaptor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Transformer ruggedized telemetry link (TRTL) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20VaultGard � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20NPServe � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20HMi � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 21Uninterruptible Power Supply (UPS) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 21
www.eaton.com/cooperpowerseries 3
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
System architecture
Main Enclosure Diagram
The Main Enclosure serves as the central connection point for TRTL devices
HMI• Touchscreen• VaultGard webpage views• NPServe webpage views• TRTL real-time data displayNPServe
• Local/Remote input• Control Relays • Pumps • Lights • Fans • Remote Racking• Intrusion Alarm• UPS Alarms and Status
VaultGard• Enhanced network monitoring• Network relay communication• TRTL Configuration capability• DNP mapping• Concentrates and collects all communication devices on system
Transformer RuggedizedTelemetry Link
• Smart Relay inputs or 3rd party devices• Network Protector Relay• Transformer Liquid Level• Transformer Temperature• Transformer Analog Pressure• Ambient Temperature• Float Switches• Other 3rd party gauges and sensors
• Inputs for
Local/Remote• Removes remote control ability of smart relays
UPS/Battery• 1/120VAC Output• Low battery alarm• AC Fail alarm• Lithium Iron Battery
• Reduced maintenance• Resistance to temp fluctuations• Long life (2x over Lithium lon)• Low inert gas emissions
Figure 1 . Main enclosure communication diagram .
www.eaton.com/cooperpowerseries4
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Major features and benefits
Monitoring the secondary network has become more commonplace in the network underground, as out-of-sight and out-of-mind is no longer the industry norm� As part of the industry’s initiatives for providing safer environments for employees and pedestrians alike and providing remote observation through communications, intelligent decisions can now be made in the areas of predictive maintenance and failure mitigation� Eaton’s Transformer Monitoring System was designed from decades of network communications experience�
Eaton is a consistent leader in supporting existing network protectors and developing new network protector and communications technology� This expertise and understanding of network systems has been at the core of Eaton’s offerings�
Standard systems include• IP68 enclosure• Uninterruptible power system (UPS)• VaultGard communications module• NPServe controls and alarm module• HMI touch screen• Communications transceiver • TRTL 12-input gauge collection device• Rugged transformer gauges selection
Figure 2 . System architecture layout .
www.eaton.com/cooperpowerseries 5
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Transformer ruggedized telemetry link (TRTL)
Device overviewEaton’s Transformer Ruggedized Telemetry Link (TRTL) is a centralized connection device that is specifically designed to combat harsh underground vault environments� This smart design provides critical port protection for monitoring systems and gauges to last through weathering and corrosion� It further alleviates complex wiring and routing systems, which can be extremely hazardous when working in network systems�
There is no need for direct contact with any energized devices� Eaton’s new TRTL device provides easy access for field personal, and even mounts directly to the transformer (via four magnets on the backside) with bolt-on provisions� With plug-and-play installation, the TRTL communicates via Ethernet to the VaultGard and SCADA systems� The device is fully submersible to meet all vault requirements and environments� Since the TRTL does not require any exposure to energized equipment, it reduces potential arc flash concerns for users�
Features include• 12 versatile input ports
• Plug-and-play with Eaton gauges
• Full connection to communication devices and gauges
• Magnetic or bolted mounting options
• Application directly to transformer surface
• Works with Eaton or 3rd-party gauges
Benefits• Non corrosive
• IP68 3rd-party certified
• Mount on transformer, no need to open protector door
• Multi-capable input ports
• Accept 12 versatile inputs
• No calibration required
• All gauges and relay communication connect locally to TRTL
• One Ethernet cable output per transformer
• Greatly reduce main enclosure penetrations
• Greatly reduces wire pulling labor and terminations
4.00
6.50
5.75"
8.00
12 gauge or seasor inputs
Uplink
3.26
Downlink
www.eaton.com/cooperpowerseries6
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Flexible inputsThe TRTL is equipped with 12 individual inputs of which are flexible to accept varying types of gauges and sensors and designed to automatically detect what is connected to each specific input which eliminates the need to pre-configure each port�
Eaton’s smart gauges (see pages 14-17) may be used at any of the 12 input ports�
Specific inputs are dedicated for the use of third-party 4-20mA and 4-wire RTD sensors/gauges� See Table 1 for more details�
Table 1 . Main enclosure communication diagram
Compatible with 3rd Party Gauges
InputEaton Smart Gauges
TRTL Comm Port
Network Relay Data
Relay Tamper Alarm +
Local Interface Connection ++
Dry Contact (on/off) 0-5Vdc 4-20mA
4-wire RTD, 100ohm
1A
1B
1C
2A
2B
2C
3A
3B
3C
4A
4B
4C
UPLINK
DOWNLINK + Relay Tamper Alarm – 48Vdc digital input for relay cable tamper detection
++ Local Interface Connection – Provides TRTL configuration page access
www.eaton.com/cooperpowerseries 7
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Communications enclosure
Device overviewEach standard Eaton TRTL communication enclosure is designed for lasting protection for critical communication devices� Enclosures are constructed of rugged polycarbonate material, include a translucent cover for easy reading capability and are rated specifically for submersibility� In one compact design, Eaton’s communication enclosure gives users easy access to real time data for their transformer and network protector�
WER
131416
15
Output to SCADA
6 TRTL inputs
11.56
2.492.26
2.14
2.50
3.25
2.10
2.50
2.50
Clear front cover
120VAC input port
Figure 3 . Main communication enclosure (front) .
Figure 4 . Enclosure dimension detail .
www.eaton.com/cooperpowerseries8
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Package includesFor best performance capabilities, the TRTL communication enclosure full package includes:
• VaultGard – Eaton’s network communications module for equipment interface• NPServe – Digital alarm inputs, control relays, UPS monitoring, and advanced algorithms• HMi – Touchscreen interface for VaultGard, NPServe, and TRTL webpages• UPS – 120 Vac to 120 Vac uninterrupted power supply, back-up for user-specified transceiver• Rugged IP68 Submersible EnclosureSee visual below for more information�
HMi Screen (backview)
Ethernet Switch
VaultGard
UPS System
NPServe
TransceiverLocation
Figure 5 . Enclosure layout .
www.eaton.com/cooperpowerseries 9
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Device overviewThe VaultGard™ interface brings a wealth of information from the utility vault to the fingertips of utility personnel in a user-friendly web interface or into existing SCADA� Information contained in the VaultGard interface can be trended and analyzed different ways to determine a predictive maintenance schedule� Network protectors can be interconnected on a single VaultGard interface� Protectors can be opened and safety features activated remotely, mitigating potential danger to the operator before they enter the vault� Refer to VaultGard interface brochure Referance IL manual IL02400002E SA02400004E for additional details�
Features• Connect up to (6) TRTL’s• Easy to navigate on-board web pages (no software needed)• Comprehensive data monitoring (voltage, current, power
metrics, etc�)
Functions• Monitoring and remote control for a vault system• Central interface for all connected TRTL devices to on-board
web pages through a web browser• DNP3�0 protocol compatibility• Configuration for master/outstation for integration with a local
SCADA system• Alarms, logging (live and historical)/ trending/graphing of
captured data, set point control• Email alert notification• Monitoring and control of accepted digital I/O devices
Benefits• No software is required• Central hub for collecting vault data, controlling relays
remotely, and communicating vital network data to the user• Acts as a preventive maintenance tool to discover issues
before they cause system-wide and costly problems
Security• Supports RADIUS for remote access• Supports LADAP• Supports IPsec
VaultGard interface
Figure 6 . Screenshot of VaultGard™ interface .
www.eaton.com/cooperpowerseries10
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Architecture diagram
SCADA DNP -For use of VaultGard as a outstation device on the SCADA system, connect RS-485 from the DNP slave (outstation) to the SCADA master device�
DNP MASTER -Any DNP devices monitored by the VaultGard will connect to this port via RS-485� (Network Relays, HTES, NPServe)
INCOM -Single termination point for all connected INCOM Devices (MPCV relays, DIM’s, DRAM’s, NPARMS, Digitrip)
Figure 7 . VaultGard Connection Detail
www.eaton.com/cooperpowerseries 11
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Device overviewThe NPServe communications module is designed for harsh underground vault applications and is a specialized communication concentrator with high-speed processing built specifically for secure and reliable data analysis and control� It requires no software and is a key component for smart underground applications� Eaton’s NPServe module has been designed to operate over a broad temperature range, which is critical to underground environments�
NPServe communications module features
Product designThe NPServe module was designed with the horsepower to leverage intelligent solutions and algorithms needed for today’s smart grid roadmaps and will handle the most stringent security demands� The module is the key component to gather and distribute communications from IED and sensors deployed in the underground space�
• Extracts and concentrates alarm status• Provides secure remote access• Controls third-party devices• Seamlessly integrates with the VaultGard communication
system• Built-in web page views specifically designed for analysis and
application• Easy access with smart devices• Exports to SCADA, control centers, and any other
management applications• Supports advanced data algorithms
Figure 8 . NPServe .
www.eaton.com/cooperpowerseries12
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Analog and digital input control moduleNPServe is used for collecting vault and equipment data, it can also be used to communicate with the network protector for a single point of concentrated data that can be taken back to the VaultGard interface� It has the following features:
• 6 Analog Inputs• 8 Digital Inputs• (2) 120Vac, 10A dry contact control relays• (1) 240Vac, 30A dry contact control relay
Figure 9 . NPServe connection detail .
www.eaton.com/cooperpowerseries 13
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Device overviewThe HMi terminal was designed to provide utilities with easy-to-use secure monitoring and touchscreen control via the VaultGard, HTES, and NPServe network communications systems all on a single platform� The HMi offers all the remote control features that the VaultGard offers located in a safe area outside of the vault or locally at the vault� An active directory can be installed to allow access to configuration pages� With the use of NPServe, the HMi can replace the RemRack control cabinet for local operation�
HMi terminal features
Product designEaton’s HMi terminal is a rugged graphic human-interface terminal for use in a wide-range of utility and industrial applications� The HMi terminal comes standard with the following design features:
• Installed with an IP68 polycarbonate submersible cabinet • Prewired and assembled • Power supply
Key features:• Control and Display data from network protector and MV
switch via the Eaton VaultGard gateway• Activates NPARMS and operates remote racking unit directly
from the HMI• Provides secure remote access local to the vault, increasing
safety• Ability to operate any device in vault through output control
relays when used with Eaton NPServe communications module
• Preprogrammed for seamless integration
Figure 10 . HMi front view – touch screen shown .
Figure 11 . HMi back view .
www.eaton.com/cooperpowerseries14
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Heavy duty for the most extreme environmentsEaton’s array of smart monitoring gauges are the only solution on the market that are built specifically for submersible transformer environments� Eaton gauges combat the harshest conditions such as corrosion and water ingress, which can have extremely hazardous effects for utilities and public safety�
Each gauge comes equipped with non-corrosive housing, plug-and-play capabilities, are IP68 3rd-party certified and require no calibration or labeling� See table below for more details�
Catalog # E1220.0004 (mag mount with 3’ cable)
Catalog # E1220.0005 (mag mount with 10’ cable)Description:• Remotely magnetic mount mechanical dial indicator• Bushing well mounted probe with stainless steel
cable• Resettable high temp indicator• Digital output• 0 - 5V output• IP68 Submersible• Non-corrosive• 0 - 160 °C
Catalog # E1220.0006 (Bolted mount with 3’ cable)
Catalog # E1220.0007 (Bolted mount with 10’ cableDescription:• Remotely bolted mount mechanical dial indicator• Bushing well mounted probe with stainless steel
cable• Resettable high temp indicator• Digital output• 0 - 5V output• IP68 Submersible• Non-corrosive• 0 - 160 °C
Transformer gauges
3/8-18 NPT
TRANSFORMER
5.46
3.75
FLEXIBLE STAINLESS STEEL CABLE
TRANSFORMER PROBE
FLEXIBLE STAINLESS STEEL CABLE
.75
5.50
.75
7.00
.75 5.50 .75
7.00
5.46
3.75
MAGNET MOUNT TO TRANSFROMER
WALL MOUNT
Remote liquid temp gauge
www.eaton.com/cooperpowerseries 15
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Catalog#: E1220.0001Specifications• Bushing well-mounted probe• Plug-and-play with TRTL• Includes mechanical dial indicator• Digital output• Non-corrosive• 0 - 5V output• IP68 Submersible• 0 - 160 °C
Catalog #: E1220.0003Specifications• Magnet-mounted sensor • Plug-and-play with TRTL • Transformer skin temp • Easy installations • Digital output • Non-corrosive • 0 - 5V output • IP68 Submersible • 0 - 160 °C
Catalog #: E1220.0002Specifications• Bushing well mounted probe• Plug-and-play with TRTL• Resettable high temp indicator• Digital output• 0 - 5V output• IP68 Submersible• 0 - 160 °C
3/8-18 NPT
3.755.46
5.46
3/8-18 NPT
3.00Liquid temperature gauges
Catalog#: E120.0001Specifications• Flange mounted to vault wall or
unistrut• Plug-and-play with TRTL• Stainless steel mounting bracket (also
protects probe from debris)• Digital output• Non-corrosive• 0 - 5V output• IP68 Submersible• -40 - 125°C
Vault ambient temperature gauge
www.eaton.com/cooperpowerseries16
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Pressure gauges
Catalog #: E167.0003Specifications• ½” NPT tank connection• Schrader valve sample port• Plug-and-play with TRTL• Digital output• Non-corrosive• -2 – 20 PSI• IP68 Submersible
Catalog #: E167.0002Specifications• ½” NPT tank connection• 302 Waterbury valve sample port• Plug-and-play with TRTL• Digital output• Non-corrosive• -2 – 20 PSI• IP68 Submersible
Catalog #: E167.0001Specifications• 302 Waterbury valve (male) tank
connection• 302 Waterbury valve sample port• Plug-and-play with TRTL• Digital output• Non-corrosive• -2 – 20 PSI• IP68 Submersible
Catalog#: E1212.0002Specifications• Standard surface mounting provisions• Plug-and-play with TRTL• Includes mechanical dial indicator• Digital output• Non-corrosive• 0 – 5V output• IP68 Submersible
Liquid level gauge
THUMB / FLAT HEAD COMBO SCREWS PROVIDED FOR QUICK ATTACHMENT TO TRANSFORMER
5.63
2.37
www.eaton.com/cooperpowerseries 17
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Catalog #: E167.0004Specifications• Belknap 994 valve (male) tank
connection• Belknap valve sample port• Plug-and-play with TRTL• Digital output• Non-corrosive• -2 – 20 PSI• IP68 Submersible
Catalog #: E619.0002Specifications• Flange mounted to vault
wall or Unistrut• Plug-and-play with TRTL• Mounted plug down (output
is usually open)• Digital output• Mounted plug up (output is
normally closed)• Non-corrosive• IP68 Submersible
Float switch
Catalog #: E167.0005Specifications• ½” NPT tank connection• Belknap valve sample port• Plug-and-play with TRTL• Digital output• Non-corrosive• -2 – 20 PSI• IP68 Submersible
www.eaton.com/cooperpowerseries18
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Catalog #: PX0841/AB/5M00Specifications• IP68 ‘A’ Type USB Connector
to IP68 ‘B’ Type USB connector
• Mates with all TRTL and Gauge connectors
• 5m length
Catalog #: 6B14926H10Specifications• Double-ended IP68 Cat6a
connector• Cat6a Cable 10ft length
Catalog #: 6B14926H100Specifications• Double-ended IP68 Cat6a
connector• Cat6a Cable 100ft length
Catalog #: 6B14926H25Specifications• Double-ended IP68 Cat6a
connector• Cat6a Cable 25ft length
Catalog #: 6B14926H150Specifications• Double-ended IP68 Cat6a
connector• Cat6a Cable 150ft length
Catalog #: 6B14926H50Specifications• Double-ended IP68 Cat6a
connector• Cat6a Cable 50ft length
Interconnection cablesCable that provides the communication connection between the TRTL and Eaton Gauges
Cable that provides the communication connection between the TRTL and Main Enclosure/Bulkhead Ethernet Adaptor
6 TRTL Inputs
Fiber output to SCADA
Submersible Ethernet Cableavailable 25ft, 50ft, 100ft150’ lengths
One RMS Enclosurecan support up to 72gauges/sensors!
120VAC Input power
Output to SCADA
Figure 13 . Connection from main enclosure to TRTL .
To TRTL Standard 5 meters To Gauge
Sealed USB Cables Double Ended
Output to SCADA
www.eaton.com/cooperpowerseries 19
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Catalog #: 6B14924G01Descriptions• IP68 RJ45 Connector to TRTL Device input port• RJ45 Male to 8 position terminal for termination inside
bulkhead• 1”NTP thread to mount at available NWP bulkhead port
Specifications• Fully potted for IP68 submergibility• Cat6a submersible connector
Bulkhead ethernet adaptorSubmersible adaptor that provides the communication connection between the TRTL and Network Protector Relay
Pin Pair Color Function
1 2 White/Orange N/A2 2 Orange N/A3 3 White/Green N/A4 1 Blue Digital Input (Relay Tamper Alarm)5 1 White/Blue Digital Input (Relay Tamper Alarm)6 3 Green N/A7 4 White/Brown (connection to MPCV)8 4 Brown (connection to MPCV)
Input from MPCV Relay
Submersible 10’Ethernet Cable
Communication wiringinside Network Protector
Bulkhead EthernetAdaptor
Table 4 .
Figure 14 . Connection from TRTL to MPCV relay diagram .
www.eaton.com/cooperpowerseries20
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
System specifications
TRTL Specifications:Inputs ports:• 12 x USB Type B
Uplink port:• 1 x 10/100BASE-TX
• PoE IEEE802�3af Compliant
Downlink port:• 1 x Cat5E
Power supply:• 36-57VDC
• PoE IEEE 802�2 compliant
Communications:• DNP3�0, HTTP (Uplink)
• INCOM (Downlink)
Environmental:• Operation (at CPU 100% usage): -40C to 85C
Test standards:• IEC 60255-27:2013 – Impulse and Dielectric test• IEC60529 Edition: 2�1 2002 – IPX8 (Protected against effects
of continuous immersion in water)• IEC 60255-27; Sections 10�6�1�1 and 10�6�1�2 - Dry Heat test-
operational, Cold test-operational
VaultGard specifications:Serial ports• Shield Twisted Pair (support for up to 32 devices)• Isolated RS-485 Port for DNP Field Bus• Isolated RS-485 Port for DNP SCADA• DNP 3�0 Level 3
Devices supported• MPCV Relay• TRTL• HMi• Arc Flash Reduction Maintenance System Indicating
Diagnostics Module (NPARMs-IDM)• Digitrip Relay• Digital Input Module (DIM) with 8 Digital Inputs• Digital Relay Accessory Module (DRAM) with 4 Relay Outputs
DNP Field bus devices supported:• NPServe• High Thermal Event System (HTES)• TRTL
Ethernet• 10/100 Mb/s
Environmental• Operating temperature: 40 to +70°C (-40 to +158°F)• Storage Temperature: -40 to +85°C (-40 to +185°F)
Power supply• Power consumption: 4 W max�• 12 Vdc: 130 mA nominal, 300 mA max�
Physical• Height: 2�17 in�(55�12 mm)• Width: 4�67 in�(118�62 mm)• Length: 6�73 in�(170�94 mm)
NPServe specifications:Serial ports• Shield Twisted Pair
• RS-232 for remote Pendant access
• Isolated RS-485 Port for DNP Field Bus
• Isolated RS-485 Port for DNP SCADA
• 1 USB 2�0
• DNP 3�0 Level 3
Devices supported• VaultGard
• MPCV Relay
• TRTL
• 3rd Party SMART devices
• Digitrip Protective Relay
• HMi
• Arc Flash Reduction Maintenance System Indicating Diagnostics Module (NPARMs-IDM)
• Digital Input Module (DIM) with 8 Digital Inputs
• Digital Relay Accessory Module (DRAM) with 4 Relay Outputs
Ethernet:• 1 10/100BASE-TX
Analog inputs:• (6) - -5 to +5 Vdc, 150mA load
Digital Inputs:• (8) - 120Vac wetted contacts
Output contacts:• (2) – 10Amp, Form C relays
• (1) – 30Amp, N�O relay
• Configurable for timed pulse or latch
Environmental• Operating(at CPU 100% usage): -40oC to +85 °C• Storage: -40°C to +105 °C• Humidity: 5 to 95%, non-condensing
www.eaton.com/cooperpowerseries 21
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Power supply• Power Consumption: 20 W max�• Voltage Input: 120Vac
Physical• 2�36 in� H X 5�91 in� W X 8�86 in� L• Weight: 3�9 lbs /1�767 kg
HMi specifications:Serial ports• 1 x USB 2�0 OTG, 4 x USB 2�0 HOST
• 8 x General Purpose Input/ Output (GPIO)
• 4 x RS232 (can be customized to RS485 or CAN)
• 1 x HDMI
• 1 x STATA II
Ethernet:• 1 x LAN 1000M
Environmental• Operating(at CPU 100% usage): -20°C ~ 70°C
Power supply• 10W max
• 15 ~ 36V DC
Physical• 12inch display size
• 11lbs
Uninterruptible Power Supply (UPS) specifications:Input• Nominal Input Voltage: 115 ~ 230 ~ 277 Vac
• Voltage range: 90 – 305 Vac
• Inrush Current: (Vn – In nom� Load)� I2t ≤11 A ≤ 5 msec
• Frequency: 47 – 63 Hz
• Input Current: (115 – 230 Vac) 2�8 ~ 1�3 A
• Internal fuse: (factory replaceable) 4 A
• External Fuse: (recommended) MCB curve B 10 A
Output• Output Voltage (Vn) / Nominal Current (In): 12 Vdc / 6A
• Output Current In 6 A Efficiency (at 50% of rated current): ≥ 90 %
• Turn-On delay after applying input voltage: 1 sec� (max)
• Start up with Strong Load (capacitive load): Yes, Unlimited
• Dissipation power load max: 17 W
Output load:• Output voltage (at In): 10 ~ 14�4 Vdc
• Nominal current Iload 1�1 x In A: ± 5%
• Continuous current (without battery) Iload= In: 6 A
• Continuous current (with battery) Iload= In+ Ibatt: 12 A Max�
• Current Output Load (Main) Iload (4 sec�): 18 A max�
• Max� Current Output Load (Back Up) Iload (4 sec�): 12 A max�
• Push Button or Remote Input Control (RTCONN cable): Start From Battery Without Main Time Buffering
• Min (switch output off without main input): standard 5 min�
• Require SW Protection alarm against total discharge: 9-10 Vdc battery voltage
• Threshold alarm for battery almost flat: 10-11 Vdc battery voltage
Battery output:• Boost charge (25 °C) (at In): 14�4 Vdc
• Max� time Bust Charge: 15 h
• Min� time Bust Charge: 1 min�
• Trickle charge (25 °C) (at In): 13�75 Vdc
• Jumper Configuration battery type (V cell) Ni-Cd (optional): 2�23; 2�25; 2�27; 2�30; NiCd: 1�50 (10 elem�)
• Recovery Charge: 2 ~ 9 Vdc
• Charging current max Ibatt: 6 A ± 5%
• Charging current limiting Iadj: 20 – 100 % / Ibatt
• Reverse battery protection: Yes
• Sulfated battery check: Yes by Jumper
• Detection of element in short circuit: Yes
• Quiescent Current: ≤ 5 mA
• Charging Curve automatic; IUoUo: 3 stage
• Remote Input Control (RTCONN cable): Boost /Trickle / Recovery
Environment:• Ambient temperature (operation): -25 – +70°C
• Ambient temperature Storage: -40 – +85°C
• Humidity at 25°C no condensation: 95%
• Cooling: Auto convention
• MTBF (IEC 61709): > 300�000 h
www.eaton.com/cooperpowerseries22
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
www.eaton.com/cooperpowerseries 23
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Catalog data CA024009ENEffective May 2021
Transformer monitoring system catalog
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
For more information Eaton's solutions, call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.
Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton�com
Eaton’s Power Systems Division2300 Badger DriveWaukesha, WI 53188United StatesEaton�com/cooperpowerseries
© 2021 EatonAll Rights ReservedPrinted in USAPublication No� CA024009EN May 2021