TRANSFORMER DIAGNOSIS.pdf

Embed Size (px)

Citation preview

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    1/123

     © OMICRON 11/6/2014 Page: 1

    TRANSFORMER DIAGNOSIS

    Dipl.-Ing. Dr. Michael Krüger © 2006

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    2/123

     © OMICRON Page: 204.12.200411/6/2014

    Sources of Faults

       W   i  n   d   i  n  g

       C  o  r  e

       B  u  s   h   i  n  g  s

       V  e  s  s  e   l   &   O   i   l

       A  c  c  e  s  s  o  r   i  e  s

       T  a  p   C   h  a  n  g  e  r

       F  r  e  q  u  e  n  c  y

       i  n   %

    Source: Cigre_WG 12-05 „An international survey on failures in large power

    transformers in service“, Electra No. 88, 1983

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    3/123

     © OMICRON Page: 304.12.200411/6/2014

    Gas-in-Oil Analysis

    Source: Möllmann, A. u.a. „IEC/VDE Standards für flüssige Isolierstoffe zur Diagnostik

    von Transformatoren und Wandlern“, ETG Fachbericht 87: Diagnostik elektrischer

    Betriebsmittel, Berlin 2002

    Type of Fault

    Partial Discharge

    Discharge with lowEnergy

    Discharge with high

    Energy

    Thermal Fault T

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    4/123

     © OMICRON Page: 404.12.200411/6/2014

    Tests for Diagnosis

    (Fault Location)

    •Winding resistance and OLTC test•Practical examples for winding ratio,excitation current, leakage reactance

    •FRSL

    •Capacitance and dissipation factor

    •FRA

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    5/123

     © OMICRON Page: 504.12.200411/6/2014

    Universal Transformer

    Test SystemPower Amplifier

    15-400Hz

    •Up to 2000A, 2kV AC / 400A DC

    •Measurement of

    •Ratio

    •Complex Impedance•Resistances

    • …...

    C-Tanδδδδ-Prüfsystem

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    6/123

     © OMICRON Page: 604.12.200411/6/2014

    Testing OLTC

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    7/123

     © OMICRON Page: 704.12.200411/6/2014

    On-load tap changer principle (1)

    Voltage Selector

    Diverter

    Switch

    Commutating

    Resistors

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    8/123

     © OMICRON Page: 804.12.200411/6/2014

    On-load tap changer principle (2)

    Voltage Selector

    Diverter

    Switch

    Commutating

    Resistors

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    9/123

     © OMICRON Page: 904.12.200411/6/2014

    On-load tap changer principle (3)

    Voltage Selector

    Diverter

    Switch

    Commutating

    Resistors

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    10/123

     © OMICRON Page: 1004.12.200411/6/2014

    On-load tap changer principle (4)

    Voltage Selector

    Diverter

    Switch

    Commutating

    Resistors

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    11/123

     © OMICRON Page: 1104.12.200411/6/2014

    On-load tap changer principle (5)

    Voltage Selector

    Diverter

    Switch

    Commutating

    Resistors

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    12/123

     © OMICRON Page: 1204.12.200411/6/2014

    On-load tap changer principle (6)

    Voltage Selector

    Diverter

    Switch

    Commutating

    Resistors

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    13/123

     © OMICRON Page: 1304.12.200411/6/2014

    On-load tap changer

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    14/123

     © OMICRON Page: 1404.12.200411/6/2014

    Measurement of the staticresistance values of:

    1) all internal contacts (diverter

    switch contacts + tapselector switch + connectionclamps) +

    2) the winding resistance

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    15/123

     © OMICRON Page: 1504.12.200411/6/2014

    New voltage selector contact

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    16/123

     © OMICRON Page: 1604.12.200411/6/2014

    Voltage selector switch in a good

    conditionWiderstand V-Mp

    235.00

    240.00

    245.00

    250.00

    255.00

    260.00

    265.00

    270.00

    275.00

    280.00

    285.00

           1 2 3 4 5 6 7 8 9       1       0

           1       1

           1       2

           1       3

           1       4

           1       5

           1       6

           1       7

           1       8

           1       9

           2       0

           2       1

    Stufen

       W   i   d  e  r  s   t  a  n

       d   [  m     Ω     ΩΩ     Ω   ] KEMA

    OMICRON 1…21Ref. Temp.

    OMICRON 21…1Ref. Temp.

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    17/123

     © OMICRON Page: 1704.12.200411/6/2014

    Influence of the Temperature

    Maschinentransformator27kV/400kV 1100MVA

    1. Measurement: 20°C

    Last Meas.: 23°C

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    18/123

     © OMICRON Page: 1804.12.200411/6/2014

    Influence of the Temperature

    R Winding (Tap)

    0.14Ω

    0.145Ω

    0.15Ω

    0.155Ω

    0.16Ω

    0.165Ω

    000 005 010 015 020 025 030Taps

    A UP

    A DOWN

    B UP

    B DOWNC UP

    C DOWN

    012.1*)20()23(:235

    235)()(

    1

    212   °=°

    +

    +=   R R Beispiel

    T T  RT  R

    Delta =1.2%

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    19/123

     © OMICRON Page: 1904.12.200411/6/2014

    Faulty voltage selector contact

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    20/123

     © OMICRON Page: 2004.12.200411/6/2014

    Defective Voltage Selector

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    21/123

     © OMICRON Page: 2104.12.200411/6/2014

    Defective Tap Selector

    Starke Verrußung durch Erwärmung und Ablagerungen

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    22/123

     © OMICRON Page: 2204.12.200411/6/2014

    Resistance U-Mp

    R L1 (referred to 20°C)

    450.0

    500.0

    550.0

    600.0

    650.0

    700.0

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    Taps

      m   O   h  m

    R L1 1974

    R L1 20.2.02 1...19

    RL1 20.2.02 19…1

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    23/123

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    24/123

     © OMICRON Page: 2404.12.200411/6/2014

    100MVA 220/110 kV W

    R L3 (referred to 20°)

    450.0

    470.0

    490.0

    510.0

    530.0

    550.0

    570.0

    590.0

    610.0

    630.0

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    Taps

        m     O     h    m

    R L3 1974

    R L3 20.2.02 1…19

    R L3K 20.2.02 19…1

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    25/123

     © OMICRON Page: 2504.12.200411/6/2014

    Winding Resistance U-Mp After RepairResistance L1

    450.0

    470.0

    490.0

    510.0

    530.0

    550.0570.0

    590.0

    610.0

    630.0

    650.0

           1 2 3 4 5 6 7 8 9       1       0

           1       1

           1       2

           1       3

           1       4

           1       5

           1       6

           1       7

           1       8

           1       9

    Taps

       R  e  s   i  s   t  a  n  c  e

       [  m     Ω     ]     Ω     ]     Ω     ]     Ω     ]

    Factory MeasurementOMICRON 1…19

    OMICRON 19…1

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    26/123

     © OMICRON Page: 2604.12.200411/6/2014

    Delta R for U-Mp „UP“-„DOWN“

    Resistance Differenz L1 Up-Down

    -6.0

    -4.0

    -2.0

    0.0

    2.0

    4.0

    6.0

          1 2 3 4 5 6 7 8 9      1      0

          1      1

          1      2

          1      3

          1      4

          1      5

          1      6

          1      7

          1      8

          1      9

    Taps

       R  e  s   i  s   t  a  n  c  e

       [  m    Ω    ]    Ω    ]    Ω    ]    Ω    ]

    Resistance Differenz L1 Up-Down

    -30.0

    -20.0

    -10.0

    0.0

    10.0

    20.0

    30.0

    40.0

          1 2 3 4 5 6 7 8 9      1      0

          1      1

          1      2

          1      3

          1      4

          1      5

          1      6

          1      7

          1      8

          1      9

    Taps

       R  e  s   i  s   t  a  n  c  e   [  m

        Ω    ]    Ω    ]    Ω    ]    Ω    ]

    Before repair

    After repair

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    27/123

     © OMICRON Page: 2704.12.200411/6/2014

    Cleaning effect of OLTC movement

    R Winding (Tap)

    0.14 Ohm

    0.15 Ohm

    0.16 Ohm

    0.17 Ohm

    0.18 Ohm

    0.19 Ohm

    0.2 Ohm

    0 5 10 15 20Taps

    A UP

    A DOWN

    B UP

    B DOWN

    C UP

    C DOWN

    R Winding (Tap)

    0.14 Ohm

    0.15 Ohm

    0.16 Ohm

    0.17 Ohm

    0.18 Ohm

    0.19 Ohm

    0.2 Ohm

    0 5 10 15 20Taps

    A UP

    A DOWN

    B UP

    B DOWNC UP

    C DOWN

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    28/123

     © OMICRON Page: 2804.12.200411/6/2014

    Increased contact resistance on a

    diverter switch in phase AR Winding (Tap)

    0.13 Ohm

    0.135 Ohm

    0.14 Ohm

    0.145 Ohm

    0.15 Ohm0.155 Ohm

    0.16 Ohm

    0.165 Ohm

    0.17 Ohm0.175 Ohm

    0.18 Ohm

    0 2 4 6 8 10 12Taps

    A UP

    A DOWN

    B UP

    B DOWN

    C UP

    C DOWN

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    29/123

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    30/123

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    31/123

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    32/123

     © OMICRON Page: 3204.12.200411/6/2014

    Measurement of „Low Ohmic“ Windings

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    33/123

     © OMICRON Page: 3304.12.200411/6/2014

    Analysis of the TransientSwitching Behavior of the

    Diverter Switch

    T i t i l f it hi

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    34/123

     © OMICRON Page: 3404.12.200411/6/2014

    Transient signal of one switching

    procedure in detail

    1 = Diverter switch commutates from the first tap to the first commutating resistor

    2 = The second commutationg resistor is switched in parralel

    3 = shorting of the second commutating resistor and commutating to the second tap

    4 = Charging of the additional windings

    Ripple

    Slopeαααα

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    35/123

     © OMICRON Page: 3504.12.200411/6/2014

    Diagnosis of the diverter switch

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    36/123

     © OMICRON Page: 3604.12.200411/6/2014

    Ripple of a diverter switch in a

    good condition (1100MVA)Ripple

    0.0%

    0.5%

    1.0%

    1.5%

    2.0%

    2.5%

    000 005 010 015 020 025 030Taps

    A UP

    A DOWN

    B UPB DOWN

    C UP

    C DOWN

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    37/123

     © OMICRON Page: 3704.12.200411/6/2014

    Slope of a diverter switch in a

    good condition (1100MVA)Slope

    -0.6A/s

    -0.5A/s

    -0.4A/s

    -0.3A/s

    -0.2A/s

    -0.1A/s

    0.0A/s

    000 005 010 015 020 025 030

    Taps

    A UP

    A DOWN

    B UP

    B DOWN

    C UP

    C DOWN

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    38/123

     © OMICRON Page: 3804.12.200411/6/2014

    Ripple on a Diverter Switch with

    bouncing Contacts in Phase CRipple

    0.0%

    5.0%

    10.0%

    15.0%

    20.0%

    25.0%

    30.0%

    35.0%

    40.0%

    45.0%

    50.0%

    0 2 4 6 8 10 12Taps

    A UP

    A DOWN

    B UP

    B DOWN

    C UP

    C DOWN

    Sl Di S i h i h

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    39/123

     © OMICRON Page: 3904.12.200411/6/2014

    Slope on a Diverter Switch with

    bouncing Contacts in Phase CSlope

    -1.8A/s

    -1.6A/s-1.4A/s

    -1.2A/s

    -1.0A/s

    -0.8A/s

    -0.6A/s

    -0.4A/s

    -0.2A/s

    0.0A/s

    0 2 4 6 8 10 12

    Taps

    A UP

    A DOWN

    B UP

    B DOWN

    C UP

    C DOWN

    E I t ti f 500

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    40/123

     © OMICRON Page: 4004.12.200411/6/2014

    Even Interruptions of 500us can

    be detected

    530us

    Ri l f (Ti f I t ti )

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    41/123

     © OMICRON Page: 4104.12.200411/6/2014

    Ripple = f (Time of Interruption)Dauer der

    Unterbrechnung

    [ms]

    Ripple mitUnter-

    brechung [%]

    Ripple ohne

    Unter-brechung

    [%]

    Slope mit

    Unter-brechung

    [mA/s]

    Slope mit

    Unter-brechung

    [mA/s]

    0.5 4.12 1.00 -42 -2

    1 4.64 1.00 -49.17 -2

    10 32.96 1.00 -405.6 -2

    1000 100.00 1.00 -1192 -2

    Ripple OS Wicklung mit 0.5A Prüfstrom

    0.00

    20.00

    40.00

    60.00

    80.00

    100.00

    120.00

    0.1 1 10 100 1000

    Time of Interruption [ms]

       R   i  p  p

       l  e   [   %   ]

    Ripple mitUnterbrechung

    Ripple ohne

    Unterbrechung

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    42/123

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    43/123

     © OMICRON Page: 4304.12.200411/6/2014

    Ripple of an aged diverter switch

    Ripple

    3.0%

    3.5%

    4.0%

    4.5%

    5.0%

    5.5%

    0 5 10 15 20Taps

    A UP

    A DOWN

    B UPB DOWN

    C UP

    C DOWN

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    44/123

     © OMICRON Page: 4404.12.200411/6/2014

    Slope of an aged diverter switch

    Slope

    -1.1A/s

    -1.05A/s-1.0A/s

    -0.95A/s

    -0.9A/s

    -0.85A/s-0.8A/s

    -0.75A/s

    -0.7A/s

    -0.65A/s

    -0.6A/s

    0 5 10 15 20

    Taps

    A UP

    A DOWN

    B UP

    B DOWN

    C UP

    C DOWN

    Aged diverter switch

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    45/123

     © OMICRON Page: 4504.12.200411/6/2014

    Aged diverter switch

    Contact Problems (static)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    46/123

     © OMICRON Page: 4604.12.200411/6/2014

    Contact Problems (static)

    Ripple

    0.0%

    2.0%

    4.0%

    6.0%

    8.0%

    10.0%

    12.0%

    14.0%

    16.0%

    18.0%

    000 005 010 015 020 025 030Taps

    A UP

    A DOWN

    B UP

    B DOWN

    C UP

    C DOWN

    005 0.145044615Ω   0.061% 2.601% -1.75A/s 20.0A 2.9008923V

    006 0.14168819Ω   0.046% 2.253% -1.65A/s 20.0A 2.8337638V007 0.142732395Ω   0.069% 2.701% -1.75A/s 20.0A 2.8546479V

    008 0.139659045Ω   0.097% 2.903% -1.69A/s 20.0A 2.7931809V

    009 0.13919992Ω   4.612% 16.975% -11.37A/s 20.01A 2.7853904V

    009 0.1396798Ω   1.028% 14.25% -2.6A/s 20.0A 2.793596V

    009 0.139666415Ω   0.204% 14.7% -1.75A/s 20.0A 2.7933283V

    009 0.13958899Ω   0.174% 15.7% -0.56A/s 20.0A 2.7917798V

    010 0.13754698Ω   0.059% 15.666% -1.91A/s 20.0A 2.7509396V

    011 0.137932135Ω

      0.055% 3.402% -1.75A/s 20.0A 2.7586427V012 0.13525902Ω   0.086% 2.703% -1.69A/s 20.0A 2.7051804V

    013 0.12915814Ω   0.079% 3.4% -2.62A/s 20.0A 2.5831628V

    Ripple

    Contact Problems (static)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    47/123

     © OMICRON Page: 4704.12.200411/6/2014

    Contact Problems (static)

    Slope

    -12.0A/s

    -10.0A/s

    -8.0A/s

    -6.0A/s

    -4.0A/s

    -2.0A/s

    0.0A/s

    000 005 010 015 020 025 030Taps

    A UP

    A DOWN

    B UP

    B DOWN

    C UP

    C DOWN

    005 0.145044615Ω   0.061% 2.601% -1.75A/s 20.0A 2.9008923V

    006 0.14168819Ω   0.046% 2.253% -1.65A/s 20.0A 2.8337638V007 0.142732395Ω   0.069% 2.701% -1.75A/s 20.0A 2.8546479V

    008 0.139659045Ω   0.097% 2.903% -1.69A/s 20.0A 2.7931809V

    009 0.13919992Ω   4.612% 16.975% -11.37A/s 20.01A 2.7853904V

    009 0.1396798Ω   1.028% 14.25% -2.6A/s 20.0A 2.793596V

    009 0.139666415Ω   0.204% 14.7% -1.75A/s 20.0A 2.7933283V

    009 0.13958899Ω   0.174% 15.7% -0.56A/s 20.0A 2.7917798V

    010 0.13754698Ω   0.059% 15.666% -1.91A/s 20.0A 2.7509396V

    011 0.137932135Ω

      0.055% 3.402% -1.75A/s 20.0A 2.7586427V012 0.13525902Ω   0.086% 2.703% -1.69A/s 20.0A 2.7051804V

    013 0.12915814Ω   0.079% 3.4% -2.62A/s 20.0A 2.5831628V

    Slope

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    48/123

     © OMICRON Page: 4804.12.200411/6/2014

    Measurement of the shortcircuit impedance

    a) Measurement of the leakage reactance

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    49/123

     © OMICRON Page: 4904.12.200411/6/2014

    Short circuit impedance

    220kV Winding220kV

    Forces

    10kV Winding

    220kV Winding

    Leakage

    Flux

    Short circuit impedance - deviation limits

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    50/123

     © OMICRON Page: 5004.12.200411/6/2014

    p

    400kVA transformer

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    51/123

     © OMICRON Page: 5104.12.200411/6/2014

    400kVA transformerTemplate: TR Short Circuit Imp.

    Version: 1.40

    3 Phase Measurement

    Uk [V] Ik [A] P [W] f [Hz] Z [OHM] Phi [°] R [OHM] X [OHM] L [H]

    1479.40 8.89 6270 50 288.2335 74.02338 79.33485 277.1002 0.882037449

    Phase A

      f [Hz] Z [OHM] Phi [°] R [OHM] X [OHM] L [H]

      50 287.8106 74.21368 78.29901 276.9553 0.881576072

    Difference to Factory Test [%] -0.14671 0.257084 -1.30566 -0.05231 -0.05230818

    Phase B

      f [Hz] Z [OHM] Phi [°] R [OHM] X [OHM] L [H]

      50 287.9643 73.82169 80.23478 276.5607 0.880319891

    Difference to Factory Test [%] -0.09342 -0.27247 1.134345 -0.19473 -0.19472629

    Phase C

      f [Hz] Z [OHM] Phi [°] R [OHM] X [OHM] L [H]

      50 288.7539 74.01075 79.53928 277.583 0.883574133

    Difference to Factory Test [%] 0.180545 -0.01706 0.257675 0.17422 0.174219805

    Average Difference to Factory Test [%] -0.01986 -0.01082 0.028788 -0.02427 -0.02427155

    Factory Test with W-Meter

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    52/123

     © OMICRON Page: 5204.12.200411/6/2014

    Measurement of the short circuitimpedance

    b) Measurement of the AC-short circuit resistance(FRSL = Frequency response of stray losses)

    Parallel strands without twisting

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    53/123

     © OMICRON Page: 5304.12.200411/6/2014

    g

    BHV Winding

    LV Winding

    Lossesby inducedcurrents

    Parallel strands with twisting

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    54/123

     © OMICRON Page: 5404.12.200411/6/2014

    g

    Inducedcurrents arecompensated

    BHV Winding

    LV Winding

    Parallel strands with short circuit

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    55/123

     © OMICRON Page: 5504.12.200411/6/2014

    BHV Winding

    LV Winding

    Additionallossesby induced

    currents

    Equivalent circuit diagram

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    56/123

     © OMICRON Page: 5604.12.200411/6/2014

    q g

    R (f)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    57/123

     © OMICRON Page: 5704.12.200411/6/2014

    Comparison of the 3 phases

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    58/123

     © OMICRON Page: 5804.12.200411/6/2014

    Comparison of the 3 phases

    R(f)

    0.0 Ohm

    0.5 Ohm

    1.0 Ohm

    1.5 Ohm2.0 Ohm

    2.5 Ohm

    3.0 Ohm

    3.5 Ohm4.0 Ohm

    4.5 Ohm

    0 100 200 300 400 500

    Frequency (Hz)

    A

    B

    C

    Case study

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    59/123

     © OMICRON Page: 5904.12.200411/6/2014

    y

    40-MVA, Y∆∆∆∆, 121 kV/12.85 kV transformerThe transformer was removed from service because it

    produced gas, which, upon analysis, showed a hot spot

    involving paper. In the laboratories, however, none of the

    standard tests showed a fault in the windings. In fact, it was

    found that:

    • The turns ratio was correct;• The excitation current was normal;• The DC resistance was normal;•A comparative measurement of the impedance in the

    three phases showed no significant difference (less

    than 3%).

    Case study

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    60/123

     © OMICRON Page: 6004.12.200411/6/2014

    y

    40-MVA, Y∆∆∆∆, 121 kV/12.85 kV transformer

    Case study

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    61/123

     © OMICRON Page: 6104.12.200411/6/2014

    y

    40-MVA, Y∆∆∆∆, 121 kV/12.85 kV transformer

    Phase A: eight of the 13 parallel strands of this winding had been short-circuited. In this condition, the section perpendicular to the lines of

    flux was much higher and, hence, the eddy current losses

    Phase B: two parallel strands were found to be in short-circuit but the fault

    was not located in the winding after it had been dismantled

    Phase C: No fault was detected in the windings

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    62/123

    Short circuit impedance - deviation limits

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    63/123

     © OMICRON Page: 6304.12.200411/6/2014

    Diagnosis of a damaged

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    64/123

     © OMICRON Page: 6404.12.200411/6/2014

    g g

    transformer 220kV / 110kV / 10kV

    • Short circuit of the 10kV

    winding by a marten•Short circuit current Is = 52kA

    •Switching “off” time about100ms

    Result:

    Short circuit of the 10kVwinding to the core (Phase A)

    Ratio and excitation current

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    65/123

     © OMICRON Page: 6504.12.200411/6/2014

    at o a d e c tat o cu e t

    Ratio Error= -21.5% !

    Lk=f(f)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    66/123

     © OMICRON Page: 6604.12.200411/6/2014

    k ( )

    Faultywinding

    Defective 10kV winding skin-

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    67/123

     © OMICRON Page: 6704.12.200411/6/2014

    effect in the coreLow Frequencies

    High Frequencies

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    68/123

    FRA phases V und W

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    69/123

     © OMICRON Page: 6904.12.200411/6/2014

    p

    Phase: V

    Phase: W

    FRA Phases U und W

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    70/123

     © OMICRON Page: 7004.12.200411/6/2014

    Phase: W

    Phase: U

    Opened Transformer

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    71/123

     © OMICRON Page: 7104.12.200411/6/2014

    p

    DefectivePhase

    Currentlimiting

    coils

    View from the Top

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    72/123

     © OMICRON Page: 7204.12.200411/6/2014

    p

    10 kV

    110 kV

    220 kV

    View from the Top

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    73/123

     © OMICRON Page: 7304.12.200411/6/2014

    View from the Top

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    74/123

     © OMICRON Page: 7404.12.200411/6/2014

    Broken wire

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    75/123

     © OMICRON Page: 7504.12.200411/6/2014

    CAPACITANCE AND TAN DELTAMEASUREMENTS ON

    TRANSFORMERS

    Definition of Tan DeltaEquivalent Parallel Circuit Diagram and Vector Diagram

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    76/123

     © OMICRON Page: 7604.12.200411/6/2014

    Equivalent Parallel Circuit Diagram and Vector Diagram

    with

    and Frequency

    Mainly conductive losses

    Equivalent Serial Circuit Diagram

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    77/123

     © OMICRON Page: 7704.12.200411/6/2014

    RSRS

    CS

    URs

    UCs

    S S 

     R

    C  RU 

    ω δ    ==tan

    Mainly polarization losses

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    78/123

    Transformer Winding Insulation

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    79/123

     © OMICRON Page: 7904.12.200411/6/2014

    b. Model for thebehaviour of adielectric withpolarisationcharacteristic andconductivity

    d. Simplified geometrymodel for the maincomponents oil,barriers and spacers

    a. Plate condenseras a model fordielectric insulation

    c. Part of the crosssection of a powertransformer maininsulation systembetween HV and LVwindings

    e: Dielectric modelfor the insulationsystem of powertransformers

    Tan Delta (f) Pressboard Dependenton the Water Content

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    80/123

     © OMICRON Page: 8004.12.200411/6/2014

    Losses in Dielectric Material

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    81/123

     © OMICRON Page: 8104.12.200411/6/2014

    •Transport of electrons and ions

    •Losses through polarisation effects

    •Losses in dielectrics are dependent of

    •Ageing

    •Water content

    •Conductive losses by particles

    •Partial discharges

    What can C-Tan Delta tell us?

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    82/123

     © OMICRON Page: 8204.12.200411/6/2014

    •Capacity:

    • Bushings:

    • Partial breakdowns between layers

    • Incoming oil into cracks of solid insulation (RBP hard

    paper)

    •Transformer windings:

    • Change of the geometry between windings

    (deformation and displacement of windings due to

    big fault currents trough the transformer)

    What can C-Tan Delta tell us?

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    83/123

     © OMICRON Page: 8304.12.200411/6/2014

    •Dissipation factor:

    • Bushings:

    • Aging and decomposition of insulation

    • Water content

    • Bad contacted electrodes or capacitive layers

    • Cracks in the insulation

    • Partial discharges

    • Transformers:

    • Aging• Water content in the oil and in the paper

    • Contamination by particles

    Schering Bridge (1919)First application for insulation diagnosis 1924

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    84/123

     © OMICRON Page: 8404.12.200411/6/2014

    Has to be balancedfor each frequency

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    85/123

    Universal Transformer Test and

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    86/123

     © OMICRON Page: 8604.12.200411/6/2014

    Diagnosis SystemPower amplifier 15-400Hz•Outputs up to 2000A, 2kV AC / 400A DC

    •Measurement of

    •Ratio

    •Complex Impedance

    •Resistance

    • …...

    C-Tanδδδδ-Test System

    Features and Advantages of

    h D ib d T

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    87/123

     © OMICRON Page: 8704.12.200411/6/2014

    the Described Test system• One test system for complete transformer testing

    • Excellent noise suppression (50/60 Hz)

    • Variable frequency of output voltage 15…400Hz

    enables frequency sweeps

    • Most accurate instrument for field use (TD: 5*E-5 C: 0.05%)

    • Automatic test procedures with voltage and

    frequency sweeps -> saves testing time !

    • Automatic reporting and easy export to Excel

    --> saves time for post-processing !

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    88/123

    Screenshot UST-B Mode

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    89/123

     © OMICRON Page: 8904.12.200411/6/2014

    C-Tan-Delta

    M t

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    90/123

     © OMICRON Page: 9004.12.200411/6/2014

    Measurement onPowerTransformers

    High Voltage Winding

    Tapped WindingCore

    400kV Bushing

    Measuring Tap

    Low VoltageBushing

    Low Voltage Winding

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    91/123

     © OMICRON Page: 9104.12.200411/6/2014

    Transformer Winding Test

    No sepuedemostrar la imagen en estemomento.

    Test Procedure for a3-Windings Transformer

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    92/123

     © OMICRON Page: 9204.12.200411/6/2014

    No sepuedemostrar la imagen en estemomento.

    Tan Delta (f) with treated (dry) oil

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    93/123

     © OMICRON Page: 9304.12.200411/6/2014

    DF (f) H, HL, L

    0.0 %

    0.05 %

    0.1 %

    0.15 %

    0.2 %

    0.25 %

    0.3 %

    0.35 %

    0.4 %

    0.45 %

       0 .   0

       H  z

       5   0

     .   0   H  z

       1   0   0

     .   0   H  z

       1   5   0

     .   0   H  z

       2   0   0

     .   0   H  z

       2   5   0

     .   0   H  z

       3   0   0

     .   0   H  z

       3   5   0

     .   0   H  z

       4   0   0

     .   0   H  z

       4   5   0

     .   0   H  z

    H(f)

    HL(f)

    L(f)

    Tan Delta (f) with aged oil

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    94/123

     © OMICRON Page: 9404.12.200411/6/2014

    DF (f) H, HL, L

    0.0 %

    0.1 %

    0.2 %

    0.3 %

    0.4 %

    0.5 %

    0.6 %

       0 .   0

       H  z

       5   0

     .   0   H  z

       1   0   0

     .   0   H  z

       1   5   0

     .   0   H  z

       2   0   0

     .   0   H  z

       2   5   0

     .   0   H  z

       3   0   0

     .   0   H  z

       3   5   0

     .   0   H  z

       4   0   0

     .   0   H  z

       4   5   0

     .   0   H  z

    H(f)

    HL(f)

    L(f)

    Tan Delta (f) of a 110kV transformer withhigh water content

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    95/123

     © OMICRON Page: 9504.12.200411/6/2014

    DF (f) H, HL

    0.0 %

    0.2 %

    0.4 %

    0.6 %

    0.8 %

    1.0 %

    1.2 %

    1.4 %

    1.6 %

    1.8 %

       0 .   0   H  z

       5   0 .   0   H  z

       1   0   0 .   0   H  z

       1   5   0 .   0   H  z

       2   0   0 .   0   H  z

       2   5   0 .   0   H  z

       3   0   0 .   0   H  z

       3   5   0 .   0   H  z

       4   0   0 .   0   H  z

       4   5   0 .   0   H  z

    H(f)

    HL(f)

    Tan Delta 11kV-0.4kV 800KVA (1966)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    96/123

     © OMICRON Page: 9604.12.200411/6/2014

    DF HV-LV (f)

    0.0 %

    0.5 %

    1.0 %

    1.5 %

    2.0 %

    2.5 %

    0.0 Hz 50.0 Hz 100.0 Hz 150.0 Hz 200.0 Hz 250.0 Hz

    Unexpected ferquency curves8.0 %

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    97/123

     © OMICRON Page: 9704.12.200411/6/2014

    -1.0 %

    0.0 %

    1.0 %

    2.0 %

    3.0 %

    4.0 %

    5.0 %

    6.0 %

    7.0 %

    0.0 Hz 100.0 Hz 200.0 Hz 300.0 Hz 400.0 Hz 500.0 Hz

    17.0 Hz

    30.0 Hz

    80.0 Hz

    130.0 Hz230.0 Hz

    400.0 Hz

    220kV Gießharzdurchführungen

    0.4 %

    0.45 %

    0.5 %

    0.55 %

    0.6 %

    0.65 %

    0.7 %

    0.75 %

    0.8 %

    0.0Hz 50.0Hz 100.0H

    z

    150.0H

    z

    200.0H

    z

    250.0H

    z

    300.0H

    z

    350.0H

    z

    400.0H

    z

    450.0H

    z

    Phase A

    Phase BPhase C

    DF (f)

    -1.5 %

    -1.0 %

    -0.5 %

    0.0 %

    0.5 %

    1.0 %

       0

     .   0   H  z

       5   0

     .   0   H  z

       1   0   0

     .   0   H  z

       1   5   0

     .   0   H  z

       2   0   0

     .   0   H  z

       2   5   0

     .   0   H  z

       3   0   0

     .   0   H  z

       3   5   0

     .   0   H  z

       4   0   0

     .   0   H  z

       4   5   0

     .   0   H  z

    Phases Not Connected or Bad Contacts

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    98/123

     © OMICRON Page: 9804.12.200411/6/2014

    Currents throughthe windingscause additionalinductive losses

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    99/123

    DF (f)

    0.1 %

    0.3 %

    0.5 %

    0.7 %

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    100/123

     © OMICRON Page: 10004.12.200411/6/2014

    Bad contact ofshort circuit

    -1.5 %

    -1.3 %

    -1.1 %

    -0.9 %

    -0.7 %

    -0.5 %

    -0.3 %

    -0.1 %

       0 .   0

       H  z

       5   0 .   0

       H  z

       1   0   0 .   0

       H  z

       1   5   0 .   0

       H  z

       2   0   0 .   0

       H  z

       2   5   0 .   0

       H  z

       3   0   0 .   0

       H  z

       3   5   0 .   0

       H  z

       4   0   0 .   0

       H  z

       4   5   0 .   0

       H  z

    DF (f)

    0.0 %

    0.1 %

    0.2 %

    0.3 %

    0.4 %

    0.5 %

    0.6 %

    0.7 %

    0.8 %

       0 .   0

       H  z

       5   0

     .   0   H  z

       1   0   0

     .   0   H  z

       1   5   0

     .   0   H  z

       2   0   0

     .   0   H  z

       2   5   0

     .   0   H  z

       3   0   0

     .   0   H  z

       3   5   0

     .   0   H  z

       4   0   0

     .   0   H  z

       4   5   0

     .   0   H  z

    Good contacts

    of short circuit

    No sepuedemostrar la imagen en estemomento.

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    101/123

     © OMICRON Page: 10104.12.200411/6/2014

    HV Bushings

    Capacitive Bushings (1)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    102/123

     © OMICRON Page: 10204.12.200411/6/2014

    Emax= high

    A

    Emax=smaller

    A

    without

    capacitivelayers

    withcapacitivelayers

    Earthing Cap

    Capacitive Bushings (2)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    103/123

     © OMICRON Page: 10304.12.200411/6/2014

    Bushing Measuring Tap

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    104/123

     © OMICRON Page: 10404.12.200411/6/2014

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    105/123

    Bushing Fault

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    106/123

     © OMICRON Page: 10604.12.200411/6/2014

    Bushing after Explosion

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    107/123

     © OMICRON Page: 10704.12.200411/6/2014

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    108/123

    220kV RIP Bushing stored outside

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    109/123

     © OMICRON Page: 10904.12.200411/6/2014

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    110/123

    66kV Oil Circuit Breaker (USA)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    111/123

     © OMICRON Page: 11104.12.200411/6/2014

    DF (f) 69 kV OIP Bushings

    Circuit Breaker Bushing C-PF Test

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    112/123

     © OMICRON Page: 11204.12.200411/6/2014

    Circuit Breaker Bushing C-PF Test

    V TEST* [V] C meas. PF meas.[%]10032.20 2.836E-10 0.457

    10031.81 2.815E-10 0.491

    10031.55 2.853E-10 0.49310031.20 2.837E-10 0.486

    10028.73 2.855E-10 0.504

    10030.49 2.853E-10 0.449

    DF (f) 69 kV OIP Bushings 60Hz

    0.6 %

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    113/123

     © OMICRON Page: 11304.12.200411/6/2014

    0.0 %

    0.1 %

    0.2 %

    0.3 %

    0.4 %

    0.5 %

    *0.0 Hz *100.0 Hz *200.0 Hz *300.0 Hz *400.0 Hz *500.0 Hz

    1

    2

    3

    4

    56

    DF (f) 69 kV OIP Bushings 17-400Hz

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    114/123

     © OMICRON Page: 11404.12.200411/6/2014

    OIP bushings 420kV (1994)

    Tan Delta C

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    115/123

     © OMICRON Page: 11504.12.200411/6/2014

    0

    0.05

    0.1

    0.15

    0.2

    0.25

    0.3

    0.35

    0.4

    0.45

    0.5

    0 100 200 300 400

    Hz

         %

    U

    V

    W

    360

    365

    370375

    380

    385

    390

    395

    400

    405

    410

    415

    0 100 200 300 400

    Hz

        p     F

    U

    V

    W

    + 10%

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    116/123

    Defectice 110 kV RPB Bushing

    Tan Delta (U)

    0.75

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    117/123

     © OMICRON Page: 11704.12.200411/6/2014

    Tan Delta (V)

    0.3

    0.35

    0.4

    0.45

    0.5

    0.55

    0.6

    0.65

    0.7

    0 5 10 15

    kV

       %

    2V

    2N

    Tan Delta (U)

    Suspicious 400 kV OIP Bushings (1998)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    118/123

     © OMICRON Page: 11804.12.200411/6/2014

    0.0%

    0.05%

    0.1%

    0.15%

    0.2%

    0.25%

    0.3%

    0.35%

    0.4%

    0.45%

    0.5%

    0.0V 2000.0V 4000.0V 6000.0V 8000.0V 10000.0V 12000.0V 14000.0V

    U TanDelta

    V TanDelta

     W TanDelta

    Spannungsverläufe unauffällig

    Suspicious 400 kV OIP Bushings (1998)Reason ?

    Tan Delta (V)

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    119/123

     © OMICRON Page: 11904.12.200411/6/2014

    0.37%

    0.39%

    0.41%

    0.43%

    0.45%

    0.47%

    0.49%

    0.0 Hz 50.0 Hz 100.0 Hz 150.0 Hz 200.0 Hz 250.0 Hz 300.0 Hz 350.0 Hz

    U TanDelta

    V TanDelta

     W TanDelta

    Frequenzververläufe auffällig

    Suspicious 123 kV RIP BushingReason ?

    0.8%

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    120/123

     © OMICRON Page: 12004.12.200411/6/2014

    0.0%

    0.1%

    0.2%

    0.3%

    0.4%

    0.5%

    0.6%

    0.7%

    0.0 Hz 100.0 Hz 200.0 Hz 300.0 Hz 400.0 Hz 500.0 Hz

       T  a  n   D  e   l   t  a

    73

    80

    Measurement with high interference

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    121/123

     © OMICRON Page: 12104.12.200411/6/2014

    Durchführung

    Erdungsgarnitur

    HS Anschluss

    Measurement with high interference

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    122/123

     © OMICRON Page: 12204.12.200411/6/2014

  • 8/9/2019 TRANSFORMER DIAGNOSIS.pdf

    123/123

     © OMICRON Page: 12304.12.200411/6/2014

    Thank you for your Attention !