Upload
danilopoma
View
220
Download
0
Embed Size (px)
Citation preview
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
1/123
© OMICRON 11/6/2014 Page: 1
TRANSFORMER DIAGNOSIS
Dipl.-Ing. Dr. Michael Krüger © 2006
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
2/123
© OMICRON Page: 204.12.200411/6/2014
Sources of Faults
W i n d i n g
C o r e
B u s h i n g s
V e s s e l & O i l
A c c e s s o r i e s
T a p C h a n g e r
F r e q u e n c y
i n %
Source: Cigre_WG 12-05 „An international survey on failures in large power
transformers in service“, Electra No. 88, 1983
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
3/123
© OMICRON Page: 304.12.200411/6/2014
Gas-in-Oil Analysis
Source: Möllmann, A. u.a. „IEC/VDE Standards für flüssige Isolierstoffe zur Diagnostik
von Transformatoren und Wandlern“, ETG Fachbericht 87: Diagnostik elektrischer
Betriebsmittel, Berlin 2002
Type of Fault
Partial Discharge
Discharge with lowEnergy
Discharge with high
Energy
Thermal Fault T
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
4/123
© OMICRON Page: 404.12.200411/6/2014
Tests for Diagnosis
(Fault Location)
•Winding resistance and OLTC test•Practical examples for winding ratio,excitation current, leakage reactance
•FRSL
•Capacitance and dissipation factor
•FRA
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
5/123
© OMICRON Page: 504.12.200411/6/2014
Universal Transformer
Test SystemPower Amplifier
15-400Hz
•Up to 2000A, 2kV AC / 400A DC
•Measurement of
•Ratio
•Complex Impedance•Resistances
• …...
C-Tanδδδδ-Prüfsystem
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
6/123
© OMICRON Page: 604.12.200411/6/2014
Testing OLTC
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
7/123
© OMICRON Page: 704.12.200411/6/2014
On-load tap changer principle (1)
Voltage Selector
Diverter
Switch
Commutating
Resistors
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
8/123
© OMICRON Page: 804.12.200411/6/2014
On-load tap changer principle (2)
Voltage Selector
Diverter
Switch
Commutating
Resistors
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
9/123
© OMICRON Page: 904.12.200411/6/2014
On-load tap changer principle (3)
Voltage Selector
Diverter
Switch
Commutating
Resistors
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
10/123
© OMICRON Page: 1004.12.200411/6/2014
On-load tap changer principle (4)
Voltage Selector
Diverter
Switch
Commutating
Resistors
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
11/123
© OMICRON Page: 1104.12.200411/6/2014
On-load tap changer principle (5)
Voltage Selector
Diverter
Switch
Commutating
Resistors
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
12/123
© OMICRON Page: 1204.12.200411/6/2014
On-load tap changer principle (6)
Voltage Selector
Diverter
Switch
Commutating
Resistors
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
13/123
© OMICRON Page: 1304.12.200411/6/2014
On-load tap changer
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
14/123
© OMICRON Page: 1404.12.200411/6/2014
Measurement of the staticresistance values of:
1) all internal contacts (diverter
switch contacts + tapselector switch + connectionclamps) +
2) the winding resistance
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
15/123
© OMICRON Page: 1504.12.200411/6/2014
New voltage selector contact
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
16/123
© OMICRON Page: 1604.12.200411/6/2014
Voltage selector switch in a good
conditionWiderstand V-Mp
235.00
240.00
245.00
250.00
255.00
260.00
265.00
270.00
275.00
280.00
285.00
1 2 3 4 5 6 7 8 9 1 0
1 1
1 2
1 3
1 4
1 5
1 6
1 7
1 8
1 9
2 0
2 1
Stufen
W i d e r s t a n
d [ m Ω ΩΩ Ω ] KEMA
OMICRON 1…21Ref. Temp.
OMICRON 21…1Ref. Temp.
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
17/123
© OMICRON Page: 1704.12.200411/6/2014
Influence of the Temperature
Maschinentransformator27kV/400kV 1100MVA
1. Measurement: 20°C
Last Meas.: 23°C
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
18/123
© OMICRON Page: 1804.12.200411/6/2014
Influence of the Temperature
R Winding (Tap)
0.14Ω
0.145Ω
0.15Ω
0.155Ω
0.16Ω
0.165Ω
000 005 010 015 020 025 030Taps
A UP
A DOWN
B UP
B DOWNC UP
C DOWN
012.1*)20()23(:235
235)()(
1
212 °=°
+
+= R R Beispiel
T
T T RT R
Delta =1.2%
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
19/123
© OMICRON Page: 1904.12.200411/6/2014
Faulty voltage selector contact
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
20/123
© OMICRON Page: 2004.12.200411/6/2014
Defective Voltage Selector
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
21/123
© OMICRON Page: 2104.12.200411/6/2014
Defective Tap Selector
Starke Verrußung durch Erwärmung und Ablagerungen
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
22/123
© OMICRON Page: 2204.12.200411/6/2014
Resistance U-Mp
R L1 (referred to 20°C)
450.0
500.0
550.0
600.0
650.0
700.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Taps
m O h m
R L1 1974
R L1 20.2.02 1...19
RL1 20.2.02 19…1
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
23/123
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
24/123
© OMICRON Page: 2404.12.200411/6/2014
100MVA 220/110 kV W
R L3 (referred to 20°)
450.0
470.0
490.0
510.0
530.0
550.0
570.0
590.0
610.0
630.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Taps
m O h m
R L3 1974
R L3 20.2.02 1…19
R L3K 20.2.02 19…1
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
25/123
© OMICRON Page: 2504.12.200411/6/2014
Winding Resistance U-Mp After RepairResistance L1
450.0
470.0
490.0
510.0
530.0
550.0570.0
590.0
610.0
630.0
650.0
1 2 3 4 5 6 7 8 9 1 0
1 1
1 2
1 3
1 4
1 5
1 6
1 7
1 8
1 9
Taps
R e s i s t a n c e
[ m Ω ] Ω ] Ω ] Ω ]
Factory MeasurementOMICRON 1…19
OMICRON 19…1
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
26/123
© OMICRON Page: 2604.12.200411/6/2014
Delta R for U-Mp „UP“-„DOWN“
Resistance Differenz L1 Up-Down
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
1 2 3 4 5 6 7 8 9 1 0
1 1
1 2
1 3
1 4
1 5
1 6
1 7
1 8
1 9
Taps
R e s i s t a n c e
[ m Ω ] Ω ] Ω ] Ω ]
Resistance Differenz L1 Up-Down
-30.0
-20.0
-10.0
0.0
10.0
20.0
30.0
40.0
1 2 3 4 5 6 7 8 9 1 0
1 1
1 2
1 3
1 4
1 5
1 6
1 7
1 8
1 9
Taps
R e s i s t a n c e [ m
Ω ] Ω ] Ω ] Ω ]
Before repair
After repair
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
27/123
© OMICRON Page: 2704.12.200411/6/2014
Cleaning effect of OLTC movement
R Winding (Tap)
0.14 Ohm
0.15 Ohm
0.16 Ohm
0.17 Ohm
0.18 Ohm
0.19 Ohm
0.2 Ohm
0 5 10 15 20Taps
A UP
A DOWN
B UP
B DOWN
C UP
C DOWN
R Winding (Tap)
0.14 Ohm
0.15 Ohm
0.16 Ohm
0.17 Ohm
0.18 Ohm
0.19 Ohm
0.2 Ohm
0 5 10 15 20Taps
A UP
A DOWN
B UP
B DOWNC UP
C DOWN
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
28/123
© OMICRON Page: 2804.12.200411/6/2014
Increased contact resistance on a
diverter switch in phase AR Winding (Tap)
0.13 Ohm
0.135 Ohm
0.14 Ohm
0.145 Ohm
0.15 Ohm0.155 Ohm
0.16 Ohm
0.165 Ohm
0.17 Ohm0.175 Ohm
0.18 Ohm
0 2 4 6 8 10 12Taps
A UP
A DOWN
B UP
B DOWN
C UP
C DOWN
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
29/123
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
30/123
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
31/123
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
32/123
© OMICRON Page: 3204.12.200411/6/2014
Measurement of „Low Ohmic“ Windings
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
33/123
© OMICRON Page: 3304.12.200411/6/2014
Analysis of the TransientSwitching Behavior of the
Diverter Switch
T i t i l f it hi
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
34/123
© OMICRON Page: 3404.12.200411/6/2014
Transient signal of one switching
procedure in detail
1 = Diverter switch commutates from the first tap to the first commutating resistor
2 = The second commutationg resistor is switched in parralel
3 = shorting of the second commutating resistor and commutating to the second tap
4 = Charging of the additional windings
Ripple
Slopeαααα
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
35/123
© OMICRON Page: 3504.12.200411/6/2014
Diagnosis of the diverter switch
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
36/123
© OMICRON Page: 3604.12.200411/6/2014
Ripple of a diverter switch in a
good condition (1100MVA)Ripple
0.0%
0.5%
1.0%
1.5%
2.0%
2.5%
000 005 010 015 020 025 030Taps
A UP
A DOWN
B UPB DOWN
C UP
C DOWN
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
37/123
© OMICRON Page: 3704.12.200411/6/2014
Slope of a diverter switch in a
good condition (1100MVA)Slope
-0.6A/s
-0.5A/s
-0.4A/s
-0.3A/s
-0.2A/s
-0.1A/s
0.0A/s
000 005 010 015 020 025 030
Taps
A UP
A DOWN
B UP
B DOWN
C UP
C DOWN
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
38/123
© OMICRON Page: 3804.12.200411/6/2014
Ripple on a Diverter Switch with
bouncing Contacts in Phase CRipple
0.0%
5.0%
10.0%
15.0%
20.0%
25.0%
30.0%
35.0%
40.0%
45.0%
50.0%
0 2 4 6 8 10 12Taps
A UP
A DOWN
B UP
B DOWN
C UP
C DOWN
Sl Di S i h i h
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
39/123
© OMICRON Page: 3904.12.200411/6/2014
Slope on a Diverter Switch with
bouncing Contacts in Phase CSlope
-1.8A/s
-1.6A/s-1.4A/s
-1.2A/s
-1.0A/s
-0.8A/s
-0.6A/s
-0.4A/s
-0.2A/s
0.0A/s
0 2 4 6 8 10 12
Taps
A UP
A DOWN
B UP
B DOWN
C UP
C DOWN
E I t ti f 500
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
40/123
© OMICRON Page: 4004.12.200411/6/2014
Even Interruptions of 500us can
be detected
530us
Ri l f (Ti f I t ti )
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
41/123
© OMICRON Page: 4104.12.200411/6/2014
Ripple = f (Time of Interruption)Dauer der
Unterbrechnung
[ms]
Ripple mitUnter-
brechung [%]
Ripple ohne
Unter-brechung
[%]
Slope mit
Unter-brechung
[mA/s]
Slope mit
Unter-brechung
[mA/s]
0.5 4.12 1.00 -42 -2
1 4.64 1.00 -49.17 -2
10 32.96 1.00 -405.6 -2
1000 100.00 1.00 -1192 -2
Ripple OS Wicklung mit 0.5A Prüfstrom
0.00
20.00
40.00
60.00
80.00
100.00
120.00
0.1 1 10 100 1000
Time of Interruption [ms]
R i p p
l e [ % ]
Ripple mitUnterbrechung
Ripple ohne
Unterbrechung
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
42/123
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
43/123
© OMICRON Page: 4304.12.200411/6/2014
Ripple of an aged diverter switch
Ripple
3.0%
3.5%
4.0%
4.5%
5.0%
5.5%
0 5 10 15 20Taps
A UP
A DOWN
B UPB DOWN
C UP
C DOWN
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
44/123
© OMICRON Page: 4404.12.200411/6/2014
Slope of an aged diverter switch
Slope
-1.1A/s
-1.05A/s-1.0A/s
-0.95A/s
-0.9A/s
-0.85A/s-0.8A/s
-0.75A/s
-0.7A/s
-0.65A/s
-0.6A/s
0 5 10 15 20
Taps
A UP
A DOWN
B UP
B DOWN
C UP
C DOWN
Aged diverter switch
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
45/123
© OMICRON Page: 4504.12.200411/6/2014
Aged diverter switch
Contact Problems (static)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
46/123
© OMICRON Page: 4604.12.200411/6/2014
Contact Problems (static)
Ripple
0.0%
2.0%
4.0%
6.0%
8.0%
10.0%
12.0%
14.0%
16.0%
18.0%
000 005 010 015 020 025 030Taps
A UP
A DOWN
B UP
B DOWN
C UP
C DOWN
005 0.145044615Ω 0.061% 2.601% -1.75A/s 20.0A 2.9008923V
006 0.14168819Ω 0.046% 2.253% -1.65A/s 20.0A 2.8337638V007 0.142732395Ω 0.069% 2.701% -1.75A/s 20.0A 2.8546479V
008 0.139659045Ω 0.097% 2.903% -1.69A/s 20.0A 2.7931809V
009 0.13919992Ω 4.612% 16.975% -11.37A/s 20.01A 2.7853904V
009 0.1396798Ω 1.028% 14.25% -2.6A/s 20.0A 2.793596V
009 0.139666415Ω 0.204% 14.7% -1.75A/s 20.0A 2.7933283V
009 0.13958899Ω 0.174% 15.7% -0.56A/s 20.0A 2.7917798V
010 0.13754698Ω 0.059% 15.666% -1.91A/s 20.0A 2.7509396V
011 0.137932135Ω
0.055% 3.402% -1.75A/s 20.0A 2.7586427V012 0.13525902Ω 0.086% 2.703% -1.69A/s 20.0A 2.7051804V
013 0.12915814Ω 0.079% 3.4% -2.62A/s 20.0A 2.5831628V
Ripple
Contact Problems (static)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
47/123
© OMICRON Page: 4704.12.200411/6/2014
Contact Problems (static)
Slope
-12.0A/s
-10.0A/s
-8.0A/s
-6.0A/s
-4.0A/s
-2.0A/s
0.0A/s
000 005 010 015 020 025 030Taps
A UP
A DOWN
B UP
B DOWN
C UP
C DOWN
005 0.145044615Ω 0.061% 2.601% -1.75A/s 20.0A 2.9008923V
006 0.14168819Ω 0.046% 2.253% -1.65A/s 20.0A 2.8337638V007 0.142732395Ω 0.069% 2.701% -1.75A/s 20.0A 2.8546479V
008 0.139659045Ω 0.097% 2.903% -1.69A/s 20.0A 2.7931809V
009 0.13919992Ω 4.612% 16.975% -11.37A/s 20.01A 2.7853904V
009 0.1396798Ω 1.028% 14.25% -2.6A/s 20.0A 2.793596V
009 0.139666415Ω 0.204% 14.7% -1.75A/s 20.0A 2.7933283V
009 0.13958899Ω 0.174% 15.7% -0.56A/s 20.0A 2.7917798V
010 0.13754698Ω 0.059% 15.666% -1.91A/s 20.0A 2.7509396V
011 0.137932135Ω
0.055% 3.402% -1.75A/s 20.0A 2.7586427V012 0.13525902Ω 0.086% 2.703% -1.69A/s 20.0A 2.7051804V
013 0.12915814Ω 0.079% 3.4% -2.62A/s 20.0A 2.5831628V
Slope
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
48/123
© OMICRON Page: 4804.12.200411/6/2014
Measurement of the shortcircuit impedance
a) Measurement of the leakage reactance
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
49/123
© OMICRON Page: 4904.12.200411/6/2014
Short circuit impedance
220kV Winding220kV
Forces
10kV Winding
220kV Winding
Leakage
Flux
Short circuit impedance - deviation limits
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
50/123
© OMICRON Page: 5004.12.200411/6/2014
p
400kVA transformer
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
51/123
© OMICRON Page: 5104.12.200411/6/2014
400kVA transformerTemplate: TR Short Circuit Imp.
Version: 1.40
3 Phase Measurement
Uk [V] Ik [A] P [W] f [Hz] Z [OHM] Phi [°] R [OHM] X [OHM] L [H]
1479.40 8.89 6270 50 288.2335 74.02338 79.33485 277.1002 0.882037449
Phase A
f [Hz] Z [OHM] Phi [°] R [OHM] X [OHM] L [H]
50 287.8106 74.21368 78.29901 276.9553 0.881576072
Difference to Factory Test [%] -0.14671 0.257084 -1.30566 -0.05231 -0.05230818
Phase B
f [Hz] Z [OHM] Phi [°] R [OHM] X [OHM] L [H]
50 287.9643 73.82169 80.23478 276.5607 0.880319891
Difference to Factory Test [%] -0.09342 -0.27247 1.134345 -0.19473 -0.19472629
Phase C
f [Hz] Z [OHM] Phi [°] R [OHM] X [OHM] L [H]
50 288.7539 74.01075 79.53928 277.583 0.883574133
Difference to Factory Test [%] 0.180545 -0.01706 0.257675 0.17422 0.174219805
Average Difference to Factory Test [%] -0.01986 -0.01082 0.028788 -0.02427 -0.02427155
Factory Test with W-Meter
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
52/123
© OMICRON Page: 5204.12.200411/6/2014
Measurement of the short circuitimpedance
b) Measurement of the AC-short circuit resistance(FRSL = Frequency response of stray losses)
Parallel strands without twisting
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
53/123
© OMICRON Page: 5304.12.200411/6/2014
g
BHV Winding
LV Winding
Lossesby inducedcurrents
Parallel strands with twisting
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
54/123
© OMICRON Page: 5404.12.200411/6/2014
g
Inducedcurrents arecompensated
BHV Winding
LV Winding
Parallel strands with short circuit
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
55/123
© OMICRON Page: 5504.12.200411/6/2014
BHV Winding
LV Winding
Additionallossesby induced
currents
Equivalent circuit diagram
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
56/123
© OMICRON Page: 5604.12.200411/6/2014
q g
R (f)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
57/123
© OMICRON Page: 5704.12.200411/6/2014
Comparison of the 3 phases
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
58/123
© OMICRON Page: 5804.12.200411/6/2014
Comparison of the 3 phases
R(f)
0.0 Ohm
0.5 Ohm
1.0 Ohm
1.5 Ohm2.0 Ohm
2.5 Ohm
3.0 Ohm
3.5 Ohm4.0 Ohm
4.5 Ohm
0 100 200 300 400 500
Frequency (Hz)
A
B
C
Case study
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
59/123
© OMICRON Page: 5904.12.200411/6/2014
y
40-MVA, Y∆∆∆∆, 121 kV/12.85 kV transformerThe transformer was removed from service because it
produced gas, which, upon analysis, showed a hot spot
involving paper. In the laboratories, however, none of the
standard tests showed a fault in the windings. In fact, it was
found that:
• The turns ratio was correct;• The excitation current was normal;• The DC resistance was normal;•A comparative measurement of the impedance in the
three phases showed no significant difference (less
than 3%).
Case study
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
60/123
© OMICRON Page: 6004.12.200411/6/2014
y
40-MVA, Y∆∆∆∆, 121 kV/12.85 kV transformer
Case study
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
61/123
© OMICRON Page: 6104.12.200411/6/2014
y
40-MVA, Y∆∆∆∆, 121 kV/12.85 kV transformer
Phase A: eight of the 13 parallel strands of this winding had been short-circuited. In this condition, the section perpendicular to the lines of
flux was much higher and, hence, the eddy current losses
Phase B: two parallel strands were found to be in short-circuit but the fault
was not located in the winding after it had been dismantled
Phase C: No fault was detected in the windings
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
62/123
Short circuit impedance - deviation limits
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
63/123
© OMICRON Page: 6304.12.200411/6/2014
Diagnosis of a damaged
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
64/123
© OMICRON Page: 6404.12.200411/6/2014
g g
transformer 220kV / 110kV / 10kV
• Short circuit of the 10kV
winding by a marten•Short circuit current Is = 52kA
•Switching “off” time about100ms
Result:
Short circuit of the 10kVwinding to the core (Phase A)
Ratio and excitation current
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
65/123
© OMICRON Page: 6504.12.200411/6/2014
at o a d e c tat o cu e t
Ratio Error= -21.5% !
Lk=f(f)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
66/123
© OMICRON Page: 6604.12.200411/6/2014
k ( )
Faultywinding
Defective 10kV winding skin-
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
67/123
© OMICRON Page: 6704.12.200411/6/2014
effect in the coreLow Frequencies
High Frequencies
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
68/123
FRA phases V und W
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
69/123
© OMICRON Page: 6904.12.200411/6/2014
p
Phase: V
Phase: W
FRA Phases U und W
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
70/123
© OMICRON Page: 7004.12.200411/6/2014
Phase: W
Phase: U
Opened Transformer
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
71/123
© OMICRON Page: 7104.12.200411/6/2014
p
DefectivePhase
Currentlimiting
coils
View from the Top
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
72/123
© OMICRON Page: 7204.12.200411/6/2014
p
10 kV
110 kV
220 kV
View from the Top
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
73/123
© OMICRON Page: 7304.12.200411/6/2014
View from the Top
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
74/123
© OMICRON Page: 7404.12.200411/6/2014
Broken wire
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
75/123
© OMICRON Page: 7504.12.200411/6/2014
CAPACITANCE AND TAN DELTAMEASUREMENTS ON
TRANSFORMERS
Definition of Tan DeltaEquivalent Parallel Circuit Diagram and Vector Diagram
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
76/123
© OMICRON Page: 7604.12.200411/6/2014
Equivalent Parallel Circuit Diagram and Vector Diagram
with
and Frequency
Mainly conductive losses
Equivalent Serial Circuit Diagram
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
77/123
© OMICRON Page: 7704.12.200411/6/2014
RSRS
CS
URs
UCs
S S
C
R
C RU
U
ω δ ==tan
Mainly polarization losses
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
78/123
Transformer Winding Insulation
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
79/123
© OMICRON Page: 7904.12.200411/6/2014
b. Model for thebehaviour of adielectric withpolarisationcharacteristic andconductivity
d. Simplified geometrymodel for the maincomponents oil,barriers and spacers
a. Plate condenseras a model fordielectric insulation
c. Part of the crosssection of a powertransformer maininsulation systembetween HV and LVwindings
e: Dielectric modelfor the insulationsystem of powertransformers
Tan Delta (f) Pressboard Dependenton the Water Content
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
80/123
© OMICRON Page: 8004.12.200411/6/2014
Losses in Dielectric Material
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
81/123
© OMICRON Page: 8104.12.200411/6/2014
•Transport of electrons and ions
•Losses through polarisation effects
•Losses in dielectrics are dependent of
•Ageing
•Water content
•Conductive losses by particles
•Partial discharges
What can C-Tan Delta tell us?
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
82/123
© OMICRON Page: 8204.12.200411/6/2014
•Capacity:
• Bushings:
• Partial breakdowns between layers
• Incoming oil into cracks of solid insulation (RBP hard
paper)
•Transformer windings:
• Change of the geometry between windings
(deformation and displacement of windings due to
big fault currents trough the transformer)
What can C-Tan Delta tell us?
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
83/123
© OMICRON Page: 8304.12.200411/6/2014
•Dissipation factor:
• Bushings:
• Aging and decomposition of insulation
• Water content
• Bad contacted electrodes or capacitive layers
• Cracks in the insulation
• Partial discharges
• Transformers:
• Aging• Water content in the oil and in the paper
• Contamination by particles
Schering Bridge (1919)First application for insulation diagnosis 1924
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
84/123
© OMICRON Page: 8404.12.200411/6/2014
Has to be balancedfor each frequency
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
85/123
Universal Transformer Test and
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
86/123
© OMICRON Page: 8604.12.200411/6/2014
Diagnosis SystemPower amplifier 15-400Hz•Outputs up to 2000A, 2kV AC / 400A DC
•Measurement of
•Ratio
•Complex Impedance
•Resistance
• …...
C-Tanδδδδ-Test System
Features and Advantages of
h D ib d T
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
87/123
© OMICRON Page: 8704.12.200411/6/2014
the Described Test system• One test system for complete transformer testing
• Excellent noise suppression (50/60 Hz)
• Variable frequency of output voltage 15…400Hz
enables frequency sweeps
• Most accurate instrument for field use (TD: 5*E-5 C: 0.05%)
• Automatic test procedures with voltage and
frequency sweeps -> saves testing time !
• Automatic reporting and easy export to Excel
--> saves time for post-processing !
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
88/123
Screenshot UST-B Mode
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
89/123
© OMICRON Page: 8904.12.200411/6/2014
C-Tan-Delta
M t
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
90/123
© OMICRON Page: 9004.12.200411/6/2014
Measurement onPowerTransformers
High Voltage Winding
Tapped WindingCore
400kV Bushing
Measuring Tap
Low VoltageBushing
Low Voltage Winding
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
91/123
© OMICRON Page: 9104.12.200411/6/2014
Transformer Winding Test
No sepuedemostrar la imagen en estemomento.
Test Procedure for a3-Windings Transformer
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
92/123
© OMICRON Page: 9204.12.200411/6/2014
No sepuedemostrar la imagen en estemomento.
Tan Delta (f) with treated (dry) oil
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
93/123
© OMICRON Page: 9304.12.200411/6/2014
DF (f) H, HL, L
0.0 %
0.05 %
0.1 %
0.15 %
0.2 %
0.25 %
0.3 %
0.35 %
0.4 %
0.45 %
0 . 0
H z
5 0
. 0 H z
1 0 0
. 0 H z
1 5 0
. 0 H z
2 0 0
. 0 H z
2 5 0
. 0 H z
3 0 0
. 0 H z
3 5 0
. 0 H z
4 0 0
. 0 H z
4 5 0
. 0 H z
H(f)
HL(f)
L(f)
Tan Delta (f) with aged oil
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
94/123
© OMICRON Page: 9404.12.200411/6/2014
DF (f) H, HL, L
0.0 %
0.1 %
0.2 %
0.3 %
0.4 %
0.5 %
0.6 %
0 . 0
H z
5 0
. 0 H z
1 0 0
. 0 H z
1 5 0
. 0 H z
2 0 0
. 0 H z
2 5 0
. 0 H z
3 0 0
. 0 H z
3 5 0
. 0 H z
4 0 0
. 0 H z
4 5 0
. 0 H z
H(f)
HL(f)
L(f)
Tan Delta (f) of a 110kV transformer withhigh water content
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
95/123
© OMICRON Page: 9504.12.200411/6/2014
DF (f) H, HL
0.0 %
0.2 %
0.4 %
0.6 %
0.8 %
1.0 %
1.2 %
1.4 %
1.6 %
1.8 %
0 . 0 H z
5 0 . 0 H z
1 0 0 . 0 H z
1 5 0 . 0 H z
2 0 0 . 0 H z
2 5 0 . 0 H z
3 0 0 . 0 H z
3 5 0 . 0 H z
4 0 0 . 0 H z
4 5 0 . 0 H z
H(f)
HL(f)
Tan Delta 11kV-0.4kV 800KVA (1966)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
96/123
© OMICRON Page: 9604.12.200411/6/2014
DF HV-LV (f)
0.0 %
0.5 %
1.0 %
1.5 %
2.0 %
2.5 %
0.0 Hz 50.0 Hz 100.0 Hz 150.0 Hz 200.0 Hz 250.0 Hz
Unexpected ferquency curves8.0 %
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
97/123
© OMICRON Page: 9704.12.200411/6/2014
-1.0 %
0.0 %
1.0 %
2.0 %
3.0 %
4.0 %
5.0 %
6.0 %
7.0 %
0.0 Hz 100.0 Hz 200.0 Hz 300.0 Hz 400.0 Hz 500.0 Hz
17.0 Hz
30.0 Hz
80.0 Hz
130.0 Hz230.0 Hz
400.0 Hz
220kV Gießharzdurchführungen
0.4 %
0.45 %
0.5 %
0.55 %
0.6 %
0.65 %
0.7 %
0.75 %
0.8 %
0.0Hz 50.0Hz 100.0H
z
150.0H
z
200.0H
z
250.0H
z
300.0H
z
350.0H
z
400.0H
z
450.0H
z
Phase A
Phase BPhase C
DF (f)
-1.5 %
-1.0 %
-0.5 %
0.0 %
0.5 %
1.0 %
0
. 0 H z
5 0
. 0 H z
1 0 0
. 0 H z
1 5 0
. 0 H z
2 0 0
. 0 H z
2 5 0
. 0 H z
3 0 0
. 0 H z
3 5 0
. 0 H z
4 0 0
. 0 H z
4 5 0
. 0 H z
Phases Not Connected or Bad Contacts
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
98/123
© OMICRON Page: 9804.12.200411/6/2014
Currents throughthe windingscause additionalinductive losses
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
99/123
DF (f)
0.1 %
0.3 %
0.5 %
0.7 %
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
100/123
© OMICRON Page: 10004.12.200411/6/2014
Bad contact ofshort circuit
-1.5 %
-1.3 %
-1.1 %
-0.9 %
-0.7 %
-0.5 %
-0.3 %
-0.1 %
0 . 0
H z
5 0 . 0
H z
1 0 0 . 0
H z
1 5 0 . 0
H z
2 0 0 . 0
H z
2 5 0 . 0
H z
3 0 0 . 0
H z
3 5 0 . 0
H z
4 0 0 . 0
H z
4 5 0 . 0
H z
DF (f)
0.0 %
0.1 %
0.2 %
0.3 %
0.4 %
0.5 %
0.6 %
0.7 %
0.8 %
0 . 0
H z
5 0
. 0 H z
1 0 0
. 0 H z
1 5 0
. 0 H z
2 0 0
. 0 H z
2 5 0
. 0 H z
3 0 0
. 0 H z
3 5 0
. 0 H z
4 0 0
. 0 H z
4 5 0
. 0 H z
Good contacts
of short circuit
No sepuedemostrar la imagen en estemomento.
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
101/123
© OMICRON Page: 10104.12.200411/6/2014
HV Bushings
Capacitive Bushings (1)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
102/123
© OMICRON Page: 10204.12.200411/6/2014
Emax= high
A
Emax=smaller
A
without
capacitivelayers
withcapacitivelayers
Earthing Cap
Capacitive Bushings (2)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
103/123
© OMICRON Page: 10304.12.200411/6/2014
Bushing Measuring Tap
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
104/123
© OMICRON Page: 10404.12.200411/6/2014
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
105/123
Bushing Fault
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
106/123
© OMICRON Page: 10604.12.200411/6/2014
Bushing after Explosion
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
107/123
© OMICRON Page: 10704.12.200411/6/2014
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
108/123
220kV RIP Bushing stored outside
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
109/123
© OMICRON Page: 10904.12.200411/6/2014
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
110/123
66kV Oil Circuit Breaker (USA)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
111/123
© OMICRON Page: 11104.12.200411/6/2014
DF (f) 69 kV OIP Bushings
Circuit Breaker Bushing C-PF Test
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
112/123
© OMICRON Page: 11204.12.200411/6/2014
Circuit Breaker Bushing C-PF Test
V TEST* [V] C meas. PF meas.[%]10032.20 2.836E-10 0.457
10031.81 2.815E-10 0.491
10031.55 2.853E-10 0.49310031.20 2.837E-10 0.486
10028.73 2.855E-10 0.504
10030.49 2.853E-10 0.449
DF (f) 69 kV OIP Bushings 60Hz
0.6 %
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
113/123
© OMICRON Page: 11304.12.200411/6/2014
0.0 %
0.1 %
0.2 %
0.3 %
0.4 %
0.5 %
*0.0 Hz *100.0 Hz *200.0 Hz *300.0 Hz *400.0 Hz *500.0 Hz
1
2
3
4
56
DF (f) 69 kV OIP Bushings 17-400Hz
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
114/123
© OMICRON Page: 11404.12.200411/6/2014
OIP bushings 420kV (1994)
Tan Delta C
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
115/123
© OMICRON Page: 11504.12.200411/6/2014
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0.5
0 100 200 300 400
Hz
%
U
V
W
360
365
370375
380
385
390
395
400
405
410
415
0 100 200 300 400
Hz
p F
U
V
W
+ 10%
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
116/123
Defectice 110 kV RPB Bushing
Tan Delta (U)
0.75
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
117/123
© OMICRON Page: 11704.12.200411/6/2014
Tan Delta (V)
0.3
0.35
0.4
0.45
0.5
0.55
0.6
0.65
0.7
0 5 10 15
kV
%
2V
2N
Tan Delta (U)
Suspicious 400 kV OIP Bushings (1998)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
118/123
© OMICRON Page: 11804.12.200411/6/2014
0.0%
0.05%
0.1%
0.15%
0.2%
0.25%
0.3%
0.35%
0.4%
0.45%
0.5%
0.0V 2000.0V 4000.0V 6000.0V 8000.0V 10000.0V 12000.0V 14000.0V
U TanDelta
V TanDelta
W TanDelta
Spannungsverläufe unauffällig
Suspicious 400 kV OIP Bushings (1998)Reason ?
Tan Delta (V)
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
119/123
© OMICRON Page: 11904.12.200411/6/2014
0.37%
0.39%
0.41%
0.43%
0.45%
0.47%
0.49%
0.0 Hz 50.0 Hz 100.0 Hz 150.0 Hz 200.0 Hz 250.0 Hz 300.0 Hz 350.0 Hz
U TanDelta
V TanDelta
W TanDelta
Frequenzververläufe auffällig
Suspicious 123 kV RIP BushingReason ?
0.8%
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
120/123
© OMICRON Page: 12004.12.200411/6/2014
0.0%
0.1%
0.2%
0.3%
0.4%
0.5%
0.6%
0.7%
0.0 Hz 100.0 Hz 200.0 Hz 300.0 Hz 400.0 Hz 500.0 Hz
T a n D e l t a
73
80
Measurement with high interference
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
121/123
© OMICRON Page: 12104.12.200411/6/2014
Durchführung
Erdungsgarnitur
HS Anschluss
Measurement with high interference
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
122/123
© OMICRON Page: 12204.12.200411/6/2014
8/9/2019 TRANSFORMER DIAGNOSIS.pdf
123/123
© OMICRON Page: 12304.12.200411/6/2014
Thank you for your Attention !