Upload
ismail-oezkan
View
28
Download
1
Tags:
Embed Size (px)
Citation preview
TOPRAKLAMA HESABI :
600 X 600
Soil resistivity has been considered average of values of
attached document to letter No. dated December 6 , 2004 of EES
Primary data related to earthing design :
PLEASE REFER TO ATTACHED DRAWING.
SHORT CIRCUIT CURRENT : KA50
PHASE S.C CURRENT : 1
SOIL RESISTIVITY :
SURFACE LAYER RESISTIVITY (GRAVEL) : 3000
BURIAL DEPTH OF EARTHING GRID :
EARTHING CALCULATION FOR
RUDESHUR 400 KV POWER PLANT S/S
RATED SYMMETRICAL THREE PHASE
Ohm-Meter
m
m
SURFACE LAYER THICKNESS : 0.1
AREA OCCUPIED BY EARTHING GRID :
m
80
0.7
m2
TIME DURATION OF GROUND FAULT : Sec.0.5
MAXIMUM TEMPERATURE OF AMBIENT : oC50
K RATIO OF SINGLE PHASE TO THREE
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
2 / 3
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
m
50
=
3Nrod = No. of required rod = 100 Lr = the length of each rod in m =
LR = Nrod X LrLT = LC + 1.15LR
Lc = NX*X + NY*Y = 13 X
600A = X*Y = 600 X
=
13
15600 m total length of burial mesh.
Spacing between parallel conductor.
N0. of Horizontal burial conductors.
N0. of Vertical burial conductors.1 =
13
The area occupied by burial grid.
600
360000 m2
+ 13 X
13.0
13.0
The estimated distance for
600
50
600
+
+
1 =
1- EARTH RESISTANCE CALCULATION : RGRID
The estimated distance between earth wires is 50 meter.
D = 50
600
50
m has been resulted by trial & error method.
=300 15945 m
[Eq.52 IEEE-Std 80-2000]0.064
300
h : Depth of earthing conductor burial
15600 +LT =
LR = total length of all rod in m =
1D
YN X
1D
XNY
)20/Ah1
1(1
20A
1
TL
1
gR
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
3 / 4
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
=
1.0
X 1.0 = kA
+
+
Cross section of Riser conductor is:
Cross section of Grid conductor is:
= 237.3
240
240
Sq.mm
Sq.mm
So :
1.72 X 104X 0.00393 X
50
Amm2
1
TCAP : Thermal capacity per unit volume from Table 1(IEEE-std 80), in J/(cm3. C)
= 503.422 X ln
234 450
234
Sq.mm
r : Thermal coefficient of resistivity at reference temperature Tr in 1/ C
r : Resistivity of the ground conductor at reference temperature Tr in µ -cm
Ko : 1/ or (1/ r)-Tr in 1/ C
tc : Duration of current in Sec.
Tm : Maximum allowable temperature in C
Ta : Ambient temperature in C
Tr : Reference temperature for material constant in C
o : Thermal coefficient of resistivity at 0 C in 1/ C
[Eq.40 IEEE-Std 80-2000]
Amm2: Conductor Cross Section in sqmm
I : r.m.s Current in kA = Iearth Fault
2- EARTHING CONDUCTORS CROSS SECTION CALCULATION :
Cross Section of earthing conductor is proportional with Earth fault current value.
It is estimated earth fault current from rated symmetrical 3phase S.C current with
these factors :
K1 For Power plant (P.P) S.S
0.75 For Intermediate or far from P.P or transmission S.S
0.6 For End termination or distribution & very far from P.P S.S
50
Therefore :
Iearth Fault = ISC(3ph) * K = 50
RUDESHUR 400 KV PP S/S.So K = for
)ln(
/)10(
0
0
4
2
a
m
rrc
mm
TK
TK
TCAPtIA
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
4 / 5
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
We suppose this current have 50 kA amplitude.
50So : kAILG=3I0=
return to neutral of other substation's transformers via penetrating to earth
so cause hazardous voltages.
Just transmission line impedance is considered for calculation. In Fig 1 equivalent S.C.
is sketched. It must be noted some approximation are applied which :
Fig.1
1- It is supposed behind supposed length of line is slack bus.
2- Fault resistance (RG) is neglected.
- Neutral of transformer return current
3-1 ZERO-SEQUENCE FAULT CURRENT CALCULATION :
It must be noted S.C. current in P.P. have two component.One component
return to neutral of transformer of P.P trough earthing mesh & second part
2) Secondly should be calculated S f or effects of :
- Shield wire effects a) induction
b) conduction
Sf : fault current division factor
Ig : rms symmetrical grid current in A
I0 : zero-sequence fault current in A
So : 1) Firstly should be calculated I0
3- FAULT CURRENT AND DIVISION FACTOR CALCULATION :
Penetrating current to earth result hazardous touch, step & transfer voltages.
Therefore penetrating fault current should be calculated.
[Eq.63 IEEE-Std 80-2000]
03I
IS
g
f
)( 00
0XXXJRRR
VI F
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
5 / 6
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
m
0
1
1
RG
For
single shield wire
For
double shield wire0.0740.189
+ j 0.73582
0.0068406
1.8936
rC = 1.8442
+ j
/km
GMR=
0.379 + j 0.147
1.17902263
0.8076469
ZSpan : Per span self-impedance of the overhead guard wire ( )
Ztowe : Tower/pole footing impedance ( )
Ztower = 10
b) Conduction effect factor : ref.[3]
Electrical parameters of Guard wire :
The impedance of a ladder for sufficiently long line is :
ZeqS : Impedance of ladder networks ( )
1.8936 + j 0.7358 )
/km
1000
For Guard wire 7No.8 =single shield wire m= 0.09
double shield wire m= 0.17
kV Transmission line have shield wire so m = 0.16
3-2-1 SHIELD WIRE EFFECTS CALCULATION : ref.[3]
3-2 DIVISION FACTOR CALCULATION :
a) Induction effect factor :
Diversion factor of current due to guard wire induction according ref.[3]:
Sf(Shield-induct.) = ( 1 - m )
0.778
Number of incoming or outgoing line which have one guard wire : N1Shield =
Number of incoming or outgoing line which have two guard wire : N2Shield =
+N2Shield
Zeq(2Shield)
=
Sf = Sf(shield-cond.) x (1-m) =
Sf(shield-cond.)=
1
RG
N1Shield
Zeq(1Shield)
0.926
+
832.8
200=
For single shield wire
For double shield wire
TowerSpan
SpanSpan
eqS ZZZZ
Z42
2
(1000
)(mSpanZZ gSpan
TowerSpan
SpanSpan
eqS ZZZZ
Z42
2
)(
10log0028938.0000988.0GW
e
CgGMR
DfjfrZ
fDe 4.658
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
6 / 7
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
Vb : Base voltage
Zb : Base impedance
X0N : Zero-sequence reactance of networkx1N : Positive-sequence reactance of network in per-unitx2N : Negative sequence reactance of network in per-unitSb : Base power
XS1 : Secondary winding voltage impedance of transformer
x0S1 : Secondary winding zero-sequence reactance of transformer in per-unit
X1N : Positive sequence reactance of network
Ib : Base current
ilg : I lg in per-unit
i0lg : Zero-sequence of ilg
XP1 : Primary winding voltage impedance of transformer
x0P1 : Primary winding zero-sequence reactance of transformer in per-unit
It : Current supplied by local transformer (A)
it : It in per-unit
i0t : Zero-sequence of it
Ilg : Iine to ground fault current according to above fig.
sequence impedances of network and power transformer.
3-2-2 NEUTRAL OF TRANSFORMER RETURN CURRENT CALCULATION :
Following figure has sketched equivalent circuit for positive, negative and zero -
Definition of Required parameters:
X 0 N
X 2 N
X 1 N
I P.U
i 0g
i 0 ti 0 N
X 0 t
X - t
X + t
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
7 / 8
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
1
IG = (Ilg - It )*Sf = 32.15 kA
It = it * Ib = kA8.67
ilg
3= 36.6572109.97 It is known that : iolg =
6.358096 ==> it = 3*i0t =
ilg =Ilg
Ib=
0.13
There are parrallel transformer . Hence equivalent x0t shall be :
0.13x0t total=x0t
Ntrans.=
It is considerd k= 0.6
19.1
Also :
=> x0N= 0.0273
According to the transformer data :
x0t =
0.0091
400 kV 0.45466
For calculating zero sequence impedance of network :
Sb = 315 MVA Vb = kA
507.9
4.619
b
b
bV
SI
3
b
b
bS
VZ
2
ph
bN
I
VX
3
13 b
NN
Z
Xx 1
1
N
N
x
xK
1
02
3
tn
nt
xx
xii
00
0lg00
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
8 / 9
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
3 X 100 = 849
d = h= D = 50
[Eq.89 IEEE-Std 80-2000]
Dm =
LC =
[Eq.91 IEEE-Std 80-2000]16411.294
15945 0.0202 0.7
1.00
600 LR = Lr x Nrod = 300
2.6106
D : spacing between parallel conductors in m Ly : maximum length of the grid in the y direction in m
Lx : maximum length of the grid in the x direction in m
Lp = 2400 A = 360000
V
LR : total length of all ground rods in mA : area of the grid in m2
LC : total length of conductor in the horizontal grid in m
Lr : length of each ground rod in m
1.2054
h0=1m (grid reference depth)
LP : peripheral length of the grid in m on the grid in m
Dm : maximum distance between any two points
1
13.288
1
Lx = Ly =
Em = 493.1
600
4- HAZARDOUS VOLTAGES ( TOUCH & STEP ) CALCULATION :4-1 MESH OR TOUCH VOLTAGE :
Em : Mesh voltage
[Eq.84 IEEE-Std 80-2000]
1.3038
13.288
[Eq.80 IEEE-Std 80-2000]
[Eq.81 IEEE-Std 80-2000]
[Eq.83 IEEE-Std 80-2000]
Grid have grounding rod in the corners.
: Spatial soil resistivity
Km : Geometrical factor
Ki : Corrective factor
IG/LM : Average current per unit of effective buried length of the grounding conductor
[Eq.85 IEEE-Std 80-2000]
[Eq.86 IEEE-Std 80-2000]
[Eq.87 IEEE-Std 80-2000]
[Eq.88 IEEE-Std 80-2000]
M
Gimm
L
IKKE
)12(
8ln.
.4..8
).2(
..16ln
2
1 22
nK
K
d
h
dD
hD
dh
DK
h
iim
1iiK
0
1h
hK h
dcba nnnnn ...
P
Ca
L
Ln
.2
A
Ln Pb
.4
yxLL
A
yx
cA
LLn
.7.0
.
22
yx
md
LL
Dn
nKi .148.0644.0
R
yx
rCM L
LL
LLL
2222.155.1
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
9 / 10
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
X X X
12213.8=
[Eq.93 IEEE-Std 80-2000]
KS : Geometrical factor
Ki : Corrective factor
V132.0ES=80 0.24 2.61 32.15
KS = 0.24013
LS = 12214
IG/LS : Average current per unit of effective buried length of the grounding conductor
[Eq.93 IEEE-Std 80-2000]
4-2 STEP VOLTAGE :
ES : Mesh voltage
: Soil resistivity
[Eq.92 IEEE-Std 80-2000]
S
GiS
SL
IKKE
RCS LLL 85.075.0
)5.01(11
.2
11 2n
SDhDh
K
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
10 / 11
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
803000
2X 0 +
5- STEP & TOUCH VOLTAGE CRITERIA : (maximum allowable voltages limits)
[Eq.30 IEEE-Std 80-2000]
[Eq.33 IEEE-Std 80-2000]
[Eq.27 IEEE-Std 80-2000]
hS : thickness of the surface material in m
For 50 kg body weight
For 50 kg body weight
Estep : step voltage in V
Etouch : touch voltage in V
CS : surface layer derating factor
S : resistivity of the surface material in .m
tS : duration of shock current in seconds
= 0.70
Estep = (1000 + 6 X 0.70
1 - )0.09(
0.09CS= 1-
)X0.116
=
X 3000 )X0.116
0.5
Etouch = (1000 + 1.5 X 0.70 X 3000 679 V0.5
= 2225 V
S
SSStept
CE116.0
)61000(70
S
SSToucht
CE116.0
)5.11000(70
09.02
)1(09.0
1S
S
Sh
C
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
11 / 12
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG
mm2
mm2
V
V
6- FINAL RESULTS :
GRID
240
240
EARTHING CONDUCTORS CROSS SECTION
RISER
EARTHING RESISTANCE Rg : 0.064
E step (TOLERABLE) :
E touch (TOLERABLE) :
2225
GROUND POTENTIAL RISE GPR : 2.07 Kv
FAULT STEP VOLTAGE ES :
V
679.3 V
Estep(TOLERABLE)<132
7- REFERENCES :
Power Systems. "
IEEE guide for safety in AC substation grounding.
1. ANSI/ IEEE-std 80-2000
2. DIN 57141 - VDE 0141/19
VDE- standard for earthing system in A.C installations.
5. Design of high-voltage open-terminal station BS 7354:1990
6. IEEE-Std 142-1991
" IEEE Recommended Practice for Grounding of Industrial and Commercial
< Etouch(TOLERABLE)
3. B.Thapar and Sunil K.Madan; " CURRENT FOR DESIGN OF GROUNDING
SYSTEMS ", IEEE trans. on power apparatus and systems .
4. Practical applications of ANSI/IEEE standard 80-1986, IEEE guide for safety.
1986 .
vol. PAS-103,NO. 9,September 1984.
FAULT MESH VOLTAGE EM : 493.1
DATEAPPR2APPR1CHECKPREPREV
SHEET / CONT
12 / 13
REV CMT - R - U - C - 06 - ET - 801DWG.
No.
TITLE:
RUDESHUR SIMPLE CYCLE POWER
PLANT
AND 400kV SUBSTATION
EARTHING SYSTEM CALCULATION
UNIT INTERNATIONAL S.A
ISLAMIC REPUBLIC OF IRAN
MAH-TAAB GOSTAR CO.
DWG NO: 7102-RSH-E-CN-4-01 1 002 REV: G
SIEMENSPOWER GENERATION
CUSTOMER:OWNER:
19.05.05
28.05.05
06.06.05
26.06.05
A S
A S
A S
A S
F GH
F GH
F GH
F GH
A GD
A GD
A GD
A GD
M SH
M SH
M SH
M SH
C
D
E
F
12.07.05A SF GHA GDM SHG