Tp 01900001 e

Embed Size (px)

Citation preview

  • 7/28/2019 Tp 01900001 e

    1/16

    A Practical Approach to Arc Flash Hazard Analysis and ReductionWhite Paper

  • 7/28/2019 Tp 01900001 e

    2/16

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    By:

    H. Wallace Tinsley III

    Member, IEEEEaton Electrical130 Commonwealth DriveWarrendale, PA 15086

    Michael Hodder

    Member, IEEE

    Eaton Electrical4120B Sladeview CresMississauga, ON L5L 5Z3

    Presented at the 2004 IEEE IAS Pulp and Paper Industry Conference in Victoria, BC: IEEE 2004 - Personal use of this material is permitted.

    TABLE OF CONTENTS

    Abstract ....................................................................

    I. Introduction ..........................................................A. Standards

    B. Arc Flash Analysis

    II. Generalization of Arc Flash ..............................A. Fault Magnitudes

    B. Constant Energy

    C. Overcurrent Device Responses

    III. Time, Current, & Energy Relationship ...........A. Relationship Equations

    B. Sotware Application

    IV. System Models & Analysis ..............................A. Data Collection

    B. Unbalanced Faults

    C. Analysis Philosophy

    V. Considerations & Solutions ...............................

    VI. Conclusions ........................................................

    Acknowledgement .................................................

    References ...............................................................

    12

    3

    6

    11

    121213

    13

  • 7/28/2019 Tp 01900001 e

    3/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    ABSTRACT

    Recent eorts to quantiy the dangersassociated with potential arc fash hazardsrely on overcurrent protection to remove agiven ault condition. The eectiveness ovarious devices is determined by a clearingtime related to the maximum availableault current or each system location. Asindustrial and commercial acilities begin to

    embrace arc fash labeling procedures andbegin to recognize arc fash prevention asa part o a complete saety program, thecurrent method o calculation will allow themto quantiy the incident energy (cal/cm2)associated with a maximum, three-phaseault condition. Most aults producecurrent magnitudes less than the three-phase maximum. This paper will consider

    ault current magnitudes less than thato the maximum, threephase condition

    and discuss the resulting calculations orincident energy across the range o cur-rent magnitudes. Under these additionalscenarios, the perormance o variousovercurrent protection devices will bedemonstrated. Associated considerations

    or design, modeling, and maintenancewill be presented.

  • 7/28/2019 Tp 01900001 e

    4/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    Index Terms Constant Energy C-Line, Arc Flash Hazard,Unbalanced Faults, Worst-Case Scena

    I. INTRODUCTION

    Extensive research and experimentation have led to

    the development o detailed calculation methods or

    determining the magnitude and intensity o Arc Flash

    Hazards. These methods have been presented in IEEEStandard 1584 2002 and the NFPA 70E 2000

    Edition. Recommended practice now requires that

    the incident energy due to an Arc Flash be quantifed

    at each system location potentially accessed by

    authorized personnel while the equipment is

    energized.

    This requirement suggests the need or a thoughtul

    understanding o the power system and the meth-

    ods o calculation. This paper provides a ramework

    o considerations on which to base the methods o

    calculation presented in the most current standards.

    These considerations include worstcase scenarios,

    data collection or analysis, design concerns, and

    maintenance.

    A. Standards

    NFPA 70E-2000 Edition, Table 3-3.9.1 requires acil-

    ity personnel to wear Personal Protective Equipment

    (PPE) when perorming various tasks in locations

    susceptible to potential Arc Flash Hazards.[1] These

    requirements are mandated on the basis o feld

    experience and are categorized by associated voltage

    levels. The Hazard/Risk Category is determined by the

    nature o the work to be completed, the operating

    voltage, and the available short circuit current or thatgeneral location in the electrical distribution system.

    The Hazard/Risk Category reers to the appropriate

    protective clothing and personal protective equip-

    ment (PPE) to be utilized.

    In 2002, the IEEE reported the results o extensive

    laboratory experiments and calculations. IEEE

    Standard 1584 2002 describes the procedures

    and provides direction or an accurate means o

    determining a sae Arc Flash Boundary and

    associated Hazard Level.

    The basis or this method is experimental data

    recorded rom simulated arcs corresponding to bolt-

    ed, three-phase ault current magnitudes measured

    at the terminals o an experimental enclosure.

    B. Arc Flash Analysis

    The Arc Flash analysis requires the completion o a

    Short Circuit Study and a Coordination Study. Theresults o the Arc Flash calculations are based on the

    calculated values o ault current magnitudes ound

    in the short circuit study and the associated

    clearing times o overcurrent protection devices

    as determined by the coordination study.

    The goal o this type o analysis is to determine the

    incident energy potentially present during an arc

    ash event. The magnitude o the incident energy is

    calculated on the basis o the available ault current,

    the clearing time o associated system protection,

    and the physical parameters o the system location.

    Associated with this calculation is the determination

    o an approach distance within which the incidentenergy level is above 1.2 cal/cm2. Appropriate Per-

    sonal Protection Equipment (PPE) shall be used when

    working on or near energized equipment within the

    ash protection boundary.[1]

    The results o the approach boundary and incident

    energy calculations may be displayed in labels

    on equipment enclosures to inorm and direct

    acility personnel with respect to the potential arc

    ash hazard.

    2

  • 7/28/2019 Tp 01900001 e

    5/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    II. GENERALIZATION OF ARC FLASH

    For proper evaluation o a power system with respect

    to potential Arc Flash hazards, accurate generalization

    o these hazards is imperative to describe the

    worst-case scenario. To understand the worst-case

    conditions, one must relate potential ault magni-

    tudes to the clearing time associated with various

    overcurrent devices.

    Figures 1 & 2

  • 7/28/2019 Tp 01900001 e

    6/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    A. Fault Magnitudes

    IEEE Standard 1584 2002 cautions, it is important

    to determine the available shortcircuit current or

    modes o operation that provide both the maximum

    and the minimum available short-circuit currents.[2]

    The importance o this statement is demonstrated

    when an o-peak maintenance scenario is compared

    with the ull load operating condition. A hazardous

    arc ash condition may arise rom various causes,

    and oten occurs during maintenance. Maintenance

    tasks are oten perormed at times when the acility

    and/or its processes are not ully operational.

    Although the power system is energized, some o

    the contributing motor loads may be shut down.

    Thereore, during maintenance operations, when

    the propensity or arc ash conditions is high, the

    available ault current may be signifcantly lowerthan the calculated maximum.

    To demonstrate the eect o various scenarios, we

    have modeled a sample system that represents three

    acilities that are supplied by a single utility substa-

    tion. A portion o this system is shown in Figures 1

    and 2. In the Figure 1, all contributing motors are in

    service and the utility contribution is at a maximum.

    In Figure 2, the low voltage motors have been

    reduced to 10% o ull-load and the medium voltage

    motors have been removed. The same is true or the

    adjacent neighbors and the total ault contribution at

    a typical 480V substation is signifcantly decreased.The magnitude o the available bolted ault current

    is decreased rom Figure 1 to Figure 2 by approxi-

    mately 30%. The arcing current is also reduced by

    approximately 30% between the two fgures. For the

    calculation o incident energy, we should consider the

    range defned by this minimum calculation and this

    maximum calculation or any given location.

    B. Constant Energy

    By the method presented in IEEE Standard 1584

    2002, incident energy (E) is calculated or specifc

    system locations. This calculated value o energy is

    determined by the physical environment at the given

    location and the duration o a previously calculated

    magnitude o arcing ault current. The duration o the

    ault condition is dependent on the clearing time o

    the upstream overcurrent protection. This clearing

    time is determined by the actual magnitude o

    arcing ault current or a given occurrence.

    For a given location, there exists a series o potential

    arcing ault current magnitudes and theoretical

    clearing times or which incident energy remains

    constant. Several o these series are shown in Figure

    3. On a log-log plot, these combinations o constant

    energy points with respect to time and current

    appear as a linear line segments. For a typical low-

    voltage, grounded, enclosed substation, these

    selected lines correspond to the PPE classes outlinedin IEEE Standard 1584 2002. The lowest line shown

    in Figure 3 represents a constant energy o 1.2cal/cm2.

    This corresponds to the upper limit o PPE Class 0.

    The uppermost line represents the maximum value

    o 40 cal/cm2 or which PPE Class 4 provides sufcient

    protection. Above this line, no PPE class has been

    Figure 3

    4

  • 7/28/2019 Tp 01900001 e

    7/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    C. Overcurrent Device Responses

    For the majority o system locations that are

    protected by a use, the minimum available arcingault current is the basis o the worst-case calculation

    or incident energy. (See Figure 4.)

    For a system location protected by a circuit breaker,

    the worstcase calculations vary with the regions o

    the clearing characteristic. When the considered range

    o ault current magnitudes alls completely within

    any region o the timecurrent curve (TCC) across

    which the time remains constant, the maximum

    available ault current will result in the calculation o

    the worst-case incident energy. Such regions include

    defnite-time relays and defnite-time delay regions o

    electronic trip unit characteristics. (See Figure 5.) For

    regions o the TCC where the tripping characteristicis inverse or based on the I2t or I4t model, the

    lower arcing ault values will correspond to longer

    clearing times; resulting in the worst-case scenario.

    (See Figure 5.)

    Figure 4

    Figure 5

  • 7/28/2019 Tp 01900001 e

    8/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    III. TIME, CURRENT, & ENERGY RELATIONSHIP

    A. Relationship Equations

    In order to demonstrate the worst-case arc-ash

    scenario across a given range o arcing ault currents,constant-energy lines can be plotted on the TCC plot

    in conjunction with tripping characteristics o various

    devices.

    For voltage levels less than 15kV, the IEEE 1584

    2002 presents the equation or incident energy as

    shown in Equation (1) [2]. The values or the variables

    shown in this equation are presented in Table 1. In

    equation (1), the units o energy are Joules/cm2.

    Equation (2) shows Equation (1) algebraically

    rearranged in order to calculate values or time with

    respect to a given set o parameters. The conversion

    actor between Joules and calories has also been

    included so that the units o Energy (E) in Equation (2)are cal/cm2.

    Equation (1):

    Where:

    E is energy inJoules

    /cm

    2

    .C is a calculation actor, equal to1.0 or voltages above 1kV and1.5 or voltages at or below 1kV.

    K1 is -0.792 or open confgurations (no enclosure) andis -0.555 or closed confgurations (enclosed).

    K2 is 0 or ungrounded and HRG systems andis -0.133 or grounded systems.

    Ia the magnitude o the arcing ault current (kA)that may be determined according to IEEE1584 2002, equation (1).

    G is the gap between conductors (mm).t is the duration o the arc (seconds).x is the distance exponent.D is the distance rom the arc to the worker (mm).

    Equation (2):

    Where:

    t is the duration o the arc (seconds).E is energy in cal/cm

    2.

    C is a calculation actor, equal to1.0 or voltages above 1kV and1.5 or voltages at or below 1kV.

    K1 is -0.792 or open confgurations (no enclosure) andis -0.555 or closed confgurations (enclosed).

    K2 is 0 or ungrounded and HRG systems andis -0.133 or grounded systems.

    Ia the magnitude o the arcing ault current (kA)that may be determined according to IEEE1584 2002, equation (1).

    G is the gap between conductors (mm).x is the distance exponent.D is the distance rom the arc to the worker (mm).

    Equation (3) shows the linear relationship between

    time and arcing current with respect to a given

    energy and specifc system parameters shown in

    Table 1. With the aid o curveftting sotware [3], this

    relationship was ound consistent or all systemconfgurations considered.

    Equation (3):

    Where:

    t is time in seconds.k is a unique constant based on specifc system

    parameters (See Table 1 or a summary and thediscussion below or details.)

    Ia is the magnitude o arcing ault current.b is a constant value = -1.081.

    E=(4.184)C10[K1 + K2 + 1.081 log [Ia]+ 0.0011G]

    [t/0.20][610x

    /Dx]

    E (0.20) 4.1667 ____________________________________t =

    (4.184)C10[K1 + K2 + 1.081 log [Ia]+ 0.0011G]

    [610x

    /Dx]

    t =k (Ia)b

    6

  • 7/28/2019 Tp 01900001 e

    9/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    Constant k is determined or each system location

    according to system parameters and a distance actor

    related to the equipment type and the system location

    voltage.

    This determination was made according to the

    ollowing steps:

    1. For each system location considered, a fnite

    series o time-current ordered pairs (Ia, t) was

    ound, or which incident energy remains

    constant. (See Equation (1) and Figure 3)

    2. This series o ordered pairs (Ia, t) was

    provided as input or the curve-ftting

    sotware [3].

    3. The resulting time versus current plot was

    consistently ftted with a curve o the ormshown in Equation (3). The constant b (-1.081)

    remained constant regardless o the system

    parameters. The constant k was ound to be

    unique or each new set o parameters.

    The system parameters are shown in Table 1 and

    include: system voltage, equipment type, bus gap

    (mm), working distance (mm), enclosure confgura-

    tion, and grounding. For some typical systemlocations, Table 1 shows the resulting values or

    the unique constant k.

    With a point defned on a TCC plot by the magnitude

    or arcing ault current and the associated clearing

    time or a specifc device; it is useul to defne a

    corresponding line that represents all combinations

    o time and arcing current or which energy remains

    constant with respect to the given point. This line on

    the TCC plot is called a C-line, and the points (Ia, t)

    along this line o constant energy can be defned by

    the constant C in Equation (4).

    Table 1

  • 7/28/2019 Tp 01900001 e

    10/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    Equation (4):

    For a given system location (defned by k), C is a

    unique constant describing the relationship o a fnite

    series o time and current combinations or which

    energy remains constant. For increasing energy, C

    is also increasing. Using this relationship, any two

    regions on a TCC can be compared to determine the

    worst-case scenario.

    Consider the clearing time or both the maximum and

    minimum ault conditions and let the ordered pair,

    (Ia1, t1), represent the maximum arcing ault current

    and the associated clearing time. Let the ordered pair,

    (Ia2, t2), represent the minimum arcing ault current

    and the associated clearing time. Compare as ollows:

    I C1 > C2, then E1 > E2 and vice versa. The larger value

    or C will correspond to the energy (E) greater value.

    Using the relationship one can quickly determine

    the worstcase condition between any number o sce-

    narios (time and arcing current) at a given location.

    B. Sotware Application

    On a standard time-current curve (TCC), sotware

    packages could use a location-specifcC-lineto

    provide a visual representation or the severity o

    several incident energy calculations within the range

    o possible arcing ault conditions at a given location.

    Provided with the values shown or k in Table 1, a

    C-linecan be generated or each device with respect

    to the bus location immediately downstream or withrespect to a selected bus downstream o several

    devices. To aid in overcurrent device coordination, the

    unique C-linewill visually demonstrate which setting

    regions might be adjusted to reduce the arc ash haz-

    ard. Figure 6 shows the tripping characteristics o two

    devices. The electronic-trip circuit breaker is shown as

    the 480V main breaker o a typical unit substation. The

    use characteristic is representative o the primary

    device on the 13.8kV side o the source transormer.

    Ater determining maximum and minimum

    magnitudes o the available bolted ault currents

    at the substation bus, the corresponding arcing ault

    magnitudes can be calculated. These arcing ault

    current magnitudes are calculated according to

    IEEE Standard 1584 2002 using specifc system

    parameters. Given these parameters, the appropriate

    value or k may be selected rom Table 1 or alterna-tively, k can be calculated or system parameters not

    ound in the table.

    In Figure 6, the maximum arcing ault current magni-

    tude (Ia1) o 15.7kA is shown. For an arc ash event at

    the substation bus, the associated clearing time o the

    main breaker will be used to determine the incident

    energy or this ordered pair (Ia1, t1). A clearing time o

    0.323 seconds is shown or t1.

    t

    ________C =k (Ia)

    -1.081

    t1

    Set C1

    =

    /k (Ia1)-1.081

    t2

    and C2

    = /k (Ia2)-1.081

    Figure 6

    8

  • 7/28/2019 Tp 01900001 e

    11/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    Similarly, or an arc ash event on the line side o

    the main breaker or the secondary terminals o the

    substation transormer, the incident energy is deter-

    mined by the clearing time o the primary use. Thispoint on the plot or the maximum arcing current and

    associated clearing time is shown as (15.7kA, 4.1s).

    Figure 6 also shows the minimum magnitude o the

    available arcing ault current at the substation bus.

    This minimum value o available ault current

    (Ia2 = 9.1kA) relates to the systemoperating scenario

    when motor contributions are the lowest. The time

    required to clear the potential arc ash event rom

    the substation bus is 2.7 seconds, and is shown in

    the long-delay region o the circuit breaker trip unit.

    Likewise, or an event on the line side o the substa-

    tion main breaker or the secondary terminals o thetransormer, the time required or the primary use

    to clear the ault is ound to be 90 seconds.

    Using the points that correspond to the maximum

    value o arcing ault current, a uniqueC-lineis drawn

    or each protective device characteristic in Figure 7.

    From Equation (4), the C-lineor each device is deter-mined with the value o k selected rom Table 1 and

    the time-current pairs associated with the maximum

    available arcing ault current.

    By visual inspection o Figure 7, it is shown that, or

    both protective devices, the greatest incident energy

    is present under the minimum ault condition. This is

    evident because the point on the tripping characteris-

    tic o each device that is associated with the minimum

    arcing ault magnitude is shown above theC-line

    that passes through the similar point associated with

    the maximum available ault current. Each time-cur-

    rent point on a TCC that is above a givenC-linehasa corresponding value or incident energy (E) that is

    greater than the value o incident energy (E) associ-

    ated with all points shown on or below thisC-line.

    Figure 7 Figure 8

  • 7/28/2019 Tp 01900001 e

    12/16

    www.eatonelectrical.com/arcash

    A Practical Approach to Arc Flash Hazard Analysis and Reduction

    The plotting o the C-Line line may be automated

    within a sotware package, but can be quickly plotted,

    by hand. For the main substation breaker in this par-

    ticular scenario, the ollowing steps are demonstratedin Figure 8:

    1. For a typical, solidly grounded, low voltage

    switchgear location, select the value or k

    rom Table 1: 0.6841.

    The tripping characteristic o the main breaker is

    plotted in Figure 8. The breakers maximum clearing

    time at the maximum arcing ault current o 15.7kA is

    shown to be 0.323 seconds.

    2. Select (Ia1, t1) to correspond to the maximum

    arcing ault current and the associated

    clearing time: (15.7kA, 0.323).

    3. Calculate C rom Equation (4):

    Remember,Cisonlyanenergyspecifcconstant.

    4. Select Ia2: 9.1kA

    Thisvaluecanbeanyothercurrentvalueontheplot,but itisconvenienttousethecalculatedminimumvalue.

    5. Calculate t2 using Equation (4):

    6. Connect the two points with a line segment.

    ThisistheC-Lineassociatedwiththesubstation mainbreaker.

    Using the C-Line in Figure 8, one can be visually

    observe that the minimum arcing ault condition has

    a higher incident energy that the maximum arcing

    condition. Following the determination o the worst-

    case scenario, system changes may be recommended

    or specifed to reduce the incident energy potentially

    present at the substation bus.

    Figure 9 shows a change in settings or the main

    breaker and a change in use type or the primary

    device. In both cases, the original C-lines are still

    shown or comparison. For the electronic-trip circuit

    breaker, the maximum magnitude or arcing ault

    current now corresponds to with the worst-case

    scenario. For the primary use, the minimum magni-

    tude or arcing ault current remains the worst-case

    t ________C=k (Ia)

    -1.081

    0.323 ________________C=0.6841 (15.7 103)

    -1.081

    16.213103

    C=